Acson SL15C Guide d'installation

Catégorie
Climatiseurs split-system
Taper
Guide d'installation

Ce manuel convient également à

CEILING/FLOOR
EXPOSED CONVERTIBLE
SPLIT TYPE AIR CONDITIONERS
CEILING EXPOSED
INSTALLATION MANUAL
IM-CEE-1004-ACSON
Part No.: R08019025472
1-1
English
OUTLINE AND DIMENSIONS
Indoor Unit (5CEE / CEE Series)
All dimensions are in mm
Outdoor Unit (5SL / SL15C / CR)
928
65
400
230
630
218
1080
All dimensions are in mm/(in)
LKL
N
C
M
(1.2)
30
A
D
O
(0.1)
3
B
(2.6)
65
(3.1)
80
N
F
E
C
G
H
JI
(0.7)
19
Dimension A B C D E F G H I J K L M N O
5SL / SL15C /CR 700 521 250 485 175 36 95 93 86 68 441 130 111 15 18
(27.5) (20.5) (9.8) (19.1) (6.8) (1.4) (3.7) (3.6) (3.3) (2.6) (17.3) (5.1) (4.3) (0.5) (0.7)
1-2
Dimension A B C D E F G H J K L M N P Q R
5SL / SL20C / CR
855
648
328 303 309
630
49 116 75 187 98 392 362 126 603 164
5SL / SL25C / CR
(33.7)
(25.5)
(12.9) (11.9) (12.2)
(24.8)
(1.9) (4.6) (3.0) (7.4) (3.9) (15.4) (14.3) (5.0) (23.7) (6.5)
5SL / SL28C / CR
750 730
(29.5) (28.7)
Outdoor Unit (5SL / SL30C)
All dimensions are in mm/(in)
745.5
25.0
141.0 141.0
20.0448.0
20.0
1030.0
852.0
45.8
62.3
400.0
40.0 40.0320.0
All dimensions are in mm/(in)
A
QP
P
M
N
15.0
15.0
39.0
39.0
R
A
D
C 5.0
E20.0
F
20.0
B
2.5
20.0
K
G
141.0
C5.0
160.0 H
L
64
.
5
J
Outdoor Unit (5SL / SL Series)
1-3
English
! CAUTION
Please take note of the following important points when
installing.
Do not install the unit where leakage of flammable
gas may occur.
If gas leaks and accumulates around the unit, it
may cause fire ignition.
Ensure that drainage piping is connected properly.
If the drainage piping is not connected properly, it
may cause water leakage which will dampen the
furniture.
Do not overcharge the unit.
This unit is factory pre-charged.
Overcharge will cause over-current or damage to
the compressor.
Ensure that the unit’s panel is closed after service or
installation.
Unsecured panels will cause the unit to operate
noisily.
Sharp edges and coil surfaces are potential locations
which may cause injury hazards.
Avoid from being in contact with these places.
Before turning off the power supply, set the remote
controller’s ON/OFF switch to the “OFF” position
to prevent the nuisance tripping of the unit. If this is
not done, the unit’s fans will start turning automatically
when power resumes, posing a hazard to service
personnel or the user.
Do not operate any heating apparatus too close to
the air conditioner unit. This may cause the plastic
panel to melt or deform as a result of the excessive heat.
Ensure the color of wires of the outdoor unit and the
terminal markings are same to the indoors
respectively.
IMPORTANT : DO NOT INSTALL OR USE THE
AIR CONDITIONER UNIT IN A LAUNDRY ROOM.
! WARNING
Installation and maintenance should be performed by
qualified persons who are familiar with local code and
regulation, and experienced with this type of appliance.
All field wiring must be installed in accordance with the
national wiring regulation.
Ensure that the rated voltage of the unit corresponds to
that of the name plate before commencing wiring work
according to the wiring diagram.
The unit must be GROUNDED to prevent possible hazard
due to insulation failure.
All electrical wiring must not touch the refrigerant
piping, or any moving parts of the fan motors.
Confirm that the unit has been switched OFF before
installing or servicing the unit.
