Legrand HB350W-L3 High Bay Line Voltage Occupancy Sensor for Wet Locations Guide d'installation

Taper
Guide d'installation
Wattstopper
®
High Bay • Line Voltage • Passive Infrared
IP65 Occupancy Sensors for Wet Locations
Installation Instructions • Instructions d’Installation • Instrucciones de Instalación
No: 24141 – 02/17 rev. 1
Catalog Number • Numéro de Catalogue • Número de Catálogo: HB350W-L3
Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
DESCRIPTION AND OPERATION
The HB350W-L3 occupancy sensors is designed for automatic lighting control in high bay wet location applications. The sensor is
modular and are made up of two parts, a Sensor Module (HB350W) and a Lens (L3). The sensor uses a set of DIP switches to set the
time delay and PIR sensitivity as explained on page 2. The HB350W-L3 provides a single load controlling relay.
INSTALLATION OVERVIEW
1. Review the ADJUSTMENTS section and complete any
necessary DIP switch setting changes.
2. Mount the sensor so the lens is below the edge of the fixture
and away from the lamps. Heat from the lamps could affect
the sensor operation.
Make sure that you have the appropriate accessories for the
sensor mounting configuration. (See Mounting Options.)
3. Assemble any necessary mounting accessories and attach
them to the sensor module. Make sure that the flying leads
from the sensor module cable are accessible inside the
fixture.
4. Connect the line voltage and load wires to the sensor leads
as shown in the applicable Wiring Diagram for the sensor
module.
Do not allow bare wire to show.
Make sure all connections are secure.
Check all gaskets for watertight fit.
5. Check sensor operation. Refer to the TESTING section.
6. Attach the Lens to the HB350W-L3 as shown in the sensor
assembly drawing.
SPECIFICATIONS
Voltages .................................................................. 120/277VAC,60Hz
Load Requirements
@120VAC, 60Hz .......................................0-800W ballast or tungsten
@277VAC, 60Hz ........................................................0-1200W ballast
@120VAC ................................................................................... 1/6 hp
Wiring cable .......... 3 or 4-conductor 18AWG stranded, UL Style 2517
Unit Dimensions ......................................... 4.08” diameter, 1.88” thick
Threaded nipple ..........................................0.81” diameter, 0.40” long
fits standard 1/2” electrical conduit fitting
Weight .................................................................. 0.28 lb (130 grams)
Material ............... Polycarbonate, UL94-5VA flame retardant material,
UV resistant, indoor use only,
minimum plastic wall thickness 2.5mm
Environment ................................................................ IP65 Compliant
Operating temperature ........................ -40°F (-40°C) to 131° F (55°C)
Storage temperature ............................ -40°F (-40°C) to 176°F (80°C)
Operating humidity ...............................5 to 95% RH, non-condensing
Maximum Dew Point ........................................................29°C (85°F)
US Patents: ..................................................5,640,113 and 5,804,991
CAUTION
TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE INSTALLING THE SENSOR.
HB350W (sensor module)
HBL3W (lens module)
Tightening ring
Sensor Assembly
DIP switches
2
Switch 1 2 PIR SENSITIVITY
OFF OFF High
ON OFF NORMAL
OFF ON Medium
ON ON Low
1 2 3 4 5 6 7 8 9 10
ON OFF OFF OFF OFF ON ON OFF N/A N/A
Switch 3 4 5 6 7 TIME DELAY
ON ON ON ON ON 15 seconds
OFF ON ON ON ON 5 minutes
OFF OFF ON ON ON 10 minutes
OFF OFF OFF ON ON 15 minutes
OFF OFF OFF OFF ON 20 minutes
OFF OFF OFF OFF OFF 30 minutes
PIR Sensitivity (Switches 1-2)
The factory setting (Normal) is suitable for most applications, but
it may be necessary to adjust the PIR sensitivity if there is any
environmental interference causing false triggers or if sensitivity
needs to be increased for your particular application. Use DIP
switches 1 & 2 to adjust sensitivity.
