Drawing No. LP1142 Effective 08 2021
SPECIFICATIONS
Note: The PM-50 4.3 inch host accepts a maximum of 5
modules while the 3.5 inch host accepts a maximum of 3.
Only one module from each function type (i.e. communication,
relay, analog output) can be installed.
1. POWER: Power is supplied by the PM-50 host device.
Must use a Class 2 circuit according to National Electrical
Code (NEC), NFPA-70 or Canadian Electrical Code (CEC),
Part I, C22.1 or a Limited Power Supply (LPS) according to
IEC/EN 60950-1 or Limited-energy circuit according to IEC/
EN 61010-1.
Max Power: 0.9 W
2. Setpoint Output: Field installable module
Type: Four FORM-A relays
Isolation: 3000 Vrms for 1 min.
Contact Rating:
One Relay Energized: 3 Amps @ 250 VAC or 30 VDC
(resistive load).
With all relays energized, the max current is 1 A per Relay
Relay Restrictions - Only the following combinations are
valid:
RELAY GROUP 1 RELAY GROUP 2
RELAY 1 RELAY 2 RELAY 3 RELAY 4
30 VDC max 30 VDC max
Mains 250 VAC max Mains 250 VAC max
30 VDC max Mains 250 VAC max
Mains 250 VAC max 30 VDC max
Note: When relay contacts are connect to Mains, the Mains
should be Overvoltage category II, Polution degree 2
Life Expectancy: 100 K cycles min. at full load rating.
External RC snubber extends relay life for operation with
inductive loads
3. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: -10 to 55 °C
Storage Temperature Range: -40 to 85 °C
Vibration to IEC 68-2-6: Operational 5-500 Hz, 2 g
Shock to IEC 68-2-27: Operational 10 g
Operating and Storage Humidity: 0 to 85% max. RH non-
condensing
Altitude: Up to 2000 meters
Mains voltage is Overvoltage category II and in Pollution
degree 2 environment.
4. CERTIFICATIONS AND COMPLIANCES:
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
IEC/EN 61010-1
RoHS Compliant
UL Hazardous: File # E317425
Rugged IP25 enclosure
5. CONSTRUCTION: Plastic enclosure with IP25 rating. For use
only in an approved enclosure.
6. CONNECTIONS: High compression cage-clamp terminal
blocks
Wire Strip Length: 0.32-0.35" (8-9 mm)
Wire Gauge Capacity: Four 28 AWG (0.32 mm) solid,
two 20 AWG (0.61 mm) or one 16 AWG (2.55 mm)
7. WEIGHT: 1.8 oz (51 g)
HARDWARE INSTALLATION
Installing a Module
To a 4.3 inch Host
1. To install a module on the tall side of a 4.3 inch host, align the
latches of the module with the host case such that the
backplane connector shroud on the module cover aligns with
the backplane connector opening in the host case.
2. To install a module on the short side of a 4.3 inch host, rotate
the module 180 degrees and align the latches on the host
with the module case so that the I/O connector is facing
downward.
3. Insert the host latches into the openings in the module case
by slightly deflecting the latches inward.
4. Press the module into the host case evenly until the latches
engage.
5. Install Module Locks between each module as shown by fully
inserting the legs of the Module Locks into the slots in the
case until the button on the Module Lock aligns with the hole
provided in the case. Press fit the button into the hole. Repeat
this installation between each module in your system to
provide the most secure installation.
6. When you have finished adding modules, the rear cover
should be installed in the same manner as the modules.
WARNING - Disconnect all power to the unit before
installing or removing modules.
AVERTISSEMENT - Débranchez l’alimentation électrique
de l’appareil avant d’installer ou de retirer des modules.
Installation of the product must comply with National Electrical
Code (NEC), NFPA-70 or Canadian Electrical Code (CED) or any
local regulation Authority.
Short Side
Tall Side
Position 1
Rear Cover
It is recommended that a
relay module be installed
in Module Position 1 only
(shown below).