HeatStar ERXL150-N Le manuel du propriétaire

Catégorie
Chauffe-eau
Taper
Le manuel du propriétaire
FOR YOUR SAFETY:
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WARNING: If the information in these instructions are not followed exactly, a fire or explosion may result causing
property damage, personal injury or loss of life.
18677XL
ENERCO Group, Inc., 4560 W. 160TH ST., CLEVELAND, OHIO 44135 • 866-447-2194
LANGUAGES INCLUDED
•ENGLISH
•FRENCH
•SPANISH
Heatstar ERXL
Gas-Fired Low-Intensity Infrared Heaters Approved
For Residential Garage/Commercial Applications
XL
ER
OPERATING INSTRUCTIONS
AND OWNER’S MANUAL
Model #
ERXL-40 ERXL-60
ERXL-80 ERXL-100
ERXL-125 ERXL-150
ERXL-175
READ INSTRUCTIONS CAREFULLY: YOUR SAFETY IS IMPORTANT TO YOU AND TO OTHERS Read and
follow all instructions. Place instructions in a safe place for future reference. Do not allow anyone who has
not read these instructions to assemble, light, adjust or operate the heater.
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause
property damage, injury or death. Read the installation, operating and maintenance instructions
thoroughly before installing or servicing this equipment.
- WHAT TO DO IF YOU SMELL GAS
Open Windows
DO NOT try to light any appliance.
DO NOT use electrical switches.
DO NOT use any telephone in your house. Immediately call your local gas supplier from a telephone remote from the
area of the leak. Follow the gas supplier’s instructions.
Do not touch any electrical switch; do not use any phone in your building.
Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
If you cannot reach your gas supplier, call the Fire Department.
E-2
Enerco | Heatstar ERXL Series Heater Operating Instructions and Owner’s Manual
SECTION 1:Introduction
Heatstar ERXL models are low-cost, field assembled infrared heaters
that are easy to install and require only minimal maintenance. They
are designed to provide years of economical operation and
trouble-free service.
Checking Shipment
Check the shipment against the Bill of Lading for shortages. Also,
check for external damage to cartons. Note any shortages, and/
or external damage to cartons on the Bill of Lading in the presence
of the delivery trucker. The delivery trucker should acknowledge
any shortages or damage by initializing this “noted” Bill of Lading.
Immediately report any claims for damaged material, or shortages
that were not evident at the time of shipment, to the carrier and your
Enerco Group, Inc Factory Representative.
Installer Responsibility
All heaters and associated gas piping should be installed in
accordance with applicable specifications and this installation made
only by firms (or individuals) well qualified in this type of work.
Consult local building inspectors, Fire Marshals or your local Enerco
Group, Inc Factory Representative for guidance.
Heatstar ERXL heaters are installed on the basis of information
given in a layout drawing, which together with the cited codes and
regulations, comprise the basic information needed to complete the
installation. The installer must furnish all needed material that is not
furnished as standard equipment, and it is his responsibility to see that
such materials, as well as the installation methods he uses result in a
job that is workmanlike and in compliance with all applicable codes.
Enerco Group, Inc Factory Representatives have had training and
experience in the application of this equipment and can be called on
for suggestions about installation which can save material and money.
GENERAL HAZARD WARNING:
FAILURE TO COMPLY WITH THE PRECAUTIONS AND
INSTRUCTIONS PROVIDED WITH THIS HEATER, CAN
RESULT IN DEATH, SERIOUS BODILY INJURY AND
PROPERTY LOSS OR DAMAGE FROM HAZARDS OF
FIRE, EXPLOSION, BURN, ASPHYXIATION, CARBON
MONOXIDE POISONING, AND/OR ELECTRICAL
SHOCK.
ONLY PERSONS WHO CAN UNDERSTAND AND
FOLLOW THE INSTRUCTIONS SHOULD USE OR
SERVICE THIS HEATER.
IF YOU NEED ASSISTANCE OR HEATER INFORMATION
SUCH AS AN INSTRUCTIONS MANUAL, LABELS, ETC.
CONTACT THE MANUFACTURER.
WARNING:
YOUR SAFETY IS IMPORTANT TO YOU AND TO
OTHERS, SO PLEASE READ THESE INSTRUCTIONS
BEFORE YOU OPERATE THIS HEATER.
WARNING:
FIRE, BURN, INHALATION, AND EXPLOSION
HAZARD. KEEP SOLID COMBUSTIBLES, SUCH AS
BUILDING MATERIALS, PAPER OR CARDBOARD,
A SAFE DISTANCE AWAY FROM THE HEATER AS
RECOMMENDED BY THE INSTRUCTIONS NEVER
USE THE HEATER IN SPACES WHICH DO OR MAY
CONTAIN VOLATILE OR AIRBORNE COMBUSTIBLES,
OR PRODUCTS SUCH AS GASOLINE, SOLVENTS,
PAINT THINNER, DUST PARTICLES OR UNKNOWN
CHEMICALS.
WARNING:
THIS PRODUCT CAN EXPOSE YOU TO CHEMICALS
INCLUDING LEAD AND LEAD COMPOUNDS, WHICH
ARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE
CANCER AND BIRTH DEFECTS OR OTHER REPRODUCTIVE
HARM. FOR MORE INFORMATION VISIT WWW.
P65WARNINGS.CA.GOV
WARNING: Fuels used in liquefied propane
gas appliances, and the products of combustion of such
fuel, can expose you to chemicals including benzene,
which is known to the state of California to cause cancer
and cause birth defects or other reproductive harm, for
more information go to www.P65Warnings.ca.gov
CONTENTS
Section 1 INTRODUCTION ...............................................................2
Section 2 PLANNING ........................................................................3
Section 3 INSTALLATION & ASSEMBLY ............................................ 6
Section 4 ENGINEERING SPECIFICATIONS ......................................13
Section 5 VENTING/DUCTING ........................................................14
Section 6 GAS PIPING .................................................................... 17
Section 7 WIRING .......................................................................... 18
Section 8 OPERATION MAINTENANCE ........................................... 18
Section 9 TROUBLESHOOTING .......................................................21
REPLACEMENT PARTS ....................................................................22
WARRANTY INFORMATION ...........................................................28
E-3 Operating Instructions and Owner’s ManualEnerco | Heatstar ERXL Series Heater
SECTION 2: Planning
The following codes and instructions should be followed when
planning the installation of the Heatstar ERXL heater. In addition
to these instructions, the warnings in (Section 1) must be carefully
adhered to since improper installation may lead to property damage,
injury, or death.
