Nicheless Underwater LED Lights | Owner’s Manual Nicheless Underwater LED Lights | Owner’s Manual ENGLISH Page 9
NOTE: Service
Loop not applicable
for Junction Box
Installations.
Vertical Installation
12VAC Magnetic Pool Transformer,
see table 3.2 for more details
The light face must be completely
snug with the light fitting without
any protrusion from the light fixture.
Conduit to 12VAC Magnetic Transformer
12VAC Magnetic Transformer
The light must be installed with the
light face completely snug with the
light fitting, without any protrusion
from the light fixture, and in
accordance with applicable local
codes and AHJ (Authority Having
Jurisdiction) requirements.
Figure 3. Standard installation with 1.5” pool wall fitting
3.3 Wet Area Installations
For wet area lighting within 10 feet (3M) of a pool or spa, use 6 Watt
Models ONLY. Except when the luminaire is adequately guarded, the
luminaire shall be installed in areas not subject to incidental contact from
people, pets, vehicles, and foot traffic.
Section 4. Wiring Options for Controlling
Jandy® Nicheless LED Lights
NOTE: Always consider the cable length when calculating the input
voltage at the transformer. The maximum run of service between
transformer and lights should not exceed 150ft. in length, inclusive
of the use of a J Box or not.
To the extent allowed by local installation codes in effect in the installation
jurisdiction and capacity of the electrical equipment, multiple Jandy lights
may be controlled with a single switch and a 12VAC magnetic transformer
so their colors may be synchronized.
IMPORTANT NOTE: All xtures must be tied into the same transformer,
circuit or switch for synchronization to occur. The use of Solid Core over
Stranded wire and terminating Bus Bars is strongly recommended.
4.1 Wiring to an AquaLink® Controller
The Jandy Nicheless LED Lights can be controlled by an AquaLink
controller. Connect the transformer powering the lights to one of the
auxiliary relays in the AquaLink.
Refer to Figure 4 to connect the Jandy Nicheless LED Lights to the Power
Center.