Range Range Top Cubic Feet per Minute
I ventilation uptlons
Width Configuration (min requirement)
30" or 36" Pro Wall Hood
30" 4 burners 800 CFM 30" or 36" Custom Insert w/optional blower
42" Island Hood w/optional blower
4 burners with griddle 800 CFM 36" or 42" Pro Wall Hood
36" 36" Custom Insert w/optional blower
6 burners 1100 CFM
42" or 48" Island Hood w/optional blower
48" or 54" Pro Wall Hood**
48" 6 burners with griddle 1200 CFM 48" Custom Insert w/optional blower
54" Island Hood w/optional blower
IMPORTANT NOTES:
It is recommended that a THERMADOR PROFESSIONAL ® wall or island hood or custom insert is used with
THERMADOR PROFESSIONAL ranges. Refer to www.thermador.com for a complete selection of ventilation options,
blowers, and accessories.
* For high output gas ranges (60,000 BTU or greater), the minimum of one (1) CFM of ventilation per 100 BTU is
recommended. If the range has a griddle, add 150 CFM to the estimated blower capacity. Additional blower capacity
may be required for longer duct runs.
For island applications, it is recommended to use a hood width that exceeds the width of the range by 6" (152mm),
overlapping the range by a minimum of 3" (76mm) on each end. CFM = "cubic feet per minute" (standard blower
capacity rating).
Step 2: Cabinet Preparation
The range is a free standing unit. If the unit is to be
placed adjacent to cabinets, the clearances shown in
Figure 1 are required. The same clearances apply to
island installations, except for the overhead cabinets,
which must have a space wide enough to accept the
flared island hood.
• Any openings in the wall behind the range and in the
floor under the range must be sealed.
• The gas and electrical supply should be within the
zones shown in Figure 3 on page 7.
• When installing against a combustible surface, a High
Shelf or Low Backguard is required. A THERMADOR ®
High Shelf or Low Backguard must be purchased
separately (see chart on page 17).
• When using the Flush Island Trim, THERMADOR
recommends a minimum 12" (305 mm) rear clearance
to a combustible surface (see Figure 1, Cabinet
Clearances). Clearances from non-combustible
materials are not part of the ANSI Z21.1 scope and are
not certified by CSA. Clearances of less than 12"
(305 mm) must be approved by the local codes and/or
by the local authority having jurisdiction.
• When the range is installed against a combustible side
wall a minimum clearance of 5" (127mm) is needed
from the side of the range to the wall.
• Always keep appliance area clear from combustible
materials, gasoline and other flammable vapors and
liquids.
• The maximum depth of overhead cabinets installed on
either side of the hood is 13" (330mm).
• Do not obstruct the flow of combustion and ventilation
air to the unit.
There is a 36" (914mm) minimum clearance required
between the top of the cooking surface and the bottom of
an unprotected cabinet. A 30" (762mm) clearance can be
used when the bottom of the wood or metal cabinet is
protected by not less than 1/4" (6mm) of a flame retardant
material covered with not less than No. 28 MSG sheet
steel, 0.015" (0.38 mm) thick stainless steel, 0.024" (0.61
mm) aluminum, or 0.02" (0.51 mm) thick copper.
Flame retardant materials bear the mark:
UNDERWRITERS LABORATORIES INC. CLASSIFIED
MINERAL AND FIBER BOARDS SURFACE BURNING
CHARACTERISTICS, followed by the flame spread and
smoke ratings. These designations are shown as "FHC
(Flame Spread/Smoke Developed)." Materials with "O"
flame spread ratings are flame retardant. Local codes may
allow other flame spread ratings. It is the responsibility of
the installer to ensure installation is in accordance with
these ratings.
English 4