National Standards and Applicable
Codes
Gas Codes:
The type of gas appearing on the nameplate must be the
type of gas used. Installation must comply with local codes
and recommendations of the local gas company, and the
National Fuel Gas Code, ANSI Z223.1 – latest revision,
(same as NFPA Bulletin 54) or the Natural Gas and Propane
Installation Code, CSA B149.1.
Clearance between the heater and its vent and adjacent
combustible material (which is part of the building or its
contents) shall be maintained to conform with the Standard
for Installation of Gas Appliances and Gas Piping, NFPA-54 /
ANSI Z223.1 – latest revision, National Fuel Gas Code or the
Natural Gas and Propane Installation Code, CSA B149.1.
Aircraft Hangers:
Installation in aircraft hangers must be in accordance with
the Standard for Aircraft Hangers, ANSI / NFPA-409 – latest
revision.
Heaters in aircraft storage or service areas shall be installed
at a height of 10 feet above the upper surface of wings
or engine enclosures of the highest aircraft which may be
housed in the hanger. (This should be measured from the
bottom of the heater to the wing or engine enclosure,
whichever is highest from the floor.)
In other sections of aircraft hangers, such as shops or offices,
heaters must not be installed less than 8 feet above the
floor.
Heaters installed in aircraft hangers shall be located so as
not to be subject to damage by aircraft, cranes, moveable
scaffolding or other objects.
Public Garages:
Installations in garages must be made in accordance with the
Standard for Parking Structures, NFPA-88A – latest revision
or the Standard for Repair Garages, NFPA-88B – latest
revision.
Heaters must not be installed less than 8 feet above
the floor. Minimum clearances to combustibles must be
maintained from vehicles parked below the heater.
When installed over hoists, minimum clearances to
combustibles must be maintained from the uppermost point
on the hoist.
Venting:
The venting must be installed in accordance with NFPA-54 /
ANSI Z223.1 or CSA 149.1– latest revision, National Fuel Gas
Code. Partial information with regard to this code is provided
in (Section 5) of this installation manual with regard to size
and configurations for venting arrangements.
Any portion of flue pipe passing through a combustible wall
must be dual insulated or have an approved thimble. Refer to
ANSI-Z223.1 or CSA149.1– latest revision.
Hazardous Locations:
Where there is the possibility of exposure to combustible
airborne material or vapor, consult the local Fire Marshal, the
fire insurance carrier or other authorities for approval of the
proposed installation.
Critical Considerations
Heatstar ERXL is a suspended heater. Therefore, its stability,
flexibility, and safety are very important. Before starting
installation, be sure the system can meet the following
requirements.
Maintain specified clearances to combustibles, and safe dis-
tance from the heat-sensitive material, equipment and work
stations.
The stated clearances to combustibles represent a surface
temperature of 90°F (30°C) above room temperature.
Building materials with low heat tolerance (such as plastic,
vinyl siding, canvas, etc.) may be subject to degradation at
lower temperatures. It is the installers responsibility to assure
that adjacent materials are protected from degradation.
Provide a suspension with vertical length of chain or swinging
rod which has at least 2 inches of horizontal travel for each
burner in a straight run. Be sure the suspension system is
sufficiently flexible to accommodate thermal expansion which
occurs as the system heats up (see Figure 6 on page 12).
Provide access to burners for servicing, preferable on both
sides, above and behind the burner for removal.
Provide a minimum of 18 inches of clearance between burn-
ers and building walls. (Always observe minimum clearances
to combustibles.)
Be sure the heater has a downward pitch of one-half inch per
20 feet away from the burner. (1.25 cm per 6.1 m)
Provide signs in storage areas to specify maximum stacking
height to maintain required clearances to combustibles.
Plan location supports (see Figure 2A-G starting on page 8).
Locate a support near all elbows.
The installation must conform with local building codes or
in the absence of local codes, with the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the Natural Gas and Pro-
pane Installation Code, CSA B149.1.
If an external electrical source is utilized, the heater, when
installed, must be electrically grounded in accordance with
the National Electrical Code, ANSI/ NFPA 70 or current
Canadian Electrical Code, CSA C22.1.
Available Venting Kits
F102848 4" Vertical Vent Kit
F102849 6" Vertical Vent Kit
F102860 4" Stainless Steel Horizontal Vent Kit
E-4
Enerco | Heatstar ERXL Series Heater Operating Instructions and Owner’s Manual
Clearances To Combustibles
TABLE 1: Minimum Clearances to Combustibles (Use Figure 1 on page 5 as a Guide)
Reflector Type Position ERXL-40 ERXL-60 ERXL-80 ERXL-100 ERXL-125 ERXL-150 ERXL-175
Standard
Reflector
(Horizontal)
A
B
C
D
6" (15.25cm)
30" (76.25 cm)
55" (140 cm)
30" (76.25 cm)
6" (15.25cm)
30" (76.25 cm)
55" (140 cm)
30" (76.25 cm)
6" (15.25cm)
36" (30.5 cm)
55" (140 cm)
36" (30.5 cm)
6" (15.25cm)
36" (30.5 cm)
74" (188 cm)
36" (30.5 cm)
6" (15.25cm)
36" (30.5 cm)
87" (221 cm)
36" (30.5 cm)
6" (15.25cm)
36" (30.5 cm)
87" (221 cm)
36" (30.5 cm)
8" (20.5 cm)
36" (30.5 cm)
87" (221 cm)
36" (30.5 cm)
45° Reflector Tilt
A
B
C
E
F
12" (30.5 cm)
30" (76.25 cm)
55" (140 cm)
36" (30.5 cm)
60" (152.5 cm)
12" (30.5 cm)
30" (76.25 cm)
55" (140 cm)
36" (30.5 cm)
60" (152.5 cm)
18" (46 cm)
36" (30.5 cm)
55" (140 cm)
36" (30.5 cm)
60" (152.5 cm)
18" (46 cm)
36" (30.5 cm)
74" (188 cm)
