HOMCOM 823-041V80BK Mode d'emploi

Catégorie
Climatiseurs mobiles
Taper
Mode d'emploi

Ce manuel convient également à

1
IN221100360V01_US_CA
823-041V80_823-041V81
PORTABLE AIR CONDITIONER
USER MANUAL
IMPORTANT, RETAIN FOR FUTURE REFERENCE: READ CAREFULLY
EN
2
Contents
AIR CONDITIONER SAFETY ....................................................................3
PARTS AND FEATURES ...........................................................................7
INSTALLATION REQUIREMENTS.............................................................8
INSTALLATION INSTRUCTIONS...............................................................9
STEP 1 - UNPACK AIR CONDITIONER...............................................9
STEP 2 - TWIST THE EXHAUST HOSE CONNECTOR ONTO
EXHAUS...........................................................................................10
STEP 3 - CONNECT EXHAUST HOSE TO THE AIR
CONDITIONER.................................................................................10
STEP 4 - INSTALL WINDOW PANELS...............................................10
STEP 5 - COMPLETE INSTALLATION................................................11
CONTROL PANEL ...................................................................................12
BUTTONS ........................................................................................13
REMOTE CONTROL.........................................................................14
SAFETY PROTECTIONS.........................................................................14
AIR CONDITIONER USE.........................................................................15
DRAIN THE INTERNAL WATER ..............................................................15
MANUAL DRAINAGE ........................................................................15
CONTINUOUS DRAINAGE ...............................................................16
CARE AND MAINTENANCE.....................................................................16
SURFACE CLEANING ......................................................................16
FILTER CLEANING ..........................................................................16
INTERNAL WATER TANK .................................................................17
STORAGE.........................................................................................17
TROUBLESHOOTING.............................................................................18
3
The safety of you and others is very important.
We have provided many important safety messages in this manual and on your
appliance. Always read and follow all instructions.
This is the safety alert symbol, which warns about potential hazards,
which could injure or kill you and others. All safety messages will follow
this symbol, along with the words 'DANGER', 'WARNING' or 'CAUTION'.
The words mean:
An imminently hazardous situation. You could be
seriously injured or killed if you do not
immediately follow instructions.
A potentially hazardous situation which, if not
avoided, could result in serious injury or death.
A potentially hazardous situation which, if not
avoided, may result in moderate or minor injury
All messages will explain what the hazard is, how to reduce the risk of injury and the
consequences if instructions are not properly followed.
IMPORTANT SAFETY INSTRUCTIONS
WARNING: To reduce the risk of fire, electrical shock, injury to persons or damage when
using the air conditioner, follow basic precautions, including the following:
Appliance shall be stored in a well-ventilated area, where the room size is no less than
2
4 m .
● Read all of the instructions before using this appliance.
● Plug into a grounded three prong outlet.
● Do not remove ground prong.
● Do not use an adapter.
● Do not use an extension cord.
● Do not operate the air conditioner if it has a damaged cord or plug, if it is not working
properly or if it has been damaged or dropped.
● The air conditioner should be serviced only by qualied service personnel. Call an
authorised service company for examination, repair or adjustment.
● Disconnect power before servicing and cleaning.
AIR CONDITIONER SAFETY
4
● NOTE: Switching off the appliance via the power button does NOT disconnect the
appliance from the power supply.
● Do not install or use the air conditioner in any area where the atmosphere contains
combustible gases or where the atmosphere is contaminated. Avoid any chemicals
coming in to contact with your air conditioner.
● Do not store anything directly on top of the air conditioner.
● Under guided supervision, this appliance can be used by children aged eight years and
above, provided they understand the potential risks and hazards. Under guided
supervision, this appliance can be used by persons with disabilities or persons without
experience, provided they understand the potential risks and hazards.
● This appliance is not intended for people (including children) with reduced physical,
sensory or mental capabilities, or lack of experience and knowledge, unless they have
been given supervision or instruction concerning use of the appliance by a person
responsible for their safety. Children should be supervised to ensure that they do not
play with the appliance.
● Use two or more people to move and install this air conditioner.
● Never operate the air conditioner without the filters in place.
● Do not use the air conditioner near a bathtub, shower, wash basin or other wet area.
● Do not use means to accelerate the defrosting process or to clean, unless
recommended by the manufacturer.
