Nice HySecurity SlideSmart CNX Slide Gate Operator Guide d'installation

Catégorie
Ouvre-porte
Taper
Guide d'installation

Ce manuel convient également à

Installation and Programming Manual
SlideSmart
CNX
CNX 15
Vehicular slide gate operator with SmartCNX™ Controller
www.ApolloGateOpeners.com | (800) 878-7829 | [email protected]
2
TABLE OF CONTENTS
SlideSmart CNX 15
Troubleshooting/Alerts/Faults/Errors .. 35-41
Appendix A - Vehicle Detector Loops .......42
Appendix B - French Translations ........ 43-46
Warranty ....................................................47
Specications ............................................48
Table of Contents ........................................2
Safety Requirements .............................. 3-10
Features .....................................................11
Unpack the Operator .................................12
Operator Position ......................................13
Prepare an Installation Site .................. 14-15
Attach Back Cover .....................................16
Install Chain Kit ..........................................17
Attach Target Magnet and Chain Cover ....18
Wiring and Power ................................ 19-20
Controller Connections .............................21
User Interface ............................................22
Initial Setup ................................................23
Operator Congurations ...........................24
Bi-Parting Gate Setup ................................25
Controller Inputs ........................................26
Set IES Sensitivity ......................................27
Entrapment Sensor Wiring - BlueBUS .......28
Entrapment Sensor Wiring ........................29
List of Entrapment Sensors ........................30
SmartCNX - Hy5B Module ........................31
Relay Outputs - Basic ................................32
Maintenance ..............................................33
Firmware Updates and Debug Data ..........34
www.ApolloGateOpeners.com | (800) 878-7829 | [email protected]
3
SAFETY REQUIREMENTS
SAFETY MESSAGES
The safety messages below inform you about potential
hazards that can result in injury. Safety messages
speci cally address level of exposure to operator and are
preceded by one of four words:
DANGER, WARNING,
CAUTION
or NOTICE.
DANGER
Indicates a hazardous situation which, if not avoided,
WILL result in DEATH or SERIOUS INJURY.
WARNING
Indicates a hazardous situation which, if not avoided,
COULD result in DEATH or SERIOUS INJURY.
CAUTION
Indicates a hazardous situation which, if not avoided,
COULD result in MINOR or MODERATE INJURY.
NOTICE
Addresses practices not related to personal injury.
Indicates damage to equipment is probable if the
hazardous situation is not avoided.
COMMON INDUSTRIAL SYMBOLS
These international safety symbols may appear on
product or in its literature to alert of potential personal
injury hazards. Obey all safety messages that follow these
symbols to avoid possible injury or death.
Symbol Safety Hazard
Attention -
Take Notice
Danger -
Keep Away
Entrapment Zone
Possible Pinch Point
www.ApolloGateOpeners.com | (800) 878-7829 | [email protected]
4
IMPORTANT SAFETY INSTRUCTIONS
Hazards, associated with automatic gates,
can be reduced with proper site design,
installation, and use. Installers, maintenance
crews, and owners/users must read and
follow the safety requirements found in
HySecurity® product manuals.
It is important that only quali ed installers
handle installation of HySecurity Gate
vehicular gate operators. A “quali ed”
installer has one of the following:
1.
A minimum of three years experience
installing similar equipment.
2.
Proof of attending a HySecurity Technical Training
seminar within the past three years.
3.
Signi cant manufacturer endorsements of technical
aptitude in gate operator installation and operation.
Underwriter Laboratories (UL) and the American Society
for Testing and Materials (ASTM) are responsible for
current safety standards and regulations regarding gate
operators and automated gates. All aspects of gate
installation must comply with the appropriate safety
standard. For the most up-to-date ASTM F2200 Gate
and Fence Standards, refer to www.astm.org. For UL
325 Safety Standard, refer to www.ul.com. Consult local
government agencies for up-to-date rules and regulations
as certain municipalities have established licensing, codes
or regulations that regulate automated gate system
design and installation.
GENERAL SAFETY INFORMATION
A gate operator is only a component in a gate system.