36" (30.5 cm)
60" (152.5 cm)
18" (46 cm)
36" (30.5 cm)
87" (221 cm)
36" (30.5 cm)
60" (152.5 cm)
18" (46 cm)
36" (30.5 cm)
87" (221 cm)
36" (30.5 cm)
60" (152.5 cm)
18" (46 cm)
36" (30.5 cm)
87" (221 cm)
36" (30.5 cm)
60" (152.5 cm)
U-Tube Standard
(Horizontal)
A
B
C
D
6" (15.25cm)
30" (76.25 cm)
55" (140 cm)
30" (76.25 cm)
6" (15.25cm)
30" (76.25 cm)
55" (140 cm)
30" (76.25 cm)
6" (15.25cm)
36" (30.5 cm)
55" (140 cm)
36" (30.5 cm)
6" (15.25cm)
36" (30.5 cm)
74" (188 cm)
36" (30.5 cm)
6" (15.25cm)
36" (30.5 cm)
87" (221 cm)
36" (30.5 cm)
6" (15.25cm)
36" (30.5 cm)
87" (221 cm)
36" (30.5 cm)
8" (20.5 cm)
36" (30.5 cm)
87" (221 cm)
36" (30.5 cm)
U-Tube Opposite
45°
A
B
C
F
12" (30.5 cm)
30" (76.25 cm)
55" (140 cm)
60" (152.5 cm)
12" (30.5 cm)
30" (76.25 cm)
55" (140 cm)
60" (152.5 cm)
18" (46 cm)
36" (30.5 cm)
55" (140 cm)
60" (152.5 cm)
18" (46 cm)
36" (30.5 cm)
74" (188 cm)
60" (152.5 cm)
18" (46 cm)
36" (30.5 cm)
87" (221 cm)
60" (152.5 cm)
18" (46 cm)
36" (30.5 cm)
87" (221 cm)
60" (152.5 cm)
18" (46 cm)
36" (30.5 cm)
87" (221 cm)
60" (152.5 cm)
U-Tube Full 45°
A
B
C
E
F
12" (30.5 cm)
30" (76.25 cm)
55" (140 cm)
36" (30.5 cm)
60" (152.5 cm)
12" (30.5 cm)
30" (76.25 cm)
55" (140 cm)
36" (30.5 cm)
60" (152.5 cm)
18" (46 cm)
36" (30.5 cm)
55" (140 cm)
36" (30.5 cm)
60" (152.5 cm)
18" (46 cm)
36" (30.5 cm)
74" (188 cm)
36" (30.5 cm)
60" (152.5 cm)
18" (46 cm)
36" (30.5 cm)
87" (221 cm)
36" (30.5 cm)
60" (152.5 cm)
18" (46 cm)
36" (30.5 cm)
87" (221 cm)
36" (30.5 cm)
60" (152.5 cm)
18" (46 cm)
36" (30.5 cm)
87" (221 cm)
36" (30.5 cm)
60" (152.5 cm)
Unvented Above A 36" (30.5 cm) 36" (30.5 cm) 36" (30.5 cm) 36" (30.5 cm) 36" (30.5 cm) 36" (30.5 cm) 36" (30.5 cm)
WARNING:
FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY OR DEATH.
In all situations, clearances to combustibles must be maintained. Failure to observe clearances to combustibles may result in property
damage, severe injury, or death.
Minimum clearances must be maintained from vehicles parked below the heater. Signs should be posted in storage areas to specify
maximum stacking height to maintain required clearances to combustibles.
Caution should be used when running the system near combustible materials such as wood, paper, rubber, etc. Consideration should be
given to partitions, storage racks, hoists, building construction, etc.
TABLE 1 gives minimum acceptable clearances to combustibles. Clearances as shown in TABLE 1 are not for use in four-sided enclosures.
E-5 Operating Instructions and Owner’s ManualEnerco | Heatstar ERXL Series Heater
D
A
C
STANDARD REFLECTOR
A
E
C
E
45 DEGREE REFLECTOR TILT
C
A
EF
U-TUBE OPPOSITE 45 DEGREE
A
CD
U-TUBE STANDARD
C
E
A
E
U-TUBE FULL 45
BE
FRONT AND BACK CLEARANCE
Clearances To Combustibles
Figure 1: Clearances To Combustibles (Refer to TABLE 1 on page 4)
A
C
EF
STANDARD REFLECTOR
D
A
C
A
C
D
“U”-Tube, Standard
A
C
D
F
“U”-Tube, Opposite 45°
F
C C
AA
E
A
F
“U”-Tube, Full 45°
C
AC
B
B
Front and Back Clearance
E-6
Enerco | Heatstar ERXL Series Heater Operating Instructions and Owner’s Manual
SECTION 3: Installation & Assembly
TUBE COUPLING(14612)
KEY FOR TUBE COUPLING
(14616)
TUBE HANGER
(14585P)
HEAT EXCHANGER TUBE 10'
(06413)
TURBULATOR BAFFLE 10' (03445)
TURBULATOR BAFFLE 5' (03447)
**NOT INCLUDED WITH ALL MODELS**
**ONLY HEATERS 30' LENGTH AND UNDER**
REFLECTOR 10'
(00418A)
VENT ADAPTER
(19021)
BURNER BOX
E-7 Operating Instructions and Owner’s ManualEnerco | Heatstar ERXL Series Heater
Installation Procedure
Take maximum advantage of the building upper structure, beams, joists, purlins, etc., from which to suspend the heater. There is no
unique sequence for installation of the tubing. On-site observation will usually reveal a logical sequence. Begin the installation at the
most critical dimension. This could save time. Watch for swinging doors, overhead cranes, car lifts etc. Reflectors and tubing can be
installed as you move along. Carefully adjust system pitch at each position to level the heater. Pitch down one-half inch in 20 feet (away
from burner).
DON’T Pressure test the gas line using high pressure (greater than ½ PSIG) without closing the high-pressure shutoff cocks. Failure to do so will
result in damage to the burners.
DO Familiarize yourself with local and national
codes.
Develop a planned procedure which will conserve material and labor on the job.
Check to see that all material and equipment is on the job before starting installation.
Allow for thermal expansion of the hot tube.
Install the gas connector only as shown in instructions (see Figure 14 on page 17).
Have slip joints where required between reflectors to keep them from buckling or coming apart.
Provide 1 sq. inch of free air opening to each 1,000 BTU/hr. of heater input (but not less than 100 sq. inches) in enclosed spaces. One
opening should be within 12 inches of the top and one within 12 inches of the bottom of the enclosure.
Burner Housing
Must always be
installed horizontally.
Tube and Reflector Hanger
Install immediately after first
coupling.
Turbulator Assembly
Enerco Group, Inc normally ships Ener-Radiant heaters
with turbulators assembled into appropriate tubes.
Tube and Reflector Hanger
Suspend system from these hangers.
Minimum two (2) required per tube.
Reflectors
Alternate overlap as shown
on overview. Length of
reflector and amount of
overlap is indicated.
10' 2-1/2" ALUMINIZED
Heat Exchange Tubes
Supplied in 10 ft. lengths.
Tube Coupling Assembly
Coupling should be oriented with
slide bar on top, and all couplings
should “point” in the same direction.
Where Field Changes Occur
Turbulator Sections and Adapter are available in
sections and must be assembled before installation
(See Figure 3 for details). The number of sections
required is indicated.
