CARLO GAVAZZI PUB03CW24 Guide d'installation

Taper
Guide d'installation

Ce manuel convient également à

DUB03CW24
PUB03CW24
AC/DC voltage monitoring relay
AC/DC Spannungsüberwachungsrelais
Relais de contrôle de tension CA/CC
Relé de control de tensión CA/CC
Relè di tensione AC/DC
AC/DC spændingsmålerelæ
Installation instructions
Installationshinweise
Notice d’installation
Instrucciones de instalación
Istruzioni per l’installazione
Installationsvejledning
Mounting and installation by skilled people only!
Montage und Installation nur durch Fachpersonal!
Montage et installation par des personnes habilitées seulement!
¡El montaje e instalación ha de realizarlo sólo personal con experiencia!
Il montaggio e l’installazione va eseguito da parte di personale addestrato!
Montering og installation må kun foretages af faguddannede personer!
ENGLISH DEUTSCH
FRANÇAIS
ESPAÑOL
ITALIANO DANSK
j Connections (DUB03)
Connect the power supply
to A1 and A2 (taking care
of polarity if DC). Connect
the relay output according
to the ratings. Automatic
screwdriver can be used
(max torque 0.5 Nm).
Keep power OFF
while connecting!
k Connections (PUB03)
Connect the power supply
to terminals 2 and 10 (tak
-
ing care of polarity if DC).
Connect the relay output
according to the ratings.
Keep power OFF
while connecting!
l Setting of function and
input range
Adjust the input range set
-
ting the DIP switches 1 and
2. Select the desired func
-
tion setting the DIP switch-
es 3 to 6. To access the DIP
switches open the plastic
cover using a screwdriver
as shown on the left.
SW3 selects the status of
the relay: normally ener
-
gized (relay OFF in alarm
condition) or normally
de-energized (relay ON
in alarm condition). SW4
selects the power-ON
delay (inhibit of the alarm
at the power-ON): 1s or 6s.
SW5 selects the contact
input function: latch or not
latch of alarm enable. SW6
selects the function: under
or overvoltage.
Do not open the
DIP-switches cover
if the Power Supply
is ON
m Mechanical mounting
(DUB03)
Hang the device to the
DIN-Rail being sure that
the spring closes. Use a
screwdriver to remove the
product as shown in figure.
j Anschlüsse (DUB03)
Betriebsspannung an A1
und A2 anschließen (ach
-
ten Sie bei DC auf die
richtige Polarität) und den
Relaisausgang entspre
-
chend den Betriebsdaten
anschließen. Automatische
Schraubenzieher kön
-
nen benutzt werden
(Drehmoment max. 0,5 Nm).
Achten Sie während
dem Anschließen auf
Spannungsfreiheit!
k Anschlüsse (PUB03)
Betriebsspannung an die 2
und 10 Klemmen anschlie
-
ßen (achten Sie bei DC
auf die richtige Polarität)
und den Relaisausgang
entsprechend den
Betriebsdaten anschließen.
Achten Sie während
dem Anschließen auf
Spannungsfreiheit!
l Wahl der Funktion und
des Eingangsbereichs
Um Zugang zu den DIP-
Schaltern zu bekommen, muß
die Klappe mit Hilfe eines
Schraubenziehers - wie in der
Illustration gezeigt - geöffnet
werden. Den gewünschten
Eingangsbereich mit den DIP-
Schaltern 1 und 2 einstellen.
Die Funktion über die DIP-
Schalter 3 bis 6 auswählen.
Mit SW3 wird die Schaltart
des Relais definiert: “normal
deaktiviert” (das Relais ist
im Alarmfall an) oder “nor
-
mal aktiviert” (das Relais ist
im Alarmfall aus). Mit SW4
wird die Meßverzögerung
nach dem Anlegen der
Betriebsspannung ein
-
gestellt: 1s oder 6s. SW5
definiert die Funktion
des Kontakt-Eingangs:
Selbsthaltung oder
Alarmsperre. Mit SW6 wird
die Überwachungsfunktion
bestimmt: Über- oder
Unterspannung.
Achtung! Gerät vor
dem Öffnen der DIP-
Schalterab-deckung
spannungsfrei schal
-
ten.
m Montage (DUB03)
Befestigen Sie das Relais
auf der DIN-Schiene und
achten Sie darauf, daß die
Befestigungsfeder ein
-
gerastet ist. Benutzen Sie
einen Schraubenzieher, wie
im nebenstehenden Bild
gezeigt, um das Relais wie
-
der zu entfernen.
j Connections (DUB03)
Raccorder l’alimentation
sur A1 et A2 (respecter le
sens de polarité en version
con-tinue). Raccorder le
relais de sortie en respec
-
tant la charge admissible.
