Lumination LIS3 Series LED Indirect Suspended Luminaire Guide d'installation

Taper
Guide d'installation
gecurrent.com/lumination
© 2022 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to
change without notice. All values are design or typical values when measured under laboratory conditions.
Page 1 of 13
(Rev 04/19/23)
IND679
Installation Guide
IND679
BEFORE YOU BEGIN
Read these instructions completely and carefully.
Important notes included below and on page 3.
WARNING / AVERTISSEMENT
RISK OF ELECTRIC SHOCK
• Turn power o before inspection, installation or removal.
• Properly ground electrical enclosure.
RISK OF FIRE
• Follow all NEC and local codes.
• Use only UL approved wire for input / output connections. Minimum
size 18 AWG or 14 AWG for continuous runs.
• When using multi-branch wire circuits with a shared neutral, do not
operate any circuit with the neutral open. Also ensure all neutral
connections are secure before energizing the circuit. An open neutral
can cause an overvoltage condition at the luminaire power supply.
Prepare Electrical Wiring
Electrical Requirements
• The LED xture must be supplied with120-277 VAC,
50/60Hz or 347V, 50/60Hz and protected by a max.
20 ampere circuit breaker. Use min. 75°C supply
conductor. 347V power should only be supplied to
luminaires with voltage code “D”.
Grounding Instructions
• The grounding and bonding of the overall system
shall be done in accordance with National Electric
Code (NEC) Article 600 and local codes.
RISQUES DE DÉCHARGES ÉLECTRIQUES
• Coupez l’alimentation avant d’inspecter, installer ou déplacer le luminaire.
• Assurez-vous de correctement mettre à la terre le boîtier d’alimentation électrique.
RISQUES D’INCENDIE
• Respectez tous les codes NEC et codes locaux.
• N’utilisez que des ls approuvés par UL pour les entrées/sorties de connexion. Taille
minimum 18 AWGou 14 AWG pour les rangées continues.
• Lorsque vous utilisez des circuits câblés à branches multiples a vec un neutre commun,
ne mettez aucun circuit en service avec le neutre ouvert. Assurez-vous également que
tous les raccords neutres soit sécurisés avant de mettre le circuit sous tension.Un neutre
ouvert peut causer une condition de surtension à l’alimentation du luminaire.
Save These Instructions
Use only in the manner intended by the manufacturer.
If you have any questions, contact the manufacturer.
Components Supplied:
• Luminaire
• 2 Mounting Brackets
• End Caps (2 supplied with LISI series and ISS series)
Note: In general case,with the Starter Kit, the Starter SKU will not be required.
Tools and Components Required:
T15 torx or phillips #2 screw driver
UL Listed conduit connections per NEC/CEC for nominal
conduit trade sizes ½”or ¾”
UL Listed wireconnectors
Lumination® LED Luminaire
LIS3 Series
Table of Contents Page
Accessory Kits 2
Installation of an Independent Unit (LIS3I) 4
Installation of a Continuous Row using a Starter Kit 6
Installation of a Continuous Row with Optional
Branch Circuit
8
PSU Replacement 11
Light Engine Replacement 12
gecurrent.com/lumination
© 2022 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to
change without notice. All values are design or typical values when measured under laboratory conditions.
Page 2 of 13
(Rev 04/19/23)
IND679
Lumination® LIS3 Series Installation Guide
Accessory Kits (purchased separately)
Starter Kits
Mounting Brackets
Power Cord Kit - Options
93018007 -Starter Kit (1 row)
93022791 -Starter Kit (10 rows)
Use to connect a continuous row of
xtures to supply leads
94210 -Standard Kit (10 brackets)
Use if extra brackets are required
9308800 - Anti-snaking Kit (10 brackets)
Use if installation geometry requires
a mounting point up to 1” o axis of
continuous row
210221 -Joint Spanning Kit (5 brackets)
Use if installation geometry requires a
mounting point directly over
xture/xture junction
Comes with:
• 1x Power Feed Cable
• 1x Strain Relief
10 FT KIT
93083221: BLK
93083222: WHT
20 FT KIT
93083223: BLK
93083224: WHT
Dimming feed cable
(2 cond; includes purple and gray)
Power feed cable
(4 cond; includes black, white, green
and red (for additional circuit))
**Power and Dimming Feed Cables are #14 gauge 600V rated
Suspended Kits - Mounting Open/Unfinished Ceiling
Comes with:
• 2x Aircraft Cables
• 1x Strain Relief
Mounting cables
10 FT KIT
93035285
: 10’ Kit
20 FT KIT
93116031
: 20’ Kit
gecurrent.com/lumination
© 2022 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to
change without notice. All values are design or typical values when measured under laboratory conditions.
