Leviton DMX 24 Guide d'installation

Taper
Guide d'installation

Ce manuel convient également à

Installation Guide
DMX RELAY PANELS
Covering DMX 8, 24 & 48 Relay Panels with Master Control Module
Software Revision 2.00 and above
PK-A3200-10-02-0A© 2017 Leviton Mfg. Co., Inc.
WEB VERSION
WEB VERSION
If used in an EMERGENCY CIRCUIT, the enclosed "EMERGENCY CIRCUITS" label
shall be placed on the front of door to identify as a component of the emergency
system. If any Emergency Circuits are fed or controlled from this panel, it must be
located electrically where fed from a UPS, generator, or other guaranteed source of
power during emergency and power outage situations.
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed
including the following:
a) READ AND FOLLOW ALL SAFETY INSTRUCTIONS
b) Do not use outdoors.
c) Do not mount near gas or electric heaters.
d) Equipment should be mounted in locations and at heights where it will not readily
be subjected to tampering by authorized personnel.
e) The use of accessory equipment not recommended by manufacturer may cause
an unsafe condition.
f) Do not use this equipment for other than intended use.
SAVE THESE INSTRUCTIONS
All servicing shall be performed by qualified service personnel.
WARNINGS AND CAUTIONS
TO AVOID FIRE, SHOCK OR DEATH: TURN OFF POWER at main circuit breaker, or fuse,
and test that the power is off before wiring, opening the panel, replacing any component
servicing the relay cabinet or fixture or when changing lamps.
DO NOT CONNECT line voltage wires to low voltage terminals.
To avoid electrical overload, total external connected load should not exceed output rating.
To be installed and/or used in accordance with appropriate electrical codes and regulations.
To be installed by an electrician.
Conduit Entry Locations: The cabinets have been designed with specific locations
supporting conduit entry for line and low voltage circuits. There are specific areas of the
cabinet which are restricted from some or all types of conduit access. Reference the
Physical Installation section of this manual for specific details.
Line & Load Circuit Wiring: The line wiring should come from an over-current device and
the load circuit wiring shall go to the specific load to be controlled. On some models which
have integrated branch circuit protection, the line side of the relay has been pre-wired to a
circuit breaker. With these products, only the load side of the circuits needs to be connected.
Mount in a location where audible noise is acceptable.
When using with fluorescent ballasts, both lighting fixture and ballast must be grounded.
Use this relay cabinet only with minimum 75
o
C copper wire at 75% ampacity.
For indoor use only.
During operation, cabinet cover is to be removed by qualified personnel ONLY! Heed all
caution markings indicating the presence of high voltage. High voltage may be up to 600V.
Test each circuit for short circuits before connecting it to relay so damage to the relay and its
electronics can be avoided.
Verify that all unused power supply leads are insulated with wire nuts.
Temperature rating of field-installed conductors to the main input of the panelboard section
are on the Listed Panelboard.
WEB VERSION
Table of Contents
Certifications and Agency Standards
Specifications
Inspection
Installation
Installation Checklist
Relay Cabinet Mounting
Selection of a Mounting Location
Suggested Mounting Heights
Environmental Considerations
Preferred Areas for Conduit Entry
Step-by-Step Mounting Instructions
Line Voltage & Control Power Termination
Wiring
Testing the Circuits
Installing Relay Cards
Wiring the Relays
Control Electronics Power Wiring
DMX512
Requirements
Wiring the DMX Connector
Other Connections
Configuring Panel for DMX Control
Power Up & Installation Verification Checklist
FCC and IC Compliance Statements
Warranty Information
1
1
1
1
1
2
2
2
2
3, 4
5
6
7
7
7
8, 9, 10
11
12
12
12
12
13
14
15
15
WEB VERSION
Inspection
Carefully unpack the relay cabinet, and inspect to make sure there is no hidden shipping
damage. Report any damage to the freight carrier who delivered the system. Claims for
damages are filed with the freight carrier. In case of damaged components, your relay
cabinet may be serviced in the field with factory replacement parts.