Une visseuse électrique
peut être utilisée (couple
maximum 0,5 Nm).
Couper l’alimenta
-
tion lors des raccor-
dements!
k Connections (PUB03)
Raccorder l’entrée ten
-
sion sur les bornes 2 et
10 (respecter le sens de
polarité en version conti
-
nue). Raccorder le relais
de sortie en respectant la
charge admissible.
Couper l’alimenta
-
tion lors des raccor-
dements!
l Paramétrage de la fonc-
tion et de la gamme de
mesure
Ajuster la gamme de
mesure en paramétrant
les micro commutateurs 1
et 2. Sélectionner la fonc
-
tion désirée à l’aide des
micro-commutateurs 3 à
6. Pour accéder au micro
commutateurs ouvrir le
cache plastique en utilisant
un tournevis tel indiqué sur
la gauche.
SW3 sélectionne l’état du
relais: normalement activé
(relais désactivé en posi
-
tion alarme) ou normale-
mente désactivé (relais
activé en position alarme).
SW4 sélectionne le temps
d’alimentation (inhibition
de l’alarme lors de la mise
sous tension): 1s ou 6s.
SW5 sélectionne la fonction
du signal d’entrée: verrouil
-
lage ou inhibition de l’ac-
tivation de l’alarme. SW6
sélectionne la fonction: mini
ou maxi de tension.
Ne pas ouvrir le
couvercle des micro
commutateurs si
l’appareil est sous
tension.
m Montage mécanique
(DUB03)
Accrocher l’appareil sur le
rail DIN en s’assurant que
l’agrafe est positionnée.
Utiliser un tournevis pour
le retirer tel indiqué sur le
schéma.
j Conexiones (DUB03)
Conectar la alimentación a
A1 y A2 (tener en cuenta la
polaridad si es CC) y el relé
de salida de acuerdo a la
carga indicada. Puede usar
-
se un destornillador auto-
mático (máx. par de apriete
0,5Nm).
¡Desconecte la ali
-
mentación antes de
realizar las conexio
-
nes!
k Conexiones (PUB03)
Conectar la alimentación a
los bornes 2 y 10 (tener en
cuenta la polaridad si es
CC) y el relé de salida de
acuerdo a la carga indi
-
cada.
¡Desconecte la ali-
mentación antes de
realizar las conexio-
nes!
l Ajuste del rango de entra-
da y de la función
Seleccionar el rango de
entrada de tensión desea
-
da a través de los inte-
rruptores DIP 1 y 2, y la
función a través de los los
interruptores DIP 3, 4, 5, y
6. Para acceder a los los
interruptores DIP abrir la
tapa de plástico como indi
-
ca la figura de la izquierda.
SW3 selecciona el estado
del relé: normalmente exci
-
tado (relé OFF en condicion
de alarma) o normalmente
desexcitado (relé ON en
condicion de alarma). SW4
selecciona el retardo a la
conexión (Inhibe el dispa
-
ro durante la conexión del
relé) 1s o 6s. SW5 seleccio
-
na la función de la entrada
de contacto externa: relé
de salida enclavado o inhi
-
bido. SW6 selecciona la
función: máxima o mínima
tensión.
¡No abrir la tapa de
los interruptores
DIP bajo tensión de
alimentación
m Montaje Mecánico
(DUB03)
Sujetar el equipo al rail DIN
asegurando que las bridas
de sujeción estén cerradas.
Use un destornillador para
manipular el equipo como
indica la figura.
j Collegamenti (DUB03)
Collegare l’alimentazione
ad A1 e A2 (rispettando la
polarità se DC). Collegare
l’uscita relè secondo i valori
di carico indicati. La coppia
massima in caso di uso
di avvitatori automatici è
0,5 Nm
Staccare l’alimenta
-
zione prima di col-
legare lo strumento!
k Collegamenti (PUB03)
Collegare l’alimentazione ai
terminali 2 e 10 (rispettan
-
do il verso della corrente se
DC). Collegare l’uscita relè
secondo i valori di carico
indicati.
Staccare l’alimenta
-
zione prima di col-
legare lo strumento!
l Messa a punto della por-
tata d’ingresso e della
funzione
Selezionare la portata desi
-
derata attraverso i DIP swi-
tch 1 e 2. Selezionare la
funzione attraverso i DIP
switch da 3 a 6. Per acce
-
dere ai DIP switch aprire
lo sportellino usando un
cacciavite come mostrato
in figura.
