Simplicity 071049-00 Manuel utilisateur

Catégorie
Groupes électrogènes
Taper
Manuel utilisateur
100/150/200 Amp Automatic
Transfer Switch
with Service Disconnect and
Symphony™ II Power Management System
Operator’s Manual
Questions?
Help is just a moment away!
Call: Transfer Switch Helpline
800-743-4115 Monday - Friday 8:00 AM - 5:00 PM Central Time
NOT
for
REPRODUCTION
2 BRIGGSandSTRATTON.COM
Thank you for your purchase of this Briggs & Stratton® automatic transfer switch. This product is designed for use with specific home
standby generators and may not function with generators or remote modules produced by other manufacturers. Seek a qualified electrical
professional to determine applicability of this equipment to equipment manufactured by others. When operated and maintained according to
the instructions in this manual, your system will provide many years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with this system and how to avoid them.
We have made every effort to provide for a safe, streamlined and cost-effective installation. As each installation is unique, it is impossible
to know of and advise of all conceivable procedures and methods by which installation might be achieved. We do not know all possible
hazards and/or the results of each possible method or procedure. It is important that you read and understand these instructions thoroughly
before attempting to install or operate this equipment. Save these original instructions for future reference.
This transfer switch and optional remote modules require professional installation before use. Refer to the Installation Manual and the
installation instructions packaged with the remote modules for instructions on installation procedures. Only licensed electrical contractors
should install transfer switches and remote modules. Installations must strictly comply with all applicable federal, state and local codes,
standards and regulations. Your installer should follow the instructions completely.
Where to Find Us
You never have to look far to find Briggs & Stratton support and service for your system. Consult your Yellow Pages. There are many
authorized service dealers who provide quality service. You can also contact Technical Service by phone at 800-743-4115 between 8:00 AM
and 5:00 PM CT, or click on Find a Dealer at BRIGGSandSTRATTON.COM, which provides a list of authorized dealers.
Copyright © 2013. Briggs & Stratton Corporation
Milwaukee, WI, USA. All rights reserved.
NOT
for
REPRODUCTION
3
Table of Contents
Important Safety Instructions .............................4
Installation..........................................5
Home Owner Responsibilities ..........................................5
Owner Orientation ...................................................5
Installing Dealer/Contractor Responsibilities...............................5
Equipment Description ...............................................6
Delivery Inspection ..................................................7
Testing the Automatic Transfer Switch ...................................7
Controls ............................................8
Operation...........................................8
Enclosure Door .....................................................8
Symphony™ II Power Monitor (Optional) .................................9
Maintenance........................................10
Product Specifications .................................12
NOT
for
REPRODUCTION
4 BRIGGSandSTRATTON.COM
Important Safety Instructions
SAVE THESE INSTRUCTIONS - This manual contains important
instructions that should be followed during installation and
maintenance of the equipment.
Safety Symbols and Meanings
The safety alert symbol indicates a potential personal injury
hazard. A signal word (DANGER, WARNING, or CAUTION) is used
with the alert symbol to designate a degree or level of hazard
seriousness. A safety symbol may be used to represent the type of
hazard. The signal word NOTICE is used to address practices not
related to personal injury.
DANGER indicates a hazard which, if not avoided, will result in
death or serious injury.
WARNING indicates a hazard which, if not avoided, could result
in death or serious injury.
CAUTION indicates a hazard which, if not avoided, could result
in minor or moderate injury.
NOTICE addresses practices not related to personal injury.
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard. The warnings in this
manual, and the tags and decals affixed to the unit are, therefore,
not all-inclusive. If you use a procedure, work method or operating
technique that the manufacturer does not specifically recommend,
you must satisfy yourself that it is safe for you and others. You
must also make sure that the procedure, work method or operating
technique that you choose does not render the equipment unsafe.
Electrical Shock Read Manual
Save These Instructions
NOTICE Only qualified electricians should attempt installation
of this equipment, which must strictly comply with applicable
codes, standards and regulations.
WARNING Certain components in this product and related
accessories contain chemicals known to the State of California
to cause cancer, birth defects, or other reproductive harm. Wash
hands after handling.
WARNING Shock Hazard. Installing low and high voltage
wire in same conduit could result in death or serious
injury.
• Do not run low and high voltage wire in the same conduit unless
the insulation rating on ALL wiring is rated for 600V. See NEC
for more information.
WARNING Shock Hazard. Failure to properly ground
equipment could cause electrocution resulting in death
or seriousinjury.
• Do not touch bare wires.
• Do not use equipment with worn, frayed, bare or otherwise
damaged wiring.
• Do not handle electrical cords while standing in water, while
barefoot, or while hands or feet are wet.
• If you must work around a unit while it is operating, stand on an
insulated dry surface to reduce shock hazard.
• Do not allow unqualified persons or children to operate or
service equipment.
• In case of an accident caused by electrical shock, immediately
shut down all sources of electrical power and contact local
authorities. Avoid direct contact with the victim.
WARNING Shock Hazard. Equipment contains high voltage
that could cause electrocution resulting in death or
seriousinjury.
• Do not operate this equipment imprudently, carelessly or neglect
its maintenance.
NOTICE Improper treatment of equipment could damage it and
shorten its life.
• Use equipment only for intended uses.
• If you have questions about intended use, ask dealer or contact
Briggs & Stratton Power Products.
• Do not expose equipment to excessive moisture, dust, dirt, or
corrosive vapors.
• Remain alert at all times while working on this equipment. Never
work on the equipment when you are physically or
mentally fatigued.
• If connected devices overheat, turn them off and turn off their
circuit breaker/fuse.
NOT
for
REPRODUCTION
5
Installation
We sincerely appreciate your patronage and have made significant
effort to provide for a safe, streamlined and cost-effective
installation. Because each installation is unique, it is impossible
to know of and advise the trade of all conceivable procedures and
methods by which installation might be achieved. Neither could we
know of possible hazards and/or the results of each
method or procedure.
For these reasons, only current licensed electrical professionals
should attempt system installations. Installations must strictly
comply with all applicable codes, industry standards
and regulations.
Your equipment is supplied with this Operator’s Manual and an
Installation Manual. These are important documents and should be
retained by the owner after the installation has been completed.
Every effort has been made to make sure that the information
in this manual is both accurate and current. However, the
manufacturer reserves the right to change, alter or otherwise
improve the system at any time without prior notice.