Assemble the heater components as shown in Figures 2A, 2B, 2C, 2D, 2E, 2F and 2G. Optional reflector configurations are shown in Figure
1. Install appropriated suspension hardware, beam clamps, chain or rod at predetermined locations. Adjustment of chain length will provide
uniform pitch.
FIGURE 2: Ener-Radiant XL Overview
Vent Adapter
Used to attach the heat
exchanger tubing to vent pipe.
E-8
Enerco | Heatstar ERXL Series Heater Operating Instructions and Owner’s Manual
ALUMINIZED
ALUMINIZED
FIGURE 2A: Ener-Radiant XL Model ERXL-40
10 ft. Exchanger length. 11 ft. - 4 in. Total Heater length. 2 Suspension points as indicated.
FIGURE 2D: Ener-Radiant XL Model ERXL-100 Assembly Overview
30 ft. Exchanger length. 31 ft. - 4 in. Total Heater length. 6 Suspension points as indicated.
FIGURE 2C: Ener-Radiant XL Model ERXL-80, Assembly Overview
30 ft. Exchanger length. 31 ft. - 4 in. Total Heater length. 6 Suspension points as indicated
9' (2.75 m) Long Turbulator Section
5' (1.5 m) Long Turbulator Section
ALUMINIZED
10' 2½" (3.11m) 10' 2½" (3.11m) 10' 2½" (3.11m)
ALUMINIZED
10' 2½" (3.11m) 10' 2½" (3.11m) 10' 2½" (3.11m)
10' (3.05 m) Long Turbulator Section
10' 2½" (3.11m) 10' 2½" (3.11m)
FIGURE 2B: Ener-Radiant XL Model ERXL-60, ERXL-80, Assembly Overview
20 ft. Exchanger length. 21 ft. - 4 in. Total Heater length. 4 Suspension points indicated.
2½ OVERLAY TYP
ALUMINIZED
ALUMINIZED
ALUMINIZED
ALUMINIZED
(46 cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
10' 2½" (3.11m)
10' (3.05 m) Long Turbulator Section
E-9 Operating Instructions and Owner’s ManualEnerco | Heatstar ERXL Series Heater
FIGURE 2E: Ener-Radiant XL Model ERXL-100, ERXL-125
40 ft. Exchanger length. 41 ft. - 4 in. Total Heater length. 8 Suspension points as indicated.
FIGURE 2F: Ener-Radiant XL Model ERXL-125, ERXL-150, ERXL-175
50 ft. Exchanger length. 51 ft. - 4 in. Total Heater length. 10 Suspension points as indicated.
FIGURE 2G: Ener-Radiant XL Model ERXL-150, ERXL-175
60 ft. Exchanger length. 61 ft. - 4 in. Total Heater length. 12 Suspension points as indicated.
ALUMINIZED ALUMINIZED
10' 2½" (3.11m) 10' 2½" (3.11m)
10' 2½" (3.11m) 10' 2½" (3.11m)10' 2½" (3.11m)10' 2½" (3.11m)
ALUMINIZED ALUMINIZED ALUMINIZED ALUMINIZED
ALUMINIZED ALUMINIZED
10' 2½" (3.11m) 10' 2½" (3.11m)
10' 2½" (3.11m) 10' 2½" (3.11m)10' 2½" (3.11m)
ALUMINIZED ALUMINIZED ALUMINIZED
ALUMINIZED ALUMINIZED
10' 2½" (3.11m) 10' 2½" (3.11m)
10' 2½" (3.11m) 10' 2½" (3.11m)
ALUMINIZED ALUMINIZED
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
HANGER
18"
(46cm)
E-10
Enerco | Heatstar ERXL Series Heater Operating Instructions and Owner’s Manual
FIGURE 3: Ener-Radiant XL Dimensions & Suggested Mounting Heights
Minimum Total Length (see chart below)
Burner Side View
Burner Ratings and Heat Exchanger Lengths: (NG and LP) Suggested Mounting Heights
Model # Rate
(BTU/Hr.)
Heat Exchanger
Length Turbulator Minimum
Total Length
Typical Mounting
Height Spot
ERXL-40 40,000 10 ft. (3.05 m) 9 ft. (2.75 m) 11 ft. 4" (3.45 m) 10’ (3.05 m) - 14' (4.27 m)
ERXL-60 60,000 20 ft. (6.1 m) 10 ft. (3.05 m) 21 ft. 4" (6.50 m) 10’ (3.05 m) - 14’ (4.27 m)
ERXL-80 80,000 20 ft. (6.1 m) 10 ft. (3.05 m) 21 ft. 4" (6.50 m) 12’ (3.66 m) - 15' (4.57 m)
ERXL-80 80,000 30 ft. (9.15 m) 10 ft. (3.05 m) 31 ft. 4" (9.55 m) 12’ (3.66 m) - 15' (4.57 m)
ERXL-100 100,000 30 ft. (9.15 m) 5 ft. (1.5 m) 31 ft. 4" (9.55 m) 12’ (3.66 m) - 15' (4.57 m)
ERXL-100 100,000 40 ft. (12.2 m) None 41 ft. 4" (12.60 m) 12' (3.66 m) - 15' (4.57 m)
ERXL-125 125,000 40 ft. (12.2 m) None 41 ft. 4" (12.60 m) 14' (4.27 m) - 19' (5.79 m)
ERXL-125 125,000 50 ft. (15.25 m) None 51 ft. 4" (15.65 m) 14' (4.27 m) - 19' (5.79 m)
ERXL-150 150,000 50 ft. (15.25 m) None 51 ft. 4" (15.65 m) 15' (4.57 m) - 25' (7.62 m)
ERXL-150 150,000 60 ft. (18.3 m) None 61 ft. 4" (18.69 m) 15' (4.57 m) - 25' (7.62 m)
ERXL-175 175,000 50 ft. (15.25 m) None 51 ft. 4" (15.65 m) 15' (4.57 m) - 25' (7.62 m)
ERXL-175 175,000 60 ft. (18.3 m) None 61 ft. 4" (18.69 m) 15' (4.57 m) - 25' (7.62 m)
Burner Rear View
9.25"(23.49cm)
9.25"(23.49cm)
17.75"(45.08)
Heat Exchanger Tubing
Turbulator
(some Models)
Reector
E-11 Operating Instructions and Owner’s ManualEnerco | Heatstar ERXL Series Heater
Couplings: Tube and tube fittings are connected by wrap-around
couplings which clamp by means of a tapered,
hammer-driven lock member. The starting ends of
the coupling and lock member are identified by 1/4”
holes which are put together when starting assembly.