Specifications
Type 1 Enclosure
Operational Temperature: 32° to 104° F (0° to 40° C)
0 to 90% Humidity non condensing
Certifications and Agency Standards
UL E#: E123072
cULus LISTED UL508 / CSA C22.2 No. 14-05, Ind. Control Equip.
cULus LISTED UL924 / CSA C22.2 No. 141-10 Emergency Lighting.
FCC Part 15, Class A
Installation
Installation Checklist
Install the cabinets by following these simple steps:
Step 1: Unpack the system
Step 2: Report any damage to the freight carrier
Step 3: If appropriate, remove any covers and/or doors
Step 4: If appropriate, remove the mounting plate assembly and store where dam-
age will not occur to the electronics
Step 5: Attach the cabinet to the wall (reference stickers inside the cabinet for
proper orientation if it is in question)
Step 6: Drill conduit entry holes if KO’s are not provided and attach conduit where
appropriate
Step 7: Pull all wire into the cabinet
Step 8: Test and verify all wiring by directly connecting Line to Load - Correct any
faults and re-test wiring prior to proceeding
Step 9: If applicable, re-install any control electronics removed in step #4
Step 10: Terminate discreet input control wiring
Step 11: Terminate network control wiring
Step 12: Test each Line/Load circuit for shorts
Step 13: Terminate the feed & load wiring to each relay
Step 14: Blow out dust, dirt, or debris which has accumulated in the cabinet
Step 15: Apply power to the system
Step 16: Verify proper operation of each relay using the override buttons
Step 17: Configure cabinet per owners requirements
1
WEB VERSION
Selection of a Mounting Location
Relay Cabinet Mounting
There are several steps required when mounting your relay cabinet:
Step 1: Install the flush mounting kit if appropriate
Step 2: Plan your conduit runs & electrical room layout
Step 3: Determine the appropriate methods for mounting your cabinet to the wall
Step 4: Mount the cabinet to the wall
Step 5: Install conduit, pull wire, and other items as required
Step 6: Proceed to Line & Load Voltage termination (page 15)
Selection of a Mounting Location
Choosing a mounting location for your cabinet is critical to the overall success and ease
of installation. Each style of cabinet has it’s unique wiring requirements which must
be observed. Please review the next few pages, which describe and illustrate these
requirements.
Suggested Mounting Heights
Although successful operation is completely independent of mounting height, the
suggested mounting heights below were selected to locate the cabinet at a reasonable
and accessible working height.
Cabinet Suggested Mounting height to bottom of cabinet
8 Relay Cabinet 53" (1,359 mm)
24 Relay Cabinet 32" (826 mm)
48 Relay Cabinet 12" (318 mm)
Environmental Considerations
Cabinets generate heat (see table which follows). Make sure they are mounted
in a climate controlled space where the temperature will be 0-40
o
C (32-104
o
F)
or 20-30
o
C (68-86
o
F) if used as Emergency Lighting Power Equipment.
Reinforce the wall for strength as required for weight and local code.
Clearance on left and right side of the panel should be maintained at 1-1/2"
or greater.
Relays will click while in operation. Locate the panels where audible noise
is acceptable.
Cabinet MAX BTU/HR
8 Relay Cabinet 245
24 Relay Cabinet 583
48 Relay Cabinet 1166
Relay Cabinet Max Head Load (BTU/hr.)
2
WEB VERSION
Preferred Areas for Conduit Entry
Your relay cabinet has been designed to be easy to install with a variety of installation
options to fit many applications. However, there still are specific considerations which
must be made. One of these is the allowed, and in some cases disallowed, areas for
conduit entry. Disallowed areas are areas where conduit entry is impossible either
due to physical or code limitations. These areas are clearly marked in the following
illustrations. Once you recognize the disallowed areas for conduit entry, you can look
at the allowed areas. Each cabinet style has designated areas for low voltage and line
voltage conduit entry. Observation of these requirements will ensure smooth installation
and continued code compliance.