Page 3 of 13
(Rev 04/19/23)
IND679
Lumination® LIS3 Series Installation Guide
Accessory Kits (purchased separately)
Comes with:
• 2x Aircraft Cables
• 2x Upper Mounting Kit
o
2” canopy Cover
o
T-Bar Clips
Upper Mounting KitMounting cables
10 FT KIT
93115708
: WHT Canopy
93115710
: BLK Canopy
20 FT KIT
93115709
: WHT Canopy
93115711
: BLK Canopy
Comes with:
• 2x Aircraft Cables
• 1x Power Feed Cable
• 1x Canopy Kit
o
2 Cord Power Drop Canopy Cover
o
1 Cord Power Drop Canopy Cover
o
Canopy Cover Strain relief (2x)
o
Canopy Cover Hardware kit
• 2x Upper Mounting Kit
o
2” canopy Cover
o
T-Bar Clips
Mounting
cables
Upper Mounting
Kit
Canopy Kit Power feed cable
(4 cond; includes black, white, green
and red (for additional circuit))
Dimming feed cable
(2 cond; includes purple and gray)
10 FT KIT
93122350
: WHT with Dimming
93122352
: BLK with Dimming
93115847
: WHT No Dimming
93115849
: BLK No Dimming
20 FT KIT
93122351
: WHT with Dimming
93122353
: BLK with Dimming
93115848
: WHT No Dimming
93115850
: BLK No Dimming
Suspended Kits - Mounting + Power Open/Unfinished Ceiling
Comes with:
• 2x Aircraft Cables
• 1x Power Feed Cable
Mounting cables
10 FT KIT
93122346
: WHT with Dimming
93122348
: BLK with Dimming
93115897
: WHT No Dimming
93115899
: BLK No Dimming
20 FT KIT
93122347
: WHT with Dimming
93122349
: BLK with Dimming
93115898
: WHT No Dimming
93115900
: BLK No Dimming
Power feed cable
(4 cond; includes black, white, green
and red (for additional circuit))
Dimming feed cable
(2 cond; includes purple and gray)
**Power and Dimming Feed Cables are #14 gauge 600V rated
Suspended Kits - Mounting Finished Ceiling
Suspended Kits - Mounting + Power Finished Ceiling
gecurrent.com/lumination
© 2022 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to
change without notice. All values are design or typical values when measured under laboratory conditions.
Page 4 of 13
(Rev 04/19/23)
IND679
Lumination® LIS3 Series Installation Guide
IMPORTANT -Maximum Length of Electrical Run
LIS3 Series
Voltage
8ft Lumen Code
[84] [A0] [A2] [A7] [B2]
120V 192’ 160’ 80' 60'
277V or 347V 400’ 320 188' 132'
Please see technical data sheet for electrical properties to ensure safe installation.
Maximum driver current through connected xtures shall not exceed 15A for lumen
codes [42], [52], [62], [85], [A1], [84], [A0], [A2], [A7] or [B2]
LIS3 series luminaires come in two versions: continuous units (LIS3C series) and independent units (LIS3I series).
A continuous electrical run will consist of a number of continuous units up to a maximum current specied above.
Run lengths should be based on 8ft xtures with 4ft xtures used only to complete a row as needed. When installing
luminaires use clean gloves in order to avoid fouling the reective surface. To insure a clean xture, install the xture with the
plastic bag around the xture, and then remove plastic bag upon completion of any and all construction related activity.
If two additional circuits are included in luminaire, they must be connected in daisy chain to the same circuit breaker as per
diagram below and total current not exceeding a maximum of 15A (per above comment).
Breaker
Circuit #1
Circuit #2
Daintree Node
Identication Label
Installation of an Independent Unit(LISI)
Choose suspension method
Choose suspension method
Carefully unpack unit and inspect
for defects before installing. Wear
work gloves to prevent dirt and
oil from being transferred to the
luminaire.
NOTE: When installing luminaires use clean
gloves in order to avoid fouling the reective
surface.
1
Attach mounting bracket to ceiling
support structure either directly or
using a GE suspension
kit according to the suspension
kit instructions (see page 2).
Maximum distance between
suspension points shall not exceed
the length of the luminaire.
21
12
Daintree Node identication label
installed on luminaire back reector.
2
Remove package with smaller
label. This label is to be used for
customer oor plan or records.
gecurrent.com/lumination
© 2022 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to
change without notice. All values are design or typical values when measured under laboratory conditions.
Page 5 of 13
(Rev 04/19/23)
IND679
Lumination® LIS3 Series Installation Guide
ACline
Prepare luminaire for installation by
loosening the PSU cover screws and
removing the cover.
3
For 347V xture: Loosen PSUcover
screws and remove two covers.
4
Carefully remove appropriate
knockout for AC line input wires
(inner knockout for ½”conduit,
outer knockout for ¾” conduit).
Install listed electrical ttings in
the knockout holes for wire
protection and pass supply
conduit through electrical ttings.
5
ACline
ACline
Dimming line
(op�onal)
Dimming
wires
ACline
PSU
wires
Connect the green (ground), black
(line) and white (neutral) wires of
the AC line to the similarly colored
wires of the power supply unit
using separate UL listed wire nuts.
6
Optional dimmer: Install UL
listed electrical tting and insert
dimming control wires through.
Connect dimming control wires
(grey and violet for 0-10V or violet
and violet/whitestrip for DALI) to
the similarly colored xture wire
using separate UL listed wire nuts.
7
Clip luminaire to the previously
installed mounting brackets.
8
Dimming line
(op�onal)
Dimming
wires
ACline
PSU
wires
Dimming line
(op�onal)
Dimming
wires
ACline
PSU
wires
DALI
Fixture
Line
Neutral
Black
White
Ground Green
DALI Violet/White
DALI Violet
Black
White
Green
Violet
Grey
0-10V
Wiring Diagrams
Fixture
Line
Neutral
Ground
(0-10V)+
(0-10V)
Fix the mounting position and secure
the suspension by tightening the two
screws on both mounting brackets.
9
Replace power supply cover(s) by sliding
over the captive screws and secure by
tightening them.
Note: When installation is complete, all lead wires
and connectors shall be totally enclosed.