NOTICE Before drilling conduit entry holes, or any other holes,
cover and protect the switch and electronics to prevent dirt and
metal fragments from entering the mechanical and electrical
components. Failure to do so may result in damage or malfunction
of the switch.
NOTICE Use a vacuum to clean any dirt or metal shavings inside
the transfer switch. Do not use a blower or compressed air to clean
the inside of the transfer switch because debris may become lodged
in the electrical and mechanical components causing damage or
malfunction.
Home Owner Responsibilities
To help you make informed choices and communicate effectively
with your installation contractor(s), read and understand Owner
Orientation before contracting or starting your
equipment installation.
To arrange for proper installation, contact the store at which you
purchased your equipment, your dealer, or your utility
power provider.
The equipment warranty is VOID unless the system is installed by
licensed electrical professionals.
Owner Orientation
The illustrations provided are for typical circumstances and are
meant to familiarize you with the installation options available with
your system.
Local codes, appearance, and distances are the factors that must
be considered when negotiating with an installation professional.
As the distance from the existing electrical service increases,
compensation in wiring materials must be allowed for. This is
necessary to comply with local codes and overcome electrical
voltage drops.
These factors will have a direct effect on the overall price of your
equipment installation.
Your installer must check local codes AND obtain permits before
installing the system.
• Readandfollowtheinstructionsgiveninthismanual.
• Followaregularscheduleincaringforandusingyour
equipment, as specified in this manual.
Installing Dealer/Contractor Responsibilities
• ReadandobservetheImportantSafetyInstructions.
• Readandfollowtheinstructionsgiveninthismanual.
• Theinstallermayneedtoprovideappropriateratedcontactors
based on loads to be controlled.
• Discusswithownertheirloadprioritypreferencestodecide
on remote module priority settings.
• Checkfederal,stateandlocalcodesandauthorityhaving
jurisdiction, for questions on installation.
• Ensuregeneratorisnotoverloadedwithselectedloads.
If you need more information about the transfer switch, call 800-
743-4115, between 8:00 AM and 5:00 PM CT.
NOT
for
REPRODUCTION
6 BRIGGSandSTRATTON.COM
Equipment Description
The transfer switch is designed to transfer selected loads found
in normal residential installations to standby power in the event
of a primary power outage. The load is connected either to utility
power (normal) or home standby power (generator). The transfer
switch monitors utility and generator voltages and will automatically
connect loads to the appropriate source of power.
The Symphony™ II Power Management System is highly flexible
and utilizes individual high and low voltage modules that can be
mounted anywhere between the home’s main distribution panel and
the managed appliance. Designed to communicate via your home’s
existing power wiring, the power demand and priority sequence of
up to 8 appliance loads are relayed back to the standby generator,
effectively preventing generator overload while expanding power
range and performance. The system is scalable and additional
relays can be added as a homeowner’s power management needs
change over time.
Only a licensed electrician should complete a home standby
installation. Service conduit and conductors can be wired directly
from the watt-hour meter to the transfer switch. A separate service
entrance disconnect and associated wiring is not required when
installed per applicable federal, state and local codes, standards
andregulations.
Major components of the transfer switch are a 2 pole utility
disconnect circuit breaker, a 2 pole generator disconnect circuit
breaker, a 2 pole double throw transfer switch, transfer switch
control circuit board, Symphony II power management system
control circuit board, fused utility terminals and interconnecting
wiring. All of these components are housed in a NEMA3R
enclosure that is suitable for both indoor and outdoor installations.
The transfer switch is solenoid-operated from utility or generator
inputs and contain suitable mechanical and electrical interlock
switches to eliminate the possibility of connecting the utility service
to the generator output. It has ratings capable of switching full
utility power into the residence. In addition, a manual override lever
is provided for the transfer function.
The transfer switch control board has active circuits sensing utility
and generator voltages. It creates a signal for generator start-up,
switch transfer and retransfer when utility is restored. The transfer
switch control board provides status LED’s to indicate the power
source available.
The Symphony™ II power management system control board
contains a test button, a status LED and eight priority load LED’s. It
creates and sends signals to optional remote modules, instructing
them when to add (turn power on) or shed (turn power off) the
managedload.
The Symphony II system power line carrier technology has been
rigorously tested and has proven to be very robust. However,
certain types of devices and appliances in the home generate
‘noise’ on the power line. Such devices may include non-residential
fluorescent ballasts, dimmers, speed controls (lighting and fans),
bathroom equipment, kitchen equipment, power tools, phone
chargers, and power supplies. These types of devices have the
greatest impact on power line communication when located close
to a remote module.
AM broadcast radio, X10, power line carrier (PLC), uninterrupted
power supply (UPS), transient voltage surge suppression (TVSS)
systems, and power filter technology may also cause the Symphony
II system to not operate as intended. They may cause interference
with the Symphony II system during standby power operation.
If it is determined that power line noise is causing a communication
issue with the Symphony II system, the following changes may
remedy the issue.
• Havecommercial(nonconsumeruse)fluorescentballasts
replaced with residential use ballasts.
• HaveaEMI/RFIfilterinstalledinseriesandnearthe
problematic device.
• Havetheremotemodulerewiredtotheoppositepowerline
(Line 1 or Line 2) from that of the problematic device.
• RefertoTroubleshootingsection.
The optional 50 Amp remote module is designed for control by
the Symphony II system to add or shed appliance loads connected
to it based on a user-defined priority setting. This remote module
manages 120VAC or 240VAC, single or double pole loads up to
50 amperes. The remote module’s relay state is normally open. Its
components are housed in a NEMA4 enclosure suitable for indoor
and outdoorinstallations.
The optional low voltage remote module is designed for control
by the Symphony II system to add or shed an air conditioner, heat
pump, or low voltage contactor controlled loads based on a user-
defined priority setting. The remote module is housed in a NEMA4
enclosure suitable for indoor and outdoor installations.
NOT
for
REPRODUCTION
7
Delivery Inspection
After opening the carton, carefully inspect the transfer
switch components for any damage that may have occurred
duringshipment.
If loss or damage is noted at time of delivery, have the person(s)
making delivery note all damage on the freight bill and affix his
signature under the consignor’s memo of loss or damage. If loss
or damage is noted after delivery, contact the carrier for claim
procedures. Missing or damaged parts are not warranted.