High Voltage pass
through below control
module mounting plate
Low Voltage Area
Transformer located
underneath control
module
Transformer
connections in this
area below control
module
High Voltage Area
Grounding Points
24 & 48 Relay Cabinets Conduit Entry
(24 relay cabinet shown, 48 similar)
3
WEB VERSION
8 Relay Cabinet Conduit Entry Locations
Wiring Area
Low Voltage
Transformer
Low Voltage Conduit Entry Area
Ground Point
No Conduit Entry This Area
High Voltage Conduit Entry Area
High Voltage
Connections
Transformer
Connections
4
WEB VERSION
Mounting Provisions & Dimensions
Step-by-Step Mounting Instructions
Step 1: Locate where the cabinet will be hung on the wall. Choose a location in a dry
area that is convenient to the branch circuit panel.
Step 2: Leviton requires that cabinet mounting hardware reach through the drywall to
wall studs or other suitable solid backing. However, properly sized struts and
suitable hardware can also be used. The load must be evenly distributed to
the anchors without exceeding the recommended anchor limit. Using drywall
screws directly through drywall without a stud is not acceptable. Ensure that
adequate support at all points is provided.
Step 3: Remove the cover. Some cabinets may also require the removal of data
and/or grounding wires. Make sure that this occurs prior to removal of the
door and that they are reconnected when reinstalling the door. On cabinets
with hinges, simply lift the door off the hinges. On cabinets with screws,
remove the cover screws. Appropriately store the cover for future use.
Step 4: On the (4) relay panels only, locate the mounting plate assembly attached to
the back of the enclosure. Locate the 4 mounting screws in the 4 corners of
the rear plate. Loosen these 4 screws. Lift the entire assembly up and out of
the enclosure.
Step 5: Prior to proceeding, refer to conduit entry diagrams on prior pages which
show location of the mounting holes and allowed conduit entry locations for
each cabinet type.
Step 6: Prior to attaching the cabinet to any surface, verify that the top of the cabinet
is actually located at the top. Some cabinets have "up" arrows to aid in this
indication.
Step 7: Attach the cabinet to it’s prepared mounting surface as appropriate.
Step 8: Cut, punch, or remove knockouts for the desired conduit openings.
Pay special attention to any disallowed areas for conduit entry.
Step 9: Pull all wire, both line and low voltage as appropriate.
Step 10: Carefully and completely remove any dust, debris, metal particles, etc. from
inside the cabinet in preparation for wire termination and eventual power up.
Step 11: Proceed to the next section.
5
WEB VERSION
Line Voltage & Control Power Termination
Overview of Power Wiring - Feed\Line Wiring
Line Voltage & Control Power Termination
Overview of Power Wiring - Feed\Line Wiring
Wiring is simple. All you need is the following:
Dedicated circuit for control power - Hot, Neutral and Ground
Individual load wires leaving relays, output circuits.
NOTE: Since the panel is fed from multiple circuits, locate each one and lock-out
each feed in the OFF position.
All cabinets have ample area for conduit entries for feed, load, and control wiring.
Ensure that conduit entry is only in the allowed locations. Refer to diagrams on prior
pages for permitted locations.
Each relay panel has areas dedicated for line voltage wiring and similar orientation.
Please find on the next few pages figure which illustrate this.
6
WEB VERSION
Line Voltage & Control Power Termination
Line and Load Circuit Wiring
Wiring
Relay cabinets have multiple relay circuits of a specific type depending on the cabinet
model. For details of the different relay types, their capacities, and permitted wire sizes,
please reference the chart on page 9.
Testing the Circuits
Prior to connecting any circuit to a relay, and after all load and feed connections have
been made opposite the relay cabinet, test each circuit by following this procedure:
Step 1: Turn OFF the breaker feeding the circuit.