10
DALI
Fixture
Line
Neutral
Black
White
Ground Green
DALI Violet/White
DALI Violet
Black
White
Green
Violet
Grey
0-10V
Wiring Diagrams
Fixture
Line
Neutral
Ground
(0-10V)+
(0-10V)
DALI
Fixture
Line
Neutral
Black
White
Ground Green
DALI Violet/White
DALI Violet
Black
White
Green
Violet
Grey
0-10V
Wiring Diagrams
Fixture
Line
Neutral
Ground
(0-10V)+
(0-10V)
gecurrent.com/lumination
© 2022 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to
change without notice. All values are design or typical values when measured under laboratory conditions.
Page 6 of 13
(Rev 04/19/23)
IND679
Lumination® LIS3 Series Installation Guide
Installation of a Continuous Row using a Starter Kit
Use starter kits as a convenient way to install continuous rows. Starter kits are ordered separately (SKU 93018007 provides parts
for 1 continuous row, SKU 93022791 provides parts for 10 continuous rows).
CAUTION
THERE IS A REQUIRED DIRECTION FOR ASSEMBLING A CONTINUOUS ROW.
the row
First fixturein
the row
Next fixturein
Direc�on of connuous row installa�on
(op�onal)
Ceiling
ACline
Dimming line
The Starter & Con�nuous Run fixtures connect in rows
Continuous runs must begin with a rst unit that is suspended at both ends. Use provided end-caps from starter kits to
begin and terminate the row.
As the name implies, the Starter (if your product has such a choice) contains the beginning of the electrical connection.
This means that this xture has the only Power Drop.
The starter, when suspended, also is normally the only xture in the row with (2) suspension hangers.
The rest of the run may be suspended from a single hanger (positioned near the end where the next xture will connect).
For mechanical installation, follow steps 1-6 described earlier in these install instructions.
Connect to power harness in
driverenclosure
Connect to next fixture in
connuous row
Connect to AC line using
separateUL listed wire nuts
Connect to dimmingharness
in driverenclosure
Connect to next fixture in
connuous row
Connect to dimmingline
(op�onal) using separate
UL listed wirenuts
Use provided starter power harness as an extension
for the rst xture in the row.
1
A dimming starter harness is provided to optionally
connect the dimming through wiring to the dimming line.
2
gecurrent.com/lumination
© 2022 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to
change without notice. All values are design or typical values when measured under laboratory conditions.
Page 7 of 13
(Rev 04/19/23)
IND679
Lumination® LIS3 Series Installation Guide
Newunit
hungunit
Previously
DALI
Wiring Diagrams
Fixture
Line
Neutral
Black
White
Ground Green
DALI Violet/White
DALI Violet
Black
White
Green
Violet
Grey
0-10V
Line
Fixture
Neutral
Ground
(0-10V)+
(0-10V)
3
To add a continuous unit to a
continuous run, rst suspend the
new unit as it is done in steps 9 and
10 for the independent unit. Position
the non-power-supply end of the
luminaire near the power-supply end
of the previously hung luminaire.
4
Remove the PSU cover from the
previously hung luminaire if
present.
5
Newunit
hungunit
Previously
DALI
Wiring Diagrams
Fixture
Line
Neutral
Black
White
Ground Green
DALI Violet/White
DALI Violet
Black
White
Green
Violet
Grey
0-10V
Line
Fixture
Neutral
Ground
(0-10V)+
(0-10V)
Newunit
hungunit
Previously
DALI
Wiring Diagrams
Fixture
Line
Neutral
Black
White
Ground Green
DALI Violet/White
DALI Violet
Black
White
Green
Violet
Grey
0-10V
Line
Fixture
Neutral
Ground
(0-10V)+
(0-10V)
Align tabs
Pull out connuous wiring
withslots
Push down
to engage
Pull the continuous wiring out of the luminaire being mounted and slide the bridge of the luminaire down onto the bridge of the
already installed luminaire so that the tabs and slots at top and bottom nest into one another. The bridges will engage with a loud click
when fully mated.
6
Align tabs
Pull out connuous wiring
withslots
Push down
to engage
Align tabs
Pull out connuous wiring
withslots
Push down
to engage
7
At the beginning of the row, push
the wiring inside the cavity of the
bridge.
8
Clip one end-cap at the beginning
of the row and one at the end
(provided in the starter kits).
9
Connect the power and control
connectors of the through wiring
harness.
Replace the PSU cover(s) and
secure using the mounting screws.
Note: When installation is complete, all
lead wires and connectors shall be totally
enclosed.
10
gecurrent.com/lumination
© 2022 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to
change without notice. All values are design or typical values when measured under laboratory conditions.
Page 8 of 13
(Rev 04/19/23)
IND679
Lumination® LIS3 Series Installation Guide
Installation of a Continuous Row with Optional Branch Circuit
CAUTION
THERE IS A REQUIRED DIRECTION FOR ASSEMBLING A CONTINUOUS ROW.
the row
First fixturein
the row
Next fixturein
Direc�on of connuous row installa�on
(op�onal)
Ceiling
ACline
Dimming line
For mechanical installation, follow steps 1-6 described earlier in these install instructions.
AC from 1st circuit
Starter harness
Carefully remove appropriate knockout for ACline
input wires (inner knockout for ½” conduit, outer
knockout for ¾” conduit). Install listed electrical
ttings in the knockout holes for wire protection and
pass supply conduit through electrical ttings.
1
1st circuit connection: Connect the green (ground),
black (line) and white (neutral) wires of the AC line
to the similarly colored wires of the starter harness
using the provided push-in wire nuts (starter unit) or
connect using wire nuts if using a starter kit
(see above).
2
gecurrent.com/lumination
© 2022 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to
change without notice. All values are design or typical values when measured under laboratory conditions.