Be sure the tube ends are in line and tube ends butt
against stop pin(s) inside coupling. The slide bar is to
be hammer-driven to a point of securing the coupling
snugly to the tubes. Over-driving will result in distortion
of the coupling or slide bar lip to a point decreasing
the holding the capability of the coupling.
(See Figure 4)
Elbow Fitting Dimensions
FIGURE 5: Installation of Elbow & Coupling
Elbow Package: Stk. # F106415 Elbow Package includes:
(1) elbow, (1) coupling. Install elbow
into radiant tube sequence where plans
indicate a 90° bend (see Figure 4).
U-Tube Fitting Dimensions 180° U-Tube
Stk. # i ncludes:F106414 U-Tube Package
COUPLING ASSEMBLY
Plain Coupling - 14612
Key for Coupling - 14616
Tighten
Loosen
Hole 1
Coupling
Assembly
Impact
Block
Hole 2
When assembling coupling note
the location of Hole 1 and Hole 2
Orient coupling so that
the impact block is above
tube centerline.
TUBE COUPLING
KEY for COUPLING
FIGURE 4:
(38.73 CM)
(15.24 CM)
18" (45cm)
10"
(25cm)
(10cm)
(43cm)
9" (22cm) Radius
90°
(1) U-tube, (1) coupling
Install U-tube elbow into
radiant tube sequence where
plans indicate a 1800 bend
(see Figure 4)
(22 cm)
E-12
Enerco | Heatstar ERXL Series Heater Operating Instructions and Owner’s Manual
horizontal reflector position (standard)
angle mounting ring
radiant tube
horizontal mounting ring
hanger
reflector
top
side 45° reflector position (optional)
below
A
Chain kit - Stk. #17370
One chain kit will suspend one 10 ft. section of tube and one 10 ft.
section of reflector.
FIGURE 7: Tube and Reflector Hanger
FIGURE 7: Mounting Flange / Tube Detail
1) Insert tube 06413 into front casting to point (A).
2) Tighter all set screws marked (B) until snug.
3) After both set screws are snug, turn each
additional 1/4 turn to secure tube in place.
FIGURE 8: Burner Box / Transition Tube Detail
FIGURE 6: Typical Suspension Details
Locknut
Washer
Wood Beam
Washer
Screw Hook
min. 3/8" (10 mm)
I-Beam
Beam
Clamp
As Req'd
S-Hook
Bar Joist
Clip
Truss
Concrete
Beam
Anchor
Mounting Flange
Cap Screw
Stk. 98012
Split Lock Washer
Stk. #98527
Gasket
Stk. #12397
Burner Box
(flame observation
window facing down)
FIGURE 9: Reflector End Cap
Parts list
1 00419 Reflector End Cap (Qty 1)
2 09369 Spring Clip (Qty 4)
Flange Kit #06428XL
Kit Includes: Flange,Screws(4), Lock Washers(4), Gasket(1)
B
B
E-13 Operating Instructions and Owner’s ManualEnerco | Heatstar ERXL Series Heater
SECTION 4
Engineering Specifications
The total heating system supplied shall be design certified by CSA
under ANSI Z83.20a latest revision and CGA 2.34a latest revision.
A. Burner & Burner Controls
1. Burners shall be capable of firing with one of the fuel options as
specified on the purchase documents: Natural Gas or LP.
2. Burners shall be supplied to fire at any one of the input rates as
specified.
ERXL-40 40,000 BTU/Hr. (11.72 kW)
ERXL-60 60,000 BTU/Hr. (17.58 kW)
ERXL-80 80,000 BTU/Hr. (23.45 kW)
ERXL-100 100,000 BTU/Hr. (29.31 kW)
ERXL-125 125,000 BTU/Hr. (36.63 kW)
ERXL-150 150,000 BTU/Hr. (43.96 kW)
ERXL-175 175,000 BTU/Hr. (51.29 kW)
3. Burner shall be equipped with a direct sense silicon-carbide hot
surface ignition control system with 100% shut-off ignition device.
Power supplied to each heater shall be 120V, 60Hz, single phase.
Burners shall be rated for 1.0 Amp (run) and 5.0 Amp (start.)
4. Burner shall be equipped with thermal overload motor
protection, balanced air rotor, combustion air proving safety
pressure switch, and viewing window for flame observation.
5. When specified, in contaminated environments, the burner
shall be capable of supplying outside air to each burner for the
support of combustion.
6. All burners shall be pre-wired with a grounded electrical
cord and plug.
7. At customer’s choice, burners may be controlled with either
an optional line voltage thermostat or by optional low voltage
thermostats with an appropriate low voltage transformer relay.
8. Gas supply to the burners shall conform to the following:
1/2” NPT gas connector size
Natural Gas: 4.5” W.C. MIN, 11.0” W.C. MAX
(1.12 kPa MIN, 2.74 kPa MAX)
LP Gas: 11” W.C. MIN, 14.0” W.C. MAX
(2.74 kPa MIN, 3.48 kPa MAX)
B. Heat Exchanger
1. Radiant tubing shall be 4” (10 cm) diameter aluminized steel
supplied in 10 ft. sections (3.05 m). Sections shall be joined with
stainless steel wrap-around couplings.
2. Reflector to be of aluminum material and designed to direct all
radiant output below horizontal center line of radiant tube.
3. Heaters shall be vented according to manufacturer’s
recommendations.
Gas pressure at MANIFOLD:
Natural Gas: 3.5” W.C. (0.87 kPa)
LP Gas: 10.5” W.C. (2.61 kPa)
1/2” NPT Gas Connector Size
Gas INLET pressure:
Natural Gas: 4.5” W.C. Min (1.12 kPa MIN)
11.0” W.C. Max (2.74 kPa MAX)
LP Gas: 11.0” W.C. Min (2.74 kPa MIN)
14.0” W.C. Max (3.48 kPa MAX)
1/2” NPT Gas Connector Size
Electrical Rating: (All Models)
120V - 60Hz
1.0 AMP (Run) 5.0 AMP (Start)
Dimensions:
Flue Connection Size…………………4” (10 cm)
Outside Air Connection Size………4” (10 cm)
E-14
Enerco | Heatstar ERXL Series Heater Operating Instructions and Owner’s Manual
COMMON VENTING - (2) Heaters (Horizontal and Vertical)
Model # H = 6 ft. (1.82 m) H = 8 ft. (2.44 m) H = 15 ft. (4.57 m)
ERXL-40 D = 7" (17.8 cm) D = 6" (15.25cm) D = 6" (15.25cm)
ERXL-60 D = 7" (17.8 cm) D = 6" (15.25cm) D = 6" (15.25cm)
ERXL-80 D = 8" (20.5 cm) D = 7" (17.8 cm) D = 6" (15.25cm)
ERXL-100 D = 8" (20.5 cm) D = 8" (20.5 cm) D = 7" (17.8 cm)
ERXL-125 D = 10" (25.4 cm) D = 10" (25.4 cm) D = 8" (20.5 cm)
ERXL-150 D = 10" (25.4 cm) D = 10" (25.4 cm) D = 8" (20.5 cm)
ERXL-175 D = 10" (25.4 cm) D = 10" (25.4 cm) D = 8" (20.5 cm)
SECTION 5
Venting / Ducting
General Requirements
This heater must be vented in accordance with the specifications
contained in this manual and with the following national codes
and any state, provincial or local codes which may apply:
• Refer to National Fuel Gas Code NFPA 54/ANSI Z223.1- latest
revision.
