Legrand PN10F17FW Mode d'emploi

Taper
Mode d'emploi
Eclipse Workstation Raceway
INSTALLATION INSTRUCTIONS
Wiremold
®
Electrical Systems conform to and should be installed
and properly grounded in compliance with requirements of the
current National Electrical Code or codes administered by local
authorities. All electrical products may represent a possible
shock or fire hazard if improperly installed or used. Wiremold
electrical products are UL Listed, made for interior use only and
should be installed by qualified electrical people in conformance
with current local and/or the National Electrical Code.
1
2
3
4
5
6
16"
X
16"
X
1
2
Use a #8 (5/16" [7.9mm] head size) pan head fastener or equivalent to attach fittings to mounting surface.
Utilisez une attache a tete panoramique de calibre 8 [tete de 7,9mm (5/16")] ou une fixation equivalente pour
assujettir les raccords a la surface de montage.
Use un sujetado de cabeza plana #8 (5/16" tamaño de cabeza 7.9mm) o su equivalente para unir las instalaciones
a la superficie de montaje.
The adhesive on the PN03, PN05 and PN10 is intended to be used as an installation aid for positioning the
product. Applications with power wire, screw fasteners must be used in addition to the adhesive. Applications with
communication cable only, screw fasteners are not required but are recommended in addition to the adhesive.
Ladhésif qui se trouve sur les modèles PN03, PN05 et PN10 permet de positionner correctement le produit
lors de linstallation. Applications avec fil électrique : des vis dassemblage doivent être utilisées en plus de ladhésif.
Applications avec câble de communication seulement : des vis dassemblage ne sont pas requis mais peut etre
recommandées en plus de ladhésif.
El adhesivo del PN03, PN05 y el PN10 está destinado a usarse como una ayuda para colocar el producto.
En aplicaciones con cable de corriente debe usarse sujetadores de tornillo además del adhesivo. En aplicaciones con cable
de comunicaciones solamente, se recomienda (noes requerido) el uso de sujetadores de tornillo además del adhesivo.
41971 1200
RACEWAY WIRE FILL CAPACITIES FOR DATA/COMMUNICATIONS
CABLE/WIRE SIZE
O.D. PN03L PN05A/PN05L PN10A/PN10L
inches [mm] 20% fill* 40% Fill** 20% fill* 40% Fill** 20% fill* 40% Fill*
*
UNSHIELDED TWISTED 4-pair, 24AWG Cat 5 UTP 0.220 [5.6] 1 2 2 5 5 10
PAIR 4-pair, 24AWG Cat 3 UTP 0.190 [4.8] 2 3 3 6 7 14
TELEPHONE 2-pair, 24AWG 0.140 [3.6] 3 6 6 12 13 26
3-pair, 24AWG 0.150 [3.8] 2 5 5 10 11 23
4-pair, 24AWG 0.190 [4.8] 2 3 3 6 7 14
25-pair, 24AWG 0.410 [10.4] 0 1 1 1 2 3
COAXIAL RG58/U 0.195 [5.0] 1 3 3 6 7 13
RG59/U 0.242 [6.1] 1 2 2 4 4 9
RG62/U 0.242 [6.1] 1 2 2 4 4 9
RG6/U 0.270 [6.9] 1 2 2 3 3 7
THINAXIAL 100 Ohm 0.330 [8.4] 1 1 1 2 2 5
SHIELDED TWISTED Type 1 0.390 [9.9] 0 1 1 1 2 3
PAIR Type 2 0.465 [11.8] 0 1 1 1 1 2
Type 3 0.245 [6.2] 1 2 2 4 4 8
FIBER OPTIC 2 Strand 0.180 [4.6] 2 3 3 7 8 16
4 Strand 0.190 [4.8] 2 3 3 6 7 14
6 Strand 0.210 [5.3] 1 3 3 5 6 11
Fiber Zip Cord 0.110 [2.8] 5 9 9 19 21 42
* 20% cable fill is calculated to approximate reduction in cable capacity due to connectors mounted within raceway and fittings that may
restrict cross sectional area.
** 40% cable fill is the maximum designated cable fill based on TIA/EIA 569-A.
RACEWAY WIRE FILL CAPACITIES FOR POWER
WIRE SIZE O.D. PN03L PN05A/PN05L PN10A/PN10L
THHN/THWN
inches [mm] 20% fill* 4*
14 AWG 0.111 [2.8] 8 16 22
12 AWG 0.130 [3.3] 7 14 20
10 AWG 0.164 [4.2] –– 19
The Wiremold Company
U.S. and International:
60 Woodlawn Street • West Hartford, CT 06110
1-800-621-0049 • Outside U.S. 860 233-6251 • FAX 860-232-2062
In Canada:
850 Gartshore Street • Fergus, Ontario N1M 2W8
1-800-741-7957 • FAX 519-843-5980
© Copyright 2000 The Wiremold Company All Rights Reserved
  • Page 1 1
  • Page 2 2

Legrand PN10F17FW Mode d'emploi

Taper
Mode d'emploi

dans d''autres langues