Page 9 of 13
(Rev 04/19/23)
IND679
Lumination® LIS3 Series Installation Guide
Dimming line
(op�onal) Dimming
connecons
First circuitwires
Second circuitwires
Brown, Brown/white stripe wires
Dimming line
(op�onal) Dimming
connecons
First circuitwires
Second circuitwires
Brown, Brown/white stripe wires
Optional dimmer: Install UL listed electrical tting
and insert dimming control wires through. Connect
dimming control wires (grey and violet for 0-10V or
violet and violet/white stripe for DALI) to the similarly
colored xture wires using the provided push-in wire
nuts (starter unit) or using wire nuts (starter kit).
3
2nd circuit connection: Install listed electrical ttings
in the second knockout holes for wire protection
and pass supply conduit through electrical ttings.
The second circuit wires (line and neutral) will be
connected to the second luminaire in the continuous
run. Leave them unconnected to the brown and
brown/white stripe wires for now.
4
Push down
to engage
Align tabs
withslots
Purple, grey
Brown, brown-white
Green, black, white
Pull out
connuous
wiring
Pull the continuous wiring out of the next luminaire being mounted and slide the bridge of the luminaire down onto the bridge of the
already installed luminaire so that the tabs and slots at top and bottom nest into one another. The bridges will engage with a load click
when fully mated.
5
Push down
to engage
Align tabs
withslots
Purple, grey
Brown, brown-white
Green, black, white
Pull out
connuous
wiring
Push down
to engage
Align tabs
withslots
Purple, grey
Brown, brown-white
Green, black, white
Pull out
connuous
wiring
Brown
Brown/white stripe
DALI
Wiring Diagrams
0-10V
Neutral
Line
Ground
DALI
DALI
Black
White
Green
Violet
Violet/White
Fixture
Circuit
#1
#2
Circuit Line
Neutral
Brown
Brown/white
Neutral
Line Black
White
Fixture
Circuit
#1
#2
Circuit Line
Neutral
Brown
Brown/white
Green
Violet
Grey(18AWG)
Ground
0-10V
0-10V
Connect the power and control connectors of the
through wiring harness. Connect AC Circuit #1
(black, white and green harness) from rst xture to
AC Circuit #1 from second xture. Connect AC Circuit
# 2 (brown and brown/white stripe harness) from
rst xture to AC Circuit #2 from second xture and
connect second circuit supply lines of starter unit.
6
gecurrent.com/lumination
© 2022 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to
change without notice. All values are design or typical values when measured under laboratory conditions.
Page 10 of 13
(Rev 04/19/23)
IND679
Lumination® LIS3 Series Installation Guide
PSU
AC Circuit #2
AC Circuit #1
Black and
white wires
Dimming
Locate the black (line) and white (neutral) wires on the
PSU. Pull the wires out of the box to have good access.
7
Connecting a Unit to AC Circuit #1 or AC Circuit #2
AC Circuit #2
AC Circuit #1
AC Circuit #2
AC Circuit #1
Connect the black (line) and the white (neutral) wires
of the PSU to the AClines similarly colored wires using
the push-inwire nuts.
Connect the black (line) of the PSU with the brown
(line) AC wire using the push-in wire nut. Connect the
white (neutral) wire of the PSU with the brown/white
(neutral) AC wire using the push-in wire nut.
To terminate a mechanical run take the end cap from
the starter luminaire or starter kit and clip down onto
the last bridge.
9
Replace the PSU cover(s) and secure using the
mounting screws.
Note: When installation is complete, all wiring and
connectors shall be totally enclosed.
10
AC Circuit #1 Connections AC Circuit #2 Connections
8A 8B
gecurrent.com/lumination
© 2022 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to
change without notice. All values are design or typical values when measured under laboratory conditions.
Page 11 of 13
(Rev 04/19/23)
IND679
Lumination® LIS3 Series Installation Guide
PSU Replacement Procedure
Tools and Parts Required:
• New power supply unit (PSU)
• Wirecutter
• T15 Torx or Phillips #2screwdriver
• UL approvedwire connectors (4-pin)
Mounting bracket not shown for clarity AC
DC
Dimming
Mounting bracket not shown for clarity AC
DC
Dimming
Loosen 3 screws and remove the PSU cover.
2
Locate the DC (red and blue), AC (green, white and
black) and Dimming connections (purple and gray).
3
Disconnect the luminaire power source.
1
Other wires hiddenfor clarity
Do not cut green AC wires
Remove oldPSU
Other wires hiddenfor clarity
Do not cut green AC wires
Remove oldPSU
Cut the original DC, AC(do not cut the green wire) and
Dimming connections.
4
Unscrew the old PSU and remove.
5
DC
AC
Other wires hiddenfor clarity
Dimming
Install new PSU
DC
AC
Other wires hiddenfor clarity
Dimming
Install new PSU
Install the new PSU using a star washer under each
screw.
6
Reconnect the DC, AC, and Dimming wires using UL
approved connectors. Re-attach the PSU cover.
7
gecurrent.com/lumination
© 2022 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to
change without notice. All values are design or typical values when measured under laboratory conditions.
Page 12 of 13
(Rev 04/19/23)
IND679
Lumination® LIS3 Series Installation Guide
How To Replace Light Engine in the Field
Applicable for luminaires LIS3C4RXXXXXXXXXXXXXXXX, LIS3C8RXXXXXXXXXXXXXXXX*
* Not applicable for [A7] and [B2] lumen codes.
1
Disconnect DC power.
2
With a athead screwdriver,
unsnap clip near the end. Continue
unsnapping remaining clips.
3
With a athead screwdriver, open
access door.
4 5
Remove heatsink. Reverse steps to
install the new light engine. Reconnect the DC power.
gecurrent.com/lumination
© 2022 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to
change without notice. All values are design or typical values when measured under laboratory conditions.