Shipment contents:
• Automatictransferswitch
• Installationandoperator’smanuals
• Currenttransformers(2)
Optional components:
• 50Ampmodule
• Lowvoltagemodule(singleordualmodels)
• Symphony™IIpowermonitor
To be supplied by installer:
• Connectingwireandconduit
• Variousspecialtytools/equipment
Testing the Automatic Transfer Switch
Turn the utility service disconnect circuit breaker feeding the
transfer switch contactor to the OFF position. The system’s
automatic sequence described below will initiate. To return to utility
power, turn the utility service disconnect circuit breaker to
the ON position.
Utility Fail
The generator senses when utility voltage is below 70percent of
nominal. Engine start sequence is initiated after
6second time delay.
Engine Warm-Up
Time delay to allow for engine warm-up before transfer. Use jumper
on transfer switch control board to select delay of 20seconds
or 50 seconds.
Transfer
Transfer from utility to generator supply occurs after voltage is
above set levels. The transfer switch control board LED lights will
change from green (utility) to red (generator) and the Symphony II
status light will change blink status from Blink Blink_Pause_Blink
Blink to Blink_Pause_Blink. Minimum engine run time is
5 minutes after transfer.
Load Management
Five minutes after transfer to generator power, the remote modules
energize connected load(s) if generator power is available, starting
with the highest priority (1) through the lowest priority (8). There is
a 10 second delay between each sequential activation.
The P1 through P8 LED’s (A) on the Symphony II control board will
illuminate to show loads being added.
Loads connected to remote modules set to priorities 9 and 10
remain off for the duration of a utility power outage.
Utility Pickup
Voltage pickup level is 80 percent of nominal voltage.
Retransfer
Retransfer from generator to utility power is approximately 10
seconds after utility voltage supply is above pickup level and
minimum run time is completed. All remote module(s) will remain
OFF for five minutes after the power transfer.
Engine Cool Down
Engine will run for 60 seconds after retransfer.
WARNING Shock Hazard. Equipment contains high voltage
that could cause electrocution resulting in death or
serious injury.
• Testing must only be performed by qualified personnel.
• Do not operate this equipment imprudently, carelessly or neglect
its maintenance.
NOT
for
REPRODUCTION
8 BRIGGSandSTRATTON.COM
Controls
Other than a Manual Override lever, there are no operator controls
because this is an automatic transfer switch. The manual override
is to be used only by licensed professionals. Information on handle
use can be obtained by calling Technical Service at 800-743-4115.
Operation
To select automatic transfer operation, do the following:
1. In transfer switch, set utility disconnect circuit breaker
to ON position.
2. In transfer switch, set generator disconnect circuit breaker to
ON position.
3. Install 15 Amp fuse in generator’s control panel.
4. Set generator’s circuit breaker to ON position.
5. Set generator’s system switch to AUTO position.
The system will now be in automatic operation mode.
When the generator is providing power to the transfer switch, the
transfer switch control board is constantly monitoring generator
power and communicating with the Symphony II system
control board.
The Symphony II system will control up to 8 priorities, with priority
9 and 10 as lockouts. When total generator load meets a preset
value, the Symphony II system control board will start shedding
loads, starting with the lowest priority (highest number) load. The
Symphony II system will add or shed managed loads based on the
generator output capacity and priority settings.
The Symphony II system waits 10 seconds between adding
or shedding each load to permit the system to stabilize. If too
much load demand is seen, the Symphony II system will shed all
managed loads quickly to prevent the generator from overloading.
Once the load demand has stabilized, the Symphony II system will
re-load the generator after a 5 minute delay, as describedabove.
There is a minimum five minute delay between the time utility
power is lost and priority 1 loads are energized by the
Symphony II system.
Be aware that managed heating element energy loads (such as
electric range burners, oven, or space heaters) that were ON
when utility power was lost, will be ON when the generator begins
supplying power. It is advised that the owner check all such
managed devices to ensure they are turned OFF before generator
power appears.
Managed devices like clothes dryers that require pressing a START
button will not resume operation unless the START button is
pressed after generator power begins.
Enclosure Door
To open transfer switch door, press the spring-load door lock to the
right and pull down on the door.
To close and latch door, push door closed against enclosure. While
in this position, push door upwards. This will cause spring-load
door lock to engage and latch door in place. Enclosure door MUST
be closed and latched at all times except when system is
being serviced.
NOT
for
REPRODUCTION
9
Symphony™ II Power Monitor (Optional)
For your convenience, a Symphony II Power Monitor is available,
which provides a visual “on/off” status of each managed appliance/
load. A series of LED lights are ON when an appliance has
generator power and OFF when the appliance is in a shed mode or
does not have power. When on generator power, the consumer can
see which appliances are beingmanaged.
A decal is provided that can be labeled with the managed
appliances/loads and placed next to each priorityLED.
The monitor is plugged into any convenient standard outlet within
the home and constantly receives system status via the power
line communication technology utilized by the Symphony II Power
Management System during generator power.
Symphony II Power Monitor (Optional)
POWER LIGHT (A)
When lit, indicates that monitor detects outlet power.
When not lit, indicates that no power is present at outlet.
COMM (communication status) LIGHT (B)
When lit, indicates that unit is receiving signals from the Symphony
II controller.
When not lit, indicates that utility power is present or a fault in
Symphony II controller.
PRIORITY LIGHTS/LED’s (C)
When green LED is lit, indicates
that optional remote module set
to that priority is supplying power
to connected load during
generator power.
When not lit, indicates that
optional remote module set to
that priority is set to OFF (being
managed and Symphony II
System is not allowing power to
the unit).
All lights/LED’s are OFF when
utility power is present.
A
B
C
312113
NOT
for
REPRODUCTION
10 BRIGGSandSTRATTON.COM
Maintenance
The transfer switch is designed to be maintenance free under
normal usage. However, inspection and maintenance checks should
be made on a regular basis. Maintenance will consist mainly of
keeping the transfer switch clean.
Visual inspections should be done at least three times each
year. Access to the transfer switch and optional remote modules
must not be obstructed. Keep 3 feet (92 cm) clearance around
transfer switch. Check for an accumulation of dirt, moisture and/
or corrosion on and around the enclosure, loose parts/hardware,
cracks and/or discoloration to insulation, and damaged or
discolored components.