Step 2: Ensure that all connections and wiring between the relay cabinet and the
circuit breaker panel are complete.
Step 3: Ensure that all connections and wiring between the relay cabinet and the load
are complete.
Step 4: At the relay cabinet, connect the feed(s) for relay #1 to the load for relay
#1 with a wire nut or other appropriate means.
Step 5: Energize the circuit by turning on the circuit breaker.
Step 6: Resolve any mis-wiring, shorts, etc. for the connected circuit.
Step 7: Repeat the above steps for all circuits in all relay panels for your system.
When all circuits have been tested, disconnect all Lines from Loads and
proceed to the next section.
Installing Relay Cards
On several relay cabinet models, the relays are removable. If you have one of these
cabinets and need to add or remove relay modules, please follow these instructions:
Step 1: Locate the appropriate
location for the relay card
Step 2: Align the connector from the relay card with the relay bus board and gently
push the two together.
Step 3: Once firmly seated, use a Phillips screwdriver to drive the mounting screw
tightly in place.
NOTE: If you need to remove the relay cards that shipped installed from the factory,
remove the shipping screw located near the connector and discard. This
screw is only required for shipping and not for installation.
Mounting Screw
Location
Connector to Relay
Bus Board on bottom of
Relay Card
7
WEB VERSION
Wiring the Relays
Step 1: Connect the line (feed/circuit breaker) side of the circuit to the "input"
terminal(s) on the relay card.
Step 2: Connect the load side of the circuit to the “output” terminal(s) on the
relay card.
Step 3: Please note that relay card terminals accept the following wire sizes:
Relay Type
(Part #)
Wire
Size
Wire
Type
Torque
Max
Voltage
Tungsten
Rating
(120V)
Ballast
Rating
Motor Rating
(120V/277V)
Inductive
Ballast,
Transformer,
HID Rating
Standard
1-Pole relay
module
(RELAY-STD)
20-8
AWG
Copper
Solid or
Stranded
7 in-lbs 277V 20A 20A 1HP/2HP 20A
2-Pole relay
module
(RELAY-2PL)
20-6
AWG
Copper
Solid or
Stranded
20.5 in-lbs 277V
per pole
(480V)
20A 2HP 20A
347V relay
module
(RELAY-347)
20-6
AWG
Copper
Solid or
Stranded
20.5 in-lbs 347V 20A 20A
Latching
Relay Module
(RELAY-LAT)
20-8
AWG
Copper
Solid or
Stranded
7 in-lbs 277V 20A 20A
1HP/2HP
20A
347V 15A 15A
Wire Sizes & Capacities for Relays
Wiring Diagram for Standard 1 Pole Relay Card
(latching relay card similar)
NOTE: Circuit neutrals may follow the path of the line/load conductors through the
relay panel or the line/load conductors may pass back to the panel board to
be joined with the neutral to the load.
The diagrams on the following pages show how to wire the relay circuits.
WARNING: MISWIRING THE RELAY MODULES WILL CAUSE DAMAGE TO THE
RELAY MODULE, THE RELAY CABINET, AND POSSIBLY OTHER SYSTEMS
Line (from Distribution Panel)
Load
8
WEB VERSION
Wiring Diagram for Standard 2 Pole Relay Card
Wiring Diagram for 347V Relay Card
Load - Phase B
Line - Phase B
(from Distribution Panel)
Line - Phase A
(from Distribution Panel)
Load - Phase A
Load
Line (from Distribution Panel)
Line Voltage & Control Power Termination
Line and Load Circuit Wiring
9
WEB VERSION
Wiring Diagram of Multiple Relays
to Common Branch Circuit Breaker
Line (from Distribution Panel)
Load
Load
Load
10
WEB VERSION
Control Electronics Power Wiring
Your relay cabinet requires a specific power circuit for the control electronics.
Leviton recommends that this power circuit be dedicated specifically and used
only for power to the control electronics.
