Unitronics Vision PLC+HMI Programmable Logic Controller Manuel utilisateur

Taper
Manuel utilisateur
Unitronics
1
VisionPLC+HMI
User Guide
V130-33-RA22/V130-J-RA22
V350-35-RA22/V350-J-RA22
V430-J-RA22
12 Digital Inputs, including 1 HSC/Shaft-encoder Inputs,
2 Analog, 2 PT100/TC inputs
8 Relay Outputs
2 Analog Outputs
V130-33-TRA22/V130-J-TRA22
V350-35-TRA22/V350-J-TRA22
V430-J-TRA22
12 Digital Inputs, including 1 HSC/Shaft-encoder Inputs,
2 Analog Inputs, 2 PT100/TC inputs
4 Relay Outputs
2 Analog Outputs
4 high-speed npn Transistor Outputs
Item
V130-RA22
V130J-RA22
V130-TRA22
V130J-TRA22
V350-RA22
V350J-RA22
V350-TRA22
V350J-TRA22
V430J-RA22
V430J-TRA22
On-board I/O
Model Dependent
Screen
2.4"
3.5" Color Touch
4.3" Color Touch
Keypad
Yes
None
Function Keys
None
Yes
Com Port, Built-in
RS232/485
Yes
Yes
Yes*
Yes*
Yes*
USB device,
mini-B
None
None
Yes*
Yes*
Yes*
Com Ports, separate
order, user-installed
The user may install a CANbus port (V100-17-CAN), and one of the following:
RS232/RS485 port (V100-17-RS4/V100-17-RS4X)
Ethernet (V100-17-ET2)
Profibus Slave (V100-17-PB1)
* V430J/V350/V350J comprises both RS232/485 and USB ports; note that only one channel may be used at a time.
Standard Kit Contents
Item
V130-RA22
V130J-RA22
V130-TRA22
V130J-TRA22
V350-RA22
V350J-RA22
V350-TRA22
V350J-TRA22
V430J-RA22
V430J-TRA22
Controller
Yes
Terminal Blocks
Yes
Battery (installed)
Yes
Slides
(2 sets of key labels)
None
Yes
None
Mounting Brackets
Yes (2 parts)
Yes (4 parts)
Rubber Seal
Yes
VisionPLC+HMI Installation Guide
2
Unitronics
Symbol
Meaning
Description
Danger
The identified danger causes physical and property damage.
Warning
The identified danger could cause physical and property damage.
Caution
Caution
Use caution.
Failure to comply with appropriate safety guidelines can cause severe injury or property
damage.
Do not attempt to use this device with parameters that exceed permissible levels.
To avoid damaging the system, do not connect/disconnect the device when power is on.
Environmental Considerations
Do not install in areas with: excessive or conductive dust, corrosive or flammable gas,
moisture or rain, excessive heat, regular impact shocks or excessive vibration, in
accordance with the standards given in the product’s technical specification sheet.
Do not place in water or let water leak onto the unit.
Do not allow debris to fall inside the unit during installation.
Ventilation: 10mm space required between controller’s top/bottom edges & enclosure walls.
Install at maximum distance from high-voltage cables and power equipment.
VisionPLC+HMI
Unitronics
3
Model
Cut-out
View area
V130V130J
92x92 mm (3.622”x3.622”)
58x30.5mm (2.28"x1.2")
V350/V350J
92x92 mm (3.622”x3.622”)
72x54.5mm (2.95"x2.14")
V430J
122.5x91.5 mm (4.82”x3.6”)
96.4x55.2mm (3.79"x2.17")
Panel Mounting
Before you begin, note that the mounting panel cannot be more than 5 mm thick.
1. Make a panel cut-out of the appropriate size:
2. Slide the controller into the cut-out, ensuring that the rubber seal is in place.
3. Push the mounting brackets into their slots on the sides of the panel as shown in the figure below.
4. Tighten the bracket’s screws against the panel. Hold the bracket securely against the unit while
tightening the screw.
5. When properly mounted, the controller is squarely situated in the panel cut-out as shown in the
accompanying figures.
V130/V350/V130J/V350J
VisionPLC+HMI Installation Guide
4
Unitronics
V430J
DIN-rail Mounting (V130/V350/V130J/V350J)
1. Snap the controller onto the DIN rail as
shown in the figure to the right.