Exercise the transfer switch and Symphony II system at least once
every three months as described in Testing the Automatic Transfer
Switch and in Testing the Symphony II Power Management System
unless a power outage occurs and the entire home generator
system has gone through an automatic sequence. Allow generator
to run for at least 10minutes during exercisecycle.
Contact a licensed electrical professional to inspect and clean
the inside of the enclosure and other components of your home
generator system at least once a year.
When Calling for Assistance
You must have the Model Number and Serial Number from each
transfer switch or remote module ID label at hand if it is necessary
to contact a local service center regarding service or repair. Obtain
this information from the unit ID labels located on or inside device.
For convenience, record the information on the inside front cover of
this manual.
To contact Briggs & Stratton call 800-743-4115, between 8:00 AM
and 5:00 PM CT.
NOT
for
REPRODUCTION
11
ABOUT YOUR WARRANTY
We welcome warranty repair and apologize to you for being inconvenienced. Any Authorized Service Dealer may perform warranty repairs. Most warranty
repairs are handled routinely, but sometimes requests for warranty service may not be appropriate. For example, warranty service would not apply if
equipment damage occurred because of misuse, lack of routine maintenance, shipping, handling, warehousing or improper installation. Similarly, the warranty
is void if the manufacturing date or the serial number on the equipment has been removed or the equipment has been altered or modified. During the warranty
period, the Authorized Service Dealer, at its option, will repair or replace any part that, upon examination, is found to be defective under normal use and
service. This warranty will not cover the following repairs and equipment:
• Normal Wear: Outdoor Power Equipment, like all mechanical devices, needs periodic parts and service to perform well. This warranty does not cover
repair when normal use has exhausted the life of a part or the equipment.
• Installation and Maintenance: This warranty does not apply to equipment or parts that have been subjected to improper or unauthorized installation
or alteration and modification, misuse, negligence, accident, overloading, improper maintenance, repair or storage so as, in our judgment, to adversely
affect its performance and reliability. This warranty also does not cover normal maintenance such as adjustments, cleaning and fuse replacement.
• Other Exclusions: This warranty excludes wear items or damage or malfunctions resulting from accidents, abuse, modifications, alterations, or
improper servicing. Accessory parts are excluded from the product warranty. This warranty excludes failures due to acts of God and other force
majeure events beyond the manufacturers control. Also excluded is used, reconditioned, and demonstration equipment. 198180E, Rev. C, 12/31/2006
BRIGGS & STRATTON
MILWAUKEE, WI, USA
BRIGGS & STRATTON TRANSFER SWITCH OWNER WARRANTY POLICY
LIMITED WARRANTY
Briggs & Stratton will repair or replace, free of charge, any part(s) of the equipment that is defective in material or workmanship or both. Transportation
charges on product submitted for repair or replacement under this warranty must be borne by purchaser. This warranty is effective for the time
periods and subject to the conditions stated below. For warranty service, find the nearest Authorized Service Dealer in our dealer locator map at
BRIGGSandSTRATTON.COM.
THERE IS NO OTHER EXPRESS WARRANTY. IMPLIED WARRANTIES, INCLUDING THOSE OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE, ARE LIMITED TO ONE YEAR FROM PURCHASE, OR TO THE EXTENT PERMITTED BY LAW. ANY AND ALL IMPLIED
WARRANTIES ARE EXCLUDED. LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES ARE EXCLUDED TO THE EXTENT EXCLUSION IS
PERMITTED BY LAW. Some states or countries do not allow limitations on how long an implied warranty lasts, and some states or countries do not allow
the exclusion or limitation of incidental or consequential damages, so the above limitation and exclusion may not apply to you. This warranty gives you
specific legal rights and you may also have other rights which vary from state to state or country to country.
Effective November 1, 2005 replaces all undated Warranties and all Warranties dated before November 1, 2005
The warranty period begins on the date of purchase by the first retail consumer or commercial end user, and continues for the period of time stated in the
table above. “Consumer use” means personal residential household use by a retail consumer. “Commercial use” means all other uses, including use for
commercial, income producing or rental purposes. Once equipment has experienced commercial use, it shall thereafter be considered as commercial use for
purposes of this warranty. Equipment used for prime power in place of utility are not applicable to this warranty.
NO WARRANTY REGISTRATION IS NECESSARY TO OBTAIN WARRANTY ON BRIGGS & STRATTON PRODUCTS. SAVE YOUR PROOF OF
PURCHASE RECEIPT. IF YOU DO NOT PROVIDE PROOF OF THE INITIAL PURCHASE DATE AT THE TIME WARRANTY SERVICE IS REQUESTED,
THE MANUFACTURING DATE OF THE PRODUCT WILL BE USED TO DETERMINE THE WARRANTY PERIOD.
3 years
None
Consumer Use
Commercial Use
WARRANTY PERIOD
NOT
for
REPRODUCTION
12 BRIGGSandSTRATTON.COM
Automatic Transfer Switch
Product Specfications
Model 071048
Rated Maximum Load Current
a 25°C (77°F)* ..............................................................100 Amps
Rated AC Voltage. ..............................................................250 Volts
Poles ............................................................................................... 2
Frequency ................................................................................60 Hz
Fault Current Rating ..........22,000 RMS Symmetrical Amperes on Utility Side
................................. 10,000 RMS Symmetrical Amperes on Generator Side
Normal Operating Range ...............-28.8°C (-20°F) to 40°C (104°F)
Weight ........................................................................27 kg (59 lbs)
Model 071049
Rated Maximum Load Current
a 25°C (77°F)* ..............................................................200 Amps
Rated AC Voltage. ..............................................................250 Volts
Poles ............................................................................................... 2
Frequency ................................................................................60 Hz
Fault Current Rating ..........
25,000 RMS Symmetrical Amperes on Utility Side
................................. 10,000 RMS Symmetrical Amperes on Generator Side
Normal Operating Range ...............-28.8°C (-20°F) to 40°C (104°F)
Weight ........................................................................28 kg (63 lbs)
This transfer switch is a UL Listed device.
Model 071054
Rated Maximum Load Current
a 25°C (77°F)* ..............................................................200 Amps
Rated AC Voltage. ..............................................................250 Volts
Poles ............................................................................................... 2
Frequency ................................................................................60 Hz
Fault Current Rating ..........25,000 RMS Symmetrical Amperes on Utility Side
................................. 10,000 RMS Symmetrical Amperes on Generator Side
Normal Operating Range ...............-28.8°C (-20°F) to 40°C (104°F)
Weight ........................................................................28 kg (63 lbs)
Model 071070
Rated Maximum Load Current
a 25°C (77°F)* ..............................................................150 Amps
Rated AC Voltage. ..............................................................250 Volts
Poles ............................................................................................... 2
Frequency ................................................................................60 Hz
Fault Current Rating ..........