Page 13 of 13
(Rev 04/19/23)
IND679
Lumination® LIS3 Series Installation Guide
This device complies with Part 15 of the FCC Rules. Operation is subject tothe following two conditions: (1) This device may not cause harmful
interference,and (2) this device must accept any interference received, including interference that may cause undesired operation. This Class [A] RFLD
complies with the Canadian standard ICES-005. CeDEFRde la classe [A]est conformeà la NMB-005du Canada.
Note: This equipment has been tested and found to comply with the limits for a Class Adigital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in a residentialarea is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense.
Troubleshooting
Symptom Solution
Luminaires will not turn on • Check that the color of the supply side wires match the color of the wires they are connected to.
• Check that the LED driver connector is fully engaged to the LED light engine connector.
Luminaire on through wiring
will not turn on
• Check that the through wiring connector from the previous xture in the linear row is fully engaged
to the malfunctioning luminaire.
Luminaire to luminaire mating in
continuous run is loose
• Ensure that both upper and lower connecting features are correctly engaged.
• Ensure that through wires are correctly routed in the wiring notch.
Suspension methodwon’t engage
with luminaire
• Check that the suspension method is one of the approved types in the installation instruction.
gecurrent.com/lumination
© 2022 Current Lighting Solutions, LLC. Tous droits réservés. GE et le monogramme GE sont des marques déposées
de General Electric Company et sont utilisés sous licence. Les informations fournies sont sujetes à modifications sans
préavis. Toutes les valeurs données sont théoriques ou typiques lorsque mesurées sous conditions de laboratoire.
Page 14 of 26
(Rev 04/19/23)
LUM_IND679_LIS3_install_R01
Manuel d’Installation
IND679
AVANT DE COMMENCER
Lisez ces instructions entièrement et avec soins.
Des remarques importantes sont données
ci-dessous et à la page 3.
WARNING / AVERTISSEMENT
RISK OF ELECTRIC SHOCK
• Turn power o before inspection, installation or removal.
• Properly ground electrical enclosure.
RISK OF FIRE
• Follow all NEC and local codes.
• Use only UL approved wire for input / output connections. Minimum
size 18 AWG or 14 AWG for continuous runs.
• When using multi-branch wire circuits with a shared neutral, do not
operate any circuit with the neutral open. Also ensure all neutral
connections are secure before energizing the circuit. An open neutral
can cause an overvoltage condition at the luminaire power supply.
Préparation du câblage électrique
Conditions d’alimentation électrique
• L’appareil DEL doit être alimenté en 120/277 VCA,
50/60 HZ ou 347 V, 50/60 HZ et protégé par un
disjoncteur de 20 Amp max. Utilisez des conducteurs
d’alimentation de 75°C min. L’alimentation en 347 V
ne devrait être utilisée que pour les luminaires avec
tension de classe “D”.
Instructions de mise à la masse
• Les connections et mises à la masse de l’ensemble
du système doit se faire en accord avec l’article 600
du National Electric Code (NEC) et des codes locaux.
RISQUES DE DÉCHARGES ÉLECTRIQUES
• Coupez l’alimentation avant d’inspecter, installer ou déplacer le luminaire.
• Assurez-vous de correctement mettre à la terre le boîtier d’alimentation électrique.
RISQUES D’INCENDIE
• Respectez tous les codes NEC et codes locaux.
• N’utilisez que des ls approuvés par UL pour les entrées/sorties de connexion. Taille
minimum 18 AWGou 14 AWG pour les rangées continues.
• Lorsque vous utilisez des circuits câblés à branches multiples a vec un neutre commun,
ne mettez aucun circuit en service avec le neutre ouvert. Assurez-vous également que
tous les raccords neutres soit sécurisés avant de mettre le circuit sous tension.Un neutre
ouvert peut causer une condition de surtension à l’alimentation du luminaire.
Conservez ces instructions
Utilisez exclusivement de la manière prévue par le fabricant.
Si vous avez des questions, contactez le fabricant.
Composants fournis:
• Luminaire
• 2 Supports de montage
• Capuchons (2 fournis avec les séries LISI et séries ISS)
Remarque: En général, avec le kit de démarrage, le SKU de démarrage ne
sera pas requis.
Outils et accessoires requis:
• Torx T15 ou tournevis Phillips No 2
• Raccords de conduits classés UL suivant NEC/CEC pour
des tailles de conduits nominales commerciales ½ ou ¾
po (12,7 ou 19,1 mm)
• Raccords de câbles classés UL
Luminaire Lumination® DEL
Séries LIS3
Table des matières Page
Kits d’accessoires 16
Installation d’un appareil indépendant (LIS3I) 18
Installation d’une le continue avec utilisation d’un
kit de démarrage
20
Installation d’une le continue avec circuit dérivé
optionnel
22
Remplacement PSU (Unité d’alimentation) 25
Remplacement de l’alimentation du luminaire 26
gecurrent.com/lumination
© 2022 Current Lighting Solutions, LLC. Tous droits réservés. GE et le monogramme GE sont des marques déposées
de General Electric Company et sont utilisés sous licence. Les informations fournies sont sujetes à modifications sans
préavis. Toutes les valeurs données sont théoriques ou typiques lorsque mesurées sous conditions de laboratoire.