2. When properly mounted, the controller is
squarely situated on the DIN-rail as
shown in the figure to the right.
UL Compliance
The following section is relevant to Unitronics’ products that are listed with the UL.
The following models: V130-33-R34, V130-J-R34, V130-T4-ZK1, V350-35-RA22, V350-J-RA22,
V350-35-R34, V350-J-R34, V430-J-R34
are UL listed for Hazardous Locations.
The following models: V130-33-B1,V130-J-B1,V130-33-TA24,V130-J-TA24,V130-33-T38,V130-J-T38
V130-33-TR20,V130-J-TR20,V130-33-TR34,V130-J-TR34,V130-33-RA22,V130-J-RA22,
V130-33-TRA22,V130-J-TRA22,V130-33-T2,V130-J-T2,V130-33-TR6,V130-J-TR6,V130-33-R34,
V350-35-B1, V130-T4-ZK1, V350-J-B1,V350-35-TA24,V350-J-TA24,V350-35-T38,V350-J-T38,
V350-35-TR20,V350-J-TR20,V350-35-TR34,V350-J-TR34,V350-35-TRA22,V350-J-TRA22,
V350-35-T2,V350-J-T2,V350-35-TR6,V350-J-TR6,V350-S-TA24,V350-JS-TA24,V350-35-RA22,
VisionPLC+HMI
Unitronics
5
V350-J-RA22,V350-35-R34, V430-J-B1,V430-J-TA24,V430-J-T38, V430-J-R34,V430-J-RH2,
V430-J-TR34,V430-J-RA22,V430-J-TRA22,V430-J-T2,V430-J-RH6
are UL listed for Ordinary Location.
For models from series V130, V130-J, V430, that include “T4” or “J4” in the Model name, Suitable for
mounting on the flat surface of Type 4X enclosure.
For examples: V130-T4-R34, V130-J4-R34, V430-J4-T2
UL Ordinary Location
In order to meet the UL ordinary location standard, panel-mount this device on the flat surface
of Type 1 or 4 X enclosures
UL Ratings, Programmable Controllers for Use in Hazardous Locations,
Class I, Division 2, Groups A, B, C and D
These Release Notes relate to all Unitronics products that bear the UL symbols used to mark products
that have been approved for use in hazardous locations, Class I, Division 2, Groups A, B, C and D.
Caution
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, or Non-
hazardous locations only.
Input and output wiring must be in accordance with Class I, Division 2 wiring methods and in
accordance with the authority having jurisdiction.
WARNINGExplosion Hazardsubstitution of components may impair suitability for Class I,
Division 2.
WARNING EXPLOSION HAZARD Do not connect or disconnect equipment unless power
has been switched off or the area is known to be non-hazardous.
WARNING Exposure to some chemicals may degrade the sealing properties of material
used in Relays.
This equipment must be installed using wiring methods as required for Class I, Division 2 as
per the NEC and/or CEC.
Panel-Mounting
For programmable controllers that can be mounted also on panel, in order to meet the UL Haz Loc
standard, panel-mount this device on the flat surface of Type 1 or Type 4X enclosures.
Relay Output Resistance Ratings
The products listed below contain relay outputs:
Programmable controllers, Models: V430-J-R34, V130-33-R34,V130-J-R34 and V350-35-R34,
V350-J-R34
When these specific products are used in hazardous locations, they are rated at 3A res.
Except for models V430-J-R34, V130-33-R34, V130-J-R34, V130-T4-ZK1 and V350-35-R34,
V350-J-R34,when these specific products are used in non-hazardous environmental conditions,
they are rated at 5A res, as given in the product’s specifications.
Communication and Removable Memory Storage
When products comprise either USB communication port, SD card slot, or both, neither
the SD card slot nor the USB port are intended to be permanently connected, while the USB port is
intended for programming only.
Removing / Replacing the battery
When a product has been installed with a battery, do not remove or replace the battery unless the
power has been switched off, or the area is known to be non-hazardous.
VisionPLC+HMI Installation Guide
6
Unitronics
Please note that it is recommended to back up all data retained in RAM, in order to avoid losing data
when changing the battery while the power is switched off. Date and time information will also need to
be reset after the procedure.