NOTE: If any Emergency Circuits are fed or controlled from this panel, it must be
located electrically where fed from a UPS, generator, or other guaranteed
source of power during emergency and power outage situations.
To connect your relay cabinet’s control electronics to power, please follow these steps:
Step 1: Connect the relay cabinet to the circuit panel using conduit.
Step 2: Remove all cuttings and dirt.
Step 3: Run a dedicated circuit from the circuit panel or distribution panel to the relay
panel for the control electronics. Make sure the power is OFF at the breaker.
Step 4: Wire the circuit as shown in the following figure:
Multi-Tap Transformer
24 & 48 Relay Cabinets Control Electronics Power Wiring
NOTE: The transformer leads can be found in the lower right corner on the 8 cabinet
and underneath the control module on the right hand side of the 24 and 48
cabinet.
NOTE: The 48 cabinet has two sets of leads which can be connected in parallel to
the same dedicated circuit.
NOTE: Branch circuit wiring must be a minimum of 14 AWG.
Step 6: Connect the circuit’s ground wire to the relay cabinet.
Step 7: Keep the circuit OFF until all wires are terminated, tested, and
double checked.
Cap off unused leads
with wire connectors
Dedicated Circuit
347V - Orange
277V - Brown
120V - Black
Neutral White
11
WEB VERSION
DMX 512
The digital control panel accepts DMX512 signals, an industry standard signal widely
used in the theater and advanced architectural. This protocol offers fast response and
guaranteed messaging between the controller and the receiving device(s) allowing for
a precision not capable with other control protocols. Incorporating DMX directly into your
device adds the opportunity to use theatrical consoles, theatrical station controls, and
advanced architectural systems to control some or all of the relays in the relay cabinet.
Extended information available in the System Design Guide.
(Information about this guide can be found on page 1)
Requirements
DMX has specific wiring, wire type, topology, and termination requirements.
Please reference the System Design Guide for additional information on this topic.
Wiring the DMX Connector
Step 1: Connect leads per the following wiring diagram.
Step 2: Twist strands of each lead tightly (making sure that there are no stray strands)
and push firmly into appropriate plug connector location.
Step 3: Tighten the screws on the plug connector - making sure that no bare
conductor is showing.
Step 4: Tie the Drain/Shield wires together and insulate using a small piece of heat
shrink tubing.
Step 5: Install termination jumpers as required. Termination can be accomplished
on the control board by jumpering the 2 pin header to the left of the DMX
connector.
Other Connections
The digital control panel also accepts a variety of other signals. For more details
regarding the configurations for other interface options refer to the Advanced
Programming Guide found on the Leviton website at www.leviton.com.
12
WEB VERSION
Configuring Panel for DMX Control
DMX is an ANSI standard control protocol originally birthed from the entertainment
industry. DMX is still used in the entertainment industry, but also in many architectural
applications.
The settings for DMX are described in this chapter.
Main Menu – Select Configuration
Configuration - System Setup
System Setup – DMX-512
DMX512 SETUP M: DISABLED (NOTE: For nearly all applications, DMX
model should be set to forced)
Operational Mode
DMX has several operational modes which define how DMX controls the
relay cabinet. The available operational modes are as follows:
Disabled - The cabinet can be programmed to not listen to DMX
commands. This is useful when you do not have any DMX devices
hooked up to the system.
PRI ON - REL OFF - DMX operates in last action mode for DMX channels
at the same priority level as DMX when levels are greater than 0, and
relinquishes control to other channels when the value=0 (last action).
PRI OFF-REL ON - Relinquishes control to other priority levels when
the DMX channel level is greater than 0, and operates in last action
mode at the priority level of DMX to turn the relays off when the DMX
channel level=0.
Forced - Means that DMX will always have control over other control
sources of the same priority.
DMX512 SETUP START ADDR: 1
DMX Start Address
W
hen DMX is used to control relays in the cabinet, each relay requires the
assignment of a DMX channel, or none, whichever is appropriate. This
setting quickly sets and sequentially renumbers all relays in the cabinet,
starting at the given start channel. Valid values for DMX channels are 1-512.
