4
NOTE: Instead of cementing the smaller pipe to the
rain cap, a fi eld-supplied stainless steel screw may be
used to secure the 2 components together when fi eld
disassembly is desired for cleaning. (See Figure 4.)
WARNING!
Do not operate the furnace with rain cap
removed. Recirculation of combustion
products may occur, or water may accumulate
inside larger combustion air pipe and fl ow
into the burner enclosure. Failure to follow
this warning could result in product damage
or improper operation, personal injury or
death.
6. Cement fi eld supplied furnace combustion air and
vent pipes to concentric vent termination assem-
bly.
7. Run furnace through a complete heat cycle to
ensure combustion air and vent pipes are properly
connected to concentric vent termination connec-
tions.
Procedure 2 - Side Wall Termination
1. Determine the best location for termination kit.
• Termination kit should be positioned where the
vent vapors will not damage plants/shrubs, or air
conditioning equipment.
• Termination kit should be positioned where it will
not be affected by wind eddies or currents that
may allow recirculation of combustion products
or unwanted intake of airborne leaves or light
snow.
• Termination kit should not be positioned where
it may be damaged by foreign objects such as
stones, balls, etc.
• Termination kit should not be positioned where
the vapors may be objectionable.
2. Cut one hole, 5 inch diameter if using a 3" kit or a
4 inch diameter hole if using 2" kit.
3. Partially assemble the concentric vent termination
kit per Figures 1 and 2.
a. Cement Y concentric vent fi tting to larger diameter
kit pipe. (See Figure 1.)
b. Cement rain cap to smaller diameter kit pipe.
(See Figure 1.)
4. Install cemented Y concentric fi tting and pipe as-
sembly through structure's hole (See Figure 5).
NOTE: do not allow insulation or other materials to
accumulate inside pipe assembly when installing
through hole.
5. Secure the assembly to the structure as shown
in Figure 5 using fi eld supplied metal strapping or
equivalent support material. NOTE: Ensure termina-
tion location clearance as shown in Figure 5.
NOTE: If assembly needs to be extended, the 2
pipes supplied in the kit may be replaced by using
the same diameter, fi eld supplied SDR-26 PVC
(D2241) pipe. Do not expand dimension "D" more
than 60 inches (See Figure 2).
CAUTION:
DO NOT use fi eld supplied couplings to extend
pipes. Airfl ow restriction will occur and the
furnace pressure switch may cause intermit-
tent operation.
WARNING!
Do not operate the furnace with rain cap
removed. Recirculation of combustion prod-
ucts may occur, or water may accumulate
inside larger combustion air pipe and fl ow
into the burner enclosure. Failure to follow
this warning could result in product damage
or improper operation, personal injury or
death.
6. Cement fi eld supplied furnace combustion air and vent
pipes to concentric vent termination assembly.
7. Run furnace through a complete heat cycle to
ensure combustion air and vent pipes are properly
connected to concentric vent termination connec-
tions.
Figure 4. Rain Cap to Vent Pipe Alternate Assembly
DRILL CLEARANCE HOLE IN
RAIN CAP AND PILOT HOLE
IN VENT PIPE
STAINLESS STEEL SCREW
(FIELD SUPPLIED)