UL des zones ordinaires:
Pour respecter la norme UL des zones ordinaires, monter l'appareil sur une surface plane de type de
protection 1 ou 4X
Certification UL des automates programmables, pour une utilisation en
environnement à risques, Class I, Division 2, Groups A, B, C et D.
Cette note fait référence à tous les produits Unitronics portant le symbole UL - produits qui ont été
certifiés pour une utilisation dans des endroits dangereux, Classe I, Division 2, Groupes A, B, C et D.
Attention
Cet équipement est adapté pour une utilisation en Classe I, Division 2, Groupes A, B, C et
D, ou dans Non-dangereux endroits seulement.
Le câblage des entrées/sorties doit être en accord avec les méthodes
de câblage selon la Classe I, Division 2 et en accord avec l’autorité compétente.
AVERTISSEMENT: Risque d’Explosion – Le remplacement de certains composants rend
caduque la certification du produit selon la Classe I, Division 2.
AVERTISSEMENT - DANGER D'EXPLOSION - Ne connecter pas ou ne débranche pas
l'équipement sans avoir préalablement coupé l'alimentation électrique ou la zone est
reconnue pour être non dangereuse.
AVERTISSEMENT - L'exposition à certains produits chimiques peut dégrader les propriétés
des matériaux utilisés pour l'étanchéité dans les relais.
Cet équipement doit être installé utilisant des méthodes de câblage suivant la norme Class I,
Division 2 NEC et /ou CEC.
Montage de l'écran:
Pour les automates programmables qui peuvent aussi être monté sur l'écran,
pour pouvoir être au standard UL, l'écran doit être monté dans un coffret avec une surface plane de
type 1 ou de type 4X.
Certification de la résistance des sorties relais
Les produits énumérés ci-dessous contiennent des sorties relais:
Automates programmables, modèles : V430-J-R34, V130-33-R34,V130-J-R34 and
V350-35-R34,V350-J-R34
Lorsque ces produits spécifiques sont utilisés dans des endroits dangereux, ils supportent
un courant de 3A charge résistive.
Excepté les modèles: V430-J-R34, V130-33-R34,V130-J-R34, V130-T4-ZK1 et V350-35-R34,
V350-J-R34 lorsque ces produits spécifiques sont utilisés dans un environnement non dangereux, ils
sont évalués à 5A res, comme indiqué dans les specifications du produit Plages de températures
Communication et de stockage amovible de mémoire (carte mémoire)
Produits comprend un port USB de communication, soit un port carte SD ou les deux, ni le port SD, ni
le port USB ne sont censés être utilisés en permanence, tandis que l'USB est destiné à la
programmation uniquement.
Retrait / Remplacement de la batterie
Lorsqu'un produit a été installé avec une batterie, retirez et remplacez la batterie seulement si
l’alimentation est éteinte ou si l’environnement n’est pas dangereux.
Veuillez noter qu'il est recommandé de sauvegarder toutes les données conservées dans la RAM, afin
d'éviter de perdre des données lors du changement de la batterie lorsque l'alimentation est coupée. Les
informations sur la date et l'heure devront également être réinitialisées après la procédure
VisionPLC+HMI
Unitronics
7
Wiring
Do not touch live wires.
Install an external circuit breaker. Guard against short-circuiting in external wiring.
Use appropriate circuit protection devices.
Unused pins should not be connected. Ignoring this directive may damage the device.
Double-check all wiring before turning on the power supply.
Caution
To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·cm).
Do not use tin, solder, or any substance on stripped wire that might cause the wire
strand to break.
Install at maximum distance from high-voltage cables and power equipment.
Wiring Procedure
Use crimp terminals for Use crimp terminals for wiring;
- Controllers offering a terminal block with pitch of 5mm: 26-12 AWG wire (0.13 mm2 3.31 mm2).
- Controllers offering a terminal block with pitch of 3.81mm: 26-16 AWG wire (0.13 mm2 1.31 mm2).
1. Strip the wire to a length of 7±0.5mm (0.270–0.300“).
2. Unscrew the terminal to its widest position before inserting a wire.
3. Insert the wire completely into the terminal to ensure a proper connection.
4. Tighten enough to keep the wire from pulling free.
Input or output cables should not be run through the same multi-core cable or share
the same wire.
