Philips DDNG485 Manuel utilisateur

Taper
Manuel utilisateur
64 mm (2.52 in)
68 mm (2.68 in)
108 mm (4.25 in)
95 mm (3.74 in)
105 mm (4.13 in)
1
45 mm
(1.77 in)
45 mm
(1.77 in)
Installation Instructions
Instructions d’installation
Installationsanweisungen
Instrucciones de instalación
Istruzioni per l’installazione
Installatie-instructies
インストー ル 手 順
安装指示
50° C (122° F)
0° C (32° F)
90%
SELV/Class 2 (UL)
12 V 200 mA
70 mA +(1.6 x DyNet Port 2
load current) @ 12 V
60 mA +(0.7 x DyNet Port 2
load current) @ 24 V
µP
AUX
+ V
D +
D -
GND
SHLD
+ 12V
D +
D -
GND
SHLD
2
IEC Overvoltage Category III
Devices must be installed by a
qualied electrician in accordance with
all national and local electrical and
construction codes and regulations.
Les appareils doivent être installés par un
électricien diplômé conformément à tous les
codes et réglementations électriques et de
construction nationaux et locaux.
Die Geräte sind von einem qualizierten Elektriker
in Übereinstimmung mit allen geltenden
Vorschriften zu installieren.
Los dispositivos deben ser instalados por un
electricista calicado y cumpliendo todas las
normas y regulaciones, tanto nacionales como
locales, sobre instalaciones eléctricas y obras.
I dispositivi devono essere installati da un
elettricista qualicato in conformità con le norme
locali e nazionali vigenti in materia di costruzioni
edilizie e installazione di impianti elettrici.
De apparaten moeten worden aangebracht
door een gekwaliceerde elektricien en in
overeenstemming met alle nationale en
plaatselijke elektriciteits- en bouwvoorschriften.
装置付け際は、資格の電気技師に依頼
国おび地域の電気おび建設の法令に
従 ってくだ さい 。
根据国家/地区及当地的电气与建筑规范和法规,该设
备必须由有资质的电工进行安装。
.
DDNG485
RS-485/DMX512
Gateway
IEC Pollution Degree II
GND AUX
0.4 Nm
3.5 Lb-in
0.3-2.5mm2
22-12 AWG
<20 m
Port 1 Port 2
SHLD
GND
D+
D-
+12 V
AUX
SHLD
GND
D+
D-
+12 V
2 A 2 A
3
DDNG485
Port 1 Port 2
RS-485
• DyNet Trunk
• DMX512
• etc.
RS-485
• DyNet Spur
4 A
4 B
Port 1
Port 2
Port 1
Port 2
RS-485
DyNet Spur
RS-485
DyNet Spur
800m
RS-485
DyNet Trunk
AZZ 411 1222 R21
© 2022 Signify Holding. All rights reserved. Specications are subject to
change without notice. No representation or warranty as to the accuracy or
completeness of the information included herein is given and any liability
for any action in reliance thereon is disclaimed. Philips and the Philips
Shield Emblem are registered trademarks of Koninklijke Philips N.V. All other
trademarks are owned by Signify Holding or their respective owners.
www.dynalite.com
Federal Communications Commission (FCC) Compliance Notice: Radio Frequency NoticeThis equipment has been tested and found to comply with the
limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions,
may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment o and on, the user is encouraged
to try to correct the interference by one or more of the following measures: Reorient or relocate the receiving antenna. Increase the separation between the
equipment and receiver. Connect the equipment into an outlet on a circuit dierent from that to which the receiver is connected. Consult the dealer or an
experienced radio/TV technician for help. Any modications not approved by the manufacturer of this device could void the user’s authority to operate this device.
This Class B digital apparatus complies with Canadian ICES-003: CAN ICES-3(B)/NMB-3(B). Cet appareil numerique de la classe B est conforme a la norme NMB-
003 du Canada: CAN ICES-3(B)/NMB-3(B).
Installation of a home and building automation and control system shall comply with IEC 60364 (all parts). The temperature limits and current-carrying capacities
for the communication wires specied in IEC 60364-5-52 shall not be exceeded.
Port 1 Port 2
DyNet - up to 800m
Power supplied by
controllers or DDNP1501
To network devices To network devices
Port 1 Port 2
DDNP1501
For cable runs over 300 m (1000 ft), or baud rates over 9600 bps, 120 Ω, 2 W end-of-line
resistors must be installed across the D+ and D- terminals on the rst and last devices.
5
4 C
  • Page 1 1
  • Page 2 2

Philips DDNG485 Manuel utilisateur

Taper
Manuel utilisateur

dans d''autres langues