Page 15 of 26
(Rev 04/19/23)
LUM_IND679_LIS3_install_R01
Lumination® Séries LIS3 Manuel d’Installation
Kits d’accessoires (achetés séparément)
Kits de démarrage
Supports de montage
Kit câble d’alimentation - Options
93018007 - Kit de démarrage (1 le)
93022791 - Kit de démarrage (10 les)
Utilisé pour raccorder une le continue
d’appareils aux ls d’alimentation
94210 - Kit standard (10 supports)
À utiliser si des supports
supplémentaires sont nécessaires
9308800 - Kit antivibratoire (10 supports)
À utiliser si le prol de l’installation demande
un point de montage désaxé jusque 25 mm
d’une le en continu
210221 - Kit de pont de raccordement (5 supports)
À utiliser si le prol de l’installation demande
un point de montage directement au-dessus
appareil/jonction appareil
Livré avec:
• 1 x Câble alimentation
• 1 x Détendeur
KIT DE 3 M
93083221: Noir
93083222: Blanc
KIT DE 6 M
93083223: Noir
93083224: Blanc
Câble d’alimentation
de gradation
(2 fils; Y compris mauve et gris)
Câble d’alimentation
(4 fils; Y compris noir, blanc, vert et rouge
(pour circuit supplémentaire)
**Les câbles d’alimentation et de gradation sont de gauge 14, classe 600 V
Kits suspendus – Montage Plafond Ouvert/Non fini
Livré avec:
• 2 x câbles aériens
• 1 x détendeur
Câbles de montage
KIT DE 3 M
93035285
: Kit de 3 m
KIT DE 6 M
93116031
: Kit de 6 m
gecurrent.com/lumination
© 2022 Current Lighting Solutions, LLC. Tous droits réservés. GE et le monogramme GE sont des marques déposées
de General Electric Company et sont utilisés sous licence. Les informations fournies sont sujetes à modifications sans
préavis. Toutes les valeurs données sont théoriques ou typiques lorsque mesurées sous conditions de laboratoire.
Page 16 of 26
(Rev 04/19/23)
LUM_IND679_LIS3_install_R01
Lumination® Séries LIS3 Manuel d’Installation
Kits d’accessoires (achetés séparément)
Livré avec:
• 2 x câbles aériens
• 2 x kits de montage supérieur
o
Couvercle de protection 50 mm
o
Clips de barre en Té
Kit de montage
supérieur
KIT DE 3 M
93115708
: Protection Blanc
93115710
: Protection Noir
KIT DE 6 M
93115709
: Protection Blanc
93115711
: Protection Noir
Livré avec:
• 2 x câbles aériens
• 1 x Câble d’alimentation
puissance
• 1 x kit de protection
o
Couvercle de protection avec passage 2 fils
o
Couvercle de protection avec passage 1 fil
o
Détendeur couvercle de protection (2 x)
o
Kit de visserie pour couvercle
de protection
• 2 x Kit montage supérieur
o
Couvercle de protection 50 mm
o
Clips de barre en Té Câbles de
montage
Kit de montage
supérieur
Kit protection Câble d’alimentation
(4 fils; Y compris noir, blanc, vert et
rouge (pour circuit supplémentaire)
Câble d’alimentation
de gradation
(2 fils; Y compris mauve et gris)
KIT DE 3 M
93122350
: Blanc avec gradation
93122352
: Noir avec gradation
93115847
: Blanc sans gradation
93115849
: Noir sans gradation
KIT DE 6 M
93122351
: Blanc avec gradation
93122353
: Noir avec gradation
93115848
: Blanc sans gradation
93115850
: Noir sans gradation
Kits suspendus – Montage + Alimentation Plafond Ouvert/Non fini
Livré avec:
• 2 x câbles aériens
• 1 x Câble d’alimentation
puissance
Câbles de montage
Câbles de montage
KIT DE 3 M
93122346
: Blanc avec gradation
93122348
: Noir avec gradation
93115897
: Blanc sans gradation
93115899
: Noir sans gradation
KIT DE 6 M
93122347
: Blanc avec gradation
93122349
: Noir avec gradation
93115898
: Blanc sans gradation
93115900
: Noir sans gradation
Câble d’alimentation
(4 fils; Y compris noir, blanc, vert et rouge
(pour circuit supplémentaire)
Câble d’alimentation
de gradation
(2 fils; Y compris mauve et gris)
**Les câbles d’alimentation et de gradation sont de gauge 14, classe 600 V.
Kits suspendus – Montage Plafond fini
Kits suspendus – Montage + alimentation Plafond fini
gecurrent.com/lumination
© 2022 Current Lighting Solutions, LLC. Tous droits réservés. GE et le monogramme GE sont des marques déposées
de General Electric Company et sont utilisés sous licence. Les informations fournies sont sujetes à modifications sans
préavis. Toutes les valeurs données sont théoriques ou typiques lorsque mesurées sous conditions de laboratoire.
Page 17 of 26
(Rev 04/19/23)
LUM_IND679_LIS3_install_R01
Lumination® Séries LIS3 Manuel d’Installation
IMPORTANT – Longueur maximum du chemin de câble
Séries LIS3
Tension
Code Lumen 2,4 m
[84] [A0]
[A2]
[A7] [B2]
120 V 58.5 m 48.8 m 24.4 m 18.3 m
277 V ou 347 V
121.9 m 97.6 m 57.3 m 40.2 m
Veuillez consulter la che technique pour les caractéristiques
électriques pour garantir une installation sûre.
Le courant maximum de l’alimentation par les appareils raccordés ne peut excéder
15 A pour les codes lumen [42], [52], [62], [85], [A1], [84], [A0], [A2], [A7] or [B2].
Les luminaires des séries LIS3 sont livrés en 2 versions : appareils en continu (séries LIS3C) et appareils indépendants (séries
LIS3I). Une le électrique continue va consister en un nombre d’appareils en ligne jusqu’au courant maximum spécié ci-dessus.