● Keep the appliance away from ignition sources, such as open flames, an operating gas
appliance or electric heater. Do not pierce or burn.
● Be aware that refrigerants may not contain an odour. -The maximum refrigerant charge
amount: NPLA1-05C/X1E-6.7Oz, NPLA1-06C/X1E-8.3Oz.
● Store the appliance in a place where mechanical damage is prevented.
Any person who is involved with working on or breaking into a refrigerant circuit, should
hold a current valid certicate from an industry-accredited assessment authority, which
authorises their competence to handle refrigerants safely in accordance with an
industry recognised assessment specification. Servicing shall only be performed as
recommended by the manufacturer. Maintenance and repair, requiring the assistance
of other skilled personnel, shall be carried out under the supervision of the person
competent in the use of flammable refrigerants.
● Prior to beginning work on systems containing flammable refrigerants, safety checks
are necessary to ensure the risk of ignition is minimal. Work shall be undertaken under
a controlled procedure to minimise the risk of a flammable gas or vapour being present
while the work is being performed. All maintenance staff and others working in the local
area shall be instructed on the nature of work being carried out. Avoid working in
confined spaces. The area around the workspace shall be sectioned o. Ensure the
area is safe by controlling flammable material.
● Check the area with an appropriate refrigerant detector before and during work, so you
can be made aware of potential flammable atmospheres. Ensure the leak detection
equipment being used is suitable for use with flammable refrigerants (no sparking,
adequately sealed and properly safe).
● If hot work is conducted on the refrigeration equipment or associated parts, fire
extinguishing equipment must be nearby. Have a dry power or CO² fire extinguisher
next to the charging area.
● If working on the refrigeration system requires exposing pipes that contain flammable
refrigerants, you must not use sources of ignition – this is a fire or explosion hazard.
Keep all ignition sources, including cigarettes, far away from the site of installation,
repairing and disposal – flammable refrigerants could be released into the surrounding
area.
● Before work taking place, check the surrounding area, ensuring there are no flammable
hazards or ignition risks. 'No Smoking' signs must be displayed.
● Before breaking into the system or conducting any hot work, the area must be open or
well ventilated, so any released refrigerants can be safely released into the
atmosphere.
5
● Do not apply any permanent inductive or capacitance loads to the circuit without
ensuring that it will not exceed the permissible voltage and current of the equipment.
Intrinsically safe components are the only types that can be worked on in a flammable
atmosphere. The test apparatus must be the correct rating. Replace components only
with parts specied by the manufacturer. Parts, not specified by the manufacturer, may
ignite the refrigerant, causing a fire or explosion hazard.
● Check that cabling is not subject to wear, corrosion, excessive pressure, vibration, sharp
edges or any other adverse environmental eects. Also check for ageing or continual
vibration from sources, such as compressors and fans.
● Never use sources of ignition when searching for refrigerant leaks, such as halide
torches or any other naked flames.
● Electronic leak detectors can be used to detect flammable refrigerants however, the
sensitivity may not be adequate or may need recalibration (detection equipment must be
calibrated in a refrigerant-free area). Ensure the detector is not a potential source of
ignition and is suitable for the refrigerant used. Set the leak detection equipment at a
percentage of the LFL of the refrigerant – it must be calibrated to the right refrigerant
and the appropriate percentage of gas (25% maximum) is conrmed.
● Leak detection fluids are suitable for use with most refrigerants however, the use of
detergents containing chlorine must be avoided - the chlorine may react with the
refrigerant and corrode the copper. If a leak is suspected, all naked flames must be
extinguished. If a leakage is found that requires brazing, all of the refrigerant shall be
recovered from the system or isolated (by shutting off valves). Oxygen free nitrogen
(OFN) shall be purged through the system both before and during the brazing process.
● When breaking into the refrigerant circuit to make repairs – or for any other purpose –
conventional procedures shall be used. However, it is important that best practice is
followed since flammability is a consideration. This procedure must be followed:
- Remove refrigerant.
- Purge the circuit with inert gas.
- Evacuate.
- Purge again with inert gas.
- Open the circuit by cutting or brazing.
● The refrigerant charge shall be recovered into the correct recovery cylinders. The
system shall be 'ushed' with OFN to render the unit safe. This process may need to be
repeated several times. Compressed air or oxygen shall not be used for this task.
