Tripp Lite S3MT-60K600V Le manuel du propriétaire

Catégorie
Alimentations sans interruption (UPS)
Taper
Le manuel du propriétaire
1
Owner’s Manual
S3MT-Series 3-Phase
Input Transformers:
480V-208V and 600V-208V
Models:
S3MT-60K480V, S3MT-100K480V, S3MT-60K600V, S3MT-100K600V
1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support
Copyright © 2021 Tripp Lite. All rights reserved.
WARRANTY REGISTRATION
Register your product today and be
automatically entered to win an ISOBAR
®
surge protector in our monthly drawing!
tripplite.com/warranty
Español 21 • Français 41
2
1. Introduction ................................................................................. 3
2. Important Safety Warnings .......................................................... 5
3. Installation .................................................................................. 6
3.1 Mechanical Data ...................................................................................6
3.2 Package Inspection ..............................................................................7
3.3 Unpacking the UPS ...............................................................................7
3.4 Package Contents .................................................................................9
3.5 Cabinet Overview ................................................................................10
3.6 Power Cables ......................................................................................12
3.7 Transformer-to-UPS Connection Line Diagram ...................................13
3.8 Multiple Transformer Connections ...................................................... 15
3.8.1 S3MT-60K480V/S3MT-60K600V to S3M50K or S3M60K UPS ........................ 15
3.8.2 S3MT-100K480V/S3MT-100K600V to S3M80K or S3M100K UPS .................. 15
4. Operations ................................................................................. 16
4.1 Over-Temperature Protection ..............................................................16
4.1.1 Over-Temperature Red Warning LED Light ................................................... 16
4.1.2 Over-Temperature Protection Relay and Thermal Switch ............................. 16
5. Specifications ............................................................................ 17
6. Storage ...................................................................................... 19
7. Warranty and Regulatory Compliance ........................................ 19
Table of Contents
3
1. Introduction
Tripp Lite’s S3MT-60K480V and S3MT-100K480V input isolation transformers provide 480V (Delta) to 208V (Wye) step-
down and Isolation protection to the connected UPS and its load. The S3MT-60K600V and S3MT-100K600V Input isolation
transformers provide 600V (Delta) to 208V (Wye) step-down and isolation protection to the connected UPS and its load.
The transformer has input isolation to mitigate utility line surges and spikes, while protecting the UPS. The transformer
includes a built in breaker at the transformer output side for protection. The ball-bearing fans maintain quiet operation (four
fans for 60K models, three large fans for 100K models). An overheat-sensing relay and switch combine with a warning light
to provide over-temperature warning and overheating protection. The UPS system’s small footprint and quiet acoustic profile
enable installations with minimal space and noise impact. All transformer models feature rugged stainless steel housings with
front panels similar to the S3M-Series 208V 3-Phase UPS line.
UPS Model Series Number Capacity Description
S3MT-60K480V AG-050D 60kW 480V to 208V Input Isolation Transformer
S3MT-100K480V AG-0510 100kW 480V to 208V Input Isolation Transformer
S3MT-60K600V AG-050F 60kW 600V to 208V Input Isolation Transformer
S3MT-100K600V AG-050E 100kW 600V to 208V Input Isolation Transformer
Typical applications
4-Wire (3Ph+N+PE) IT equipment loads in government, manufacturing, hospitals, industrial settings and corporate settings
that have 480V or 600V electrical mains and 208V/120V or 220V/127V IT Loads.
Key Features
• Isolation protection to the UPS input, with stepped-down input from 480V (Delta) to 208V/120V (Wye) or 600V (Delta) to
208V/120V (Wye)
• Circuit breaker and overheating protection
• 96.5% to 97.5% efficiency
• Wide input voltage and frequency operating range:
Voltage: -20% to +25% @ 100% load and 40-70 Hz
• Insulation class: 180°C material
• Reliability-tested according to ISTA-3B for vibration, shock, drop (tip test)
• UL and CSA TUV certifications
• Rugged stainless steel housing shipped ready for installation
• 2-year warranty
4
1. Introduction
Typical Configurations
These 480V Input Transformers may be purchased separately or as part of kit model with a Tripp Lite S3M Series 3-Phase UPS:
Input
Transformer Models
Maximum
Constant Load
Compatible with
208V 3Ph UPS
Kit Models: UPS + Transformer
Kit Models Kit Models Include
480V
S3MT-60K480V 60kW 50-60kW UPS
S3M50K-60K4T
S3M50K UPS +
S3MT-60K480V
S3M60K-60K4T
S3M60K UPS +
S3MT-60K480V
S3MT-100K480V 100kW 80-100kW UPS
S3M80K-100K4T
S3M80K UPS +
S3MT-100K480V
S3M100K-100K4T
S3M100K UPS +
S3MT-100K480V
600V
S3MT-60K600V 60kW 50-60kW UPS
S3M50K-60K6T
S3M50K UPS +
S3MT-60K600V
S3M60K-60K6T
S3M60K UPS +
S3MT-60K600V
S3MT-100K600V 100kW 80-100kW UPS
S3M80K-100K6T
S3M80K UPS +
S3MT-100K600V
S3M100K-100K6T
S3M100K UPS +
S3MT-100K600V
480V,
600V,
208V/120V,
(Wye)
UPS
UPS
WYE-
Load
208/120V
220/127V
WYE-
Load
208/120V
220/127V
208V/120V,
(Wye)
5
CAUTION! Risk of electrical shock! Hazardous live parts inside this unit are energized from the transformer even when
the breaker is turned off.