Les longueurs des les doivent être basées sur des appareils de 8 pi (2,4 m) avec des appareils de 4 pi (1,2 m) utilisés uniquement
pour terminer une le suivant besoin. Lors de l’installation des luminaires, portez des gants propres pour éviter d’abimer la surface
rééchissante. Pour vous assurer un appareil propre, installez celui-ci avec un sac plastique tout autour et ensuite enlevez-le à la
n de chacun et de tous les travaux de construction y relatifs.
Si deux circuits additionnels sont compris dans le luminaire, ils doivent être connectés en guirlande au même disjoncteur suivant
le diagramme ci-dessous et le courant total ne peut pas dépasser un maximum de 15 A (suivant les remarques ci-dessus).
Disjoncteur
Circuit No 1
Circuit No 2
Nœud Daintree
Étiquette d’identication Installation d’un appareil indépendant (LISI)
Choose suspension method
Choisissez la méthode de suspension
Déballez l’appareil avec soin et
inspectez-le pour des défauts avant
installation. Portez des gants de
travail pour éviter que des saletés
ou
de la graisse ne passe au luminaire.
REMARQUE: Lors de l’installation des luminaires,
portez des gants propres pour éviter de salir la
surface rééchissante.
1
Attachez les supports de montage à
la structure de support du plafond
soit directement soit en utilisant
un kit de suspension GE suivant les
instructions du kit de suspension (voir
page 2). La distance maximum entre
les points de suspension ne devra pas
dépasser la longueur du luminaire.
21
Étiquette d’identication du nœud
Daintree installée au bas du réecteur
du luminaire.
2
Enlevez l’emballage avec la plus petite
étiquette. Cette étiquette servira au
plan d’implantation du client ou pour
ses archives.
12
gecurrent.com/lumination
© 2022 Current Lighting Solutions, LLC. Tous droits réservés. GE et le monogramme GE sont des marques déposées
de General Electric Company et sont utilisés sous licence. Les informations fournies sont sujetes à modifications sans
préavis. Toutes les valeurs données sont théoriques ou typiques lorsque mesurées sous conditions de laboratoire.
Page 18 of 26
(Rev 04/19/23)
LUM_IND679_LIS3_install_R01
Lumination® Séries LIS3 Manuel d’Installation
ACline
Préparez le luminaire pour son
installation en desserrant les vis du
couvercle du PSU (unité d’alimentation)
et en enlevant le couvercle.
3
Pour les appareils à 347 V:
Desserrez les vis du couvercle PSU
(unité d’alimentation) et enlevez
deux couvercles
4
Enlevez avec précaution le bouchon
défonçable pour les ls d’entrée de la ligne
CA (bouchon intérieur pour conduit de ½ po
(12,7 mm), bouchon extérieur pour conduit
de ¾ po (19,1 mm)). Installez dans les trous
défoncés les raccords électriques listés pour
la protection des ls et passez le conduit
d’alimentation au travers des raccords.
5
ACline
Ligne CA
Ligne CA
Fils de
gradation
Ligne de gradation
(optionnelle)
Fils PSU
(Unité
d’alimentation)
Raccordez les ls vert (masse),
noir (ligne) et blanc (neutre) à la
ligne CA aux ls de même couleurs
de l’alimentation en utilisant des
connecteurs séparés classés UL.
6
Gradateur optionnel: Installez le
connecteur électrique classé UL et
insérez les ls de contrôle du gradateur.
Raccordez les ls de contrôle du
gradateur (gris et violet pour 0 – 10 V ou
violet et violet/rayé blanc pour DALI) aux
ls de l’appareil de mêmes couleurs avec
des connecteurs séparés classés UL.
7
Agrafez le luminaire aux supports
installés précédemment.
8
Ligne CA
Fils de
gradation
Ligne de gradation
(optionnelle)
Fils PSU
(Unité
d’alimentation)
Dimming line
(op�onal)
Dimming
wires
ACline
PSU
wires
DALI
Fixture
Line
Neutral
Black
White
Ground Green
DALI Violet/White
DALI Violet
Black
White
Green
Violet
Grey
0-10V
Wiring Diagrams
Fixture
Line
Neutral
Ground
(0-10V)+
(0-10V)
Décidez la position de montage et
xez la suspension en serrant les deux
vis sur les deux supports de montage.
9
Remettez en place le(s) couvercle(s) de
l’alimentation en les glissant sur les vis
noyées et xez-les en les serrant.
REMARQUE: Lorsque l’installation est terminée,
tous les ls d’entée et les connecteurs seront
entièrement enfermés.
10
DALI
Fixture
Line
Neutral
Black
White
Ground Green
DALI Violet/White
DALI Violet
Black
White
Green
Violet
Grey
0-10V
Wiring Diagrams
Fixture
Line
Neutral
Ground
(0-10V)+
(0-10V)
DALI 0-10 V
Ligne - Noir
Neutre - Blanc
Terre - Vert
(0-10 V)+
- Violet
(0-10 V)-
- Gris
Ligne - Noir
Neutre - Blanc
Terre - Vert
(0-10 V)+
- Violet/Blanc
(0-10 V)-
- Violet
AppareilAppareil
Schémas de raccordement
gecurrent.com/lumination
© 2022 Current Lighting Solutions, LLC. Tous droits réservés. GE et le monogramme GE sont des marques déposées
de General Electric Company et sont utilisés sous licence. Les informations fournies sont sujetes à modifications sans
préavis. Toutes les valeurs données sont théoriques ou typiques lorsque mesurées sous conditions de laboratoire.
