Danfoss System Manager, AK-SM 800A series Guide d'installation

Taper
Guide d'installation
Installation Guide
System Manager
AK-SM 800A series
© Danfoss | DCS (vt) | 2020.04
AN307930531782en-000101 | 1
080R9342
A N307930531782en-000101
-10 °C< t
amb
< 50 °C
14 °F < t
amb
< 120 °F
0 – 95% RH, non condensing
IP20
Danfoss
80Z817
mm
mm
Relay 1/2
Canbus
100 - 240 V
AC
MODBUS 1/2
LON / TP78
Ethernet 0
T 8
mm
mm
43
mm
Supply Relay 1 Relay 2
LON-version
Canbus
(for future use)
(for future use)
(for future use)
Listed
UL file: E31024
61B5
Class 2 or LPS in accordance with NEC.
For supply connections, use 16 AWG or
larger wires rated for at least 75 °C (167 °F).
Use copper conducters only.
Enclosure rating type 1
FCC ID: X02SPB209A
IC ID: 8713A-SPB209A
TP 78-version
100 – 240 V
AC
CAN bus
MODBUS
1
(Danfoss)
MODBUS 2
(RS485)
TP 78
LON 1
TP 78
LON 2
TP 78
LON 3
TP 78
LON 4
LON
MODBUS
1 MODBUS 2
Panel mount
Wall mount
Front side
Danfoss
80Z818
T10
© Danfoss | DCS (vt) | 2020.04
2 | AN307930531782en-000101
Danf
oss
80Z820
Terminering
Termination
Terminierung
Terminaison
Terminación
Connectivity
Selve installationen af datakommunikationskablet skal overholde de krav, som er nævnt i dokumentet “Datakommunikation imellem
ADAP-KOOL® Køleanlægsstyringer”. Litteraturnummer = RC8AC901.
The actual installation of the data communication cable must comply with the requirements mentioned in the document “Data
communication between ADAP-KOOL® Refrigeration controls”. Literature sheet number = RC8AC902.
Beim Verlegen des Datenkommunikationskabels sind die im dokument “Datenkommunikation zwischen ADAP-KOOL®
Kälteanlagenregelsysteme“ enthaltenen Anforderungen einzuhalten. Literaturnummer = RC8AC903.
L’installation elle-même du câble de transmission de données doit respecter les contraintes citées dans le document
Transmission de données ADAP-KOOL® Commande d’installation frigorifiques”. Référence documentaire = RC8AC904.
La instalación práctica del cable de comunicación de datos debe cumplir con los requisitos mencionados en el documento
“Comunicación de datos entre controles de refrigeración ADAP-KOOL®”. Número de documento = RC8AC907.
MODBUS
LON
TP78
Canbus
Ethernet 1 (for future use)
(Accessible outside)
Ethernet 0 (WAN)
(Recessed inside)
Ethernet WiFi Access point
1. Activate WiFi access point from local screen
2. Follow on-screen instructions
When all cables have been mounted on the different units, the
cable must be terminated.
A section must be terminated at both ends. The section must
be terminated using either an external resistor or a contact.
Please see the relevant device.
A repeater will normally terminate two cable sections.
The termination should be made with a 120-ohm resistor. (The
resistor can be in the range 100 – 130 ohms.)
A repeater will always terminate two cable sections.
Repeater
System unit
System unit
Termination = 120 Ω
Danfoss
Out
120
Ω
© Danfoss | DCS (vt) | 2020.04
AN307930531782en-000101 | 3
0 = Master
1 - 9 = Slave
Initial settings:
1. Legal terms
2. Select language for local screen
3. Set up user
4. Set Date/time
5. Select Units
6. Set Communication
7. OK and Finish
Konfiguration, Configuration, Konfiguration, Configuration, Configuración
See User Guide: BC316842192932en-001001
AK-SM 800
Initial settings wizard
First time start-up
AK-SM 820A
AK-SM 850A
AK-SM 880A
IMPORTANT!
Method 1: Offline
Download firmware from
sm800a.danfoss.com
Method 2: Online
Use software update utility in the web
interface.
Address
Adresse
Dirección
SOFTWARE UPDATE
© Danfoss | DCS (vt) | 2020.04
4 | AN307930531782en-000101
ADAP-KOOL®
The Product contains electrical components
And may not be disposed together with domestic waste.
Equipment must be separate collected with Electrical and Elec-
tronic waste. According to Local and currently valid legislation.
Statements for the AK-SM 800A
FCC COMPLIANCE STATEMENT
CAUTION: Changes or modifications not expressly approved could void your authority to use this equipment
This device complies with Part 15 of the FCC Rules. Operation to the following two conditions: (1) This device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that may cause undesired operation
INDUSTRY CANADA STATEMENT
This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may
not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisée aux deux
conditions suivantes : (1) l'appareil ne doit pas produire de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique
subi, même si le brouillage est susceptible d'en compromettre le fonctionnement.
NOTICE
FCC COMPLIANT NOTICE
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate
radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio
or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by
one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
Modifications: Any modifications made to this device that are not approved by Danfoss may void the authority granted to the user by the FCC to
operate this equipment.
Any regulatory related concerns contact: global_approvals@danfoss.com
Danfoss Cooling
11655 Crossroads Circle
Baltimore, Maryland 21220
United States of America
global_approvals@danfoss.com
www.danfoss.com
EU CONFORMITY NOTICE
Hereby, Danfoss A/S declares that the radio equipment type AK-SM 800A is in compliance with Directive 2014/53/EU.
The full text of the EU declaration of conformity is available at the following internet address: www.danfoss.com
Danfoss A/S
Nordborgvej 81
6430 Nordborg
Denmark
global_approvals@danfoss.com
www.danfoss.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Danfoss System Manager, AK-SM 800A series Guide d'installation

Taper
Guide d'installation