Disconnect from the main power supply before servicing
the air conditioner unit.
DO NOT pull out the power cord when the power is ON.
This may cause serious electrical shocks which may result
in fire hazards.
Keep the indoor and outdoor units, power cable and
transmission wiring, at least 1m from TVs and radios, to
prevent distorted pictures and static. {Depending on the
type and source of the electrical waves, static may be heard
even when more than 1m away}.
SAFETY PRECAUTIONS
Disposal requirements
Your air conditioning product is marked with this symbol. This means that electrical and electronic products shall
not be mixed with unsorted household waste.
Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of the refrigerant,
of oil and of other parts must be done by a qualified installer in accordance with relevant local and national legislation.
Air conditioners must be treated at a specialized treatment facility for re-use, recycling and recovery. By ensuring
this product is disposed of correctly, you will help to prevent potential negative consequences for the environment
and human health. Please contact the installer or local authority for more information.
Batteries must be removed from the remote controller and disposed of separately in accordance with relevant local
and national legislation.
NOTICE
This manual provides the procedures of installation to ensure a safe and good standard of operation for the air
conditioner unit.
Special adjustment may be necessary to suit local requirements.
Before using your air conditioner, please read this instruction manual carefully and keep it for future reference.
INSTALLATION MANUAL
1-4
Important information regarding the refrigerant used
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent gases into the atmosphere.
Refrigerant type: R410A R407C
GWP
(1)
value: 1975 1652.5
(1)
GWP = global warming potential
Please fill in with indelible ink,
1 the factory refrigerant charge of the product,
2 the additional refrigerant amount charged in the field and
1 + 2 the total refrigerant charge
on the refrigerant charge label supplied with the product.
The filled out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the service cover).
1 factory refrigerant charge of the product:
see unit name plate
(2)
2 additional refrigerant amount charged in the field
3 total refrigerant charge
4 Contains fluorinated greenhouse gases covered by the Kyoto Protocol
5 outdoor unit
6 refrigerant cylinder and manifold for charging
(
(2)
In case of multiple indoor systems, only 1 label must be adhered*, mentioning the total factory refrigerant charge of all
indoor units connected in the refrigerant system.
Periodical inspections for refrigerant leaks may be required depending on European or local legislation. Please contact your
local dealer for more information.
* on the outdoor unit
OR
IMPORTANT
1-5
English
Figure A
Preliminary Site Survey
Electrical supply and installation shall conform to the
local authority (e.g. National Electrical Board).
Voltage supply fluctuation must not exceed ±10% of the
rated voltage. Electricity supply lines must be
independent of welding transformers which can cause
high supply fluctuation.
Ensure that the installation location is convenient for
wiring and piping.
Standard Mounting
Ensure that the overhead supports are strong enough to hold
the weight of the unit. Position the hanger rods (wall
mounting bracket for floor standing), and check for its
alignment with the unit as shown in Figure A. Also, check
that the hangers are secured and the base of the fan coil unit
is leveled in both horizontal directions, taking into account
the gradient for drainage flow as recommended in Figure B.
INSTALLATION OF THE INDOOR UNIT
1073.0
535.5268.0
485.0 145.0
336.0 134.5
630.0
Figure B
10.0mm
Please ensure that the following steps are taken:
Check the gradient for drainage flow as recommended in Figure B.
Provide clearance for easy servicing and optimal air flow as shown in Figure C.
The indoor unit must be installed such that there is no short circuit of the cool discharge air with the warm
return air.
Do not install the indoor unit where there is direct sunlight shining on the unit. The location should be
suitable for piping and drainage installation. The unit must be a large distance away from the door.