The other parts of the gate system can include the
gate, the external safety sensors, access controls, and
vehicle detectors. To have a gate system that provides
for safety, security, and reliable operation it is essential
these components operate together as a system. It is
the responsibility of the system designer and/or installer
to ensure any safety or operational issues have been
addressed.
WARNING
To reduce the risk of injury or death:
1. READ AND FOLLOW ALL INSTRUCTIONS.
2. Never let children operate or play with gate controls.
Keep the remote control away from children.
3. Always keep people and objects away from the
gate. NO ONE SHOULD CROSS THE PATH OF THE
MOVING GATE.
4. Test the gate operator monthly. The gate MUST
reverse on contact with a rigid object or stop when
an object activates the non-contact sensors. After
adjusting the force or the limit of travel, retest the
gate operator. Failure to adjust and retest the gate
operator properly can increase the risk of injury or
death.
5. Use the emergency release only when the gate is not
moving.
6. KEEP GATES PROPERLY MAINTAINED. Read the
user’s manual. Have a quali ed service person make
repairs to gate hardware.
7. The entrance is for vehicles only. Pedestrians must
use separate entrance.
8. SAVE THESE INSTRUCTIONS.
SAFETY REQUIREMENTS
www.ApolloGateOpeners.com | (800) 878-7829 | [email protected]
5
IDENTIFYING GATE OPERATOR CATEGORY AND UL 325 USAGE CLASS
The UL 325 standard covers gate operators. Within this safety standard several Usage Classes are described that de ne
different types of installations where gate operators can be applied. Some operators are restricted in their usage application.
Appropriate Usage Classes are shown in the Speci cations.
Class I
Class I: Intended for use in a location of one to four single
family dwellings or a parking area associated with one to
four single family dwellings.
Class II
Class II: Intended for use in a commercial location or building
such as a multi-family housing units ( ve or more single family
units) hotels, garages, retail stores or other buildings servicing
general public.
Class III
Class III: Intended for use in an industrial location or building
such as factories or loading docks or other locations not
accessible by the general public.
Class IV
Class IV: Intended for use in guarded industrial locations or
buildings such as an airport security area or other restricted
access location, not servicing general public, in which access
is monitored by security personnel or via closed circuitry.
SAFETY REQUIREMENTS
www.ApolloGateOpeners.com | (800) 878-7829 | [email protected]
6
VEHICULAR TRAFFIC ONLY
WARNING
This automatic gate operator is not designed nor is it intended for pedestrian traf c. Vehicular gate operators must
by their nature be powerful to function reliably. This power can cause injury or death. Accordingly, direct all pedestrian
traf c to a separate walk-through gate.
Install this gate operator only when:
z
The operator is appropriate for the construction of
the gate and the usage Class of the gate.
z
All openings of a horizontal slide gate are guarded or
screened from the bottom of the gate to a minimum
of 1.83 m (6 ft) above the ground to prevent a 57.2 mm
(2-1/4 in) diameter sphere from passing through the
openings anywhere in the gate, and in that portion of the
adjacent fence that the gate covers in the open position.
z
All exposed pinch points are eliminated or guarded.
z
Guarding is supplied for exposed rollers.
The operator is intended for installation only on gates used
for vehicles. Pedestrians must be supplied with a separate
access opening. The pedestrian access opening shall be
designed to promote pedestrian usage. Locate the gate
such that persons will not come in contact with the vehicular
gate during the entire path of travel of the vehicular gate.
The gate must be installed in a location so that enough
clearance is supplied between the gate and adjacent
structures when opening and closing to reduce the risk
of entrapment. Swinging gates shall not open into public
access areas.
The gate must be properly installed and work freely
in both directions prior to the installation of the gate
operator. Do not over-tighten the operator clutch or
pressure relief valve to compensate for an improperly
installed, improperly functioning, or damaged gate.