Allow for voltage drop and noise interference with I/O lines used over an extended distance.
Use wire that is properly sized for the load.
The controller and I/O signals must be connected to the same 0V signal.
I/Os
V130/V350/V130J/V350J/V430J-RA22 models comprise a total of 12 inputs, 8 relay outputs and
2 analog outputs.
V130/V350/V130J/V350J/V430J-TRA22 models comprise a total of 12 inputs, 4 relays outputs,
4 npn outputs and 2 analog outputs.
Input functionality can be adapted as follows:
12 inputs may be used as digital inputs. They may be wired, in a group, and set to either
npn or pnp via a single jumper.
In addition, according to jumper settings and appropriate wiring:
- Inputs 5 and 6 can function as either digital or analog inputs.
- Input 0 can function as high-speed counter, as part of a shaft-encoder,
or as normal digital input.
- Input 1 can function as either counter reset, as part of a shaft-encoder,
or as normal digital input.
- If input 0 is set as high-speed counters (without reset), input 1 can function
as normal digital input.
- Inputs 7-8 and 9-10 can function as digital, thermocouple, or PT100 inputs; Input 11 can also
serve as the CM signal for PT100.
VisionPLC+HMI Installation Guide
8
Unitronics
Input Jumper Settings
The tables below show how to set a specific jumper to change input functionality. To access the I/O
jumpers, you must open the controller according to the instructions beginning on page 13.
Incompatible jumper settings and wiring connections may seriously damage the controller.
Digital Inputs 0-11: Set Type
Set to
JP12 (all Inputs)
npn (sink)
A
pnp (source)*
B
Inputs 7/8: Set Type - Digital or RTD/TC #1
Set to
JP1
JP2
JP3
Digital*
A
A
A
Thermocouple
B
B
B
PT100
B
A
B
Inputs 9/10: Set Type - Digital or RTD/TC #0
Set to
JP5
JP6
JP7
Digital*
A
A
A
Thermocouple
B
B
B
PT100
B
A
B
Input 11: Set Type - Digital or CM for PT100
Set to
JP11
Digital*
A
CM for PT100
B
Input 5: Set Type - Digital or Analog #3
Set to
JP4
JP10
Analog Output 0: Set to Voltage/Current
Digital*
A
A
Set to
JP13
Voltage
B
A
Voltage*
A
Current
B
B
Current
B
Input 6: Set Type - Digital or Analog #2
Set to
JP8
JP9
Analog Output 1: Set to Voltage/Current
Digital*
A
A
Set to
JP14
Voltage
B
A
Voltage*
A
Current
B
B
Current
B
*Default settings
VisionPLC+HMI
Unitronics
9
I/O Wiring
npn (sink) Input
Input wiring
HSC input wiring
pnp (source) Input
Input wiring
HSC input wiring
Shaft-encoder
VisionPLC+HMI Installation Guide
10
Unitronics
Analog Input
Analog input wiring, current (2/3 wire)
Analog input wiring, current (4-wire), and voltage
Shields should be connected at the signal’s source.
The 0V signal of the analog input must be connected to the controller’s 0V.
Thermocouple
Type
Temp. Range
Wire Color
ANSI (USA)
BS1843 (UK)
mV
-5 to 56mV
B
200 to 1820˚C
(300 to 3276˚F)
+Grey
-Red
+None
-Blue
E
-200 to 750˚C
(-328 to 1382˚F)
+Violet
-Red
+Brown
-Blue
J
-200 to 760˚C
(-328 to 1400˚F)
+White
-Red
+Yellow
-Blue
K
-200 to 1250˚C
(-328 to 2282˚F)
+Yellow
-Red
+Brown
-Blue
N
-200 to 1300˚C
(-328 to 2372˚F)
+Orange
-Red
+Orange
-Blue
R
0 to 1768˚C
(32 to 3214˚F)
+Black
-Red
+White
-Blue
S
0 to 1768˚C
(32 to 3214˚F)
+Black
-Red
+White
-Blue
T
-200 to 400˚C
(-328 to 752˚F)
+Blue
-Red
+White
-Blue
Thermocouple 0: use Input 9 as
negative input and 10 as positive.
Thermocouple 1: use Input 7 as
negative input and 8 as positive.