Flushing shall be achieved by breaking the vacuum in the system with OFN and
continuing to fill until the working pressure is achieved, then venting into the
atmosphere, and finally pulling down to a vacuum. This process shall be repeated until
no refrigerant is within the system. When the final OFN charge is used, the system shall
be vented down to atmospheric pressure to enable work to take place. This operation is
absolutely vital if brazing operations on the pipe-work are to take place. Ensure the
outlet for the vacuum pump is not close to any ignition sources and there is proper
ventilation.
● In addition to conventional charging procedures, the following requirements shall be
followed. – Ensure that contamination of different refrigerants does not occur when
using charging equipment. Hoses or lines shall be as short as possible to minimise the
amount of refrigerant contained in them.
– Cylinders shall be kept upright.
– Ensure the refrigeration system is earthed prior to charging the system with refrigerant.
– Label the system when charging is complete (if not done already).
– Take extreme care, ensuring you do not overll the refrigeration system.
● Before recharging the system, pressure test it with OFN. Conduct a leak test when
charging is complete - do this before commissioning. Before leaving the site, conduct a
follow up leak test.
6
● Before carrying out this procedure, it is essential that the technician is completely
familiar with the equipment and all its detail. It is recommended that all refrigerants are
recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall
be taken in case analysis is required prior to reuse of reclaimed refrigerant. Before
doing this task, take an oil and refrigerant sample, so it can be analyzed before reuse of
reclaimed refrigerant. It is essential that electrical power is available before the task is
commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure ensure that:
- Mechanical handling equipment is available, if required, for handling refrigerant
cylinders.
- All personal protective equipment is available and is being used correctly.
- The recovery process is supervised at all times by a competent person.
- Recovery equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold, so the refrigerant can be removed from
various parts of the system.
f) Make sure the cylinder is situated on the scales before recovery takes place.
g) Start the recovery machine and operate in accordance with the manufacturer's
instructions.
h) Do not overll cylinders (no more than 80 % of volume liquid ).
i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
j) When the cylinders have been filled correctly and the process completed, make sure the
cylinders and the equipment are removed from site promptly and all isolation valves on
the equipment are closed o.
k) Recovered refrigerants shall not be charged into another refrigeration system, unless it
has been cleaned and checked.
● Label all equipment, stating that it has been decommissioned and emptied of refrigerant
– ensure it is dated and signed. There must also be a label stating it contains a
ammable refrigerant.
● When removing refrigerants from a system, either for servicing or decommissioning,
ensure it is done safely. When transferring the refrigerant into cylinders, ensure that
only appropriate refrigerant recovery cylinders are employed. Ensure the correct
number of cylinders for holding the total system charge are available. All cylinders to be
used, are designated for the recovered refrigerant and labelled for that refrigerant (i.e.
special cylinders for the recovery of refrigerant). Cylinders shall be complete with
pressure relief valve and associated shut off valves. Remove empty cylinders and, if
possible, wait for them to cool before recovery. The recovery equipment shall be in
good working condition with a set of instructions concerning the equipment - it must be
suitable for the recovery of flammable refrigerants. In addition, a set of calibrated
weighing scales shall be available and in good working condition. Hoses shall be
complete with leak-free disconnect couplings and in good condition. Before using the
recovery machine, ensure it is properly working, has been properly maintained and that
any associated electrical components are sealed to prevent ignition in the event of a
refrigerant release. Consult manufacturer if in doubt. The recovered refrigerant must be
returned to the supplier in the correct recovery cylinder, and the relevant Waste
Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in
cylinders. If compressors or compressor oils need removing, ensure they have been
evacuated to an acceptable level, so flammable refrigerants do not remain within the
lubricant. The evacuation process shall be carried out prior to returning the compressor
to the suppliers. Only electric heating to the compressor body shall be employed to
accelerate this process. When oil is drained from a system, it shall be carried out safely.
READ AND SAVE THESE INSTRUCTIONS
7
1. Control panel
2. Air outlet
3. Caster
4. Air intake
5. Filter
6. Fastener
7. Air intake
8. Handle
9. Plug storage area
10. Power cord cover
11. Drain port
12. Power supply
13. Drain cover and plug
14. Remote control
15. Connector
16. Exhaust hose
17. Adapter
18. Window kits
19. Window kits screw (buttery nut)
PARTS AND FEATURES
8
INSTALLATION REQUIREMENTS
LOCATION REQUIREMENTS
Place the air conditioner on a flat, level surface in a location that is at least 50cm from all
walls.