WARNING! The unit intended for installation in a controlled environment.
CAUTION! A transformer can present a risk of electric shock and high short circuit current. The following precaution should
be observed when working on the transformer:
• Remove watches, rings or other metal objects.
• Use tools with insulated handles.
To reduce the risk of electric shock, disconnect the transformer and UPS from the mains supply before performing
maintenance or service.
Servicing of the 3-phase transformer and UPS should be performed by Tripp Lite certified personnel with knowledge of the
3-phase transformer and UPS and all required precautions.
The transformer is extremely heavy. Caution should be taken in moving and positioning equipment. The instructions contained
within this manual are important and should be closely followed at all times during installation and follow-up maintenance of
the 3-phase transformer and UPS.
CAUTION!
The transformer has a dangerous level of heat. If the transformer’s front-panel red LED indicator is on,
the unit’s outlets may have a dangerous level of heat.
All servicing on this equipment must be carried out by Tripp Lite-certified service personnel.
Before conducting any maintenance, repair or shipment, first ensure everything is turned off completely
and disconnected.
Special Symbols – The following symbols are used on the transformer to warn you of precautions:
RISK OF ELECTRIC SHOCK - Observe the warning that a risk of electric shock is present.
CAUTION - REFER TO THE OWNER’S MANUAL for information regarding important operating and
maintenance instructions.
SAFE GROUNDING TERMINAL - Indicates THE primary safe ground.
2. Important Safety Warnings
SAVE THESE INSTRUCTIONS
This manual contains important instructions for models S3MT-60K480V / S3MT-100K480V / S3MT-60K600V /
S3MT-100K600V that should be followed during installation and maintenance of the transformer and UPS.
6
3. Installation
3.1 Mechanical Data
Physical Requirements
Leave space around the cabinet for operation and ventilation (Figure 3-1):
1. Leave at least 23.6 in. (600 mm) space in the front for ventilation
2. Leave at least 20 in. (500 mm) space at the right and left for operation
3. Leave at least 20 in. (500 mm) space at the back for ventilation
Figure 3-1
23.6”
(600 mm)
47.2”
(1200 mm)
33.5”
(850 mm)
20”
(500 mm)
20”
(500 mm)
20”
(500 mm)
20”
(500 mm)
23.6”
(600 mm)
7
3. Installation
3.2 Package Inspection
1. Don’t lean the transformer cabinet when removing it from the packaging.
2. Check the appearance to see if the transformer cabinet was damaged during transport. Do not power on the transformer
cabinet if any damage is found. Contact the dealer immediately.
3. Check the accessories against the packing list and contact the dealer in case of missing parts.
3.3 Unpacking the UPS
1. Hold the sliding plate steady. Cut and remove the binding
straps (Figure 3-2).
Figure 3-2
2. Remove the plastic bag and the outer carton (Figure 3-3).
Figure 3-3
8
3. Installation
3. Remove the foam packing material and the beveled pallet
(Figure 3-4).
Figure 3-4
4. Remove the screws securing the cabinet to the pallet
(Figure 3-5).