25,000 RMS Symmetrical Amperes on Utility Side
................................. 10,000 RMS Symmetrical Amperes on Generator Side
Normal Operating Range ...............-28.8°C (-20°F) to 40°C (104°F)
Weight ........................................................................28 kg (63 lbs)
NOT
for
REPRODUCTION
Manual operario
100/150/200 Amperios Interruptor de
transferencia automática
con seccionador de servicio y sistema degestión
de energía Symphony™ II
Preguntas?
La ayuda es justa un momentolejos!
Llamada: Línea Directa de generador de hogar
800-743-4115 M-F 8-5 CT
NOT
for
REPRODUCTION
2 BRIGGSandSTRATTON.COM
Gracias por comprar este conectador automático de Briggs & Stratton®. Este producto está diseñado para utilizarse con generadores de
reserva domésticos específicos y puede no funcionar con generadores o módulos remotos producidos por otros fabricantes. Recurra a un
electricista profesional cualificado para determinar si este equipo se puede utilizar con equipo fabricado por terceros. Si se utiliza y mantiene
de acuerdo con las instrucciones de este manual, su sistema le proporcionará muchos años de funcionamiento fiable.
Este manual contiene información de seguridad para que usted conozca los peligros y riesgos propios de este sistema y cómo evitarlos.
Se ha realizado el máximo esfuerzo para que la instalación resulte segura, sencilla y económica. Debido a que cada instalación es única,
es imposible conocer y recomendar todos los procedimientos y métodos posibles para efectuarla. No conocemos todos los riesgos y/o
resultados posibles de cada método o procedimiento existente. Es importante que lea y comprenda perfectamente estas instrucciones antes
de intentar instalar o utilizar este equipo. Guarde estas instrucciones para futuras consultas.
Este conectador y los módulos remotos opcionales deben ser instalados por un profesional antes de utilizarlos. Consulte la sección de
instalación de este manual y las instrucciones de instalación que vienen con los módulos remotos. Los conectadores y los módulos remotos
sólo deben ser instalados por electricistas con licencia. Las instalaciones deben cumplir estrictamente la totalidad de los códigos, estándares
y regulaciones federales, estatales y locales vigentes. El instalador debe seguir las instrucciones detalladamente.
Para futuras consultas
Llene la siguiente información y conserve su factura para facilitar la identificación de la unidad en caso de que surjan problemas relacionados
con la compra en el futuro.
Copyright © 2013. Briggs & Stratton Corporation
Milwaukee, WI, USA. Reservados todos los derechos.
NOT
for
REPRODUCTION
3
Tabla de contenido
Instrucciones Importantes deSeguridad......................4
Instalación ..........................................5
Responsabilidades del propietario.......................................5
Orientación al propietario .............................................5
Re sponsabilidades del distribuidor / técnicoinstalador ......................5
Descripción del equipo ...............................................5
Inspección en el momento de la entrega..................................6
Controles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Funcionamiento ......................................8
Puerta de la caja ....................................................8
Monitor de alimentación Symphony™ II (opcional) .........................9
Mantenimiento ......................................10
Especificaciones del producto............................12
NOT
for
REPRODUCTION
4 BRIGGSandSTRATTON.COM
Instrucciones importantes deseguridad
GUARDE ESTAS INSTRUCCIONES - Este manual contiene
instrucciones importantes que se deben seguir durante la
instalación y el mantenimiento delequipo.
Símbolos sobre la seguridad y significados
El símbolo de alerta de seguridad indica un posible riesgo
para su integridad física. Se utiliza una palabra de señalización
(PELIGRO, ADVERTENCIA o ATENCIÓN) junto con el símbolo de
alerta para designar un grado o nivel de gravedad de riesgo. Se
puede utilizar un símbolo de seguridad para representar el tipo
de riesgo. La palabra de señalización AVISO se utiliza para hacer
referencia a una práctica no relacionada con una lesión física.
PELIGRO indica un riesgo que, de no evitarse, provocará la
muerte o lesiones de gravedad.
ADVERTENCIA indica un riesgo que, de no evitarse, podría
provocar la muerte o lesiones de gravedad.
ATENCIÓN indica un riesgo que, de no evitarse, podría provocar
lesiones leves o moderadas.
AVISO hace referencia a una práctica no relacionada con una lesión
física.
El fabricante no puede prever toda circunstancia que conlleve
un riesgo potencial. Por tanto, las advertencias de este manual,
así como las etiquetas y calcomanías adheridas a la unidad, no
incluyen todos los riesgos posibles. Si utiliza un procedimiento,
método de trabajo o técnica de uso no recomendado
específicamente por el fabricante, deberá asegurarse de que es
seguro tanto para usted como para otras personas. También deberá
asegurarse de que el procedimiento, método de trabajo o técnica de
uso que elija no hace que el equipo sea inseguro.
Guarde estas instrucciones
Descarga eléctrica
Lea el manual
AVISO La instalación de este equipo debe cumplir estrictamente
la totalidad de los códigos, estándares y regulaciones vigentes,
por lo que sólo debe ser llevada a cabo por un
electricista cualificado.
ADVERTENCIA Determinados componentes en este producto
y los accesorios relacionados contienen sustancias químicas
declaradas cancerígenas, causantes de malformaciones, y otros
defectos congénitos por el Estado de California. Lávese las
manos después de manipular estos elementos.
ADVERTENCIA Peligro de descarga. La instalación de un
cable de baja y alta tensión en el mismo conducto podría
provocar lesiones graves o incluso la muerte.
• No tienda un cable de baja y alta tensión en el mismo conducto
a menos que el valor nominal de aislamiento en TODO el
cableado sea de 600 V. Para obtener más información, consulte
el NEC.
ADVERTENCIA Peligro de descarga. Una conexión a tierra
defectuosa del equipo podría provocar electrocución, así
como lesiones graves o incluso la muerte.
• No toque los cables pelados.
• No utilice el equipo con cables desgastados, deshilachados o
deteriorados de cualquier otra forma.