SW3 seleziona lo stato del
relè: normalmente eccita
-
to (relè spento in stato di
allarme) o normalmente
diseccitato (relè acceso in
stato di allarme). SW4 sele
-
ziona il ritardo all’avvio (ini-
bizione del funzionamento
del relè all’avvio): 1s o 6s.
SW5 seleziona la funzio
-
ne dell’ingresso di contat-
to: bloccaggio o inibizione
del funzionamento del relè.
SW6 seleziona la funzione:
sovra o sottotensione.
Non aprire lo spor
-
tello DIP-switch se
l’alimentazione è
collegata!
m Montaggio sulla guida
DIN (DUB03)
Agganciare lo strumento
alla guida DIN verificando
la chiusura della molla. Per
rimuovere il prodotto dalla
guida usare un cacciavite
come mostrato in figura.
j Tilslutninger (DUB03)
Tilslut forsyningsspændingen
til A1 og A2 (vaer opmaerk
-
som på polariteten ved DC).
Tilslut relæudgangen i over
-
ensstemmelse med data.
Automatskruetrækker kan
anvendes (max. moment 0,5
Nm).
Forsyningen skal
være koblet fra,
mens forbindelserne
etableres!
k Tilslutninger (PUB03)
Tilslut forsyningsspændin
-
gen til 2 og 10 terminaler
(husk korrekt polaritet ved
DC). Tilslut relæudgangen
i overensstemmelse med
data.
Forsyningen skal
være koblet fra,
mens forbindelserne
etableres!
l Indstilling af funktions-
og indgangsområde.
Indstil indgangsområdet
med DIP-switch 1 og 2.
Vælg det ønskede funk
-
tionsområde med DIP-
swich’ene 3 til 6. For at få
adgang til DIP-swich’ene
åbnes plastikdækslet med
en skruetrækker som vist
til venstre.
SW3 vælger relæets sta
-
tus: Normal aktiveret (relæ
OFF i alarmsituation) eller
normal uaktiveret (relæ
ON i alarmsituation). SW4
vælger opstartsforsinkelse
(undertrykkelse af alarm
ved tilslutning af forsy
-
ningsspænding): 1 sek. eller
6 sek. SW5 vælger funktio
-
nen af kontaktindgangen:
Selvhold eller undertrykkel
-
se af alarmfunktion. SW6
vælger funktionen: over-
eller underspænding.
Beskyttelsesdæk
-
slet over DIP-
switches må ikke
fjernes, når forsy
-
ningsspændingen er
tilsluttet
m Mekanisk montering
(DUB03)
Monter systemet på DIN-
skinnen, og sørg for, at fje
-
deren låser. Afmontering af
systemet foretages ved at
anvende en skruetrækker
som vist i figuren.
DUB03CW24-PUB03CW24 / code 8021877/070219 http://www.carlogavazzi.com/ CARLO GAVAZZI
L
N(-)
A1
A2 15
16 18
U
12 - 240V
AC/DC (+)
L
N(-)
10 1
43
U
2
12 - 240V
AC/DC (+)
ON: 6 ± 0.5 s
OFF: 1 ± 0.5 s
ON: LATCH
OFF: NOT LATCH
ON: OVER
OFF: UNDER
ON: N.D.
OFF: N.E.
ON OFF: 24V
OFF OFF: 48V
ON ON: 115V
OFF ON: 240V
n Startup and adjustment
Check if the input range
is correct. Turn the power
ON. The green LED is ON.
Adjust the level, delay
and hysteresis (difference
between the alarm ON and
the alarm OFF thresholds)
knobs to the desired value.
When the voltage exceeds
(or drops below) the set
point for more than the set
delay time, red LED (flash
-
ing during the delay time)
turns ON. Relay and yellow
LED turn ON if the relay
is normally de-energized,
they turn OFF if normally
energized.
o Note
The packing material
should be kept for redeliv
-
ery in case of replacement
or repair.
p Terminals
Power supply
Relay output
Each terminal can accept
up to 2 x 2.5 mm
2
wires
(DUB03).
n Einschalten und
Einstellungen
Betriebsspannung kontrol
-
lieren und einschalten - die
grüne LED leuchtet. Stellen
Sie an den Drehknöpfen
den gewünschten
Grenzwert, die Hysterese
und die Alarmverzögerung
ein.
Wenn die Meßspannung
den eingestellten Grenzwert
länger als die vorgewähl
-
te Verzögerungszeit über-,
beziehungsweise unter
-
schreitet (Auswahl über
DIP-Schalter SW6), schal
-
tet der Ausgang und die
rote LED leuchtet (blinkt
während der Verzögerung).
