Unitronics IO-ATC8 Manuel utilisateur

Taper
Manuel utilisateur
Unitronics Industrial Automation
1
IO-ATC8 User Guide
I/O Expansion Module 8 Analog/Thermocouple Inputs
The IO-ATC8 is an I/O Expansion Module
that can be used in conjunction with
specific Unitronics OPLC controllers.
The module offers 8 inputs that may be
set as either analog or thermocouple
inputs via wiring, jumper and software
settings.
The interface between the module and the
OPLC is provided by an adapter.
The module may either be snap-mounted
on a DIN rail, or screw-mounted onto a
mounting plate.
1 5
2
3
6
4
Component identification
1
Module-to-module connector
2
Communication status indicator
3
Input connection points, I4 to I7
4
Input status indicators
5
Module-to-module connector port
6
Input connection points, I0 to I3
Before using this product, it is the responsibility of the user to read and understand this document and
any accompanying documentation.
All examples and diagrams shown herein are intended to aid understanding, and do not guarantee
operation. Unitronics accepts no responsibility for actual use of this product based on these examples.
Please dispose of this product in accordance with local and national standards and regulations.
Only qualified service personnel should open this device or carry out repairs.
User safety and equipment protection guidelines
This document is intended to aid trained and competent personnel in the installation of this equipment as
defined by the European directives for machinery, low voltage, and EMC. Only a technician or engineer trained
in the local and national electrical standards should perform tasks associated with the device’s electrical wiring.
Symbols are used to highlight
information relating to the user’s
personal safety and equipment
protection throughout this document.
When these symbols appear, the
associated information must be read
carefully and understood fully.
Symbol
Meaning
Description
Danger
The identified danger causes physical
and property damage.
Warning
The identified danger can cause
physical and property damage.
Caution
Caution
Use caution.
Failure to comply with appropriate safety guidelines can result in severe personal injury or
property damage. Always exercise proper caution when working with electrical equipment.
UG_IO-ATC8 I/O Expansion Module
2
Unitronics Industrial Automation
Check the user program before running it.
Do not attempt to use this device with parameters that exceed permissible levels.
To avoid damaging the system, do not connect / disconnect the device when the power is on.
Environmental Considerations
Do not install in areas with: excessive or conductive dust, corrosive or flammable gas,
moisture or rain, excessive heat, regular impact shocks or excessive vibration.
Leave a minimum of 10mm space for ventilation between the top and bottom edges of the
device and the enclosure walls.
Do not place in water or let water leak onto the unit.
Do not allow debris to fall inside the unit during installation.
Mounting the Module
DIN-rail mounting
Snap the device onto the DIN rail as shown below; the module will be squarely situated on the DIN rail.
60mm
(2.362")
3.5mm
(0.137")
14mm
(0.55")
80mm
(3.15")
93mm
(3.66")
44.5mm
(1.75")
UG_IO-ATC8 I/O Expansion Module
Unitronics Industrial Automation
3
Screw-Mounting
The figure below is not drawn to scale. It may be used as a guide for screw-mounting the module.
Mounting screw type: either M3 or NC6-32.
4mm
5.8mm
(0.228")
85mm
(3.346")
80mm
(3.15")
68.4mm
(2.693")
93mm
(3.66")
4mm (x2)
(0.16")
(0.16")
UG_IO-ATC8 I/O Expansion Module
4
Unitronics Industrial Automation
Connecting Expansion Modules
An adapter provides the interface between the OPLC and an expansion module. To connect the I/O module to
the adapter or to another module:
1. Push the module-to-module connector into the port located on the right side of the device.
Note that there is a protective cap provided with the adapter. This cap covers the port of the final
I/O module in the system.
To avoid damaging the system, do not connect or disconnect the device when the
power is on.
1 2
Component identification
1
Module-to-module
connector
2
Protective cap
Wiring
Do not touch live wires.
Unused pins should not be connected. Ignoring this directive may damage the device.
Do not connect the ‘Neutral or ‘Line’ signal of the 110/220VAC to the device’s COM pins.
Double-check all wiring before turning on the power supply.
Wiring Procedures
Use crimp terminals for wiring; use 26-12 AWG wire (0.13 mm 23.31 mm2) for all wiring purposes.
1. Strip the wire to a length of 7±0.5mm (0.2500.300 inches).
2. Unscrew the terminal to its widest position before inserting a wire.
3. Insert the wire completely into the terminal to ensure that a proper connection can be made.
4. Tighten enough to keep the wire from pulling free.
To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·m).
Do not use tin, solder, or any other substance on stripped wire that might cause the wire strand to break.
Install at maximum distance from high-voltage cables and power equipment.