VisionPLC+HMI
Unitronics
11
RTD
PT100 (Sensor 0): use Input 9 and 10, related to CM signal.
PT100 (Sensor 1): use Input 7 and 8, related to CM signal.
4 wire PT100 can be used by leaving one of the sensor leads unconnected.
Analog Outputs
npn Outputs (TRA22)
Relay Outputs
RA22
TRA22
VisionPLC+HMI Installation Guide
12
Unitronics
Increasing Contact Life Span
To increase the life span of the
relay output contacts and protect
the device from potential damage
by reverse EMF, connect:
A clamping diode in parallel with each
inductive DC load
An RC snubber circuit in parallel with each
inductive AC load
Power Supply
The controller requires an external 24VDC power supply.
The power supply must include double insulation. Outputs must be rated as
SELV/PELV/Class2/Limited Power.
Use separate wires to connect the functional
earth line (pin 3) and the 0V line (pin 2) to the
system earth ground.
Install an external circuit breaker. Guard
against short-circuiting in external wiring.
Double-check all wiring before turning
on the power supply.
Do not connect either the ‘Neutral’ or ‘Line’
signal of the 110/220VAC to device’s 0V pin
In the event of voltage fluctuations or non-
conformity to voltage power supply
specifications, connect the device to
a regulated power supply.
Earthing the PLC+HMI
To maximize system performance, avoid electromagnetic interference by:
Mounting the controller on a metal panel.
Connect each common and ground connection directly to the earth ground of your system.
For ground wiring uses the shortest and thickest possible wire.
VisionPLC+HMI
Unitronics
13
Communication
V130/ V130J/V350J
These models comprise a built-in RS232/RS485 serial port (Port 1)
V430J/ V350/V350J
These models comprise built-in ports: 1 USB and 1 RS232/RS485 (Port 1).
Note that physically connecting a PC to the controller via USB suspends RS232/RS485
communications via Port 1. When the PC is disconnected, RS232/RS485 resumes.
RS232/RS485 Port
Turn off power before making communications connections.
Caution
Always use the appropriate port adapters.
Caution
Signals are related to the controller’s 0V; the same 0V is used by the power supply.
The serial port is not isolated. If the controller is used with a non-isolated external device,
avoid potential voltage that exceeds ± 10V.
Use RS232 to download programs from a PC, and to communicate with serial devices and
applications, such as SCADA.
Use RS485 to create a multi-drop network containing up to 32 devices.
Pinouts
The pinouts below show the PLC port signals.
RS232
RS485**
Controller Port
Pin #
Description
Pin #
Description
Pin #1
1*
DTR signal
1
A signal (+)
2
0V reference
2
(RS232 signal)
3
TXD signal
3
(RS232 signal)
4
RXD signal
4
(RS232 signal)
5
0V reference
5
(RS232 signal)
6*
DSR signal
6
B signal (-)
* Standard programming cables do not provide connection points for pins 1 and 6.
** When a port is adapted to RS485, Pin 1 (DTR) is used for signal A,
and Pin 6 (DSR) signal is used for signal B.
Note that it is possible to establish a PC to PLC connection using RS232 even when the PLC is set to
RS485 (this eliminates the need to open the controller to set jumpers).
To do so, remove the RS485 connector (pins 1 & 6) from the PLC and connect a standard RS232
programming cable.
Note that this is possible only if DTR and DSR signals of RS232 are not used (which is the standard
case).
VisionPLC+HMI Installation Guide
14
Unitronics
Setting RS232/RS485 Communication Parameters, V430J
This port may be set to either RS232 or RS485 via DIP switches:
The table shows the DIP switches factory default settings. Use the table to adapt the settings.
Switch Settings
1
2
3
4
5
6
RS232*
ON
OFF
OFF
ON
OFF
OFF
RS485
OFF
ON
ON
OFF
OFF
OFF
RS485 with
termination**
OFF
ON
ON
OFF
ON
ON
* Default factory setting
** Causes the unit to function as an end unit in an RS485 network
USB Port
Caution
The USB port is not isolated.
Make sure that the PC and the controller are grounded to same potential.
The USB port may be used for programming, OS download, and PC access.
Setting RS232/RS485 Communication Parameters, V130/V350/V130J/V350J
This port may be set to either RS232 or RS485 via jumper.