Permanently mounted controls intended for user
activation must be located at least 1.83 m (6 ft) away
from any moving part of the gate and where the user is
prevented from reaching over, under, around or through
the gate to operate the controls.
z
Exception: Emergency access controls only accessible
by authorized personnel (e.g.  re, police, EMS) may be
placed at any location in the line-of-sight of the gate.
The Stop and/or Reset button must be located in the line-
of-sight of the gate. Activation of the reset control shall
not cause the operator to start.
A minimum of two (2) WARNING SIGNS shall be installed,
in the area of the gate. Each placard is to be visible by
persons located on the side of the gate on which the
placard is installed.
For gate operators utilizing a non-contact sensor
(Photo Eye):
z See instructions on the placement of non-contact
sensors for each type of application.
z Care shall be exercised to reduce the risk of nuisance
tripping, such as when a vehicle trips the sensor while
the gate is still moving.
z One or more non-contact sensors shall be located
where the risk of entrapment or obstruction exists,
such as the perimeter reachable by a moving gate or
barrier.
For a gate operator utilizing a contact sensor (Edge):
z One or more contact sensors shall be located where
the risk of entrapment or obstruction exists, such as
at the leading edge, trailing edge, and postmounted
both inside and outside of a vehicular horizontal slide
gate.
z A hardwired contact sensor shall be located and its
wiring arranged so that the communication between
the sensor and the gate operator is not subjected to
mechanical damage.
z A wireless device such as one that transmits radio
frequency (RF) signals to the gate operator for
entrapment protection functions shall be located
where the transmission of the signals are not
obstructed or impeded by building structures, natural
landscaping or similar obstruction. A wireless device
shall function under the intended end-use conditions.
z One or more contact sensors shall be located on the
inside and outside leading edge of a swing gate.
Additionally, if the bottom edge of a swing gate is
greater than 152 mm (6 in) but less than 406 mm (16
in) above the ground at any point in its arc of travel,
one or more contact sensors shall be located on the
bottom edge.
USE OF VEHICLE DETECTORS
Use of vehicle detectors (loop detectors) is strongly
encouraged to prevent damage to vehicles caused by
gates closing on them. This is not considered to be a
safety item as vehicle detectors cannot provide protection
to pedestrians. In some situations, photoelectric devices
may be used as vehicle detectors, but should be wired
accordingly.
SAFETY REQUIREMENTS
www.ApolloGateOpeners.com | (800) 878-7829 | [email protected]
7
GATE CONSTRUCTION AND SAFETY
Gate construction plays a very important role in ensuring
the safety of any automated gate system. The standard
for gate construction is ASTM F2200. Below are key
areas to address in gate design for safety. For complete
information consult the standard. Copies of the standard
are available at:
https://www.astm.org/Standards/F2200.htm.
Another source of information is available from DASMA,
the Door and Access System Manufacturer’s Association.
The Association publishes Technical Data Sheets, one of
which concerns ASTM F2200. For more information, see:
http://www.dasma.com/PDF/Publications/
TechDataSheets/OperatorElectronics/TDS370.pdf.
General Requirements for gate construction:
z
Gates shall be constructed in accordance with the
provisions given for the appropriate gate type listed.
Refer to ASTM F2200 for additional gate types.
z
Gates shall be designed, constructed and installed to not
fall over more than 45 degrees from the vertical plane,
when a gate is detached from the supporting hardware.
z
Gates shall have smooth bottom edges, with vertical
bottom edged protrusions not exceeding 0.50 in (12.7
mm) other than the Exceptions listed ASTM F2200.
z
The minimum height for barbed wire shall not be less than
6 ft (1.83 m) above grade. The minimum height for barbed
tape shall not be less than 8 ft (2.44 m) above grade.
z
An existing gate latch shall be disabled when a manually
operated gate is retrotted with a powered gate operator.
z
A gate latch shall not be installed on an automatically
operated gate.
z
Protrusions shall not be permitted on any gate.