• No manipule los cables eléctricos si se encuentra en una zona
húmeda, está descalzo o tiene las manos o los piesmojados.
• Si tiene que trabajar junto a una unidad en funcionamiento,
manténgase en una superficie aislada y seca para reducir el
riesgo de descarga eléctrica.
• No permita que personas no cualificadas o niños utilicen o
reparen el equipo.
• En caso de accidente provocado por una descarga eléctrica,
desconecte inmediatamente todos los suministros de energía
eléctrica y póngase en contacto con las autoridades locales.
Evite el contacto directo con la víctima.
ADVERTENCIA Peligro de descarga. El equipo contiene alta
tensión que podría provocar electrocución, así como
lesiones graves o incluso la muerte.
• No utilice este equipo de un modo imprudente, sin tener cuidado
o con negligencia en cuanto a su mantenimiento.
AVISO Un tratamiento inadecuado del equipo podría estropearlo
y acortar su vida útil.
• Utilice el equipo sólo para los usos previstos.
• En caso de dudas sobre su uso, diríjase al distribuidor o a Briggs
& Stratton Power Products.
• No exponga el equipo a un exceso de humedad, polvo, suciedad
o vapores corrosivos.
• Manténgase alerta en todo momento cuando utilice este equipo.
Nunca lo utilice ni manipule en condiciones de fatiga física o
mental.
• Si se calientan excesivamente los dispositivos conectados,
apáguelos y abra sus interruptores o quite sus fusibles.
NOT
for
REPRODUCTION
5
Instalación
Agradecemos sinceramente que nos haya elegido, por lo que
hemos realizado un esfuerzo importante para que la instalación
resulte segura, sencilla y económica. Debido a que cada
instalación es única, es imposible conocer y recomendar todos
los procedimientos y métodos posibles para efectuarla. Tampoco
conocemos todos los riesgos y/o resultados posibles de cada
método o procedimiento.
Por tanto, la instalación del sistema sólo puede ser llevada a
cabo por electricistas profesionales con licencia vigente. Las
instalaciones deben cumplir estrictamente la totalidad de los
códigos, estándares de la industria y regulaciones vigentes.
Su equipo se suministra con este “Manual de instalación y del
operario” combinado. Se trata de un documento importante que el
propietario debe conservar después de haber terminado
la instalación.
Se ha realizado el máximo esfuerzo para reunir en este manual la
información más precisa y actualizada. No obstante, el fabricante se
reserva el derecho de modificar, alterar o mejorar de cualquier otra
forma el sistema en cualquier momento y sin previo aviso.
AVISO Antes de taladrar los orificios de entrada de conductos
o cualquier orificio para montar accesorios, tape y proteja el
conectador y el panel de control para evitar que la suciedad
y fragmentos de metal entren a los componentes mecánicos
y eléctricos. No hacerlo puede provocar daños y fallos del
conectador.
AVISO Utilice una aspiradora para limpiar toda la suciedad o
virutas de metal dentro del conectador. No utilice un soplador o
aire comprimido para limpiar el interior del conectador ya que los
residuos se pueden incrustar en los componentes mecánicos y
eléctricos y provocar daños o fallos.
Responsabilidades del propietario
Para tomar decisiones bien fundadas y comunicarse eficazmente
con el técnico instalador, lea y comprenda la sección de Orientación
al propietario antes de contratar o iniciar la instalación del equipo.
Para solicitar la instalación, póngase en contacto con la tienda en la
que adquirió el equipo, con su distribuidor o con
la compañía eléctrica.
La garantía del equipo quedará ANULADA a menos que electricistas
profesionales con licencia instalen elsistema.
Orientación al propietario
Las ilustraciones incluidas corresponden a circunstancias
habituales y tienen por objeto familiarizarle con las opciones de
instalación del sistema.
La normativa local, la apariencia y las distancias son los aspectos
que deberán tenerse en cuenta al negociar la instalación con un
profesional. Al aumentar la distancia desde el servicio eléctrico,
se deberá prever una compensación en cables y otros materiales
necesarios para cumplir la normativa local vigente y evitar caídas
de tensióneléctrica.
Estos factores tendrán un efecto directo en el precio total de la
instalación del equipo.
El instalador deberá comprobar la normativa local Y obtener los
permisos correspondientes antes de instalar el sistema.
• Leaysigalasinstruccionesqueseindicanenestemanual.
• Sigaunplanregulardecuidadoyusodelequipo,comose
indica en este manual.
Re sponsabilidades del distribuidor / técnicoinstalador
• Leaysigalasinstruccionesimportantesdeseguridad.
• Leaysigalasinstruccionesqueseindicanenestemanual.
• Esposiblequeelinstaladortengaqueproporcionar
contactores nominales adecuados con base en las cargas que
van a controlarse.
• Analiceconelpropietariolaimportanciadelasprioridadesde
carga para decidir qué ajustes se realizarán en la prioridad de
los módulos remotos.
• Sitienedudassobrelainstalación,consultelos
códigos federales, estatales y locales, así como a la
autoridadcompetente.
• Asegúresedequelascargasseleccionadasnosobrecarguen
el generador.
Si necesita más información sobre el conectador, llame al 800-743-
4115 entre 8:00 a. m y 5:00 p. m., Hora del Centro.
Descripción del equipo
El conectador está diseñado para transferir las cargas seleccionadas
de una instalación residencial normal al suministro de reserva en
caso de una interrupción de alimentación primaria. La carga se
conecta al suministro de alimentación de la red pública (normal)
o al suministro doméstico de reserva (generador). El conectador
monitoriza las tensiones de la red pública y del generador y conecta
automáticamente las cargas a la fuente de alimentaciónapropiada.
El sistema de gestión de energía Symphony™ II es muy flexible y
utiliza módulos de tensión alta y baja individuales que se pueden
montar en cualquier lugar entre el panel de distribución principal
doméstico y el aparato gestionado. Dado que está diseñado para
comunicarse a través del cableado de alimentación doméstico
existente, la demanda de alimentación y la secuencia de prioridades
de hasta 8 cargas de aparatos se transmiten de vuelta al
generador de reserva, lo que evita con eficacia que el generador se
sobrecargue y amplía el alcance y la eficiencia de la alimentación.
El sistema puede crecer y se pueden añadir relés adicionales
conforme cambien las necesidades de gestión de alimentación del
propietario doméstico con el paso del tiempo.