Das Relais zieht an und die
gelbe LED leuchtet, wenn
mit DIP-Schalter SW3 als
“normal deaktiviert” defi
-
niert. Bei “normal aktiviert”
fällt das Relais ab und die
gelbe LED verlöscht.
o Bemerkungen
Heben Sie bitte die
Originalverpackung für
eventuelle Rücksendungen
an die Serviceabteilung auf.
p Anschlußklemmen
Betriebsspannung
Relaisausgang
Klemmenanschluß bis max.
2 x 2,5 mm
2
je Klemme
(DUB03).
n Mise en service et réglage
Vérifier si la gamme de
mesure est correcte.
Mettre sous tension. La
LED verte est allumée.
Ajuster la valeur, le temps
et l’hystérésis (différence
entre le seuil d’alarme acti
-
vé et désactivé) à l’aide du
potentiomètre à la valeur
désirée. Quand la tension
excède (ou chute au-des
-
sous) du seuil au-delà du
temps programmé, la LED
rouge s’allume (clignote
-
ment pendant la durée).
Le relais et la LED jaune
sont activés si le relais est
normalement désactivé, ils
sont désactivés si normale
-
ment activés.
o Note
L’emballage doit être
conservé lors du retour du
matériel en cas de rempla
-
cement ou de réparation.
p Borniers
Alimentation
Sortie relais
Chaque borne peut accep
-
ter des câbles 2 x 2,5 mm
2
(DUB03).
n Ajuste y puesta en mar-
cha
Comprobar que el rango
de entrada es correcto.
Alimentar el equipo, el LED
verde se enciende, ajustar
los potenciómetro frontales
al valor deseado de ten
-
sión, histéresis y tiempo de
retardo. Cuando la tensión
sea superior (o inferior) al
valor ajustado, el LED rojo
parpadeará durante el tiem
-
po de retardo y se pone
a ON. El relé de salida y
el LED amarillo se ponen
a ON si el relé esta nor
-
malmente desexcitado y se
ponen a OFF si el relé esta
normalmente excitado.
o Nota
El embalaje deberá ser
guardado para reenviar el
equipo en caso de repara
-
ción o cambio.
p Terminales
Alimentación
Inhibición
Relé de salida
Cada terminal admi
-
te 2 cables de 2,5 mm
2
(DUB03).
n Accensione e regolazione
Controllare la correttezza
della portata. Alimentare
lo strumento. Il LED verde
si accende. Regolare le
manopole di livello, istere
-
si (differenza fra la soglia
di intervento e quella di
disinserzione dell’allarme) e
ritardo al valore desiderato.
Quando la tensione supe
-
ra (o scende al di sotto)
del valore impostato per
più del tempo di ritardo il
LED rosso (che lampeggia
durante il tempo di ritardo)
si accende. Il relè e il LED
giallo si accendono se il
relè è normalmente disec
-
citato, si spengono se è
normalmente eccitato.
o Nota
Conservare l’imballo origi
-
nale in caso di sostituzione
o riparazione.
p
Terminali di collegamento
Alimentazione
Uscita relè
Ad ogni morsetto possono
essere collegati 2 fili di 2,5
mm
2
(DUB03).
n Opstart og justering
Kontroller, at indgangs
-
området er korrekt. Tilslut
forsyningsspændingen.
Den grønne lysdiode tæn
-
des. Indstil knapperne
for niveau, forsinkelse og
hysterese (forskellen imel
-
lem punkterne, hvor alarm
er aktiveret og ikke aktive
-
ret) til den ønskede værdi.
Stiger indgangsspændin
-
gen over (eller falder under)
den indstillede værdi i læn
-
gere tid end tidsforsinkel-
sen, vil den røde lysdiode
(blinker under tidsforsinkel
-
sen) aktiveres. Relæet og
den gule lysdiode aktive
-
res, hvis relæet normalt er
afbrudt, de afbrydes, hvis
de normalt er aktiveret.
o Bemærk
Gem emballagen til brug
ved returnering i forbindel
-
se med erstatningsleveran-
ce eller reparation.
p Terminaler
Spændingsforsyning
Relæudgang
Hver terminal kan accepte
-
re kabel op til 2 x 2,5 mm
2
(DUB03).
DUB03CW24-PUB03CW24 / code 8021877/070219 http://www.carlogavazzi.com/ CARLO GAVAZZI
DUB03 PUB03
A1, A2 2, 10
15, 16, 18 1, 4, 3
Responsibility for disposal / Verantwortlichkeit für Entsor-
gung / Responsabilité en matière d’élimination / Respon-
sabilidad de eliminación / Responsabilità di smaltimento/
Ansvar for bortskaffelse:
The product must be disposed of at the relative recycling
centres specified by the government or local public author
-
ities. Correct disposal and recycling will contribute to the prevention
of potentially harmful consequences to the environment and persons.