I/O WiringGeneral
Input or output cables should not be run through the same multi-core cable or share the same wire.
Allow for voltage drop and noise interference with input lines used over an extended distance. Use wire
that is properly sized for the load.
UG_IO-ATC8 I/O Expansion Module
Unitronics Industrial Automation
5
Analog Inputs
Shields should be connected at the signal source.
Inputs may be set as either thermocouple, current, or voltage. To set an input:
- Use the appropriate wiring as shown below.
- Open the device and set the jumpers according to the instructions beginning on page 6.
The adapter and the COM signals of the analog inputs must be connected to the same 0V signal.
The COM signals of each channel are internally shorted.
When set to current/voltage, each 2 inputs share a common COM signal.
UG_IO-ATC8 I/O Expansion Module
6
Unitronics Industrial Automation
Opening the Device
Before opening the device, touch a grounded object to discharge any electrostatic
charge.
Avoid touching the PCB board directly.
Turn power off and disconnect all leads before opening the device.
In order to change the jumper settings of a specific input, first open the device by prying off its back, using the
blade of a flat-bladed screwdriver. The insertion points for the screwdriver are located on both sides of the
module.
1. Open the first side of the device by inserting the blade between the 2 plastic moldings as shown below, then
gently pushing up.
2. Taking care not to damage the cable, open the other side of the device by inserting the blade where shown
below, then gently pushing up.
UG_IO-ATC8 I/O Expansion Module
Unitronics Industrial Automation
7
3. Gently remove the top of the
device as shown.
4. The jumpers are shown at right.
Change the jumper settings as
required, in accordance with the
tables shown on the next page.
UG_IO-ATC8 I/O Expansion Module
8
Unitronics Industrial Automation
Jumper Settings
The tables below show how to set a specific jumper to change the functionality of a specific input.
To open the device and access the jumpers, refer to the instructions beginning on page 6.
Caution
Incompatible jumper settings and wiring may severely damage the device.
Jumper #
Thermocouple*
Voltage
Current
Input 0
1
B
A
A
2
B
A
B
Input 1
3
B
A
A
4
B
A
B
Input 2
5
B
A
A
6
B
A
B
Input 3
7
B
A
A
8
B
A
B
Input 4
9
B
A
A
10
B
A
B
Input 5
11
B
A
A
12
B
A
B
Input 6
13
B
A
A
14
B
A
B
Input 7
15
B
A
A
16
B
A
B
* Default factory setting.
UG_IO-ATC8 I/O Expansion Module
Unitronics Industrial Automation
9
IO-ATC8 Technical Specifications
Max. current consumption
40mA maximum from the adapter’s 5VDC
Typical power consumption
0.2W@5VDC
Status indicator
(RUN)
Green LED:
Lit when a communication link is established between module and OPLC.
Blinks when the communication link fails.
Thermocouple Inputs
Number of inputs
8. See Note 1.
Input type
Thermocouple, differential inputs. See Note 2.
Input range
As shown in table below.
Isolation
None
Conversion method
Voltage to frequency
Resolution
0.1ºC (0.1ºF) See Note 3.
Conversion time
100mSec minimum, according to the filter type selected in software settings
Input impedance
>10MΩ
Cold junction compensation
Local, automatic
Cold junction compensation
error
±1.5ºC (±2.7ºF) maximum
Absolute maximum rating
±0.6VDC
Linearity error
0.04% maximum of full scale
Error limit
0.4% of input value
Warm-up time
Typically ½ hour, ±1ºC (±1.8ºF) repeatability
Status indicators
(OUT OF RANGE)
Red LEDsLit when the corresponding input measures an analog value in
excess of the input range. See Note 4.
Thermocouple input ranges
Type
Temperature range
Wire color
ANSI (USA)
BS 1843 (UK)
mV
-5 to 56mV
-
-
B
200 to 1820°C
+ Grey
+ None
(300 to 3276°F)
- Red
- Blue
E
-200 to 750°C
+ Violet
+ Brown
(-328 to 1382°F)
- Red
- Blue
J
-200 to 760°C
+ White
+ Yellow
(-328 to 1400°F)
- Red
- Blue
K
-200 to 1250°C
+ Yellow
+ Brown
(-328 to 2282°F)
- Red
- Blue
N
-200 to 1300°C
+ Orange
+ Orange
(-328 to 2372°F)
- Red
- Blue
R
0 to 1768°C
+ Black
+ White
(32 to 3214°F)
- Red
- Blue
S
0 to 1768°C
+ Black
+ White
(32 to 3214°F)
- Red
- Blue
T
-200 to 400°C
+ Blue
+ White
(-328 to 752°F)
- Red
- Blue
Analog Inputs
Number of inputs
8 (single-ended) See Note 1.