PIR Sensitivity (switches 1&2) .....................Normal
Time Delay (switches 3-7) .................... 15 minutes
Override (switch 8) ....Occupancy control enabled
Factory Switch Settings (N/A = not applicable, no effect)
Time Delay (Switches 3-7)
Use DIP switches 3 to 7 to adjust the time delay.
ADJUSTMENTS
The sensor is pre-set at the factory to meet the requirements of
most applications. Review this section if your application requires
changing factory pre-sets.
Sensor factory pre-sets are as follows (default settings are bold):
Override (Switch 8)
The override disables the occupancy control feature of the
HB350W-L3 sensor module. When occupancy control is disabled,
the load remains ON as long as the sensor is powered.
Switch 8 Load Effect
OFF Controlled by Occupancy
ON PIR override. Load always ON
COVERAGE AREA
The coverage area is determined by the lens. The lenses are interchangeable with any HB350W series sensor module.
For a description of lens coverage patterns, see the LENS COVERAGE section in this instruction sheet.
HB350W-L3 attached to a watertight light xture using
HBEM3W
MOUNTING OPTIONS
As shown in the illustration, the HB350W-L3 can be attached
directly to a watertight fixture or junction box that is equipped
with a threaded nipple. The center of the threaded nipple
should be no more than approximately one inch (1”) from the
bottom of the fixture to avoid blocking the sensor’s view.
The HBEM3W extender module allows attaching the sensor to
the side of the fixture so that the lens can be positioned below
the bottom edge of the fixture. The wiring cable is threaded
through it and into the fixture for connection. The two sides of
the HBEM3W snap together to protect the cable.
The extender housing is not watertight, but the inner flange
rings on the chase nipple and the HB350W-L3 housing fit into
grooved rubber rings on the the cable. This keeps moisture
from entering the fixture and sensor at those locations.
HB350W-L3 attached to a watertight light xture
Wet location
light fixture
(supplied by
others)
Threaded female
1
/
2
connector (supplied by others)
HB350W
sensor
Wet location
light fixture
(supplied by others)
HB350W-Lx sensor
HBEM3W
Extender
housing
Chase nipple
Threaded nut
Rubber washer
3
LENS COVERAGE
The HB350W-L3 has a multi-cell, multi-tier Fresnel lens with a 360° view. Coverages shown in the diagrams are maximum. They
represent coverage for full-step walking motion, with no barriers or obstacles. Temperature variations may affect coverages and sensor
detection.
IMPORTANT START-UP INFORMATION
A 60-second start-up period occurs during initial installation and
after a power failure of 5 minutes or more. After applying power to
the sensor wait at least 60 seconds for the sensor to begin detecting
occupancy and the load to turn ON. It may turn ON during the start-
up period, depending on the state of the relay when power was off.
If the sensor detects occupancy during the start-up, when the
load turns ON it stays ON as long as the sensor continues to
detect motion, plus the Time Delay.
If no occupancy is detected during the 60-second start-up, the
load may come on anyway during the start-up. If no occupancy
is detected by the time the start-up is complete, the relay opens
and the load turns OFF.
WIRING
Neutral
Black Red
White
Line (Hot)
HB350W
Load
120/277VAC Wiring (HB350W)
HB350W-L3 360° Lens.
The -L3 has a high density lens
that covers a 24’ diameter area
at a height of 20’ as shown in
the coverage diagrams.
HB350W-L3 side coverage pattern





&HLOLQJ
&RYHUDJH6LGH9LHZ
* Ambient temperature variations in unconditioned spaces may affect sensor detection and coverage areas.