Dieses Produkt muss bei einem geeigneten von der Regierung oder
lokalen öffentlichen Autoritäten anerkannten Recyclingbetrieb entsorgt
werden. Ordnungsgemäße Entsorgung und Recycling tragen zur
Vermeidung möglicher schädlicher Folgen für Umwelt und Personen bei.
Éliminer selon le tri sélectif avec les structures de récupération indiquées
par l’État ou par les organismes publics locaux. Bien éliminer et recycler
aidera à prévenir des conséquences potentiellement néfastes pour l’en
-
vironnement et les personnes.
Eliminar mediante recogida selectiva a través de las estructuras de
recogida indicadas por el gobierno o por los entes públicos locales. La
correcta eliminación y el reciclaje ayudarán a prevenir consecuencias
potencialmente negativas para el medioambiente y para las personas.
Smaltire con raccolta differenziata tramite le strutture di raccolte indi
-
cate dal governo o dagli enti pubblici locali. Il corretto smaltimento e il
riciclaggio aiuteranno a prevenire conseguenze potenzialmente negative
per l’ambiente e per le persone.
Produktet skal bortskaffes på en lokal, godkendt genbrugsstation.
Korrekt bortskaffelse og genbrug vil bidrage til at mindske eventuelle
skadelige konsekvenser for miljøet, mennesker og dyr.
General warnings:
- Read carefully the present instruction manual. If the device is used in
a manner not specified by the manufacturer the protection function may
be impaired.
- All operations concerning installation, or unmounting, of device or
modules shall be carried out by qualified personnel and after having
disconnected all power sources.
- A readily accessible overcurrent protection (fuse or circuit breaker)
shall be incorporated in the building installation wiring.
UL Notes:
- Use 60 or 75°C copper (CU) conductor and wire size No. 30-14 AWG,
stranded or solid (DIN models only)
- Terminal tightening torque of 4.4Lb-In” (DIN models only)
- Being these devices Overvoltage Category III they are: “For use in a
circuit where devices or system, including filters or air gaps, are used
to control overvoltages at the maximum rated impulse withstand vol-
tage peak of 4.0 kV. Devices or system shall be evaluated using the
requirements in the Standard for Transient Voltage Surge Suppressors,
UL 1449.
- The devices shall be installed in a pollution degree 2 environment or
better.
- For UL61010 compliance: The plug-in models shall be used with Carlo
Gavazzi ZPD11, ZPD11A or ZPD11XA DIN Rail Sockets.
Avertissements généraux:
- Lire attentivement ce manuel d’instructions. Si le dispositif est utilisé
d’une manière autre que celle spècifièe par le fabricant, la fonction de
protection peut être altérée.
- Toutes les opérations concernant l’installation, le démontage du di-
spositif et des modules doivent être effectuées par du personnel qualifié
et uniquement après avoir déconnecté les sources d’alimentation et de
puissance.
-
Une protection contre les surintensités facilement accessible (fusible
ou disjoncteur) doit être intégrée au câblage d’installation du bâtiment.
Notes UL:
- Utilisez un conducteur en cuivre (CU) à 60 °C ou à 75 °C, calibre de
fil AWG30 à AWG14 ( 0.06mm
2
à 2.1mm
2
) Toronnè ou solide (modèles
DIN uniquement).
- Couple de serrage des bornes de 0.5Nm (4.4Lb-In), (modèles DIN
uniquement).
- S’agissant de ces dispositifs de catégorie de surtension III, ils sont:
«Pour une utilisation dans un circuit où des dispositifs ou un système, y
compris des filtres ou des éclateurs, sont utilisés pour contrôler les sur-
tensions au maximum de la tension de tenue nominale aux impulsions
de 4.0 kV. Les appareils ou systèmes doivent être évalués conformém-
ent aux exigences de la norme UL 1449 pour les limiteurs de surtension
transitoire certifiés pour le Canada.
- Le dispositif doit être installé dans un environnement de degré de
pollution 2 (ou mieux) et seulement par des gens qualifiés.
- Pour la conformité UL61010: les modèles enfichables doivent être
installés avec des modèles de DIN rail socle Carlo Gavazzi ZPD11,
ZPD11A ou ZPD11XA.
  • Page 1 1
  • Page 2 2

CARLO GAVAZZI PUB03CW24 Guide d'installation

Taper
Guide d'installation
Ce manuel convient également à