• CANADA: Refer to Natural Gas and Propane Installation Code
CSA B149.1- latest revision.
The heater may be vented to the outdoors either vertically or
horizontally.
Optional outside air supply may be directed to the heater
horizontally or vertically.
Be sure that the method selected for venting heater complies with
all codes as required for each particular location
The use of single-wall vent pipe (26 gauge) is recommended. A
section of double-wall vent pipe is recommended when passing
through the roof or wall.
Exhaust end of heater will accept a 4' (10 cm) vent pipe using
the vent adapter. Install the vent adapter with the seam on top,
secure all vent joints with a minimum of 3 #8 x 3/8" sheet metal
screws and seal all joints using a high temperature silicone sealant.
If condensation in the flue is a problem, the flue length should be
shortened or insulated.
Vent pipe must be sloped downward away from the burner 1/4"
(0.6 cm) for ever 10' (3m).
VENT LENGTHS:
Maximum total vent length allowed in thirty (30’) (9.15 m) feet.
Maximum outside air supply duct allowed thirty (30’) (9.15 m) feet.
Maximum total vent length plus outside air supply length shall not
exceed fifty (50’) (15.25 m) feet.
NOTE:
A total of two (2) elbows are allowed for vent and
outside air supply combination. Subtract 5' feet (1.5 m) per
additional elbow from maximum length allowed if 3 or more elbows
are used.
Install a minimum 18" (30 cm) straight length of duct for air intake
or vent before any Tee or elbow.
Alternative Arrangements / Optional Equipment for Venting
Unvented Operation
a) Sufficient ventilation must be provided in the amount of 4 CFM
per 1,000 BTU/hr. firing rate.
b) Refer to ANSI Z223.1 - latest revision, NFPA-54 and local codes
for additional information.
c) Use of optional outside combustion air is not recommended with
unvented heaters due to pressure considerations. Refer to page
16
Horizontal Venting
a) Four (4”) inch (10 cm) O.D. flue pipe is required. Thirty (30’)
(9.15 m) feet maximum length is recommended.
b) All flue joints should be sealed using suitable product such as
General Electric RTV106 or Permatex Form-A-Gasket Red High
Temperature Silicone Adhesive Sealant.
c) Do not install any elbow or 45 fitting to bring vent lower than
the horizontal tube system.
d) Vent terminal should be installed at a height sufficient to prevent
blockage by snow.
1) Vent must exit building not less than seven (7’) feet (2.13 m)
above grade when located adjacent to public walkways.
2) Vent must terminate at least three (3’) feet (.91 m) above
any forced air inlet located within ten feet (10’) (3.05 m).
3) Vent must terminate at least four (4’) feet (1.2 m) below,
four (4’) feet (1.2 m) horizontally from, or one (1’) foot
(30.5 cm) above any door, window, or gravity inlet into any
building.
4) Vent terminal shall be located at least twelve (12”) inches
(30.5 cm) from any opening through which vent gases could
enter the building.
5) Vent terminal must be beyond any combustible over hang
Vertical Venting
a) Four (4”) inch (10 cm) O.D. flue pipe, maximum thirty (30’) feet
(9.15 m) in length may be used as shown with approved vent
cap. (See General Requirements on this page for additional
information.)
b) An insulated thimble may be required to pass through
combustible structures (check local codes).
c) All flue joints should be sealed using suitable products (see
recommendation for horizontal venting.)
Common Venting
a) Horizontal run to vent must never exceed 75% of the vertical
height of the vent. Refer to ANSI Z223.1 - latest revision, NFA-54
for proper vent sizes and installation.
b) Open area of common vent must equal the sum of the open
area of individual vents connected to it. (See chart below and
diagrams - page 14.)
c) Use double wall vent as required (check codes.)
d) All joints must be sealed using suitable products.
e) Connections to common stack must be positioned to avoid direct
opposition between streams of combustion gases.
E-15 Operating Instructions and Owner’s ManualEnerco | Heatstar ERXL Series Heater
FIGURE 12: Common Roof Venting
HORIZONTAL COMMON VENTING
VERTICAL COMMON VENTING
SIDE VIEW
TOP VIEW
Type "B" Vent required outdoors.
Vent Adapter Stk. #19021
At least 1/4" per foot rise or pitch
must be maintained on horizontal
runs from heater to vent.
Roof
Secure all joints with 3 (minimum) #8 x 3/8"
sheet metal screws and seal all joints.
H
Approved Vent Cap
Type "B" Vent required outdoors.
Vent Adapter Stk. #19021
Outside Wall
H
Vent Cap
Flashing
Wall Thimble
(If Applicable)
Burner Box Burner Box
Burner Box
Burner Box
Burner Box
Burner Box
D
Burner Box Burner Box
D
4” Aluminized steel Heat Exchange Tube
4” Aluminized steel Heat Exchange Tube
Type "B" Vent required outdoors.
Vent Adapter Stk. #19021
Outside Wall
Secure all joints with 3 (minimum) #8 x 3/8"
sheet metal screws and seal all joints.
H
Vent Cap
Wall Thimble
(If Applicable)
Burner Box
Burner Box
D
D
E-16
Enerco | Heatstar ERXL Series Heater Operating Instructions and Owner’s Manual
FIGURE 10: Unvented Operation
36”
36”
A
1. Ventilation equal to 4 CFM per 1,000 BTU/HR firing rate must
be provided in unvented heater installations
2. For dimensions A "unvented" refer to ( Figure 1- Minimum
Clearances to Combustibles.)
FIGURE 10A: Single Wall
Single wall vent run
Single wall terminal end
FIGURE 10b: Double Wall
Double wall vent run
Double wall terminal end
FIGURE 11: Vertical Venting
18" (45cm)
18" (45cm) Min. 3'-0" (91cm) Min.
8"(20cm) to 10"(25cm) Max.
6' (182cm) Min.
18" (45cm) Min. 3'-0" (91cm) Min.
6' (182cm) Min.