HB350W-L3 top coverage pattern
Coverage Top View
12 60612
0
12
6
6
12
24 ft
TESTING
1. When mounting and wiring are complete, cover up the sensor to prevent it from detecting motion.
2. Apply power to the sensor and light fixture. Lights may turn ON during the 60-second start-up period.
3. Wait for the start-up period to end. For the next 1 to 2 minutes the sensor runs through a self-diagnostic routine.
4. If the load came on during the start-up period, wait for it to turn OFF, indicating the self diagnostic routine is complete.
5. Uncover the sensor and confirm that when the sensor detects motion, it’s red LED blinks and the light turns ON.
6. Disconnect power.
7. Attach the lens as shown in the assembly drawing. Tighten securely to ensure that seal is complete.
800.879.8585
www.legrand.us/wattstopper
No. 24141 – 02/17 rev. 2
© Copyright 2017 Legrand All Rights Reserved.
© Copyright 2017 Tous droits réservés Legrand.
© Copyright 2017 Legrand Todos los derechos reservados.
Wattstopper warranties its products to be free
of defects in materials and workmanship for a
period of five (5) years. There are no obligations
or liabilities on the part of Wattstopper for
consequential damages arising out of, or in
connection with, the use or performance of this
product or other indirect damages with respect
to loss of property, revenue or profit, or cost of
removal, installation or reinstallation.
Wattstopper garantit que ses produits sont
exempts de défauts de matériaux et de fabrication
pour une période de cinq (5) ans. Wattstopper
ne peut être tenu responsable de tout dommage
consécutif causé par ou lié à l’utilisation ou
à la performance de ce produit ou tout autre
dommage indirect lié à la perte de propriété, de
revenus, ou de profits, ou aux coûts d’enlèvement,
d’installation ou de réinstallation.
Wattstopper garantiza que sus productos
están libres de defectos en materiales y mano
de obra por un período de cinco (5) años. No
existen obligaciones ni responsabilidades por
parte de Wattstopper por daños consecuentes
que se deriven o estén relacionados con el
uso o el rendimiento de este producto u otros
daños indirectos con respecto a la pérdida
de propiedad, renta o ganancias, o al costo
de extracción, instalación o reinstalación.
WARRANTY INFORMATION INFORMATIONS RELATIVES À LA GARANTIE INFORMACIÓN DE LA GARANTÍA
TROUBLESHOOTING
To confirm proper operation, review the Start-Up and Testing information.
Red LED on sensor module does not blink:
Check for proper sensor wire connections and make sure they are tightly secured.
Red LED blinks but lights do not turn ON:
1. Make sure that power to the sensor has been ON continuously for at least one minute, then
a. Turn OFF power to the sensor.
The relay will close.
b. Turn ON power to the sensor.
The load should come ON. If not, continue with step 2.
2. Check power connections to the load.
3. Check all sensor wire connections. Verify the load wire is tightly secured.
Lights will not turn OFF:
1. If there is no motion from people or equipment in the sensor’s view but the red LED blinks, look for any nearby source of infrared
energy (heat) in motion, such as turbulent air from a heating or cooling supply, or other sources such as heat from the fluorescent
lamps in the fixture.
Mount the sensor so that it’s lens is below the edge of the fixture and does not directly view the lamps.
Divert the air supply away from the sensor, or move the sensor.
2. Verify time delay set in switches 3-7. The time delay can be set from 15 seconds to 30 minutes. Ensure that the time delay is set to
the desired delay and that there is no movement within the sensor’s view for that time period.
3. Check Override DIP switch setting. If switch 8 is ON, the PIR is overridden. Occupancy control functions are overridden and the
load stays ON.
4. Check sensor wire connections. Verify that all connections are complete.
ORDERING INFORMATION
Catalog # Description
HB350W-L3 120/277VAC IP65 Sensor module in watertight enclosure with coverage @ 20’ mounting height and 24’ diameter
Optional mounting accessories
HBEM3W Extender module with 1 chase nipple, extender housing, rubber washer, two threaded nuts
All units are White.
To order preassembled custom configurations of sensors, lenses and mounting accessories, contact technical support.