Figure 3-5
5. Lift the cabinet with a forklift and remove the packing pallets (Figure 3-6).
Figure 3-6
9
3. Installation
3.4 Package Contents
Contents TL P/N S3MT-60K480V S3MT-60K600V S3MT-100K480V S3MT-100K600V
Input Transformer 1 1 1 1
Owner’s Manual 933D05 1 1 1 1
Bottom Skirts 103922A 2 2 2 2
Bottom Skirts 103923A 2 2 2 2
Screws for Skirts 3011C3 24 24 24 24
10
3. Installation
3.5 Cabinet Overview
1
Over-Temperature Alarm LED
2
Cooling Fans
3
Breaker with Trip
4
Cabling Terminals
5
Bottom Entry Knockouts
(for Power Cable Entry and Exit)
Rear View,
S3MT-60K480V / S3MT-60K600V
Rear View,
S3MT-100K480V / S3MT-100V600V
Front View
1
2 2
5
4
3
Front View (Terminal Block without Cover), S3MT-60K480V / S3MT-60K600V
11
3. Installation
Front View (Terminal Block without Cover), S3MT-100K480V / S3MT-100K600V
3
4
5
12
3. Installation
3.6 Power Cables
The cable design shall comply with the voltages and currents provided in this section, and in accordance with local electrical codes.
WARNING!
UPON STARTUP, ENSURE YOU ARE AWARE OF THE LOCATION AND OPERATION OF THE EXTERNAL
ISOLATORS CONNECTED TO THE UPS INPUT/BYPASS SUPPLY OF THE UTILITY DISTRIBUTION PANEL.
ENSURE THESE SUPPLIES ARE ELECTRICALLY ISOLATED AND POST ANY NECESSARY WARNING SIGNS TO
PREVENT INADVERTENT OPERATION.
Cable Sizes
UPS Model
Cable Sizes (THHW wiring at 75°C)
AC Input AC Output Neutral Grounding Lug
Gauge Torque Gauge Torque Gauge Torque Gauge Torque
S3MT-
60K480V
50mm
2
Max.
50mm
2
x2
25N•m
50mm
2
Max.
50mm
2
x2
25N•m
70mm
2
x2
Max.
70mm
2
x2
25N•m
50mm
2
Max.
50mm
2
x2
25N•m M8
S3MT-
60K600V
35mm
2
Max.
50mm
2
x2
25N•m
50mm
2
Max.
50mm
2
x2
25N•m
70mm
2
x2
Max.
70mm
2
x2
25N•m
50mm
2
Max.
50mm
2
x2
25N•m M8
S3MT-
100K480V
70mm
2
x2
Max.
120mm
2
x2
50N•m
70mm
2
x2
Max.
95mm
2
x2
50N•m
120mm
2
x2
Max.
120mm
2
x2
50N•m
95mm
2
Max.
120mm
2
50N•m M10
S3MT-
100K600V
50mm
2
Max.
70mm
2
x2
50N•m
70mm
2
x2
Max.
95mm
2
x2
50N•m
120mm
2
x2
Max.
120mm
2
x2
50N•m
95mm
2
Max.
120mm
2
50N•m M10
13
3.7 Transformer-to-UPS Connection Line Diagram
Connections are shown below for the cabinet with built-in input isolator transformer, breakers and the red over-temperature LED.
Figure 3-7: Connection Line Diagram for S3MT-60K480V / S3MT-100K480V
3. Installation
Input Transformer
Red LED (Lit = Over-Temperature, Off = Normal)
Output 208/120V AC,
3-Phase, 4-Wire +
Ground to the UPS Input
Output 208/120V,
220/127V,
3-Phase, 4-Wire +
Ground to Load
Maintenance Breaker
Bypass Breaker
Mains Breaker
Battery input: +/–120V DC
Output Breaker
PFC STSInverter
Charger
Delta In 480V/208V Wye
Transformer Cabinet
UPS
Breaker
3PH
Trip
AC Input 480V AC
14
3. Installation
Figure 3-8: Connection Line Diagram for S3MT-60K600V/ S3MT-100K600V
Input Transformer
Red LED (Lit = Over-Temperature, Off = Normal)
Maintenance Breaker
Bypass Breaker
Mains Breaker
Battery input: +/–120V DC
Output Breaker
PFC STSInverter
Charger
Delta In 600V/208V Wye
Transformer Cabinet
UPS
Breaker
3PH
Trip
AC Input 600V AC
Output 208/120V AC,
3-Phase, 4-Wire +
Ground to the UPS Input
Output 208/120V,
220/127V,
3-Phase, 4-Wire +
Ground to Load
15
3.8 Multiple Transformer Connections
3.8.1 Connections for S3MT-60K480V/S3MT-60K600V to S3M50K or S3M60K UPS
Transfomer input is Delta 3-Wire (3Ph + Ground) And transformer output is Wye 4-Wire (3Ph + N + Ground).
Figure 3-8: UPS (Rear View) Transformer Cabinet (Front View)
3.8.2 Connections for S3MT-100K480V/S3MT-100K600V to S3M80K or S3M100K UPS
Transfomer input is Delta 3-Wire (3Ph + Ground) And transformer output is Wye 4-Wire (3Ph + N + Ground).