The accompanying figure shows the jumper factory
default settings.
These jumpers may be used to:
Set communications to RS485, by setting both COMM
jumpers to ‘485’.
Set RS485 termination, by setting both TERM jumpers
to ‘OFF’.
To access the jumpers, you must open the controller
according to the instructions on page 13.
VisionPLC+HMI
Unitronics
15
Opening the Controller
Before performing these actions, touch a grounded object to discharge any electrostatic charge.
Avoid touching the PCB board directly. Hold the PCB board by its connectors.
1. Turn off the power supply, disconnect, and dismount the controller.
2. The back cover of the controller comprises 4 screws, located in the corners.
Remove the screws, and pull off the back cover.
Changing I/O Settings
After opening the controller and exposing the I/O board, you can change the jumper settings according
to the table shown above.
Changing Communication Settings (V130/V350/V130J/V350J Only)
1. To access the communication jumpers, hold the I/O PCB board by its top and bottom connectors
and steadily pull the board off.
2. Locate the jumpers, and then change the settings as required, according to the jumpers settings
shown on page 12.
Closing the Controller
1. Gently replace the board. Make certain that the pins fit correctly into their matching receptacle.
Do not force the board into place; doing so may damage the controller.
2. Replace the back cover of the controller and fasten the corner screws.
Note that you must replace the back cover securely before powering up the controller.
VisionPLC+HMI Installation Guide
16
Unitronics
VisionPLC+HMI
V130-33-TRA22/V130-J-TRA22
V350-35-TRA22/V350-J-TRA22
V430-J-TRA22
Technical Specifications
Order Information
Item
V130-33-TRA22
PLC with Classic panel, Monochrome display 2.4"
V130-J-TRA22
PLC with Flat panel, Monochrome display 2.4"
V350-35-TRA22
PLC with Classic panel, Color touch display 3.5’’
V350-J-TRA22
PLC with Flat panel, Color touch display 3.5’’
V430-J-TRA22
PLC with Flat panel, Color touch display 4.3’’
You can find additional information, such as wiring diagrams, in the product’s installation guide
located in the Technical Library at www.unitronics.com.
Power Supply
Item
V130-TRA22
V130J-TRA22
V350-TRA22
V350J-TRA22
V430J-TRA22
Input voltage
24VDC
Permissible range
20.4VDC to 28.8VDC with less than 10% ripple
Max. current
consumption
See Note 1
npn inputs
245mA@24VDC
270mA@24VDC
270mA@24VDC
pnp inputs
200mA@24VDC
230mA@24VDC
230mA@24VDC
Notes:
1. To calculate the actual power consumption, subtract the current for each unused element from the maximum
current consumption value according to the values below:
Backlight
Ethernet
card
Relay Outputs
(per output)
All Analog Outputs,
voltage/current
V130/J
10mA
35mA
5mA
48mA/30mA*
V350/J/V430J
20mA
35mA
5mA
48mA/30mA*
*If the analog outputs are not configured, then subtract the higher value.
Digital Inputs
Number of inputs
12. See note 2
Input type
See note 2
Galvanic isolation
None
Nominal input voltage
24VDC
Input Voltage
Normal digital input
High Speed Input. See Note
3
pnp (source)
0-5VDC for Logic ‘0’
17-28.8VDC for Logic ‘1’
0-3VDC for Logic ‘0’
20.4-28.8VDC for Logic ‘1’
npn (sink)
17-28.8VDC for Logic ‘0’
0-5VDC for Logic ‘1
20.4-28.8VDC for Logic ‘0’
0-3VDC for Logic ‘1
Input Current
I0, I1: 5.4mA@24VDC
I2-I11: 3.7mA@24VDC
Input impedance
I0, I1: 4.5KΩ
I2-I11: 6.5KΩ
Response Time
10ms typical, when used as normal digital input
Input Cable length
Normal digital Input
Up to 100 meters
VisionPLC+HMI
Unitronics
17
High Speed Input
Up to 50 meters, shielded, see Frequency table below
High speed inputs
Specifications below apply when wired as HSC/shaft-encoder. See Note 2
Frequency, HSC
Driver type
pnp/npn
Push-pull
Cable length (max.)