NOTE: Ensure there is at least 50cm of space between the air conditioner and wall,
making sure there is proper airow.
Keep the air conditioner free of any obstructions such as drapes, curtains, blinds, etc.
The exhaust hose should be free of any obstructions.
Do not place the air conditioner on an unstable or raised surface - it could fall and cause
damage or injury.
Do not place the air conditioner in direct sunlight or near heat sources such as baseboard
heaters, stoves, etc.
The window panel can be installed in a window with an opening between 50-102cm.
9
ELECTRICAL REQUIREMENTS
!WARNING
Electrical Shock Hazard
Plug into a grounded three prong outlet.
Do not remove the ground prong from the power cord plug.
Do not use an adapter.
Do not use an extension cord.
Failure to do so can result in death, fire or electrical shock.
POWER SUPPLY CORD
Wiring Requirements
● 115 Volt, 60Hz, 15-amp fused grounded three prong outlet
● Using a time-delay fuse or time-delay circuit breaker is recommended.
● Use a dedicated circuit only.
NOTE: Do not operate any other electrical appliances on this circuit or you may trip the
circuit breaker/fuse.
If the power cord is damaged, do not use - contact customer service for a replacement.
To test the power supply cord before operation:
1. Plug the power cord into a grounded three prong outlet.
2. Press the 'Test' button, then press and release the 'Reset' button to restore power.
REQUIRED GROUNDING METHOD
This air conditioner must be grounded.
The air conditioner is equipped with a power supply cord
that has a three prong grounding plug.
The power supply cord must be plugged into a mating,
grounded three prong outlet, in accordance with all local
codes and ordinances.
INSTALLATION INSTRUCTIONS
!WARNING
Excessive Weight Hazard
Use two or more people to move and install air conditioner.
Failure to do so can result in back or other injury
STEP 1 - UNPACK AIR CONDITIONER
10
STEP 3 - CONNECT EXHAUST HOSE TO THE AIR CONDITIONER
IMPORTANT: When connecting the hose, the air conditioner must be close enough to the
window, so you will not dislodge the window seal plate. Once the hose is connected, move
the air conditioner 20” (51 cm) from the wall.
A. Slide the exhaust hose assembly from the outer air outlet to the right.
B. The assembly is completed when the convex point of the inner joint and the concave
point of the air outlet are stuck.
STEP 4 - INSTALL WINDOW PANELS
Depending on the size of your window opening, use the main panel and one or both of the
extension panels.
A. Open the window and place the main window panel there.
NOTE: The window assembly is designed to accommodate either a vertical or horizontal
slide window.
Vertical Slide Window Horizontal Slide Window
Remove packaging materials. Save the carton and the foam packaging for storing the
air conditioner when not in use. NOTE: There are NO packing materials inside the air
conditioner to remove - do not open the cabinet.
Properly dispose of/recycle all packing material.
Handle the air conditioner gently.
Keep the air conditioner upright and level. Do not set the air conditioner on its side,
front, back or upside down.
11
B. Take out the buttery nut from the bag, then disassemble the screws in the following
direction.
C. Lock the buttery nut on panel A, but not too tight - keep a space of 2.5mm.
D. Connect with panel B, then adjust the panel(s) to the width or height of the window as
shown.
E. Fasten the buttery nut to fix the window slide set.
STEP 5 - COMPLETE INSTALLATION
Close the window as far as the window slide set, so this covers the window opening
completely. Place the device at least 50 cm away from walls and other objects.
F. Lock the two screws as shown below.
12
NOTE:
Some window installations may require the extension panels to be trimmed.
Slide the adapter downwards and assure the adapter installed is in a good position.
Check the slant panel direction matches the seal-plate direction.
Do not bend the exhaust hose more than 45° to keep good ventilation.
!WARNING
Electrical Shock Hazard
Plug into a grounded three prong outlet.
Do not remove the ground prong from the power cord plug.
Do not use an adapter.
Do not use an extension cord.
Failure to do so can result in death, fire or electrical shock.