Sólo un electricista con licencia debe realizar la instalación
doméstica de reserva. El conducto y los conductores de servicio se
pueden cablear directamente desde el contador de vatios/hora hasta
el conectador. No es necesario instalar un seccionador de entrada
de servicio distinto, con su correspondiente cableado, para cumplir
los códigos, los estándares y las regulaciones federales, estatales y
localescorrespondientes.
NOT
for
REPRODUCTION
6 BRIGGSandSTRATTON.COM
Los principales componentes del conectador son un disyuntor
bipolar de desconexión de la red pública, un disyuntor bipolar
de desconexión del generador, un conectador bipolar de 2
posiciones de contacto, la tarjeta de circuito impreso de control del
conectador, la tarjeta de circuito impreso de control del sistema
de gestión de energía Symphony II, los terminales con fusibles
de tensión de la red pública y el cableado de interconexión. Todos
estos componentes se encuentran en una caja tipo 3R según
NEMA, que es adecuada para uso en interiores y a laintemperie.
El conectador es accionado por un solenoide alimentado desde
entradas de la red pública o del generador y tiene interruptores de
enclavamiento mecánicos y eléctricos, adecuados para eliminar
la posibilidad de conectar la red pública a la salida del generador.
Sus valores nominales son suficientes para conectar toda la
alimentación de la red pública a la residencia. Asimismo, para la
función de transferencia hay una palanca de cancelación manual.
La tarjeta de control del conectador tiene circuitos activos que
detectan las tensiones de la red pública y del generador. Genera una
señal para el arranque del generador, conectador y retransferencia
cuando se restablece la tensión en la red pública. La tarjeta de
control del conectador cuenta con LED de estado que indican la
fuente de energíadisponible.
La tarjeta de control del sistema de gestión de energía Symphony™
II contiene un botón de prueba, un LED de estado y ocho LED de
carga de prioridad. Este sistema crea y envía señales a módulos
remotos opcionales, para indicarles cuándo añadir (encender la
alimentación) o eliminar (apagar la alimentación)
la carga gestionada.
La tecnología de soporte de la línea de alimentación del sistema
Symphony II ha pasado por pruebas rigurosas y ha demostrado
ser muy resistente. Sin embargo, ciertos tipos de dispositivos y
aparatos en el hogar generan “ruido” en la línea de alimentación.
Tales dispositivos pueden incluir balastras para tubos fluorescentes
para uso no residencial, reguladores de voltaje, controles de
velocidad (iluminación y ventiladores), equipo de baño, equipo
de cocina, herramientas motorizadas, cargadores de teléfono y
suministro de alimentación. Estos tipos de dispositivos tienen un
impacto extenso sobre la comunicación de la línea de alimentación
cuando se ubican cerca de un módulo remoto.
La señales de transmisión de radio AM, X10, el soporte de línea
de alimentación (PLC), la fuente de alimentación ininterrumpida
(UPS), los sistemas de supresión de voltaje transitorio (TVSS) y la
tecnología de filtro de alimentación también pueden hacer que el
sistema Symphony II no funcione como es debido. Estos pueden
provocar interferencia con el sistema Symphony II durante la
operación de la alimentación de reserva.
Si se determina que el ruido de la línea de alimentación está
provocando un problema de comunicación con el sistema
Symphony II, los cambios siguientes pueden solucionarlo.
• Sustituirlasbalastrascomerciales(deusoindustrial)paratubos
fluorescentes por balastras de uso residencial.
• InstalarunfiltroEMI/RFIenserieycercadel
dispositivo problemático.
• Cambiarelcabledelmóduloremotoalalíneadealimentación
opuesta (línea 1 o línea 2) de la del dispositivo problemático.
• ConsultelasecciónResolucióndeproblemas.
El módulo remoto opcional de 50 A está diseñado de tal forma que
el sistema Symphony controle la adición o eliminación de cargas
de aparatos conectados a él con base en una configuración de
prioridades definida por el usuario. Este módulo remoto gestiona
cargas monopolares o bipolares de 120V CA o 240V CA de hasta 50
A. Por lo general, el relé del módulo remoto está abierto. Todos sus
componentes se encuentran en una caja tipo 4 según NEMA, que es
adecuada para uso en interiores y a laintemperie.
El módulo remoto de tensión baja opcional está diseñado de
tal forma que el sistema Symphony II controle la adición o
eliminación de las cargas controladas por el contactor del aire
acondicionado, de la bomba de calor o de tensión baja, con base
en una configuración de prioridades definida por el usuario. El
módulo remoto se encuentra en una caja tipo 4 según NEMA, que
es adecuada para uso en interiores y a la intemperie.
Inspección en el momento de la entrega
Después de abrir la caja de cartón, con cuidado inspeccione los
componentes del conectador para detectar cualquier daño que
pudiera haber ocurrido durante el envío.
Si detecta faltas o daños en el momento de la entrega, solicite a
la persona que realiza la entrega que anote todos los daños en Ia
nota de entrega y que la firme bajo el área de pérdidas y daños
del remitente. Si se detectan faltas o daños después de la entrega,
póngase en contacto con el transportista para solicitar información
sobre el procedimiento de reclamación. La garantía no cubre las
partes faltantes o dañadas.
Contenido del envío:
• Conectadorautomático
• Manualdeinstalaciónydeloperario
• Transformadoresdecorriente(2)
Componentes opcionales:
• Módulode50A
• Módulodetensiónbaja(modelossencillosodobles)
• MonitordealimentaciónSymphony™II
Equipo que el instalador debe suministrar:
• Cableyconductodeconexión
• Herramientas/equiposespecialesdiversos
NOT
for
REPRODUCTION
7
Prueba del conectador automático
Coloque el disyuntor de desconexión de servicio de la red pública
que alimenta al contactor del conectador en la posición “OFF”.
Iniciará la secuencia automática del sistema que se describe más
abajo. Para volver a utilizar el suministro de alimentación de la red
pública, coloque el disyuntor de desconexión del servicio de la red
pública en la posición “ON”.
Fallo de la red pública
El generador detecta cuándo la tensión de la red pública está por
debajo del 70% de la nominal. Tras un retardo de 6segundos, se
inicia la secuencia de arranque del motor.
Calentamiento del motor
Retardo de tiempo para permitir el calentamiento del motor antes
de la transferencia. Utilice el puente de la tarjeta de control del
conectador para seleccionar el retardo de 20 segundos
o 50 segundos.
