TE-6300F Series Flush Mount Sensors Installation Instructions 1
Refer to the QuickLIT website for the most up-to-date version of this document.
Applications
The TE-6300F Series Flush Mount Temperature
Sensor is a device that measures air temperature, via a
temperature sensing element, thermally bonded to a
metal electrical box cover. The sensor is designed for
direct connection to a supervisory controller.
Installation
Dimensions
IMPORTANT: The TE-6300F Series Flush Mount
Temperature Sensor is intended to provide an input
to equipment under normal operating conditions.
Where failure or malfunction of the sensor could
lead to personal injury or property damage to the
controlled equipment or other property, additional
precautions must be designed into the control
system. Incorporate and maintain other devices,
such as supervisory or alarm systems or safety or
limit controls, intended to warn of or protect against
failure or malfunction of the sensor.
IMPORTANT : Le TE-6300F Series Flush Mount
Temperature Sensor est destiné à transmettre des
données entrantes à un équipement dans des
conditions normales de fonctionnement. Lorsqu'une
défaillance ou un dysfonctionnement du sensor
risque de provoquer des blessures ou
d'endommager l'équipement contrôlé ou un autre
équipement, la conception du système de contrôle
doit intégrer des dispositifs de protection
supplémentaires. Veiller dans ce cas à intégrer de
façon permanente d'autres dispositifs, tels que des
systèmes de supervision ou d'alarme, ou des
dispositifs de sécurité ou de limitation, ayant une
fonction d'avertissement ou de protection en cas de
défaillance ou de dysfonctionnement du sensor.
IMPORTANT: Do not install the TE-6300F Series
Flush Mount Temperature Sensor probe in ambient
temperatures beyond the specified 32 to 104°F
(0 to 40°C) temperature range. Installing the
temperature sensor probe in ambient temperatures
beyond this range may damage the unit and void the
warranty.
Figure 1: Flush Mount Sensor with Logo
Dimensions, in. (mm)
4 -1/2
(114.3)
2 -3/4
(69.85)
F
i
g
:
D
i
m
TE-6300F Series Flush Mount Sensors
Installation Instructions
TE-63xxF-0, TE-63xxF-1
Part No. 24-4034-255, Rev. C
Issued March 2016
24- 4034-255, Rev. C
TE-6300F Series Flush Mount Sensors Installation Instructions2
Mounting
Location Considerations
Consider the following mounting location guidelines:
Avoid areas subject to excessive vibration,
electrical noise, direct sunlight, or the effects of
radiant heat.
Keep electrical wiring as short as possible to
minimize temperature error.
Mounting the Temperature Sensor
Mount the temperature sensor as follows:
1. Remove the appropriate knockout on the standard
utility conduit box for the application.
2. Make the wiring connection to the system
components.
Note: To make wiring easier, the sensor may be
suspended from the conduit box using the rubber band.
Note: Level the sensor for appearance; however, the
sensor functions normally when not level.
3. Mount the sensor to the wallbox or electrical box
using the screws provided.
Wiring
For 1k ohm nickel temperature sensors, wire
resistance can cause approximately 1F° (0.56C°) of
error for every 250 ft (76 m) run of 18 AWG wire, or
every 100 ft (31 m) run of 22 AWG wire. For 1k ohm
platinum temperature sensors, wire resistance can
cause approximately 1F° (0.56C°) of error for every
150 ft (46 m) run of 18 AWG wire, or every 50 ft (15 m)
run of 22 AWG wire. To minimize error due to field
wiring, limit the total resistance of all nickel temperature
sensor wiring to 3 ohms, and all 1k ohm platinum
temperature sensor wiring to 2 ohms.
The 10k ohm thermistor applications tolerate relatively