CONTROL PANEL
1. Plug the power cord into a grounded three prong outlet.
2. Press the 'Reset' button on the power cord to ensure the safety plug is providing
power to the air conditioner.
DRY
13
BUTTONS
A. TIMER BUTTON
Set a time (1-24-hours) for the air conditioner to turn on or o. When a 'Time Delay' is
programmed, the timer indicator light will illuminate.
While the air conditioner is operating:
1. Press the 'Timer' button.
2. Press the 'Up/Down' arrow to select the number of hours you want the air conditioner to
work before turning o.
While the air conditioner is o:
1. Press the 'Timer' button.
2. Press the 'Up/Down' arrow to select the number of hours you want the air conditioner to
work before turning o.
NOTE: Wait approximately five seconds for the settings to save.
To cancel the timer:
● Press the 'Timer' button once, the hours remaining will flash, then press the timer button
again and the timer will be canceled.
B. FAN SPEED BUTTON
When the air conditioner is in use, the fan can be adjusted from low to high.
NOTE: The fan speed cannot be adjusted when the unit is in 'Dry' mode.
● Press the 'Fan Speed button' to switch speeds. The fan speed indicator will illuminate.
C. UP AND DOWN ARROW BUTTONS
Adjusts the temperature or hours in 'Time Delay'.
To Set the Temperature:
The temperature can be set between 62-86º F (17-30º C) when the air conditioner is in
'Cool' mode.
1. Press the 'Mode' button until the 'Cool' mode is selected.
2. Press the up or down arrow to select a temperature.
NOTE: The temperature cannot be set when in 'Fan' or 'Dry' mode.
NOTE: Press the up and down arrows at the same time to choose between ºC or ºF being
displayed.
D. CONTROL PANEL DISPLAY
Displays the set temperature in degrees Fahrenheit or degrees Celsius, or the hours
remaining in a time delay.
E. MODE BUTTON
Press the 'Mode' button to change modes. The corresponding indicator will illuminate:
Cool – Cools the room to the set temperature
Dry – Reduces the humidity in the room
Fan – Circulates the air in the room without cooling
F. POWER BUTTON
Turn the air conditioner on/o.
NOTE: Pressing the power button does NOT disconnect the appliance from the power
supply.
G. SLEEP MODE BUTTONS
Select 'Sleep' mode by pressing the 'Timer' and the 'Down' arrow at the same time.
14
REMOTE CONTROL
1) Power on and o: When the unit is plugged in, press the 'P' button to
turn on the unit. Press again to turn the unit o.
2) Mode Selection: Press the Cool, Dry or Fan mode.
3) Fan Speed: Press the High or Low button to adjust the fan speed.
When the unit is in Dehumidier mode, the fan speed cannot be
changed.
4) Temperature Setting: When the unit is in cool mode, you can select
your desired temperature. Press the ▲ or ▼ to select your desired
temperature setting.
5) SLEEP MODE: When in air conditioning mode, press the SLEEP
Button on the remote control.
6) TIMER
Auto-On: Press the TIMER button when the unit is off to set up the
Auto-on timer. Press the ▲ or ▼ to set timer within 1-24 hours.
Auto-O: Press the TIMER button when the unit is On to set up the
Auto-off timer. Press the ▲ or ▼ to set timer within 1-24 hours. To
cancel the timer, press the TIMER button until it is turned o.
7) ºC/ ºF
Press this button to switch temperature unit.
NOTE:
● Insert the two AAA batteries.
● Do not use rechargeable batteries.
● When replacing the battery, replace the two batteries at
the same time. Do not mix old and new batteries.
● If you do not use this unit for a long time, please take out
the battery of the remote control and store it properly.
WARNING
● If the battery liquid of the remote control leaks on your skin or clothes, please rinse with
plenty of water as soon as possible; if you find a leak, please do not use the remote
control.
● If you swallow the battery liquid, rinse your mouth and seek medical attention as soon
as possible. The chemical substances in the battery may burn or cause other health
hazards.
1. Water full safety alarm and shut off protection function
When the water volume exceeds its alarm level in chassis, the 'water full' icon will light.
You need to drain the water and restart the unit. For more information about how to drain,
refer to the 'Drainage' instructions. If the unit is not shut down manually, it will go to its
original operating status automatically once the water is fully drained. Or connect the
power to restart the unit again.
