Danfoss Electrically operated expansion valves, type AKVH 10 Guide d'installation

Taper
Guide d'installation
©Danfoss A/S (AC / scg 02-2011 DKRCC.PI.VA1.G2.53-520H5211
068R9820
068R9820
AKVH 10 - 0,1, 2, 3, 4, 5, 6
c 75
d 67
In solder 3/8" / 10 mm
Out solder 1/2" / 12 mm
Dyse, Düse, Orifice, Orificio R 744
n
Best.nr.
Code no.
Bestell-Nr.
N° de code
Núm. de código
Rated capacity kW
Refrigeration 1) Freezing 2)
0 068F0722 0.4 0.8
1 068F0723 1.1 2.2
2 068F0724 1.7 3.5
3 068F0725 2.6 5.4
4 068F0726 4.3 8.7
5 068F0727 6.7 13.6
6 068F0728 10.7 21.7
Instructions
Electrically operated expansion valve
AKVH 10-n (n= 0-6)
1) Rated capacities are based on:
Condensing temperature tc =0
o
C
Subcooling tsub = 4K
Evaporating temperature te = -5
o
C
Superheating tsup = 5K
2) Rated capacities are based on:
Condensing temperature tc =0
o
C
Subcooling tsub = 4K
Evaporating temperature te = -25
o
C
Superheating tsup = 5K
©Danfoss A/S (AC /scg) 02-2011 DKRCC.PI.VA1.G2.53-520H5211
Clip-on coil
Ny
New
Neu
Neuf
Nueva
Brugt
Used
Gebraucht
Usagé
Usado
Ambient temperatur range:
-50°C < t
amb
< 50°C
-58°F < t
amb
< 120°F
Media temperatur range
-50°C < t media < 60°C
-58°F < t media < 140°F
Do not insulate
Media:
HCFC, HFC,R744
Max working pressure :
AKVH 10-0 to 6 Ps 90 barg / MWP 1305 psig
Max test pressure :
PT 129 barg / 1870 psig
Max differential pressure:
MOPD = P1 - P2 = 35 bar/505 psi
Note: If operated consistently at or near
MOPD, the service interval will decrease.
Pakningen skal
skiftes, hvis ventilen
adskilles
The gasket must be
exchanged, if the
valve is dismantled
Bei Zerlegung des
Ventils muß die Dich-
tung ausge wechselt
werden.
Changer le joint
chaque fois que la
vanne est démontée
Es preciso cambiar la
junta si se desmonta
la válvula
Instructions
  • Page 1 1
  • Page 2 2

Danfoss Electrically operated expansion valves, type AKVH 10 Guide d'installation

Taper
Guide d'installation