Figure C
Utensils, Furnitures Or Built-
In Architectural Features Must
Not Protrude More Than
250.0mm
Min
300.0mm
Min
500.0mm
Min 250.0mm
Min 400.0mm
Min 250.0mm
Min 250.0mm
Min 1.0m
Ceiling Type
Floor Standing Type
1-6
UNDER CEILING INSTALLATION
Install the Suspension Bolts
1. Install the suspension bolts so that it can support the indoor unit.
2. Adjust distance to ceiling before installation.
3. Refer to the dimension given to install the unit.
Install the Indoor Units
1. Insert the suspension bolts into the fittings of the hanger bracket.
2. Set the nuts and washer on the both side of the metal fittings.
3. Secure it with nuts.
4. Attach the hanger cover (4 pcs) to the units.
Suspension Bolt
Hanger Cover
Hanger Cover
Suspension Bolt
Hanger Rod
28.0
Floor Standing Installation
479.0 Min 547.0
Mounting Bracket
509.0
458.0
Min 301.0
Min 759.0
Rear Piping Hole
Floor
123.0
78.0
40.0
307.4
1-7
English
1. Refer to the dimension as illustrated when installing the mounting bracket.
2. When the rear piping, determine the pipe hose position. Drill the pipe hole at the slight downward slant to the outdoor side.
Mounting Bracket
Wall
Piping and Drain Hose Installation ( Under Ceiling Type)
1. The piping direction can be 2 ways as illustrated.
2. The drain hose is only 1 way.
Rear Piping and Drain Hose Rear Piping Hose
Upper Piping
OR
Hook the unit on the
mounting bracket
Piping and Drain Hose Installation (Floor Standing Type)
Wall
OR
Piping and Drain Hose
Wall
Piping and Drain Hose
How to Install the Drain Hose
1. Remove the two screws and the drain pipe holder.
2. Cut a slit for the drain hose hole.
3. Place the drain hose on the v-shape area and secure it
with drain pipe holder and two screws.
Slit for Drain Hose Hole
Screws
Drain Pipe Holder
1-8
How to Remove Air Inlet Grille
1. Remove the air inlet grille by both hands as the direction
shown.
2. Loosen the screw for fixing the panel arm (3 screw, left,
right and center). Do not remove the screw at this time.
Air Inlet Grille
Axis of the
Front Panel
Rib
Grille Holder (Center)
(Optional)
Screw
Air Inlet
Grille Holder
Grille Holder (Center)
Grille Holder (L/R)
3. Move the air inlet grille upward, and then turn it
backwards. (Do not use too much force).
4. Remove the grille holder (both left and right side). After
that, remove to air intake grille.
5. Remove the grille holder (center) from the panel.
How to Install the Air Filter
(A)
(A)
(B) (B)
Snap in the filter in order to secure it
Install the filter to the panel in the (A)
direction follow by (B) to secure the filter.
To Adjust the Vane Direction
Adjust the vane linkage as the direction shown to get the
required vane direction
Dimension of the fresh air intake hole
70.0
Ø 3.0
70.0
Ø 64.0
1-9
English
INSTALLATION OF FRESH AIR INTAKE
1. Knock out the fresh air intake hole at the top panel
2. Assemble the axial fan, fresh air adapter, filter and dust hose as shown in figure below.
3. Connect the wire to the control box as indicated in the wiring diagram below:
INSTALLATION OF THE OUTDOOR UNIT
The outdoor unit must be installed in such a way, so as to
prevent short circuit of the hot discharged air or obstruction
to the smooth air flow. Please follow the installation
clearance shown in the figure. Select the coolest possible
place where intake air temperature is not greater than the
outside air temperature (maximum 45°C).
Installation Clearance
Return Air
Discharge Air
NOTE : If there is any obstacle higher than 2m, or if there
is any obstruction at the upper part of the unit,
please allow more space than the figure indicated
in the above table.
Dimension A B C D
Minimum Distance
300 1000 300 500
(mm)
Service Access
Return Air
WIRED OR
WIRELESS
REMOTE
CONTROLLER
LCD/WIRELESS
SLM
DC SWG
TWIN
ROOM
ID
OD
TRANSFORMER
DC.ION
HIGH MED
LOW
WTP
LIVE
COMP.
L
N2 N1
INDOOR COIL SENSOR
RETURN AIR SENSOR
AS
2" DUCT HOSE
ASSY. FRESH AIR ADAPTER
FILTER FRESH AIR INTAKE
TOP PANEL
FA
FA : FRESH AIR
4. The axial fan model are as follow.
a. ebm axial fan. 8556A - pin type.
b. ebm axial fan. 8556N - wire type.
