Operating the generator TEC29 EV
20
8.6 Display messages
Display message
Description
Generator behaviour Measures
LOW BATTERY
The battery voltage has fallen
below the minimum value for
starting up (9 V).
The generator does not start. Charge the battery.
OIL CHANGE
The number of prescribed oper-
ating hours has been reached for
changing the engine oil.
The generator continues to run. Change the oil (see chapter
“Changing the oil (fig. 7,
page 6)” on page 26), then
restart the generator by pressing
and holding down the start but-
ton.
NO FUEL
The fuel in the tank is in reserve.
The generator continues to run. Refuel.
OIL ALERT
Insufficient engine oil.
The generator stops. Fill up with oil (see chapter
“Checking the oil level” on
page 21).
GENERATOR ALERT!
General alarm message
Example: The control ring on the
throttle valve of the carburettor
(stepper motor) is faulty.
The generator stops. Check the system by referring to
the troubleshooting table.
If the problem persists, contact
the manufacturer's branch office
in your country (addresses on the
back page).
OVERLOAD!
The consumers generate an
overload at the output.
The inverter switches off, there-
fore no voltage is supplied but
the engine carries on running
until it goes off.
Reduce the connected load and
start the generator again.
SHORT CIRCUIT
The consumers cause a short cir-
cuit at the output.
The inverter switches off, there-
fore no voltage is supplied but
the engine carries on running
until it goes off.
Check the connected consum-
ers then start the generator
again.
OVER TEMPERATURE
Overheating
The inverter switches off so no
voltage is supplied to cool the
generator, but the engine car-
ries on running.
Leave the engine to cool down
for a few minutes then start the
generator again.
LOW POWER ENGINE
The inverter supply voltage has
dropped.
The generator stops. Reduce the connected load and
start the generator again.