Consult ASTM F2200 for exceptions.
z
Gates shall be designed, constructed and installed
such that their movement shall not be initiated by
gravity when an automatic operator is disconnected.
z
For pedestrian access in the vicinity of an automated
vehicular gate, a separate pedestrian gate shall be
provided. The pedestrian gate shall be installed
in a location such that a pedestrian shall not come
in contact with a moving vehicular access gate. A
pedestrian gate shall not be incorporated into an
automated vehicular gate panel.
z
Any non-automated gate that is to be automated shall be
upgraded to conform to the provisions of this speci cation.
z
This speci cation shall not apply to gates generally
used for pedestrian access and to vehicular gates not
to be automated.
z
Any existing automated gate, when the operator
requires replacement, shall be upgraded to conform to
the provisions of this speci cation in effect at that time.
SAFETY REQUIREMENTS
The following provisions shall apply to Class I, Class II,
Class III, and Class IV vehicular horizontal slide gates:
All weight bearing exposed rollers 8 ft (2.44 m), or less,
above grade shall be guarded or covered.
All openings shall be designed, guarded, or screened
from the bottom of the gate to the top of the gate or a
minimum of 72 inch (1.83 m) above grade, whichever is
less, to prevent a 2-1/4 inch (57 mm) diameter sphere
from passing through the openings anywhere in the gate,
and in that portion of the adjacent fence that the gate
covers in the open position. The gate panel shall include
the entire section of the moving gate, including any back
frame or counterbalance portion of the gate.
A gap, measured in the horizontal plane parallel to the
roadway, between a xed stationary object nearest the
roadway (such as a gate support post) and the gate frame
when the gate is in either the fully open position or the
fully closed position, shall not exceed 2-1/4 inches (57
mm).
z Exception: All other xed stationary objects greater
than 16 inches (406 mm) from the gate frame shall not
be required to comply with this section.
Positive stops shall be required to limit travel to the
designed fully open and fully closed positions. These
stops shall be installed at either the top of the gate, or at
the bottom of the gate where such stops shall horizontally
or vertically project no more than is required to perform
their intended function.
All gates shall be designed with sufcient lateral stability
to assure that the gate will enter a receiver guide. Consult
ASTM F2200 for details on various gate panel types.
www.ApolloGateOpeners.com | (800) 878-7829 | [email protected]
8
MAINTENANCE OF GATE SYSTEMS
To keep your automated gate system performing both
safely and reliably it is important to ensure that the
components of that system are functioning properly.
At least monthly:
z Disconnect the gate operator and manually move the
gate through its range of travel. Note any squeaks
from rollers or hinges or areas of binding. The gate
should travel smoothly and quietly throughout its
range. If it does not, contact a gate professional to
correct the problem.
z
Reconnect the gate operator and perform the
following tests:
With the gate opening, block any photo eyes
and/or depress any safety edges used to protect
the open direction. The gate should stop and/or
reverse.
With the gate closing, block any photo eyes and/
or depress any safety edges used to protect the
close direction. The gate should stop and/or
reverse.
Using a suitable obstruction in the path of
the gate (a solid, immovable object), run the
gate in the open direction until it contacts the
obstruction. The gate should stop and reverse.
Using a suitable obstruction in the path of
the gate (a solid, immovable object), run the
gate in the close direction until it contacts the
obstruction. The gate should stop and reverse.
SAFETY REQUIREMENTS
ENTRAPMENT PROTECTION
The UL 325 standard for gate operators requires a
minimum of two independent entrapment protection
means for each entrapment zone.
An entrapment zone is dened as follows:
For slide gates, any locations between a moving gate and
a counter opposing edge or surface where entrapment is
possible up to a height of 6 ft (1.83 m) above grade. Such
locations occur if at any point in travel the gap between
a moving gate and the xed counter opposing edges or
surfaces is less than 16 inches (406 mm).
All Nice HySecurity gate operators feature an Inherent
Entrapment System (IES) (UL 325 Type A) that monitors
the force on the gate during travel. This system protects
in both the open and close direction and reverses on
contact with an obstruction. The IES serves as one of the
means of entrapment protection.