10m
95kHz maximum
200kHz maximum
25m
50kHz maximum
200kHz maximum
50m
25kHz maximum
200kHz maximum
Frequency, Shaft-encoder
Driver type
pnp/npn
Push-pull
Cable length (max.)
10m
35kHz maximum
100kHz maximum
25m
18kHz maximum
100kHz maximum
50m
10kHz maximum
100kHz maximum
Duty cycle
40-60%
Resolution
32-bit
Notes:
2. V130/V350/V130J/V350J/V430J-TRA22 models comprise a total of 12 inputs.
All 12 inputs may be used as digital inputs. They may be wired in a group via a single jumper
as either npn or pnp.
In addition, according to jumper settings and appropriate wiring:
- Inputs 5 and 6 can function as either digital or analog inputs.
- Input 0 can function as a high-speed counter, as part of a shaft-encoder,
or as normal digital inputs.
- Input 1 can function as either counter reset, normal digital input, or as part of a shaft-encoder.
- If input 0 is set as a high-speed counter (without reset), input 1 can function
as a normal digital input.
- Inputs 7-8 and 9-10 can function as digital, thermocouple, or PT100 inputs; input 11 can also serve as the
CM signal for PT100.
3. If you configure an input as high-speed, you can use an end-device that comprises push-pull drive type.
In this case, the high-speed input voltage ratings for npn/pnp apply.
Analog Inputs
Number of inputs
2, according to wiring as described above in Note 2
Input type
Multi-range inputs: 0-10V, 0-20mA, 4-20mA
Input range
0-20mA, 4-20mA
0-10VDC
Input impedance
37Ω
12.77kΩ
Maximum input rating
30mA, 1.1V
±15V
Galvanic isolation
None
Conversion method
Voltage to frequency
Normal mode
Resolution, except 4-20mA
14-bit (16384units)
Resolution, at 4-20mA
3277 to 16383 (13107 units)
Conversion time
100ms minimum per channel. See Note 4
Fast mode
Resolution, except 4-20mA
12-bit (4096 units)
Resolution, at 4-20mA
819 to 4095 (3277 units)
Conversion time
30ms minimum per channel. See Note 4
Full-scale error
±0.4%
Linearity error
±0.04%
Status indication
Yes. See Note 5
VisionPLC+HMI Installation Guide
18
Unitronics
Notes:
4. Conversion times are accumulative and depend on the total number of analog inputs configured.
For example, if only one analog input (fast mode) is configured, the conversion time will be 30ms; however,
if two analog (normal mode) and two RTD inputs are configured, the conversion time will be
100ms + 100ms + 300ms + 300ms = 800ms.
5. The analog value can indicate faults as shown below:
Value: 12-bit
Value: 14-bit
Possible Cause
-1
-1
Deviates slightly below the input range
4096
16384
Deviates slightly above the input range
32767
32767
Deviates greatly above or below the input range
RTD Inputs
RTD Type
PT100
Temperature coefficient
0.00385/0.00392
Input range
-200 to 600C/-328 to 1100F. 1 to 320Ω.
Isolation
None
Conversion method
Voltage to frequency
Resolution
0.1C/0.1F
Conversion time
300ms minimum per channel. See Note 4 above
Input impedance
>10MΩ
Auxillary current for PT100
150μA typical
Full-scale error
±0.4%
Linearity error
±0.04%
Status indication
Yes. See Note 6
Cable length
Up to 50 meters, shielded
Notes:
6. The analog value can indicate faults as shown below:
Value
Possible Cause
32767
Sensor is not connected to input, or value exceeds permissible range
-32767
Sensor is short-circuited
Thermocouple Inputs
Input range
See Note 7
Isolation
None
Conversion method
Voltage to frequency
Resolution
0.1C/ 0.1F maximum
Conversion time
100ms minimum per channel. See Note 4 above
Input impedance
>10MΩ
Cold junction compensation
Local, automatic
Cold junction compensation error
±1.5C/±2.7F maximum
Absolute maximum rating
±0.6VDC
Full-scale error
±0.4%
Linearity error
±0.04%
Warm-up time
½ hour typically, ±1C/±1.8F repeatability
Status indication
Yes. See Note 6 above
VisionPLC+HMI
Unitronics
19
Notes:
7. The device can also measure voltage within the range of -5 to 56mV, at a resolution of 0.01mV.
The device can also measure raw value frequency at a resolution of 14-bits (16384). Input ranges are shown
in the following table:
Type
Temp. Range
Type
Temp. Range
mV
-5 to 56mV
N
-200 to 1300˚C (-328 to 2372˚F)
B
200 to 1820˚C (300 to 3276˚F)
R
0 to 1768˚C (32 to 3214˚F)
E
-200 to 750˚C (-328 to 1382˚F)
S
0 to 1768˚C (32 to 3214˚F)
J
-200 to 760˚C (-328 to 1400˚F)
T
-200 to 400˚C (-328 to 752˚F)
K
-200 to 1250˚C (-328 to 2282˚F)
Digital Outputs
Number of outputs
4 relay. See Note 8
Output type
SPST-NO (Form A)
Isolation
By relay
Type of relay
Tyco PCN-124D3MHZ or compatible
Output current
(resistive load)
3A maximum per output
8A maximum total per common
Rated voltage
250VAC / 30VDC
Minimum load
1mA, 5VDC
Life expectancy
100k operations at maximum load
Response time
10ms (typical)
Contact protection
External precautions required (see Increasing Contact Life Span in the
product’s Installation Guide)
Notes:
8. Outputs 4, 5, 6, and 7 share a common signal.
Transistor Outputs
Number of outputs
4 npn (sink). See Note 9
Output type
N-MOSFET, (open drain)
Galvanic Isolation
None
Maximum output current
(resistive load)
100mA per output
Rated voltage
24VDC
Maximum delay OFF to ON
1s
Maximum delay ON to OFF
10s
HSO freq. range with resistive
load
5Hz-200kHz (at maximum load resistance of 1.5kΩ)
Maximum ON voltage drop
1VDC
Short-circuit protection
None
Voltage range
3.5V to 28.8VDC
Notes:
9. Outputs 0, 1, 2 and 3 share a common 0V signal.
The 0V signal of the output must be connected to the controller’s 0V.
VisionPLC+HMI Installation Guide
20
Unitronics
Analog Outputs
Number of outputs
2
Output range
0-10V, 4-20mA. See Note 10
Resolution
12-bit (4096 units)
Conversion time
Both outputs are updated per scan
Load impedance
1kΩ minimum—voltage
500Ω maximum—current
Galvanic isolation
None
Linearity error
±0.1%
Operational error limits
±0.2%
Notes:
10. Note that the range of each I/O is defined by wiring, jumper settings, and within the controller’s software.
Graphic Display Screen
Item
V130-TRA22
V130J-TRA22
V350-TRA22
V350J-TRA22
V430J-TRA22
LCD Type
STN, LCD display
TFT, LCD display
TFT, LCD display
Illumination backlight
White LED
White LED
White LED
Display resolution
128x64 pixels
320x240 pixels
480x272 pixels
Viewing area
2.4"
3.5"
4.3"
Colors
Monochrome
65,536 (16-bit)
65,536 (16-bit)
Screen Contrast
Via software
(Store value to SI 7,
values range: 0 to 100%)
Fixed
Fixed
Touchscreen
None
Resistive, analog
Resistive, analog
‘Touch’ indication
None
Via buzzer
Via buzzer
Screen brightness control
Via software
(Store value to SI 9,
0 = Off, 1 = On)
Via software
(Store value to SI 9, values range: 0 to 100%)
Virtual Keypad
None
Displays virtual keyboard when the application requires
data entry.
Keypad
Item
V130-TRA22
V130J-TRA22
V350-TRA22
V350J-TRA22
V430J-TRA22
Number of keys
20 keys,including 10
user-labeled keys
5 programmable function keys
Key type
Metal dome, sealed membrane switch
Slides
Slides may be installed in
the operating panel
faceplate to custom-label
the keys. Refer to V130
Keypad Slides.pdf.
A complete set of blank
slides is available by
separate order
Slides may be installed in
the operating panel
faceplate to custom-label
the keys. Refer to V350
Keypad Slides.pdf.
Two sets of slides are
supplied with the
controller: one set of
arrow keys, and one
blank set.
None
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23

Unitronics Vision PLC+HMI Programmable Logic Controller Manuel utilisateur

Taper
Manuel utilisateur