Legrand 4000 Series Large Steel Prewired Raceway Guide d'installation

Taper
Guide d'installation
4000 Series
Two-Piece Metal Raceway
INSTALLATION INSTRUCTIONS
Installation Instruction No.: 41403R2 – Updated July 2004
UNSHIELDED SHIELDED
TWISTED PAIR TELEPHONE TWISTED
TYPE 24 AWG, 4-PAIR 24 AWG, NO. OF PAIRS COAXIAL TWINAXIAL PAIR FIBER OPTIC
TWO STRAND (DUPLEX)
CAT. 5 CAT. 3 2 3 4 25 RG58/U RG59/U RG62/U RG6/U 100 OHM TYPE 1 TYPE 2 TYPE 3 MULTIMODE, 62.5/125µm
O.D. inches 0.220 0.190 0.140 0.150 0.190 0.410 0.195 0.242 0.242 0.270 0.330 0.390 0.465 0.245 0.190
O.D. [mm] [5.6] [4.8] [3.6] [3.8] [4.8] [10.4] [5.0] [6.1] [6.1] [6.9] [8.4] [9.9] [11.8] [6.2] [4.8]
40% fill, divided 37 50 92 80 50 10 47 30 30 24 16 11 8 29 49
40% fill, undivided 75 100 183 161 100 21 95 62 62 49 33 23 16 60 100
4000 RACEWAY WIRE FILL CAPACITIES FOR DATA/COMMUNICATIONS
NUMBER OF CONDUCTORS (40% FILL)
WIRE SIZE O.D. WITHOUT DEVICES WITH DUPLEX / RECT. DEVICES WITH SURGE / GFCI DEVICES LARGE SINGLE RECEPTACLES
THHN/THWN inches [mm] 1.59 in
2
[1025mm
2
] 2.30 in
2
[1485mm
2
] 3.00 in
2
[1935mm
2
]
UNDIVIDED DIVIDED UNDIVIDED DIVIDED UNDIVIDED DIVIDED UNDIVIDED DIVIDED
14 AWG 0.111 [2.8] 296 127 165 78 107 49 49 20
12 AWG 0.130 [3.3] 216 93 120 57 78 36 36 15
10 AWG 0.164 [4.2] 136 58 76 36 49 22 22 9
8 AWG 0.216 [5.5] 78 33 43 20 28 13 13 5
6 AWG 0.254 [6.5] 56 24 31 15 20 9 9 3
4AWG 0.324 [8.2] 34 15
3 AWG 0.352 [8.9] 29 12
2AWG 0.384 [9.8] 24 10
4000 RACEWAY WIRE FILL CAPACITY FOR POWER
Use No. 8 (5/16", 7.9mm head size) flat head fastener or equivalent to
mount base to surface.
Utiliser une attache à tête plate de calibre 8 (tête de 7.9mm, 5/16" po.)
ou une fixation équivalente pour assujettir le tube guide-fils et les rac-
cords à la surface de montage.
Use un sujetador de cabeza plana No. 8 (tamaño de cabeza: 7.9mm,
5/16" de pulgada) o su equivalente para unir la canalita y los accesorios
a la superficie de montaje.
•Grounding: Use ground location when provided or install a suitable
ground lug, ring terminal or locknut and ground bushing.
Mise à la terre: Utiliser l’emplacement de terre prévu ou poser le
matériel qui convient: patte de mise à la terre, cosse circulaire à oeil ou
écrou de blocage et manchon de terre.
Conexión a tierra: Use un localizador de tierra cuando se proporcione o
instale una orejeta de tierra, anillo terminal o contratuerca y cojinetes de
tierra apropiados.
18"
[45.7cm]
30"
[76cm]
4000B-10640B 640C
4000WC
4010B
4010D 4011
4000C075 = 12" [30.5cm] 4000C135 = 18" [45.7cm]
4000C195 = 24" [60.9cm] 4000C315 = 36" [91.4cm]
4001DA
4001DA
4000C
Precut
Covers
4014A 4015 4015D 4018
Wiremold Electrical Systems conform to and should be
installed and properly grounded in compliance with
requirements of the current National Electrical Code, Canadian
Electrical Code or codes administered by local authorities.
All electrical products may represent possible shock or fire
hazard if improperly installed or used. Wiremold electrical
products are UL Listed to U.S. and Canadian safety
standards, made for interior use only, and should be installed
in conformance with current local and/or the National
Electrical Code.
4012TX
4017
4017N
45°
4017TC
4074
4074A
4086A
4046H-2
1 2 3 4
1 2
1 2
1 2
1 2 3 4
4010DFO FiberReady™ Entrance End Fitting
1 2
3
4
4012TX
1
2 3
45°
The Wiremold Company
U.S. and International:
60 Woodlawn Street • West Hartford, CT 06110
1-800-621-0049 • FAX 860-232-2062 • Outside U.S.: 860-233-6251
Canada:
850 Gartshore Street • Fergus, Ontario N1M 2W8
1-800-741-7957 • FAX 519-843-5980
41403R2 – Updated July 2004 – For latest specs visit www.wiremold.com
© Copyright 2004 The Wiremold Company All Rights Reserved