NOTE: For other configuration options, please refer to Programming Guide
at www.leviton.com
13
WEB VERSION
Power-Up & Installation Verification Checklist
Prior to the application of power to your relay cabinet, all of the following steps
must have been successfully executed.
Inspect each relay load wiring for incomplete termination
Inspect each relay’s load wiring for terminals not completely tightened
With each relay in the "OFF" position, check for voltage between the Line & Load
terminals; there should be none.
Inspect all low voltage wiring and ensure that it is complete.
Inspect control power wiring, ensure that it is complete.
Confirm that any unused supply wires on the control power transformer have been
suitably capped.
Confirm that all connected load wiring between the relay panel and it’s load has
been completed.
Confirm that wiring between the cabinet and all low voltage devices has been
completed.
Apply power to the cabinet.
Confirm that the cabinet boots properly and returns to the status "normal" screen.
Set the Time & Date from the menu.
Update system software with the latest available software from the website, if
appropriate.
Proceed to panel programming.
14
WEB VERSION
WARRANTY INFORMATION
Limited Warranty
Leviton Manufacturing Co Inc. warrants the products represented in this manual to be free of
material and workmanship defects for a period of two years after system acceptance or two
years after shipment from Leviton, whichever comes first.
Leviton Manufacturing Co Inc. warrants the Relay Modules represented in this manual to be free
of material and workmanship defects for a period of ten years after system acceptance or ten
years after shipment from Leviton, whichever comes first.
This Warranty is limited to repair or replacement of defective equipment returned Freight Pre-
Paid to Leviton Manufacturing at 20497 SW Teton Ave., Tualatin, Oregon 97062, USA. User
shall call 1-800-959-6004 and request a return authorization number to mark on the outside of
the returning carton, to assure that the returned material will be properly received at Leviton.
All equipment shipped back to Leviton must be carefully and properly packed to avoid shipping
damage. Replacements or repaired equipment will be returned to sender freight prepaid, F.O.B.
factory. Leviton is not responsible for removing or replacing equipment on the job site, and will
not honor charges for such work. Leviton will not be responsible for any loss of use time or
subsequent damages should any of the equipment fail during the warranty period, but agree
only to repair or replace, at Leviton’s option, defective equipment returned to its plant in Tualatin,
Oregon. This Warranty is void on any product that has been improperly installed, overloaded,
short circuited, abused, or altered in any manner. This Warranty does not cover lamps, ballasts,
and other equipment which is supplied or warranted directly to the user by their manufacturer.
Neither the seller nor Leviton is liable for incidental, special, or consequential damages,
including without limitation, damage to, or loss of use of, any equipment, lost sales or profits or
delay or failure to perform this warranty obligation. There are no other implied warranties of any
kind, including merchantability or fitness for a particular purpose, but if any implied warranty
is required by the applicable jurisdiction, the duration of any such implied warranty, including
merchantability and fitness for a particular purpose, is limited to two years.
FCC COMPLIANCE STATEMENT
This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy
and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely
to cause harmful interference in which case the user will be required to correct the interference
at his own expense.
IC COMPLIANCE STATEMENT
This device complies with Industry Canada license-exempt RSS standard(s). Operation is
subject to the following two conditions: (1) this device may not cause interference, and (2) this
device must accept any interference, including interference that may cause undesired operation
of the device.
IMPORTANT! Any changes or modifications not expressly approved by the party responsible for
compliance could void the users authority to operate this equipment.
15
WEB VERSION
Guide d’installation
ARMOIRES À RELAIS DMX
Modèles à 8, 24 et 48 relais, avec module de commande principal
Versions logicielles 2.00 et plus
WEB VERSION
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56

Leviton DMX 24 Guide d'installation

Taper
Guide d'installation
Ce manuel convient également à