Input range
0-10V, 0-20mA, 4-20mA. See Note 1.
Input type
Either Normal or Fast mode, according to the filter type selected in software
UG_IO-ATC8 I/O Expansion Module
10
Unitronics Industrial Automation
settings
Conversion method
Voltage to frequency
Normal mode
Resolution at 0-10V,
0-20mA
14-bit (16384 units)
Resolution at 4-20mA
3277 to16383 (13107 units)
Conversion time
100mSec minimum per input
Fast mode
Resolution at 0-10V,
0-20mA
12-bit (4096 units)
Resolution at 4-20mA
819 to 4095 (3277 units)
Conversion time
25mSec minimum per input
Input impedance
>400KΩ—voltage
500Ω—current
Isolation
None
Absolute maximum rating
±15Vvoltage
±30mAcurrent
Linearity error
0.04% max of full scale
Error limits
0.4% of input value
Status indicators
(OUT OF RANGE)
Red LEDsLit when the corresponding input is receiving current or voltage in
excess of the input range. See Note 5.
Environmental
IP20/NEMA1
Operating temperature
0 to 50C (32 to 122° F)
Storage temperature
-20 to 60C (-4 to 14F)
Relative Humidity (RH)
5% to 95% (non-condensing)
Dimensions (WxHxD)
80mm x 93mm x 60mm (3.15 x 3.66 x 2.362”)
Weight
150g (5.3 oz)
Mounting
Either onto a 35mm DIN-rail or screw- mounted.
Notes:
1. Each input may be set as either thermocouple, voltage (0-10V), or current (0-20mA, 4-20mA)
via wiring, jumper and software settings.
2. The device can also measure voltage within the range of -5 to 56mV, at a resolution of 0.01mV.
The device can also measure raw value frequency at a resolution of 14-bits(16384).
3. The input analog value represents the measured value as shown in the following examples:
- Thermocouple: a value of 262 is represented as 26.2ºC.
- mV: value of 262 is represented as 2.62mV.
4. The value of a thermocouple may also indicate when the sensor is not connected to the input, or
when the analog value exceeds the permissible range. If such is the case, the value will be 32767.
5. The voltage or current value of analog inputs can also indicate faults, as shown in the table below.
Value: 12-bit
(Fast mode)
Value: 14-bit
(Normal mode)
Input Value
Deviates:
-1
-1
Slightly below the input range.
4096
16384
Slightly above the input range.
32767
32767
Greatly above or below the input range.
UG_IO-ATC8 I/O Expansion Module
Unitronics Industrial Automation
11
Addressing I/Os on Expansion Modules
Inputs and outputs located on I/O expansion modules that are connected to an OPLC are assigned
addresses that comprise a letter and a number. The letter indicates whether the I/O is an input (I) or an
output (O). The number indicates the I/O’s location in the system. This number relates to both the position
of the expansion module in the system, and to the position of the I/O on that module.
Expansion modules are numbered from 0-7 as shown in the figure below.
0 1 2 3 4 5 6 7 Expansion module
identification number
Adapter
The formula below is used to assign addresses for I/O modules used in conjunction with the OPLC.
X is the number representing a specific module’s location (0-7). Y is the number of the input or output on that
specific module (0-15).
The number that represents the I/O’s location is equal to:
32 + x • 16 + y
Examples
Input #3, located on expansion module #2 in the system, will be addressed as I 67,
67 = 32 + 2 • 16 + 3
Output #4, located on expansion module #3 in the system, will be addressed as O 84,
84 = 32 + 3 • 16 + 4.
EX90-DI8-RO8 is a stand-alone I/O module. Even if it is the only module in the configuration, the EX90-DI8-
RO8 is always assigned the number 7.
Its I/Os are addressed accordingly.
Example
Input #5, located on an EX90-DI8-RO8 connected to an OPLC will be addressed
as I 149, 149 = 32 + 7 • 16 + 5
UG_IO-ATC8 I/O Expansion Module
12
Unitronics Industrial Automation
UL Compliance
The products listed above may be used with compatible Unitronics PLCs.
Detailed Installation Guides containing the I/O wiring diagrams for these models, technical specifications, and
additional documentation are located in the Technical Library in the Unitronics website:
https://unitronicsplc.com/support-technical-library/
The following section is relevant to Unitronics’ products that are listed with the UL.
The following models: IO-AI4-AO2, IO-AO6X, IO-ATC8, IO-DI16, IO-DI16-L, IO-DI8-RO4,
IO-DI8-RO4-L, IO-DI8-TO8, IO-DI8-TO8-L, IO-RO16, IO-RO16-L, IO-RO8, IO-RO8L, IO-TO16,
EX-A2X are UL listed for Hazardous Locations.
