Lumination PSF Series LED Wrap Guide d'installation

Taper
Guide d'installation
LED.com
© 2023 Current Lighting Solutions, LLC. All rights reserved. Information and
specifications subject to change without notice. All values are design or typical
values when measured under laboratory conditions.
Page 1 of 4
(Rev 4/19/23)
IND639-Lumination-PSF-Series-ProLine-Switchable-Strip-Fixure-Installation-Guide_R01
Installation Guide
IND639
Lumination® LED Luminaire
ProLine® Strip Fixture Series
(PSF-Series)
BEFORE YOU BEGIN
Read these instructions completely and carefully.
WARNING/AVERTISSEMENT
RISK OF ELECTRIC SHOCK
Turn power off before inspection, installation or
removal.
Properly ground electrical enclosure.
RISK OF ELECTRIC SHOCK
Follow all NEC and local codes.
Use only Ul approved wire for input/output
connections. Minimum size 18 AWG (0.75mm²).
Do not install insulation within 3 inches (76 mm)
of luminaire top.
RISQUES DE DÉCHARGES ÉLECTRIQUES
Coupez l’alimentation avant d’inspecter, installer ou déplacer le
luminaire.
Assurez-vous de correctement mettre á la terre le boítier
d’alimentation électrique.
RISQUES D’ INCENDIE
Respectez tous les codes NEC et codes locaux.
N’utilisez que des ls approuvés par UL pour les entrées/sorties de
connexion. Taille minimum 18 AWG (0.75mm²).
Maintenir une distance de 76 mm (3 pouces) entre le luminaire et
l’isolant.
Save These Instructions
Use only in the manner intended by the manufacturer.
If you have any questions, contact the manufacturer.
This device complies with Part 15 of the FCC Rules. Operation is subject to the
following two conditions: (1) This device may not cause harmful interference,
and (2) this device must accept any interference received, including interfer-
ence that may cause undesired operation. CAN ICES-005(A)/NMB-005(A)
Note: This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful inter-
ference to radio communications. Operation of this equipment in a residen-
tial area is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.
Prepare Electrical Wiring
Electrical Requirements
• The LED luminaire must be connected to the mains
supply according to its ratings on the product label.
• Class 1 wiring should be in accordance with NEC.
Grounding Instructions
The grounding and bonding of the overall system
shall be done in accordance to local electric code
of the country where the luminaire is installed.
LED.com
© 2023 Current Lighting Solutions, LLC. All rights reserved. Information and
specifications subject to change without notice. All values are design or typical
values when measured under laboratory conditions.
Page 2 of 4
(Rev 4/19/23)
IND639-Lumination-PSF-Series-ProLine-Switchable-Strip-Fixure-Installation-Guide_R01
Lumination® (PSF - Series) Installation Guide
For safety, turn off main power
prior to installation.
1
Installation
Release latches on the side of the xture. Carefully pull down the light engine
from latch side. Set desired Power/CCT as following with screwdriver.
2
Three mounting options available
POWER H/M (Default)/L
CCT 3500K/4000K (Default)/5000K
Mounting Options
Cable Mounting
Surface MountingRod Mounting
LED.com
© 2023 Current Lighting Solutions, LLC. All rights reserved. Information and
specifications subject to change without notice. All values are design or typical
values when measured under laboratory conditions.
Page 3 of 4
(Rev 4/19/23)
IND639-Lumination-PSF-Series-ProLine-Switchable-Strip-Fixure-Installation-Guide_R01
Lumination® (PSF - Series) Installation Guide
TOGGLE/CABLE (ORDER SEPARATELY) DESCRIPTION PRODUCT ORDER CODE
Toggle/Suspension Cable 5’ CABLE HANGER,GRIPPLE,XP2TG-5FT300MMPAIR PRT0202
Toggle/Suspension Cable 10’ CABLE HANGER,GRIPPLE,XP2TG-10FT300MMPAIR PRT0203
Toggle/Suspension Cable 15’ CABLE HANGER,GRIPPLE,XP2TG-15FT300MMPAIR PRT0204
Hang xture using cables(order separately), rods(not included) or mount directly to ceiling using appropriate hardware (not included).
Cable Mounting: Cable length shall not exceed 15ft, suitable for min. 20lbs load. Hang a pair of cables from the ceiling and pass both
paddles through slots on top of xture.
Rod Mounting: Rod length shall not exceed 15ft, suitable for min. 20lbs load.. Secure two 1/2” threaded rods into structural members in
ceiling. Place a nut on each threaded rod where xture should hang. Slide xture onto threaded rods and tighten second nut onto rods to
secure xture.
Surface Mounting: Remove the rectangle knockout in the middle of housing, then install xture to intended surface using mounting
holes on both ends of xture with appropriate mounting hardware. If mounting into a joist, use 2 wood screws and 2 washers to attach to
joist. If joist is not available, use 2 toggle bolts and 2 washers to attach to plasterboard. Make sure the mounting surface can support the
weight of the xture.
3
For Cable/Rod Mounting
Install conduit tting on the knockout at left, or right, and feed the AC wires through the tting.
Option: Install conduit tting on the separate knockout against AC wires and feed the Dimming wires through the tting.
4-1
For Surface Mounting
Outlet box width shall not exceed 2in.
Pull out AC wires, Dimming wires(Option) to the xture
4-2
LED.com
© 2023 Current Lighting Solutions, LLC. All rights reserved. Information and
specifications subject to change without notice. All values are design or typical
values when measured under laboratory conditions.
Page 4 of 4
(Rev 4/19/23)
IND639-Lumination-PSF-Series-ProLine-Switchable-Strip-Fixure-Installation-Guide_R01
Lumination® (PSF - Series) Installation Guide
For Cable/Rod Mounting, refer to wiring diagram in nal page.
Connect the AC wires to the black (line) and white (neutral) input wires of the LED driver using UL listed wire connectors. Connect the
ground wire to the green grounding wire
Option: Connect the Dimming wire (violet/pink) using UL listed wire connectors.
5-1
For Surface Mounting, refer to wiring diagram in nal page.
Connect the AC wires to the black (line) and white (neutral) input wires of the LED driver using UL listed wire connectors. Connect the
ground wire to the green grounding wire.
Option: Connect the Dimming wire (violet/pink) using UL listed wire connectors.
5-2
Rotate and replace the light engine and
push back the latches.
6
Wiring diagram
Pink
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Lumination PSF Series LED Wrap Guide d'installation

Taper
Guide d'installation

dans d''autres langues