Obstacle
Obstacle
Obstacle
Obstacle
1-10
REFRIGERANT PIPING
5CE/ 5CE/ 5CE/ 5CE/
Model CE15E CE20E CE25E CE28E
/ER /ER /ER /ER
Maximum Length m 15 15 15 15
Maximum Elevation m 888 8
Maximum Number of Bends
10 10 10 10
Therefore, always select the shortest path for the piping system
and follow the recommendations as tabulated in the table.
Maximum Pipe Length And Maximum Number Of
Bends
If the pipe length is too long, both the capacity and the
reliability of the unit will decrease. As the number of bends
increases, resistance of the piping system to the refrigerant flow
increases and thus lowering the capacity, as a result the
compressor may become defective. See Figure O and
Figure P.
Indoor Unit
Figure O
Figure P
Piping Length
Indoor Unit
Max. Elevation Height
Elevation
Outdoor Unit
Maximum
Piping 20m
20.0 m
Outdoor Unit
Remove Burr
Copper Tube
Swaging Block
Ø Tube, D A (mm)
Inch mm Imperial Rigid
1/4" 6.35 1.3 0.7
3/8" 9.52 1.6 1.0
1/2" 12.70 1.9 1.3
5/8" 15.88 2.2 1.7
3/4" 19.05 2.5 2.0
Cutting Copper Tube
Piping Connection To The Units
Align the center of the piping and tighten the flare nut
sufficiently with fingers.
Finally, tighten the flare nut with the torque wrench
until the wrench clicks.
Pipe Size (mm/in) Torque (Nm)
6.35 (1/4) 18
9.53 (3/8) 42
12.7 (1/2) 55
15.88 (5/8) 65
19.05 (3/4) 78
If any brazing work is required, ensure that the nitrogen gas
is passed through coil and joints while the brazing work is
being done. This will eliminate soot formation on the inside
walls of the copper tubings.
Cut the connection pipe with a pipe cutter.
Remove burrs from cut edges of the pipes with remover.
Hold the end of the pipe downwards to prevent metal chips
from entering the pipe.
Insert the flare nuts, mounted on the connection parts of both
the indoor unit and outdoor unit onto the copper pipes.
Flare the pipe with extra length above the flaring tool as
shown in the table.
The flared edge must be even and not cracked or scratched.
1/4t
Piping Works
Do not use contaminated or damaged copper tubing. Do not remove plastic, rubber plugs and brass nuts from the valves,
fittings, tubings and coils until you are ready to connect suction or liquid line into valves or fittings.
Spanar
Torque Wrench
Indoor Piping
Flare Nut
Flared TubeFlare Joint
1-11
English
ELECTRICAL WIRING CONNECTION
Electrical Wiring Connection For 5CE / CE 15/20/25/28E Vs 5SL /SL 15/20/25/28/30C
Model
Indoor 5CE/CE15/20ER 5CE/CE25ER 5CE/CE28ER
Outdoor 5SL/SL15/20CR 5SL/SL25CR 5SL/SL28/30CR
Voltage Range**
220V – 240V /1Ph /50Hz +
!
or 208V – 230V /1Ph /60Hz +
!
Power Supply Cable Size mm
2
2.5 2.5 4.0
Number Of Conductors* 333
Interconnection Cable Size mm
2
2.5 2.5 1.5
Number Of Conductors* 557
Recommended Fuse* A 16 20 25
Electrical Wiring Connection For 5CE / CE15/20/25/28ER Vs 5SL / SL15/20/25/28/30CR
The electrical power supply must be provided
with protection devices (circuit breaker or
fuse) with all pole separation system,
minimum contact gap of 3mm.
Terminal Strip
Indoor Unit
Interconnection Cable
Terminal Strip
Outdoor Unit
Model
Indoor 5CE/CE15/20E 5CE/CE25E 5CE/CE28E
Outdoor 5SL/SL15/20C 5SL/SL25C 5SL/SL28/30C
Voltage Range** 220V – 240V /1Ph /50Hz +
!
or 208V – 230V /1Ph /60Hz +
!