long wiring before the wire resistance adds significantly
to the total resistance measured at the controller. As a
general rule, a 150 ft (46 m) two-wire 18 AWG run
contributes 2 ohms of error, or less than 1F° (0.56C°)
error over the sensor operating temperature range.
Refer to the appropriate controller documentation for
recommended sensor wiring.
Wiring Recommendations
Use the wire nuts provided for connecting the lead
wires to the controller wiring.
Figure 2: Installing a Sensor Plate to the
Conduit Box
!
CAUTION: Risk of Property Damage.
Do not apply power to the system before
checking all wiring connections. Short
circuited or improperly connected wires
may result in permanent damage to the
equipment.
MISE EN GARDE : Risque de dégâts
matériels.
Ne pas mettre le système sous tension
avant d'avoir vérifié tous les raccords de
câblage. Des fils formant un court-circuit
ou connectés de façon incorrecte
risquent d'endommager
irrémédiablement l'équipement.
IMPORTANT: Use copper conductors only. Make
all wiring connections in accordance with local,
national, and regional regulations. Do not exceed
the TE-6300F Series Flush Mount Temperature
Sensor’s electrical ratings.
IMPORTANT: Use proper Electrostatic Discharge
(ESD) precautions during installation and operation
to avoid damaging the electronic circuits. Use
electrical tape to wrap the ends of the wire leads a
minimum of 1 in. (25 mm), as well as to cover the
wire nuts.
Published in U.S.A. www.johnsoncontrols.com
TE-6300F Series Flush Mount Sensors Installation Instructions 3
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Repair Information
If the TE-6300F Series Temperature Flush Mount
Sensor fails to operate within its specifications, replace
the unit. For a replacement sensor, contact the nearest
Johnson Controls® representative.
Technical Specifications
TE-63xxF-x Series Flush Mount Temperature Sensors
Models TE-6310F-0 1k ohm Nickel Flush Mount Temperature Sensor with Logo
TE-6310F-1 1k ohm Nickel Flush Mount Temperature Sensor without Logo
TE-6350F-0 1k ohm Platinum Flush Mount Temperature Sensor with Logo
TE-6350F-1 1k ohm Platinum Flush Mount Temperature Sensor without Logo
TE-6360F-0 10k ohm Thermistor Johnson Controls Type II Flush Mount
Temperature Sensor with Logo
TE-6360F-1 10k ohm Thermistor Johnson Controls Type II Flush Mount
Temperature Sensor without Logo
Sensor Reference
Resistance
1k ohm Nickel 1k ohms at 70°F (21°C)
1k ohm Platinum 1k ohms at 32°F (0°C)
10k ohm Thermistor 10.0k ohms at 77F (25C)
Sensor Accuracy 1k ohm Nickel 0.34F° at 70F (0.19C at 21C)
1k ohm Platinum 0.35F° at 70F (0.19C at 21C), DIN Class A
10k ohm Thermistor 0.9F (0.5C) in the Range: 32 to 158F (0 to 70C)
Sensor Temperature
Coefficient
1k ohm Nickel Approximately 3 ohm/F° (5.4 ohm/C°)
1k ohm Platinum Approximately 2 ohm/F° (3.9 ohm/C°) 3850 ppm/K
10k ohm Thermistor Nonlinear Negative Temperature Coefficient, Johnson Controls Type II
Electrical Connections 22 AWG (0.6 mm Diameter) x 12 ft (3 m) braided copper wires, low
voltage insulation, half-stripped ends
Cover Plate Dimensions 2-3/4 x 4-1/2 in. (70 x 114 mm)
Operating Temperature Limits 0 to 40C (32 to 104F)
Operating Temperature Humidity 10 to 90% noncondensing
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS
WESTENDHOF 3
45143 ESSEN
GERMANY
JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA
JOHNSON CONTROLS
C/O CONTROLS PRODUCT
MANAGEMENT
NO. 22 BLOCK D NEW DISTRICT
WUXI JIANGSU PROVINCE 214142
CHINA
  • Page 1 1
  • Page 2 2
  • Page 3 3

Johnson Controls TE-6300F Series Guide d'installation

Taper
Guide d'installation

dans d''autres langues