SAFETY PROTECTIONS
15
2. Anti-frozen protection function (Optional)
When the ambient temperature Tr22ºC and the compressor runs continuously for 50
minutes, the compressor will stop running - the fan will be forced to run at high speed. The
fan speed indicator on the display board can be switched. After five minutes, the air
conditioner resumes normal operation.
3. Delay protection function of compressor
The unit oers restart protection for the compressor - it may start immediately when the
unit is on for the first time. There is a three minute delay to the restart protection after
compressor is shut down.
4. Coil and room temperature sensor failure:
1) Detect sensor failure at the beginning of turning on/off the unit.
2) When a sensor failure is detected at the beginning of turning the unit on, it will
immediately enter the failure state. If it returns to normal at this time, it will enter the
standby state.
AIR CONDITIONER USE
IMPORTANT: If the air conditioner has been tilted on its side, wait 24 hours before turning
on the air conditioner to allow the oil to return to the compressor. This will prevent it from
failing prematurely.
Hold handles on side panels to move the unit in upright position.
NOTE:
● Do not hold the louver.
● Ensure the unit is upright when handling or moving.
● Before moving or handling, drain the water in the unit completely to prevent a leakage.
DRAIN THE INTERNAL WATER
You will need a small pan to catch the water coming out of the tank. Once the tank is
empty, the unit will resume operation within a few minutes.
MANUAL DRAINAGE
1. When the water is full and the unit shuts down, turn off and unplug the unit.
2. Put the tray below the water outlet at the back of the unit.
3. Screw off the drain cover and unplug the stopper, so water can flow into the tray.
4. Plug in stopper and screw the drain cover tightly onto water outlet after drainage.
16
Notes:
● Protect the drain cover and water stopper properly.
● Move the unit carefully to avoid leakages.
● Tilt the unit slightly backwards when draining.
● Block the drain hole as soon as possible before the tray is full.
● Water stopper and drain cover must be tightly installed.
CONTINUOUS DRAINAGE
1. Screw off the drain cover and unplug the water stopper.
2. Connect the drain hole with the φ13mm drain hose (if you need the plastic drainage
pipe, please purchase it with an outer diameter of 13mm and length according to the
drainage distance), as deep as possible to avoid a leakage.
3. Pull the drain hose to the bathroom or outdoors.
Notes:
● Drain hose must be installed when there’s no water in
the tray.
● It is not recommended to drain when the unit is in
'COOL' mode, keeping enough water in the unit to
enhance the system cooling eects.
● It is suggested that to adopt continuous drainage when
unit is in 'HEAT' mode to avoid frequent drainage.
● Put the drain hose in an inaccessible place, not higher
than drainage hole and keep drain hose straight.
CARE AND MAINTENANCE
WARNING
Before cleaning and maintenance, turn off and unplug the unit.
SURFACE CLEANING
- Unplug the appliance before cleaning.
- Clean the unit surface with a damp and soft cloth - do not use chemical solvents such as
alcohol and gasoline. Any thinner, alcohol-glazer or other similar solvents is prohibited
for unit cleaning.
- Clean the air outlet or louvers with a damp cloth and detergent. Any chemical solvent is
prohibited to use for unit cleaning. Keep all chemical solvents away from the unit.
FILTER CLEANING
- Clean the filter once every two weeks for normal operation.
- Grip the filter handle and pull it out gently in the correct direction.
Clean the dirty particles in the filter by cleaner if necessary.
Immerse and wash the filter gently with warm water (about 40ºC)
mixed with neutral cleaner, then rinse and dry them thoroughly in
the shade.
17
INTERNAL WATER TANK
The 'Water Full' indicator illuminate when water has exceeded the limit.
To Empty the Internal Water Tank:
1. Turn off and unplug the unit.
2. Place a pan (not included) below the lower drain, which is on the back (near the
bottom) of the air conditioner.
3. Remove the cap and the rubber plug, then drain the water tank.
4. Reinsert the drain plug and screw the cap tightly.
5. Plug in and turn on the unit.
STORAGE
Please store the air conditioner properly if not in use.
1. Screw off the drain cover and pull out the stopper to drain water completely. Or tilt the
unit to drain water.