Power Supply Cable Size mm
2
2.5 2.5 4.0
Number Of Conductors* 33 3
Interconnection Cable Size mm
2
2.5 2.5 2.5
Number Of Conductors* 33 3
Recommended Fuse* A 16 20 25
5CE/CE15E Vs 5SL/SL15C
5CE/CE20E Vs 5SL/SL20C
5CE/CE25E Vs 5SL/SL25C
5CE/CE28E Vs 5SL/SL28C
The electrical power supply must be provided
with protection devices (circuit breaker or
fuse) with all pole separation system,
minimum contact gap of 3mm.
5CE/CE28E Vs 5SL/SL30C
Power Supply Cable
!
!
Terminal Strip
Indoor Unit
Interconnection Cable
Terminal Strip
Outdoor Unit
Power Supply Cable
COMP
L/L1
N/L2
N/L2
COMP
N
COMP
L/L1
N/L2
N/L2
COMP
L
N
L
N
1-12
Terminal Strip
Indoor Unit
Interconnection Cable
Terminal Strip
Outdoor Unit
5CE/CE15ER Vs
5SL/SL15CR
5CE/CE20ER Vs
5SL/SL20CR
5CE/CE25ER Vs
5SL/SL25CR
Power Supply Cable
Outdoor Coil Sensor
The electrical power supply must be
provided with protection devices (circuit
breaker or fuse) with all pole separation
system, minimum contact gap of 3mm.
!
Terminal Strip
Indoor Unit
Interconnection Cable
Terminal Strip
Outdoor Unit
5CE/CE28ER Vs
5SL/SL28CR
Power Supply Cable
Outdoor Coil Sensor
Terminal Strip
Indoor Unit
Interconnection Cable
Terminal Strip
Outdoor Unit
5CE/CE28CR Vs
5SL/SL30CR
Power Supply Cable
Outdoor Coil Sensor
The electrical power supply must
be provided with protection
devices (circuit breaker or fuse)
with all pole separation system,
minimum contact gap of 3mm.
!
4WV
OF
COMP
L/L1
4WV
OF
COMP
N
N/L2
N/L2
COMP
L/L1
N/L2
N/L2
A
4WV
OF
E
E
A
4WV
OF
COMP
L
N
L
N
COMP
L/L1
N/L2
N/L2
A
4WV
OF
E
E
4WV
OF
COMP
N
The electrical power supply must be
provided with protection devices
(circuit breaker or fuse) with all pole
separation system, minimum contact
gap of 3mm.
!
1-13
English
VACUUMING AND CHARGING
Purging The Piping And The Indoor Unit
Except for the outdoor unit which is pre-charged with
refrigerant, the indoor unit and the refrigerant
connection pipes must be air-purged because the
aircontaining moisture that remains in the refrigerant cycle
may cause malfunction of the compressor.
Remove the caps from the valve and the service port.
Connect the center of the charging gauge to the vacuum
pump.
Connect the charging gauge to the service port of the
3-way valve.
Start the vacuum pump. Evacuate for approximately 30
minutes. The evacuation time varies with different
vacuum pump capacity. Confirm that the charging gauge
needle has moved towards -76mmHg (0~76mmHg).
Caution
If the gauge needle does not move to 0~76mmHg,
be sure to check for gas leaks (using the refrigerant
detector) at flare type connection of the indoor and
outdoor unit and repair the leak before proceeding
to the next step.
Close the valve of the changing gauge and stop the
vacuum pump.
On the outdoor unit, open the suction valve (3 way) and
liquid valve (2 way) (in anti-clockwise direction) with
4mm key for hexagon sacked screw.
Additional Charge
The refrigerant is pre-charged in the outdoor unit. If the piping
length is less than 7.6m, then additional charge after
vacuuming is not necessary. If the piping length is more than
7.6m, then use the additional charge valve as indicated in the
table below.