Transferencia
La transferencia de la alimentación desde la red pública al generador
se produce cuando la tensión está por encima de los niveles
especificados. La luz de LED de la tarjeta de control del conectador
cambiará de verde (red pública) a rojo (generador) y la luz de estado
de Symphony II cambiará el estado intermitente de parpadeo-
parpadeo-pausa-parpadeo a parpadeo-pausa-parpadeo. El tiempo
mínimo de funcionamiento del motor después de la transferencia
es de 5 minutos.
Gestión de cargas
Cinco minutos después de la transferencia al suministro de
alimentación del generador, los módulos remotos activan las
cargas conectadas si la alimentación del generador está disponible,
comenzando con la prioridad más alta (1) hasta la prioridad más
baja (8). Hay una demora de 10 segundos entre cada
activación secuencial.
Los LED P1 a P8 en la tarjeta de control de Symphony II se
iluminarán para mostrar las cargas que se agregan.
Las cargas conectadas a los módulos remotos configurados en
las prioridades 9 y 10 permanecerán desactivadas durante la
interrupción del suministro de alimentación eléctrica de
la red pública.
Recuperación de la red pública
El nivel de recuperación de la tensión es el 80% de
la tensión nominal.
Retransferencia
La retransferencia del generador al suministro de alimentación
de la red pública tiene lugar aproximadamente 10 segundos
después de que el suministro de tensión de la red pública está por
encima del nivel de recuperación y después de que se completa el
tiempo mínimo de funcionamiento. Todos los módulos remotos
permanecerán apagados (OFF) durante cinco minutos después de la
transferencia de alimentación.
Enfriamiento del motor
El motor funcionará durante 60 segundos después de producirse
la retransferencia.
ADVERTENCIA Riesgo de descarga. Este equipo contiene
alta tensión que puede ocasionar la electrocución y, por
tanto, la muerte o lesiones graves.
• Las pruebas deben ser realizadas exclusivamente por personal
cualificado.
• No utilice este equipo de un modo imprudente, sin tener cuidado
o con negligencia en cuanto a su mantenimiento.
NOT
for
REPRODUCTION
8 BRIGGSandSTRATTON.COM
Controles
A excepción de la palanca de cancelación manual, no hay ningún
control del operario porque este es un conectador automático.
Únicamente los profesionales con licencia deben utilizar la
cancelación manual. La información sobre el uso del asa se puede
obtener comunicándose con el Servicio Técnico al 800-743-4115.
Funcionamiento
Para seleccionar el funcionamiento automático del conectador, haga
lo siguiente:
1. En el conectador, coloque el disyuntor de desconexión de la
red pública en la posición “ON”.
2. En el conectador, coloque el disyuntor de desconexión del
generador en la posición “ON”.
3. Instale el fusible de 15 A en el panel de control delgenerador.
4. Coloque el disyuntor del generador en la posición “ON”.
5. Coloque el interruptor del sistema del generador en la
posición “AUTO”.
El sistema estará entonces en el modo de
funcionamientoautomático.
Cuando el generador suministra alimentación al conectador, la
tarjeta de control del conectador supervisa permanentemente el
suministro eléctrico del generador y se comunica con la tarjeta de
control del sistema Symphony.
El sistema Symphony controlará hasta 8 prioridades, con las
prioridades 9 y 10 como bloqueos. Cuando la carga total del
generador alcance un valor predeterminado, la tarjeta de control
del sistema Symphony comenzará a eliminar cargas, iniciando con
la carga de la prioridad más baja (número más alto). El sistema
Symphony añadirá o eliminará cargas gestionadas con base en la
capacidad de salida del generador y las configuraciones
de prioridades.
El sistema Symphony espera 10 segundos entre la adición y
eliminación de cada carga para permitir que el sistema se estabilice.
Si se detecta demasiada demanda de carga, el sistema Symphony
eliminará todas las cargas gestionadas rápidamente para evitar que
el generador se sobrecargue. Una vez que la demanda de carga se ha
estabilizado, el sistema Symphony II recarga el generador después de
una demora de 5 minutos, según se describió antes.
Hay un retardo mínimo de cinco minutos entre el tiempo en que se
pierde el suministro de alimentación de la red pública y el tiempo
en que el sistema Symphony activa las cargas de prioridad 1. Si
una carga intermitente con prioridad baja (como 5 ó 6) requiere un
valor de amperios mayor que una carga con prioridad más alta, su
consumo de corriente puede producir actividad de eliminación de
carga más frecuente o imprevista. Si dichas inconsistencias son
inconvenientes, el instalador debe reajustar las configuraciones de
prioridad en los módulos remotos para solucionar el problema.
Debe ser consciente de que las cargas de energía gestionadas
de los elementos de calefacción (como hornillas, hornos o
calentadores eléctricos) que estén encendidos cuando se pierda el
suministro de alimentación de la red pública, se encenderán cuando
el generador comience a suministrar alimentación. Se aconseja
que el propietario compruebe dichos dispositivos gestionados
para asegurarse de que estén apagados antes de que se active el
suministro de alimentación del generador.
Los dispositivos gestionados como las secadoras de ropa que
requieran pulsar un botón de arranque (START) no volverán a
funcionar a menos que se pulse dicho botón después de que se
active el suministro de alimentación del generador.
Podrían producirse fluctuaciones importantes en el consumo
de carga en todos los aparatos que utilicen un elemento de
calefacción. Esto significa que la carga general total puede
variar mucho, produciendo que se perciba una gestión excesiva
de las cargas. Puede ser necesario que el instalador ajuste las
configuraciones de prioridad de los módulos remotos para
minimizar estos efectos.
Puerta de la caja
Para abrir la puerta del conectador, oprima la cerradura de la puerta
accionada con resorte hacia la derecha y jale la puerta.
Para cerrar y bloquear la puerta, empújela y ciérrela hacia la caja.
Mientras se encuentra en esta posición, empuje la puerta hacia
arriba. Esto provocará que la cerradura de la puerta accionada con
resorte se enganche y bloquee la puerta en su lugar. La puerta de
la caja DEBE estar cerrada y bloqueada en todo momento excepto
cuando se está dando mantenimiento al sistema.
NOT
for
REPRODUCTION
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36

Simplicity 071049-00 Manuel utilisateur

Catégorie
Groupes électrogènes
Taper
Manuel utilisateur