Potential entrapment zones are shown on the next page
for slide gates, but keep in mind there may be other
entrapment zones presented by the actual installation and
adjacent structures or landscape that must be protected
as well. External sensors must be used to protect against
entrapment at each location where an entrapment zone
exists. The minimum number of external sensors required
to enable automatic operation of the gate operator is as
follows:
z Slide Gates: One external sensor in the Open
direction and one external sensor in the Close
direction.
The gate operator tests for the presence of these sensors,
and if the required minimum number is not found, the
operator will only run using continuous pressure on
an Open/Close button, either on the controller, or an
external device.
www.ApolloGateOpeners.com | (800) 878-7829 | [email protected]
9
SAFETY REQUIREMENTS
Gate edge (protecting open direction)
(EDGE OPEN)
Photo eye
Protecting Leading End
(EYE CLOSE)
1
2
3
Draw-in Zone
Slide Gate Potential
Entrapment Zones
1. Draw-in zone
2. Leading end
3. Trailing end
Trailing End
Leading End
PUBLIC
SECURE
5
4
3
2
1
6
Swing Gate Potential
Entrapment Zones
1. Leading Edge
2. Bottom Edge
3. Entry / Exit
4. Posts
5. Post Pivot / Pinch Points
6. Arm Movement
SECURE
PUBLIC
Installers must identify all potential entrapment zones and
install sensors that protect these areas.
Gate edge (protecting open direction)
(EDGE OPEN)
Photo eye
Protecting Leading End
(EYE CLOSE)
1
2
3
Draw-in Zone
Slide Gate Potential
Entrapment Zones
1. Draw-in zone
2. Leading end
3. Trailing end
Trailing End
Leading End
PUBLIC
SECURE
5
4
3
2
1
6
Swing Gate Potential
Entrapment Zones
1. Leading Edge
2. Bottom Edge
3. Entry / Exit
4. Posts
5. Post Pivot / Pinch Points
6. Arm Movement
SECURE
PUBLIC
Installers must identify all potential entrapment zones and
install sensors that protect these areas.
www.ApolloGateOpeners.com | (800) 878-7829 | [email protected]
10
SAFETY REQUIREMENTS
STOP BUTTON
The stop button clears entrapment mode and
resets some faults, errors, and alarms.
The stop button on SmartCNX operators is located
on the cover.
Press the stop button while the gate is opening or
closing to stop gate travel and disable the automatic
close timer. The operator requires a new open or
close command to resume function.
Inform all users of the location of the stop button
and its function.
Figure 1. Stop Button
Stop
Button
Figure 2. DC Switch Set to OFF
Figure 3. Slide the Gate Manually
EMERGENCY RELEASE
Teach all users how to turn off electric power, loosen
the taper clamp and backdrive the operator.
To manually release the gate:
1. Remove the front cover.
2. Set DC power to OFF to disengage the motor.
Note: With DC switch OFF and AC switch ON, the
software will monitor gate position during
backdrive.
3. Manually push the gate open or close.
To return SlideSmart to automatic operation,
follow these steps:
1. Set the DC power switch to ON.
2. Press STOP or RESET to clear any faults.
3. Attach the front cover.
Note: If both DC and AC switches are OFF, the
operator will search for the target magnet to
establish limits upon power up. If the target
magnet is not recognized, the operator will
enter Learn Limits mode.
www.ApolloGateOpeners.com | (800) 878-7829 | [email protected]
11
FEATURES
INTELLIGENT FEATURES: SmartCNX™ Controller
SmartCNX installer smartphone app for full control from your phone. Save operator confi gurations and
troubleshoot system via smartphone app or USB.
User Interface - The SmartCNX controller manages 70+ confi gurable items in a simple menu driven interface.
The controller includes a library of dozens of solutions for relay logic applications.
Three confi gurable user relays plus optional SmartCNX I/O Expansion module for 8 additional relay outputs
OLED display - A 32-character OLED provides increased readability for programming and troubleshooting.
Independent adjustment for open and close gate speeds - An easy-to-use menu on the SmartCNX Controller
allows the installer to independently vary the open and close speed settings.