Cooling Only (R410A)
Heat Pump (R22)
Heat Pump (R410A)
Indoor CE15/20E CE25E CE28E
Outdoor SL15/20C SL25C SL28 C SL30C
Additional
16 39 39
Charge [g/m]
Indoor 5CE15E 5CE20E 5CE25E 5CE28E
Outdoor 5SL15C 5SL20C 5SL25C 5SL28C 5SL30C
Additional
91010 24
Charge [g/m]
Indoor CE15ER CE20ER CE25ER CE28ER
Outdoor SL15CR SL20CR SL25CR SL28CR SL30CR
Additional
24 22 22 56
Charge
[g/m]
Indoor 5CE15/20ER 5CE25ER 5CE28ER
Outdoor 5SL15/20CR 5SL25CR 5SL28CR 5SL30CR
Additional
16 10 38
Charge
[g/m]
Cooling Only (R22)
Liquid Side
Indoor Unit
Outdoor Unit
Gas Side
Low
Hi
Vacuum
Pump
Open
Close
Close
Close
Discharge Valve
Suction Valve
Service Port
Outdoor Unit
3 Ways Valve
Flare Nut
Refrigerant Piping
Allen Key
E.g. CE20E & SL20C with 15m piping length, additional piping
length is 7.4m. Thus,
Additional Charge = 7.4[m] x 16[g/m]
= 118.4[g]
1-14
STANDARD OPERATING CONDITIONS
SERVICE AND MAINTENANCE
Service Parts
Indoor Air Filter
Indoor Unit
Maintenance Procedures
1. Remove any dust adhering to the filter by using a vacuum cleaner or
wash in lukewarm water (below 40°C) with a neutral cleaning detergent.
2. Rinse the filter well and dry before placing it back onto the unit.
3. Do not use gasoline, volatile substances or chemicals to clean the filter.
1. Clean any dirt or dust on the grille or panel by wiping it with a soft
cloth soaked in lukewarm water (below 40°C) and a neutral detergent
solution.
2. Do not use gasoline, volatile substances or chemicals to clean the
indoor unit.
Period
At least once
every 2 weeks.
More frequently if
necessary.
At least once
every 2 weeks.
More frequently if
necessary.
Charge Operation
This operation must be done by using a gas cylinder and a
precise weighing machine. The additional charge is
topped-up into the outdoor unit using the suction valve via
the service port.
Remove the service port cap.
Connect the low pressure side of the charging gauge to
the suction service port center of the cylinder tank and
close the high pressure side of the gauge. Purge the air
from the service hose.
Start the air conditioner unit.
Open the gas cylinder and low pressure charging valve.
When the required refrigerant quantity is pumped into
the unit, close the low pressure side and the gas cylinder
valve.
Disconnect the service hose from service port. Put back
the service port cap.
Suction Valve
Discharge Valve
Liquid Side
Indoor Unit
Outdoor Unit
Gas Side
Low
Hi
Open
Close
Open
Open
Check
Valve
Heat Pump Unit
Cooling unit
Temperature Ts °C / °F Th °C / °F
Minimum indoor
19.4 / 66.9 13.9 / 57.0
temperature
Maximum indoor
26.7 / 80.1 19.4 / 66.9
temperature
Minimum outdoor
19.4 / 66.9 13.9 / 57.0
temperature
Maximum outdoor
46 / 114.8 24 / 75.2
temperature
Temperature Ts °C / °F Th °C / °F
Minimum indoor
10 / 50 -
temperature
Maximum indoor
26.7 / 80.1 -
temperature
Minimum outdoor
-8 / 17.6 -9 / 15.8
temperature
Maximum outdoor
24 / 75.2 18 / 64.4
temperature
Ts: Dry bulb temperature.
Th: Wet bulb temperature.
1-15
English
If any malfunction of the air conditioner unit is noted, immediately switch off the power supply to the unit.
Check the following fault conditions and causes for some simple trouble shooting tips.
TROUBLESHOOTING
Causes / Action
- Protection against frequent starting. Wait for 3 to 4 minutes for
the compressor to start operating.
- Power failure, or the fuse needs to be replaced.
- The power plug is disconnected.