The following models: EX-D16A3-RO8, EX-D16A3-RO8L, EX-D16A3-TO16, EX-D16A3-TO16L,
IO-AI1X-AO3X, IO-AI4-AO2, IO-AI4-AO2-B, IO-AI8, IO-AI8Y, IO-AO6X, IO-ATC8, IO-D16A3-RO16,
IO-D16A3-RO16L, IO-D16A3-TO16, IO-D16A3-TO16L, IO-DI16, IO-DI16-L, IO-DI8-RO4,
IO-DI8-RO4-L, IO-DI8-RO8, IO-DI8-RO8-L, IO-DI8-TO8, IO-DI8-TO8-L, IO-DI8ACH, IO-LC1, IO-LC3,
IO-PT4, IO-PT400, IO-PT4K, IO-RO16, IO-RO16-L, IO-RO8, IO-RO8L, IO-TO16, EX-A2X, EX-RC1 are
UL listed for Ordinary Location.
UL Ratings, Programmable Controllers for Use in Hazardous Locations,
Class I, Division 2, Groups A, B, C and D
These Release Notes relate to all Unitronics products that bear the UL symbols used to mark products that
have been approved for use in hazardous locations, Class I, Division 2, Groups A, B, C and D.
Caution
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, or Non-hazardous
locations only.
Input and output wiring must be in accordance with Class I, Division 2 wiring methods and in
accordance with the authority having jurisdiction.
WARNINGExplosion Hazardsubstitution of components may impair suitability for Class I,
Division 2.
WARNING EXPLOSION HAZARD Do not connect or disconnect equipment unless power has
been switched off or the area is known to be non-hazardous.
WARNING Exposure to some chemicals may degrade the sealing properties of material used in
Relays.
This equipment must be installed using wiring methods as required for Class I, Division 2 as per
the NEC and/or CEC.
Relay Output Resistance Ratings
The products listed below contain relay outputs:
Input/Output expansion modules, Models: IO-DI8-RO4, IO-DI8-RO4-L, IO-RO8, IO-RO8L
When these specific products are used in hazardous locations, they are rated at 3A res, when these specific
products are used in non-hazardous environmental conditions, they are rated at 5A res, as given in the
product’s specifications.
UG_IO-ATC8 I/O Expansion Module
Unitronics Industrial Automation
13
Certification UL des automates programmables, pour une utilisation en environnement à
risques, Class I, Division 2, Groups A, B, C et D.
Cette note fait référence à tous les produits Unitronics portant le symbole UL - produits qui ont été certifiés
pour une utilisation dans des endroits dangereux, Classe I, Division 2, Groupes A, B, C et D.
Attention
Cet équipement est adapté pour une utilisation en Classe I, Division 2, Groupes A, B, C et
D, ou dans Non-dangereux endroits seulement.
Le câblage des entrées/sorties doit être en accord avec les méthodes
de câblage selon la Classe I, Division 2 et en accord avec l’autorité compétente.
AVERTISSEMENT: Risque d’Explosion – Le remplacement de certains composants rend caduque
la certification du produit selon la Classe I, Division 2.
AVERTISSEMENT - DANGER D'EXPLOSION - Ne connecter pas ou ne débranche pas
l'équipement sans avoir préalablement coupé l'alimentation électrique ou la zone est reconnue pour
être non dangereuse.
AVERTISSEMENT - L'exposition à certains produits chimiques peut dégrader les propriétés des
matériaux utilisés pour l'étanchéité dans les relais.
Cet équipement doit être installé utilisant des méthodes de câblage suivant la norme Class I,
Division 2 NEC et /ou CEC.
Certification de la résistance des sorties relais
Les produits énumérés ci-dessous contiennent des sorties relais:
Modules d’Extensions d'E/S, modèles: IO-DI8-RO4, IO-DI8-RO4-L, IO-RO8, IO-RO8L.
Lorsque ces produits spécifiques sont utilisés dans des endroits dangereux, ils supportent
un courant de 3A charge résistive, lorsque ces produits spécifiques sont utilisés dans un environnement non
dangereux, ils sont évalués à 5A res, comme indiqué dans les specifications du produit Plages de
températures.
The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion, and without notice, to
discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of the forgoing from the market.
All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of merchantability, fitness for a
particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in this document. In no event shall Unitronics be liable for any
special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising out of or in connection with the use or performance of this information.
The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other third parties and you are not
permitted to use them without the prior written consent of Unitronics or such third party as may own them
UG_IO-ATC8.pdf 11/22
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13

Unitronics IO-ATC8 Manuel utilisateur

Taper
Manuel utilisateur

dans d''autres langues