Figure 3-9: UPS (Rear View) Transformer Cabinet (Front View)
3. Installation
WARNING: The transformer output neutral is not bonded to chassis ground. Please provide a means
to connect the transformer chassis ground to the transformer output neutral.
Note: The transformer chassis ground must be connected to earth ground.
IMPORTANT: You may view and/or download this manual from the tripplite.com website to view the
cable connections in colors.
16
4. Operation
4.1 Over-Temperature Protection
4.1.1 Over-Temperature Red Warning LED Light
The transformer includes a warning LED light on the top portion of the front panel. The light turns ON when the transformer
reaches a temperature of 160°C ±5°C, i.e. a range of 155°C to 165°C (311°F to 329°F). The light turns OFF when the
transformer cools to a temperature of 125°C ±5°C, i.e. a range of 120°C to 130°C (248°F to 266°F).
4.1.2 Over-Temperature Protection Relay and Thermal Switch
The transformer includes an over-temperature protection relay and thermal switch to protect the transformer from overheating.
At temperatures of 160°C ±5°C, i.e. a range of 155°C to 165°C (311°F to 329°F), an over-temperature protection relay and
thermal switch will activate and will open the output breaker of the transformer. Once the transformer temperature has cooled
down and the warning LED light has turned OFF, you may manually re-activate (close) the output breaker to restart normal
operation.
WARNING: It is not advised to connect two UPS in parallel when using individual transformers for
each UPS.
17
5. Specifications
Models S3MT-60K480V S3MT-60K600V S3MT-100K480V S3MT-100K600V
Description
3-Phase 60k
Input Isolation
Transformer, Delta
480V/208V Wye
3-Phase 60k
Input Isolation
Transformer, Delta
600V/208V Wye
3-Phase 100k
Input Isolation
Transformer, Delta
480V/208V Wye
3-Phase 100k
Input Isolation
Transformer, Delta
600V/208V Wye
Transformer Type Dry-Type
Input
Input Voltage 480V 600V 480V 600V
Input Voltage Operational Range and
De-Rating
-45%, +25% at 40 % Load
-20%, +25% at 100 % Load
Input Amps 101A 81A 168A 134A
Input Connections 3-Wire (L1, L2, L3, +PE)
Input Configuration Delta
Input Connection Type Copper Bar
Rated AC Input Frequency 50/60 Hz
Frequency Range and Derating 40~70 Hz
Voltage Selection No
Voltage Drop: Ratio Ouput,
No Load to Full Load
3%
Inrush Current 900A (10 ms) 710A (10 ms) 3330A (10 ms) 1160A (10 ms)
Input Isolation Yes
Output
VA Rating 60kVA 60kVA 100kVA 100kVA
Transformer Output Voltage 208/120V, (3-Phase, 4-Wire)
Output Amps 225A 374A
Transformer Output Breaker Rating 250A 250A 400A 400A
Output Watts Detailed 60,000W 60,000W 100,000W 100,000W
Output Connections 4-Wire (L1, L2, L3, +PE, +N)
Output Connection Type Copper Bar
Output Configuration Wye
Input Tranformer Output Isolation Yes
Operation
Over-Temperature Warning LED (Red)
Turns ON at 160°C ±5°C, i.e. a range of 155°C to 165°C ( 311°F to 329°F)
Turns OFF at 125°C ±5°C, i.e. a range of 120°C to 130°C (248°F to 266°F)
Over-Temperature Protection
Reset Device
Transformer output turns OFF at temperatures of 160°C ±5°C,
i.e. a range of 155°C to 165°C (311°F to 329°F).
The transformer output breaker can be turned ON manually when the
warning light turns OFF.
Insulation Class 180°C
Temperature Rise 125°C
Full Load Efficiency 96.50% 96.70%
18
5. Specifications
Models S3MT-60K480V S3MT-60K600V S3MT-100K480V S3MT-100K600V
Half Load Efficiency 97.50% 97.70%
Physical Info
Unit Height 47.2 in. (1200 mm)
Unit Width 23.6 in. (600 mm)
Unit Depth 33.5 in. (850 mm)
Unit Weight 789 lb. (358 kg) 789 lb. (358 kg) 1078 lb. (489 kg) 1049 lb. (476 kg)
Floor Loading 702 (kg/m²) 702 (kg/m²) 959 (kg/m²) 933 (kg/m²)
Unit Carton Height 55.4 in. (1407 mm)
Unit Carton Width 29.9 in. (760 mm)
Unit Carton Depth 38.8 in. (985 mm)
Unit Carton Weight 855 lb. (388 kg) 899 lb. (408 kg) 1202 lb. (545 kg) 1102 lb. (500 kg)
Tip-n-Tell Label Included on
Overpack Box
Yes
Environment
Audible Noise at 1 m 65 dB max.