Intelligent Inherent Entrapment Sensor (IES) - Any impediment to gate travel is sensed by the system, stopping
gate movement per UL 325 Safety Standards. The intelligent system monitors gate power then adapts the IES to
trip at an adjustable threshold above normal power.
Hy5B™ 2.0 vehicle detector with automatic sensitivity adjustment, advanced tailgating detection, and loop health
scoring.
Integrated HyNet™ technology provides remote management capabilities over Ethernet: Securely report gate
system status, vehicle tailgating, gate hits, failure to operate, and more, in real time to maintain perimeter security.
Additionally, confi gure email alerts to communicate issues to installer, facility or security responders.
Compatible with Nice accessories. OXI receiver, ERA and INTI transmitters and BlueBUS photo eyes.
www.ApolloGateOpeners.com | (800) 878-7829 | [email protected]
12
UNPACK THE OPERATOR
UNPACK THE OPERATOR
1. Open the box and remove the front cover, chain
cover, rear cover, edge sensor, photo eye, chain
hardware kit, and ship with kit.
2. Check the contents of the ship with kit:
a. Basic Manual
b. UL 325 required gate safety signs and zip ties
c. DASMA gate safety literature
d. Rear cover mounting hardware
e. Cover keys
f. Chain cover lock pin
g. Optional 208/230VAC and 24VDC voltage
labels
3. Lift the chassis using the lift handles.
Lift Handle
Rear Cover
Front Cover
Chain Cover
Note: You can mark the slots and conduit area on
the plywood underneath the chassis and then
use the plywood as an anchor hole template.
W
20 7/8”
(53 cm)
(COVER WIDTH)
L
15 3/8”
(38 cm)
(COVER DEPTH)
GENERAL OPERATOR DIMENSIONS
H
24 1/2”
(62 cm)
(OPERATOR
HEIGHT)
www.ApolloGateOpeners.com | (800) 878-7829 | [email protected]
13
NEW INSTALLATION
1. Make sure the pad is completely level before
installation.
2. Determine the location of the operator from the
gate (Figure 4).
3. Refer to Figure 4 for minimum dimensions for a
new concrete pad. Refer to Figure 6 for conduit
and earth ground requirements.
4. Mark the anchor hole positions on the concrete
pad (Figure 4).
5. Remove the operator and drill holes for four 1/2
inch UNC x 3-1/2 inch wedge style anchors.
6. Install the anchor bolts, mount the operator on
the bolts, put a heavy duty at washer on each
bolt, and tighten the anchor-bolt nuts.
7. Bury the earth ground rod and connect earth
ground wire to the chassis ground lug.
RETROFIT INSTALLATION
1. Remove any existing operator and anchor bolts.
2. Check the level of the concrete pad and level it if
needed.
3. Position the new SlideSmart CNX operator
around the conduit.
4. Mark the new anchor locations (Figure 4).
5. Remove the operator and drill holes for four 1/2
inch UNC x 3-1/2 inch wedge style anchors.
6. Install the anchor bolts, mount the operator on
the bolts, put a heavy duty at washer on each
bolt, and tighten the anchor-bolt nuts.
7. Route the earth ground wire and connect it to
the earth ground lug.
OPERATOR POSITION
www.ApolloGateOpeners.com | (800) 878-7829 | [email protected]
14
Gate
Chain
Operator cover footprint
PREPARE AN INSTALLATION SITE
Figure 4. Concrete Pad, Anchor Hole, and Conduit Dimensions
Figure 5. Front Installation Chain Height
www.ApolloGateOpeners.com | (800) 878-7829 | [email protected]
15
Figure 6. Conduits and Earth Ground
Figure 7. Preferred Control Wire Routing to SmartCNX Controller
PREPARE AN INSTALLATION SITE
CONDUITS STUBBED
MIN. 2” ABOVE PAD
GROUND LEVEL
INCOMING
HIGH VOLTAGE
VEHICLE
LOOP
CONTROL
WIRES
LOW VOLTAGE/
COMMUNICATION
WIRES
PRIMARY/SECONDARY
WIRES - OPTIONAL
EARTH
GROUND
CONDUIT
3 FOOT
(91cm)
MAXIMUM
Earth
Ground
rod & wire
Consult local
codes for
proper depth
The potential for
lightning discharge
exists with all gates, fences, and
gate operators. National Electric
Code (NEC) requires a separate
earth ground in addition to the
required equipment ground. A local
earth ground also serves to protect
the electronic controls.