2"(5cm) Clearance thimble
2"(5cm) Clearance thimble
required when u pipe
extends through
combustible materials
(91cm)
(91cm)
Pitch flue pipe down
toward outlet 1/4" per
foot (0.6 cm per 0.3m) for
condensate drainage.
Pitch flue pipe down
toward outlet 1/4" per
foot (0.6 cm per 0.3m) for
condensate drainage.
E-17 Operating Instructions and Owner’s ManualEnerco | Heatstar ERXL Series Heater
Outside Combustion Air Supply
The Ener-Radiant XL heater is approved for installation with an
outside air supply system. Some compounds such as halogenated
hydrocarbons or other corrosive chemicals in the air can be drawn
into the equipment and cause an accelerated rate of corrosion
of some of the heater components. The use of such chemical
compounds near the enclosure should be avoided.
IMPORTANT: If the building has a slight negative pressure or
contaminants are present in the air, an outside combustion air
supply to the heaters is strongly recommended.
For an outside air supply, a four (4”) inch (10 cm) O.D. single
wall pipe may be attached to the heater. The duct may be up to
thirty (30’) ft (9.15 m). maximum length or two (2’) ft. minimum
(0.61m) length with no more than two (2) elbows. (See General
Requirements on page 14 for additional information.)
The air supply duct may have to be insulated to prevent
condensation on the outer surface. The outside air terminal should
be securely fastened to the outside wall by drilling four (4) 1/4”
(0.635 cm) diameter holes in the outside flange; wood screws or
bolts and expansion sleeves may be used to fasten terminal.
FIGURE 13: Non-Pressurized Outside Air Supply Duct
4" (10 cm)
Seal All Joints
Outside Air
Terminal
Flex Pipe
6" (15 cm) to
12" (30 cm) Long
4" (10 cm)
Seal All Joints
Flex Pipe
6" (15 cm) to
12" (30 cm) Long
Outside Air
Terminal
NOTE:
Flue pipe requires additional
support. Flex pipe will not
support riser and outside
air terminal
Vertical Outside Air
Horizontal Outside Air
PVC Pipe, “Dryer Hose”, or equivalent may be used instead of
standard vent pipe.
SECTION 6
Gas Piping
Read applicable warnings in (Section 1) before proceeding with
Gas Pipe installation. Improper installation may result in property
damage, severe injury, or death.
Meter and service must be large enough to handle all the burners
being installed plus any other connected load. The gas line which
feed the system must be large enough to supply the required gas
with a maximum pressure drop of 1/2” water column (0.12 kPa).
When gas piping is not included in the layout drawing, the local gas
supplier will usually help in planning the gas piping.
A 1/2” tapping at each burner location must be located and
oriented as shown in (Figure 14). To check system pressure, put a
plugged 1/8” NPT tapping in the gas line at the connection to the
burner farthest from the supply. Before connecting the burners to
the supply system, verify that all high pressure testing of the gas
piping has been completed. Do not high pressure test the gas piping
with the burners connected.
Follow these instructions to ensure a professional gas supply
installation:
Support all gas piping with suitable pipe hanging
materials.
Use wrought iron or wrought steel pipe and malleable
iron fitting. All pipe fittings should be new and free
from defects. Carefully ream the pipe and tubing ends
to remove obstructions and burrs.
Use L.P. gas-resistant joint compound on all pipe
threads.
Check the pipe and tubing ends for leaks before
placing heating equipment into service. When
checking for gas leaks, use soap and water solution:
NEVER USE AN OPEN FLAME.
Install the flex gas connector as shown. The flex gas connector
accommodates expansion of the heating system and allows for easy
installation and service of the burner.
FIGURE 14: Gas Line Connection with Stainless Steel Flex Gas
Connector
Shut-Off Valve must be parallel
to burner gas inlet. The 2” (5 cm)
displacement shown is for the cold
condition. This displacement may
reduce when the system is fired.
Shut – off Valve
12"
2"
1/2" Stainless Steel Flex Gas Connector
Stk. #16401
90°
45°
45°
Heater Movement
Heater Movement
Heater Movement
Heater Movement
FIGURE 14A: Incorrect Gas Line Connection with Stainless
Steel Flex Gas Connector
E-18
Enerco | Heatstar ERXL Series Heater Operating Instructions and Owner’s Manual
SECTION 7
Wiring
Heaters are normally controlled by thermostats. Line voltage
thermostats are wired directly (see Figure 15), 24V thermostats
are wired directly by finding and removing the jumper wire on the
back of the burner box and wiring the thermostat to the terminals
(see Figure 16). Heaters must be grounded in accordance with the
National Electric Code ANSI/NFPA- 70 or current Canadian Electrical
Code, CSA C22.1. Heaters may also be controlled with a manual line
voltage switch or timer switch in place of the thermostat.
T
H
N
120v – 60 Hz
White
White
Green
Green
Supply Circuit
120v – 60 Hz
Supply Circuit
Burners
(Maximum – 2 per Thermostat)
Burners
(Maximum – 1 per Thermostat)
Black
Black
H
N
T
FIGURE 15: Line Voltage Thermostat Wiring
FIGURE 16: Low Voltage Thermostat Wiring
T
H
N
120v – 60 Hz
White
White
Green
Green
Supply Circuit
120v – 60 Hz
Supply Circuit
Burners
(Maximum – 2 per Thermostat)
Burners
(Maximum – 1 per Thermostat)
Black
Black
H
N
T
FIGURE 18: Ener-Radiant XL Burner Internal Wiring Ladder
Diagram
FIGURE 17: Ener-Radiant XL Burner Internal Wiring
If any of the original wire as supplied with the
appliance must be replaced, it must be replaced with
wiring material having a temperature rating of at
least 105°C and 600 volts.
Each burner must be electrically grounded in
accordance with the National Electric Code ANSI/
NFPA - 70 or current Canadian Electrical Code, CSA
C22.1.
VAC
120
120V 24V
Black
Black
Purple
Yellow
Yellow
Black
Black
Black
Green
Green
Orange
Transformer
White
White
White
THERMOSTAT
White
Blue
Gas Valve
Air Switch
Ignitor
Sensor
Motor / Blower Door Switch
Terminal
Bushing
120V
L2
(NEUTRAL)
White
White
White
White
White
White
Gray
Orange
Transfomer
Thermostat
Air Switch
Gas Valve
Door Switch Motor / Blower
Ignitor
Sensor
Blue
Yellow
Yellow
Purple
Black
Black
Black
Black
L2 (HOT)
24V
SECTION 8
Operation & Maintenance
Sequence of Operation
1. Turn the thermostat up. When the thermostat calls for heat,
blower motor will energize.