RH Humidity, Non-Condensing 95%
Online Thermal Dissipation,
Full Load (BTU/hr)
7167 7167 11263 11263
Storage Temperature 5°F to 140°F (-15°C to 60°C)
Operating Temperature 32°F to 104°F (0°C to 40°C)
Operating Elevation <1000 m for nominal power (over 1000 m, the power de-rating is 1% per 100 m)
Mechanical
Transformer Windings Aluminum
Cabinet Material Cold Rolled Galvanized Steel (SGCC)
Cabinet Color RAL 9011
Fan (Type/Quantity)
60K Models: 4x Ball Bearing, 120 mm (576 total CFM)
100K Models: 3x Ball Bearing, 172 x 152 mm (723 total CFM)
Reliability
Vibration ISTA - 3B
Shock ISTA - 3B
Drop ISTA - 3B (Tip Test)
Agency Approvals
Approving Agency cTUVs
Agency Standard Tested UL 1778 5th Edition
Canadian Approvals CSA 22.2-107.3-14
CE Approvals N/A
EMI Approvals N/A
RoHS/REACH Yes
19
6. Storage
Before storing the isolation transformer, ensure all connections have been disconnected and all breakers are turned OFF.
Replace all input or output access covers to avoid damaging any contacts.
The transformer must be stored in a clean, secure environment with temperatures between 5°F to 140°F (-15°C to 60°C)
and relative humidity less than 90% (non-condensing).
Store the transformer in its original shipping container, if possible.
7. Warranty and Regulatory Compliance
Limited Warranty
Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material and workmanship for a period
of 2 years from the date of initial purchase. If the product should prove defective in material or workmanship within that period, Seller will repair or replace the
product, in its sole discretion. Service under this Warranty includes parts only. International customers should contact Tripp Lite support at
[email protected]. Continental USA customers should contact Tripp Lite Customer Service at 773-869-1234 or visit tripplite.com/support/help
THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT, MISUSE, ABUSE OR NEGLECT. SELLER MAKES NO
EXPRESS WARRANTIES OTHER THAN THE WARRANTY EXPRESSLY SET FORTH HEREIN. EXCEPT TO THE EXTENT PROHIBITED BY APPLICABLE LAW, ALL IMPLIED
WARRANTIES, INCLUDING ALL WARRANTIES OF MERCHANTABILITY OR FITNESS, ARE LIMITED IN DURATION TO THE WARRANTY PERIOD SET FORTH ABOVE;
AND THIS WARRANTY EXPRESSLY EXCLUDES ALL INCIDENTAL AND CONSEQUENTIAL DAMAGES. (Some states do not allow limitations on how long an implied
warranty lasts, and some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not
apply to you. This Warranty gives you specific legal rights, and you may have other rights, which vary from jurisdiction to jurisdiction.)
Tripp Lite; 1111 W. 35th Street; Chicago IL 60609; USA
WARNING: The individual user should take care to determine prior to use whether this device is suitable, adequate or safe for the use intended. Since
individual applications are subject to great variation, the manufacturer makes no representation or warranty as to the suitability or fitness of these devices for
any specific application.
Product Registration
Visit tripplite.com/warranty today to register your new Tripp Lite product. You will be automatically entered into a drawing for a chance to win a FREE Tripp Lite product!*
* No purchase necessary. Void where prohibited. Some restrictions apply. See website for details.
WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union)
Under the Waste Electrical and Electronic Equipment (WEEE) Directive and implementing regulations, when customers buy new electrical and
electronic equipment from Tripp Lite they are entitled to:
• Send old equipment for recycling on a one-for-one, like-for-like basis (this varies depending on the country)
• Send the new equipment back for recycling when this ultimately becomes waste
Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life
support equipment or to significantly affect its safety or effectiveness is not recommended.
Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice. Photos and illustrations may differ slightly from
actual products.
WARNING: The transformer(s) is/are very heavy. Before storing the transformer, make sure to take
into account the floor loading (kg/m²) requirements listed in section 5. Specifications under
“Physical Info” to store safely.
20
1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support
20-08-282 93-3D05_RevA
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60

Tripp Lite S3MT-60K600V Le manuel du propriétaire

Catégorie
Alimentations sans interruption (UPS)
Taper
Le manuel du propriétaire