DANGER
NOTE: To reduce electrical
interference, keep as much distance
as possible between the high voltage
and low voltage conduits.
ROUTE 6 AWG
EARTH GROUND
WIRE THROUGH
CONDUIT AND
ATTACH TO
PROVIDED
GROUND LUG
HySecurity requires a concrete pad
with a minimum 2 inch extension above
ground and a pad depth of 16 inch or
at least to the frost line, whichever is
deeper. Follow local building codes to
identify the frost line.
www.ApolloGateOpeners.com | (800) 878-7829 | [email protected]
16
ATTACH BACK COVER
Do not overtighten the
top bolts on the sides.
Attach the back cover before you install the chain.
1. If 208V/230V AC incoming power is used, set
the voltage switch on the power supply to the
correct setting with a athead screwdriver before
you attach the back cover. Refer to page 20 for
more information.
2. Set the back cover on the chassis (A).
Note: Make sure that the vertical tab on the
controller mounting bracket is behind the
gasket groove in the back cover (B).
3. Tighten the back cover bolts to snug, sides rst,
and then the back (C).
4. Connect wires to stop button (D).
A
B
D
C
Connect
wires to
stop button
www.ApolloGateOpeners.com | (800) 878-7829 | [email protected]
17
INSTALL CHAIN KIT
1. Set the AC and DC switches to OFF before you
install the chain kit.
2. Install the back cover before you install the chain
kit, page 16.
3. Secure the gate so that it does not move.
4. Position the gate brackets with the center of the
chain hole at 12-7/8 inch height from the bottom
of the operator.
5. Mark the hole positions, drill holes through the
gate, put bolts through the holes, and fasten the
bolts in place.
6. Alternatively, weld the gate brackets in place
(Figure 8 and Figure 9).
7. Attach a tension bolt to each gate bracket
(Figure 10).
8. Route the chain through the idlers and sprocket
(Figure 11).
9. Connect chain ends to tension bolts with
connector link.
10. Check the length of the chain. Add or remove
chain links to make sure chain is within
adjustment.
11. Adjust the bracket eye bolts to reduce sag in the
chain to less than 3 inches.
12. Chain must be parallel to ground and gate
(Figure 9, Figure 12, Figure 13).
Figure 8. Attach Gate Bracket
CORRECT
INCORRECT
INCORRECT
Too close to gate
INCORRECT INSTALLATION
Figure 9. Correct Bracket Height
Figure 10. Attach Tension Bolt
Figure 11. Front Installation Chain Route
CORRECT
Figure 12. Correct Distance to Gate
Figure 13. Incorrect Distance to Gate
www.ApolloGateOpeners.com | (800) 878-7829 | [email protected]
18
ATTACH TARGET MAGNET AND CHAIN COVER
The SlideSmart CNX requires one target magnet as
a "home position" for the software's gate position
monitoring. Two limit sensors are provided, but only
one is used depending on operator handing.
1. Set the AC and DC switches to OFF.
2. Push the gate to the full CLOSED position.
3. Attach the target magnet to a xed link between
the sprocket and the idler furthest from the gate
opening. Point the magnet towards the operator.
LEFT HAND
GATE CLOSED
TARGET
MAGNET
OPENS THIS
DIRECTION
LIMIT
SENSOR
RIGHT HAND
GATE CLOSED
TARGET
MAGNET
OPENS THIS
DIRECTION
LIMIT
SENSOR
Figure 14. Limit Sensor and Target Magnet Position
Figure 15. Target Magnet Toward Operator
Attached to a Fixed Link
1. Align the chain cover tabs to the rear cover slots
and then push down to snap it in place.