2. When the motor approaches nominal running RPM, the air
proving switch closes and activates the ignition module.
3. The ignition module then energizes the hot surface igniter for a
timed warm-up period (approximately 45 to 60 seconds.)
4. After the warm-up period, the gas valve is energized.
5. During the last part of the sequence, the igniter is de-energized
and is converted to a flame sensing rod.
6. If a flame is detected, the gas valve remains open. When the
call for heat is satisfied, and the system control mechanism
de-energizes the burner line voltage supply, the gas valves are
turned off.
7. If no flame is detected on a single-try module, the gas valve
is closed, and the module will lockout until it is reset. Reset is
accomplished by removing power from the module for at least
five (5) seconds (thermostat cycle required.)
8. If no flame is detected on a three-trial module, the gas valve is
closed, and a purge period begins. After the purge, the module
acts to power the igniter for a second warm-up period, and a
second trial for ignition period. If flame is still not established, a
third and final purge, warm-up, and trial cycle begins. After three
trials, the module will lockout until reset. Reset is accomplished
by removing power from the module for at least five (5) seconds
(thermostat cycle required.)
9. On a three-trial module, if flame is established and lost on the
first or second trial, the gas valve is turned off, a purge, warm-up,
and trial for ignition will occur on a three-trial module, only three
trials for ignition are allowed per thermostat cycle.
E-19 Operating Instructions and Owner’s ManualEnerco | Heatstar ERXL Series Heater
Troubleshooting
CAUTION: Before opening the Ener-Radiant XL
burner door for any type of service, be sure
the gas supply has been shut off at the heater
and the electrical cord from the burner box
has been unplugged.
Blower Motor 1. Is the thermostat calling for heat? Is there
Fails to Run: 115V at the burner receptacle?
2. Check blower side door for seal. Check
door switch. Replace if necessary.
3. Check blower for obstructions. Replace
blower if necessary.
Igniter 1. Check igniter for damage. Replace if
Does Not Glow: necessary.
2. Check voltage and resistance at igniter.
(Voltage should be 115V. Resistance should
be 40-75 ohms.)
3. Check for obstructions to the air inlet and
outlet.
4. Check wiring and hose connections to the
air switch. Replace if necessary.
5. Check voltages at transformer primary and
secondary. Replace transformer or module
if necessary.
Valve Does Not Gas pressure downstream of gas control can
Come On: be measure by using a manometer and
connecting to pressure tap on control/.
1. Check to see if manual valve heater is ON.
2. Check to see if manual valve knob on
heater gas control in ON.
3. Supply gas pressure can be checked at 1/8”
NPT pressure tapping on heater external
manual valve.
4. Check to see if gas control is opening: no
manifold pressure indicates valve is closed.
If the valve is closed, either the gas valve or
the ignition module is faulty.
WARNING: Do not disconnect ground leads
inside heater. Do not interchange grounded
and ungrounded leads on transformer or
ignition module.
Burner Does Not 1. Check to see if gas lines were properly
Light: purged of air.
2. Check inlet and outlet gas pressure during
ignition period.
Natural inlet pressure should be 4.5” (1.12 kPa)
Natural outlet pressure at manifold should be 3.5” (0.87 kPa)
LP inlet pressure should be 11.0” (2.74 kPa)
LP outlet pressure at manifold should be 10.5” (2.61 kPa)
3. Check for proper orifice and air plate.
HIGH ALTITUDE
Heaters may be fired at full input up to 2000 ft. (610m) above sea
level. Above 2000 ft. (610m) a high altitude conversion kit may be
required to ensure proper burner performance, please consult the
manufacturer. Be prepared to answer factory questions regarding:
type of fuel for the proposed appliance conversion, gas pressure
available at site, and specific altitude at site. The conversion shall
be carried out by a manufacturer’s authorized representative, in
accordance with the requirements of the manufacturer, provincial,
or territorial authorities having jurisdiction and in accordance with
the requirements of the CSA B149.1 or CSA149.2 installation codes.
Maintenance
For best performance, the following maintenance procedures should
be performed before each heating season:
1. Be sure gas and electrical supply to heater are off before
performing any service or maintenance.
2. Check condition of blower scroll and motor. Dirt and dust
may be blown out with compressed air, or a vacuum cleaner
may be used. When using compressed air do not exceed 30
psi in order to not damage fragile hot surface igniter.
3. Check condition of burner. Carefully remove any dust or
debris from inside the burner box or burner cup.
4. Inspect the igniter. Replace igniter if there is excessive carbon
residue, erosion, breakage or other defects.
5. Check the inside of the firing tube with a flashlight. If carbon
or scale are present, scrape out the deposits with a wire
brush or rod, or metal plate attached to a wooden pole.
6. Check to see that the burner observation window is clean
and free of cracks or holes. Clean or replace as necessary.
7. Check the flue pipe for soot or dirt. After cleaning as
necessary, re-attach the flue pipe to the heater.
8. Outside surfaces of heater may be cleaned by wiping with a
damp cloth.
9. A qualified service agency should be contacted for service
other than routine maintenance.
10. Check vent terminal and fresh air inlet to see that they have
not been blocked during the non-heating season. If either
pipe is restricted, the air switch won’t close, resulting in a
no-heat situation.
E-20
Enerco | Heatstar ERXL Series Heater Operating Instructions and Owner’s Manual
Burner Does Not 1. Check ground wire continuity.
Stay Lit: 2. Check burner internal wiring for reversed
leads.
3. Check insulation on the igniter leads.
4. Replace module if necessary.
Honeywell Valve LED Status
The Ener-Radiant XL series Tube Heater is equipped with a
honeywell Smart Valve. This valve has a built-in diagnostic program,
which will assist in troubleshooting in the event of a valve-related
problem. The LED or (Light Emitting Diode) is located on the top of
the valve as shown in diagram below. The LED status indications are
listed below to help with the troubleshooting.
FIGURE 19:
OFF INDICATED
Off No power to the control
Bright-Dim Normal operation.
This indication shows whenever the system is
powered, unless some abnormal event has occurred.
2-Flashes Airflow providing switch remains closed longer than
30 seconds after call for heat begins (air providing
switch stuck closed.)
3-Flashes Airflow providing switch remains open longer than 30
seconds after combustion air blower is energized - or
blower does not energize.
4-Flashes White jumper wire is loose.
5-Flashes Flame signal sensed out of proper sequence.
6-Flashes System Lockout.
LED
Honeywell Smart Valve
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84

HeatStar ERXL150-N Le manuel du propriétaire

Catégorie
Chauffe-eau
Taper
Le manuel du propriétaire

dans d''autres langues