2. Keep unit running in 'Fan' mode for half a day to dry inside of unit - this will prevent
mould.
3. Turn off the unit, pull out plug and wrap the power cord around the wire-winding pillar,
insert the plug into the universal
xing hole at the back panel of the unit, then install the water stopper and drain cover.
4. Remove the heat exhaust hose to clean properly.
5. Take out the batteries from remote controller and place it in the box.
Note:
Store the unit in a dry location. Keep all accessories safe and together. Keep the unit out
the reach of children.
Note:
- Pull out the filter gently.
- Remove the filter from the back panel first, then remove the filter from the side panel -
this will stop the filters from being twisted or damaged.
- Do not squash or hit the mesh with sharp objects or brushes.
- Do not use the appliance without installing the filter.
18
TROUBLESHOOTING
First try the solutions suggested here to possibly avoid the cost of a service call.
The unit fails to
start up.
Connect the unit to a live
socket and turn it on.
Drain the water.
It is recommended to use this
unit between 5-35ºC.
Change the set temperature.
Power supply failure.
Water in the tank is full.
Ambient temperature too low
or high.
The room temperature is lower
than the set temperature in
cooling mode.
Trouble Cause Solution
There is direct sunlight Close the window curtain
The doors and windows are
open, the room is crowded or
there are other heat sources.
Dirty filter.
Close the door and window,
remove other heat sources and
add new air conditioners.
Clean or replace the filter
mesh.
Remove any clutter.
Air inlet or air outlet clogged
Bad cooling or
heating eects.
Unit makes lots of
noise.
Place the unit on a flat and firm
surface (may reduce noise).
The unit is on an uneven
surface.
The compressor
does not work. Overheat protection is active. Wait for three minutes until the
temperature decreases - the
unit will restart automatically.
The remote control is not
pointed at the signal receptor on
the unit.
Remote control is too far.
Batteries are dead. Replace the batteries
Bring the remote control close
to the air conditioner, ensuring it
is pointed at the signal receptor.
The remote control
does not work.
Contact customer service &
repair centre.
Contact customer service &
repair centre.
Drain the condensate water and
restart the unit.
Room temperature sensor
failure.
Tube temperature sensor
failure.
Water tank in chassis is full
'E1' code displays.
'E2' code displays.
Water full displays.
19
IN221100360V01_US_CA
823-041V80_823-041V81
CLIMATISEUR PORTABLE
MANUEL DINSTRUCTIONS
IMPORTANT : LIRE ATTENTIVEMENT ET CONSERVEZ CE MANUEL
POUR VOUS Y REFERER ULTERIEUREMENT.
FR
20
Table des matières
SÉCURITÉ DU CLIMATISEUR …..21
PIÈCES ET CARACTÉRISTIQUES …..25
EXIGENCES D'INSTALLATION ….26
INSTRUCTIONS D'INSTALLATION …..28
ÉTAPE 1 - DÉBALLAGE DU CLIMATISEUR …...28
ÉTAPE 2 – FIXATION DU CONNECTEUR DU TUYAU D'ÉCHAPPEMENT
SUR LE TUYAU D'ÉCHAPPEMENT …..28
ÉTAPE 3 – RACCORDEMENT DU TUYAU D'ÉCHAPPEMENT AU
CLIMATISEUR......................................................29
ÉTAPE 4 - INSTALLATION DES PANNEAUX DE FENÊTRE ………...29
ÉTAPE 5 - FIN DE L'INSTALLATION ….30
PANNEAU DE COMMANDE …...31
BOUTONS ….....32
TÉLÉCOMMANDE …...33
PROTECTIONS DE SÉCURITÉ …....34
UTILISATION DU CLIMATISEUR ….....34
VIDANGE DE L'EAU INTERNE..35
DRAINAGE MANUEL......35
DRAINAGE CONTINU... .35
ENTRETIEN ET MAINTENANCE …..35
NETTOYAGE DES SURFACES ….....36
NETTOYAGE DU FILTRE …...36
RÉSERVOIR D'EAU INTERNE ….....36
STOCKAGE …......36
DÉPANNAGE …....37
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39

HOMCOM 823-041V80BK Mode d'emploi

Catégorie
Climatiseurs mobiles
Taper
Mode d'emploi
Ce manuel convient également à

dans d''autres langues