2. For additional safety, install the lock pin to
prevent easy removal of the chain cover.
Figure 16. Attach Chain Cover
Figure 17. Install Spring Pin
www.ApolloGateOpeners.com | (800) 878-7829 | [email protected]
19
Wiring 115VAC or 208/230VAC Power
z Verify AC power supply wires and low voltage
accessory wires run through separate conduits.
The input voltage to the AC power supply may
cause interference and anomalies in SmartCNX
operation if the high voltage wires are routed
through the same conduit as the low voltage
wires.
z Maximum gate operator current draw is 7.5
Amps on a dedicated 115VAC circuit (20A
dedicated circuit is recommended).
z Maximum gate operator current draw is 4
Amps on a dedicated 208/230VAC circuit (20A
dedicated circuit is recommended).
z Make sure proper wire gauge is used for the
length of the wire run. The following tables show
the maximum allowable wire run from the power
source to the operator for various wire sizes.
WIRING AND POWER
Table 1. Wire Gauge versus Run
AC Power
14 gauge
wire
12 gauge
wire
10 gauge
wire
One
operator
115V
485 ft
(147 m)
775 ft
(236 m)
1235 ft
(376 m)
Two
operators
115V
242 ft
(73 m)
387 ft
(117 m)
617 ft
(188 m)
Table 2. Wire Gauge versus Run
AC Power
14 gauge
wire
12 gauge
wire
10 gauge
wire
One
operator
208/230V
1375 ft
(419 m)
2185 ft
(665 m)
3475 ft
(1059 m)
Two
operators
208/230V
687 ft
(209 m)
1092 ft
(332 m)
1737 ft
(529 m)
NOTICE
Table 1 and Table 2 assume a dedicated
circuit with an accessory power load up to
2A. Additional loads require that the wire size
be increased or the distance of the run be
decreased.
Figure 18. Voltage Switch Access
Figure 19. Voltage Switch Positions
Operators are factory set for incoming power of
115VAC. If 208/230VAC, change the voltage switch
on the power supply to 230VAC with a athead
screwdriver (Figure 18 and Figure 19).
www.ApolloGateOpeners.com | (800) 878-7829 | [email protected]
20
WIRING AND POWER
1. Make sure both the DC and AC power switches
are in the OFF position.
2. Connect the battery harness to the back right
hand corner of the drive module. (Figure 20)
3. Remove the junction box cover. (Figure 21)
4. Connect the incoming power supply wires to the
AC or DC (solar) terminal block inside the junction
box. Match the wire colors. (Figure 22)
5. Organize all the wire connections and put the
cover onto the junction box.
Note: For 208V/230V or solar (24V) installations,
place the label (included in the ship with kit)
over the factory default 115V 1Ø label.
6. For solar installations, remove the power switch
mounting plate and disconnect the DC wires
from the power supply. Tape or wire nut the ends
separately to prevent shorts (Figure 23).
Note: CNX operators require 24VDC rated solar
panels with a maximum open circuit voltage
of 48VDC.
7. Set both AC and DC power switches to ON
(Figure 24).
8. Software version will appear on LCD display and
then the Setup Menu.
Figure 20. Battery Harness to Drive Module
Figure 21. Junction Box Cover
Figure 22. 115VAC/230VAC and Solar DC Terminals
DANGER
Turn off AC power at the source (circuit breaker
panel) before accessing the wires in the CNX
junction box. Follow facility Lock Out/Tag Out
procedures.
G
L
N
L
G
N
LG N
Blue
(-)
Red
(+)
Blue
(-)
Red
(+)
Connect service outlet lead wires to 115VAC only.
AC
SOLAR
Figure 23. Disconnect DC Power Supply Wires
Figure 24. Set Both Power Switches to ON
www.ApolloGateOpeners.com | (800) 878-7829 | [email protected]
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

Nice HySecurity SlideSmart CNX Slide Gate Operator Guide d'installation

Catégorie
Ouvre-porte
Taper
Guide d'installation
Ce manuel convient également à