- It is possible that your delay timer has been set incorrectly.
- If the fault persist after all these verifications, please
contact the air conditioner unit installer.
- The air filter is dirty.
- The doors or windows are open.
- The air suction and discharge are clogged.
- The regulated temperature is not high enough.
- Odors may be caused by cigarettes, smoke particles, perfume
etc. which might have adhered onto the coil.
- This is caused by air humidity after an extended long period of
operation.
- The set temperature is too low, increase the temperature setting
and operate the unit at high fan speed.
- Switch off unit and call dealer.
- Refrigerant fluid flowing into the evaporator coil.
Fault
1. The compressor does not operate 3 minutes after the air
conditioner unit is started.
2. The air conditioner unit does not operate.
3. The air flow is too low.
4. Discharge air flow has bad odor.
5. Condensation on the front air grille of the indoor unit.
6. Water flowing out from the air conditioner unit.
7. Hissing air flow sound from the air conditioner unit during
operation.
If the fault persists, please call your local dealer / serviceman.
No Event CDF LED Timer LED Others LEDs Error Code
1 Room sensor open or short Blink 1 time - Blink Fan Blink E1
2 Indoor coil sensor open Blink 2 times - Blink Sleep Blink E2
3 Outdoor coil sensor open Blink 3 times - Blink Dry Blink E3
4 Compressor overload/
Indoor coil sensor short/ Blink 1 time Blink Cool Blink E4
Outdoor coil sensor short
5 Gas leak Blink 3 times Blink Cool & Dry Blink E5
6 Water pump fault Blink 2 times Blink Cool & Fan Blink E6
7 Outdoor defrost - Blink Heat -
8 Outdoor coil sensor exist Blink 5 times Blink Cool & Heat Blink E7
(MS model)
9 Hardware error (tact switch Blink 6 times Blink Heat, Cool, Blink E8
pin short) follow by Fan, Dry
Note: CDF LED : Cool/Dry/Fan LED, turns on in these modes
The unit will not detect sensor missing when the compressor is ON
1-16
MEMO
2-1
Français
CONTOUR ET DIMENSIONS
Unité Intérieure (Série 5CEE / CEE)
Toutes les dimensions sont données en mm
928
65
400
230
630
218
1080
Unité Extérieure (5SL / SL15C / CR)
LKL
N
C
M
(1,2)
30
A
D
O
(0,1)
3
B
(2,6)
65
(3,1)
80
N
F
E
C
G
H
JI
(0,7)
19
Dimension A B C D E F G H I J K L M N O
5SL / SL15C /CR 700 521 250 485 175 36 95 93 86 68 441 130 111 15 18
(27,5) (20,5) (9,8) (19,1) (6,8) (1,4) (3,7) (3,6) (3,3) (2,6) (17,3) (5,1) (4,3) (0,5) (0,7)
Toutes les dimensions sont
données en mm / (pouces)
2-2
Unité Extérieure (Série 5SL / SL)
Toutes les dimensions sont
données en mm / (pouces)
A
QP
P
M
N
15,0
15,0
39,0
39,0
R
A
D
C 5,0
E20,0
F
20,0
B
2,5
20,0
K
G
141,0
C5,0
160,0 H
L
64,5
J
Unité Extérieure (5SL / SL30C)
Toutes les dimensions sont
données en mm / (pouces)
745,5
25,0
141,0 141,0
20,0448,0
20,0
1030,0
852,0
45,8
62,3
400,0
40,0 40,0320,0
Dimension A B C D E F G H J K L M N P Q R
5SL / SL20C / CR
855
648
328 303 309
630
49 116 75 187 98 392 362 126 603 164
5SL / SL25C / CR
(33,7)
(25,5)
(12,9) (11,9) (12,2)
(24,8)
(1,9) (4,6) (3,0) (7,4) (3,9) (15,4) (14,3) (5,0) (23,7) (6,5)
5SL / SL28C / CR
750 730
(29,5) (28,7)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120

Acson SL15C Guide d'installation

Catégorie
Climatiseurs split-system
Taper
Guide d'installation
Ce manuel convient également à