Page 19 of 26
(Rev 04/19/23)
LUM_IND679_LIS3_install_R01
Lumination® Séries LIS3 Manuel d’Installation
Installation d’une le continue en utilisant le kit de démarrage
Utilisez les kits de démarrage comme moyen facile d’installer des les continues. Les kits de démarrage sont commandés séparément
(Le SKU 93018007 fournit les pièces nécessaires pour une le continue, le SKU 93022791 fournis les pièces pour 10 les continues).
ATTENTION
IL Y A UNE ORIENTATION OBLIGATOIRE POUR LASSEMBLAGE D’UNE FILE CONTINUE.
Ligne CA
Premier appareil
dans la file
Ligne de gradation
(optionnelle) Appareil suivant
dans la file
Direction de l’installation d’une file continue
Plafond
Les appareils de démarrage et de continuation de la file sont connectés en files
Démarreur
Les les continues doivent commencer par un premier appareil suspendu aux deux extrémités. Utilisez les couvercles
d’extrémité des kits de démarrage pour commencer et terminer la le.
Comme le nom l’indique, le Démarreur (si votre produit ore ce choix) contient le début du raccordement électrique. Ceci
signie que cet appareil est le seul à avoir l’alimentation.
Le Démarreur, lorsqu’il est suspendu, est normalement aussi le seul appareil dans une le avec deux crochets de suspension.
La suite de la le peut être suspendue par un seul crochet (situé près de l’extrémité où l’appareil suivant va se connecter).
Pour l’installation mécanique, suivez les étapes 1 à 6 décrites précédemment dans ces instructions d’installation.
Se raccorde au collecteur alimentation
dans le boîtier alimentation
Se raccorde à la ligne CA par
connecteurs classe UL séparés.
Se raccorde à l’appareil
suivant en file continue
Se raccorde au collecteur de gradation
dans le boîtier d’alimentation
Se raccorde à la ligne CA par
connecteurs classe UL séparés.
Se raccorde à l’appareil
suivant en file continue
Utilisez le collecteur de démarrage fournis comme
extension pour le premier appareil dans le le.
1
Un collecteur de démarrage du gradateur est fournis
pour raccorder en option le gradateur par le câblage
vers la ligne de gradation.
2
gecurrent.com/lumination
© 2022 Current Lighting Solutions, LLC. Tous droits réservés. GE et le monogramme GE sont des marques déposées
de General Electric Company et sont utilisés sous licence. Les informations fournies sont sujetes à modifications sans
préavis. Toutes les valeurs données sont théoriques ou typiques lorsque mesurées sous conditions de laboratoire.
Page 20 of 26
(Rev 04/19/23)
LUM_IND679_LIS3_install_R01
Lumination® Séries LIS3 Manuel d’Installation
DALI 0-10 V
Ligne - Noir
Neutre - Blanc
Terre - Vert
(0-10 V)+
- Violet
(0-10 V)-
- Gris
Appareil déjà
pendu
Nouvel
appareil
Ligne - Noir
Neutre - Blanc
Terre - Vert
(0-10 V)+
- Violet/Blanc
(0-10 V)-
- Violet
AppareilAppareil
Schémas de raccordement
3
Pour ajouter un appareil dans une le
continue, suspendez d’abord le nouvel
appareil comme indiqué aux étapes 9 et
10 pour l’appareil indépendant. Mettez
en place l’extrémité non alimentée du
luminaire près de l’extrémité alimentée
du luminaire antérieurement pendu.
4
Enlevez, le cas échéant, le couvercle
du PSU (alimentation) du luminaire
pendu avant.
5
DALI 0-10 V
Ligne - Noir
Neutre - Blanc
Terre - Vert
(0-10 V)+
- Violet
(0-10 V)-
- Gris
Appareil déjà
pendu
Nouvel
appareil
Ligne - Noir
Neutre - Blanc
Terre - Vert
(0-10 V)+
- Violet/Blanc
(0-10 V)-
- Violet
AppareilAppareil
Schémas de raccordement
Newunit
hungunit
Previously
DALI
Wiring Diagrams
Fixture
Line
Neutral
Black
White
Ground Green
DALI Violet/White
DALI Violet
Black
White
Green
Violet
Grey
0-10V
Line
Fixture
Neutral
Ground
(0-10V)+
(0-10V)
Retirez le câblage continu
Alignez les onglets
avec les encoches
Poussez pour
les engager
Retirez le câblage continu hors du luminaire en cours d’installation et glissez le pont du luminaire vers le bas sur le luminaire déjà
installé de manière que les onglets et les encoches au-dessus et en-dessous s’emboîtent les unes dans les autres. Les ponts vont
s’engager avec un “clic” puissant lorsqu’ils vont être tout à fait accouplés.
6
Retirez le câblage continu
Alignez les onglets
avec les encoches
Poussez pour
les engager
Retirez le câblage continu
Alignez les onglets
avec les encoches
Poussez pour
les engager
7
Au début de la le, poussez les ls
dans la cavité du pont.
8
Insérez un couvercle d’extrémité au
début de la le et un à la n (fournis
dans les kits de démarrage).
9
Raccordez les raccords
d’alimentation et de contrôle des
câbles du harnais de passage.
Remettez en place le(s)
couvercle(s) du PSU et xez-les
avec les vis de montage.
Remarque: Lorsque l’installation est
terminée, tous les ls et connecteurs doivent
être entièrement scellés.
10
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39

Lumination LIS3 Series LED Indirect Suspended Luminaire Guide d'installation

Taper
Guide d'installation