Haier AD07SL2VHA Installation Instructions Manual

Catégorie
Climatiseurs split-system
Taper
Installation Instructions Manual

Ce manuel convient également à

31-5000099 08-19 GEA
Design may vary by model number. L’aspect peut varier selon le numéro de modèle. El diseño puede variar según el número de model.
Installation Instructions
Indoor Unit Installation
Slim Duct
2
31-5000099
This manual contains installation instructions for Slim Duct indoor units. For
the FlexFit series using other style indoor units, refer to the Installation Manual
supplied with the indoor unit.
31-5000099 3
Table of Contents
IMPORTANT SAFETY INFORMATION ..............................................................4
INSTALLATION INSTRUCTIONS ..................................................................5
Step 1 ....................................................................................8
Step 2 ....................................................................................9
Step 3 ...................................................................................13
Step 4 ..................................................................................16
LIMITED WARRANTY ......................................................................... 18
4
31-5000099
IMPORTANT SAFETY INFORMATION
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE
READ AND SAVE THESE INSTRUCTIONS
WARNING
For your safety, the information in this manual must be followed to minimize the risk of
fire, electric shock, or personal injury.
Use this equipment only for its intended purpose as
described in this manual.
This heat pump must be properly installed in
accordance with these instructions before it is used.
All wiring should be rated for the amperage value
listed on the rating plate. Use only copper wiring.
All electrical work must be completed by a qualified
electrician and completed in accordance with local and
national building codes.
Any servicing must be performed by a qualified
individual.
All air conditioners contain refrigerants, which
under federal law must be removed prior to product
disposal. If you are getting rid of an old product
with refrigerants, check with the company handling
disposal.
These R-410A heat pumps systems require that
contractors and technicians use tools, equipment and
safety standards approved for use with this refrigerant.
DO NOT use equipment certified for R22 refrigerant
only.
WARNING
RISK OF ELECTRIC SHOCK. Could cause injury or death.
An adequate ground is essential before connecting
the power supply.
Disconnect all connected electric power supplies
before servicing.
Repair or replace immediately all electrical wiring that
has become frayed or otherwise damaged. Do not
use wiring that shows cracks or abrasion damage
along its length or at either end.
WARNING
RISK OF FIRE. Could cause injury or death.
Do not store or use combustible materials, gasoline or
other flammable vapors or liquids in the vicinity of this
or any other appliance.
For any service which requires entry into the
refrigerant sealed system, Federal regulations
require that the work is performed by a technician
having a Class II or Universal certification.
31-5000099 5
Installation Instructions
FOR MORE HELP, VISIT HAIERAPPLIANCES.COM/DUCTLESS OR GEAPPLIANCES.COM/DUCTLESS
BEFORE YOU BEGIN
Read these instructions completely and carefully.
IMPORTANT – Save these
instructions for local inspectors use.
IMPORTANT – Observe all governing
codes and ordinances.
Note to installer – Be sure to leave these
instructions with the owner.
Note to consumer – Keep these instructions for
future reference.
Skill level – A licensed certified technician (to
handle refrigerant R-410A, recovery, etc) and a
qualified electrician are required for installation and
service of this split heat pump system.
Use team lift for mounting the ducted unit.
Proper installation is the responsibility of the
installer.
Product failure due to improper installation is not
covered under the limited warranty.
For personal safety, this system must be properly
grounded.
Protective devices (fuses or circuit breakers)
acceptable for installation are specified on the
nameplate of each unit.
Make sure to avoid wiring or plumbing inside the
wall when installing.
CAUTION
Aluminum building wiring may present special
problems - consult a qualified electrician.
When the unit is in the STOP position, there is still
voltage to the electrical controls.
6
31-5000099
Installation Instructions: List of Materials
Required Tools for Installation
Supplied with Unit
Supplied by Installer
• 17mm, 22mm, 26mm or Adjustable Wrench
• #2 Phillips Screwdriver
• Drill
• R-410A Approved Flaring Tool
• Hex Wrench
• Hole Saw 2 1/4”
• Level
• Manifold Gauge
• Measuring Tape
• Micron Gauge
• Mini-Split Adapter (5/16”F to 1/4”M)
• Nitrogen*
• Pipe Cutter
• Razor Knife
• Reamer
• Sealant, non-expanding (for lineset hole)
• Soap/water solution or gas leakage detector
• Stud Finder
• Torque Wrench and Back-up Wrench
• Vacuum Pump
• Wire Strippers
• Refrigerant Scale
• Usual and customary HVAC hand tools
• Condensate connecting tube
• Clamp
• Flare nuts (2)
• YR-E17 wired controller
• 15 ft cable
• Insulation
• Insulated copper tubing • 14/4 (14 gauge – 4 conductor) stranded cable
• 3/4 inch PVC for condensate
• Insulation for condensate drain
• 3/8 threaded rod, washers and nuts
• 410A Refrigerant
Model Liquid (inch) Vapor (inch)
AD07SL2VH(A)/(B) 1/4 3/8
AD09SL2VH(A)/(B) 1/4 3/8
AD12SL2VH(A)/(B) 1/4 3/8
AD18SL2VH(A)/(B) 1/4 1/2
AM24LP2VHA 3/8 5/8
AM36LP2VHA 3/8 5/8
AM48LP2VHA 3/8 5/8
31-5000099 7
Installation Instructions: Introduction and Overview
Ducted Product Information
The ducted indoror unit is shipped with a wired remote
controller.
The Ducted unit will install above the ceiling or in a
soffit area. It is mounted using threaded rods that fit
into brackets that are located at all four corners of the
Ducted assembly.
The slim duct unit has a built-in condensate pump
and a float switch to avoid overflow situation and
maintaining reliable operation. An insulated condensate
fitting is included in the accessory pouch. This fitting
connects the condensate drain outlet of the unit to the
field-supplied drain piping.
When making refrigerant line connections, always use
the flare nuts provided with this equipment. Refrigerant
line connections should be wrapped with insulating tape
at the slim duct indoor unit to prevent sweating
YR-E17 Wired Controller
See wired controller manual
for more information
8
31-5000099
Installation Instructions: Introduction and Overview
Condensate Handling
The Ducted unit has a built-in condensate pump
and water level safety switch. There are also two
optional ports for gravity drainage. The condensate
pump is rated to lift water up to 27” from the point
of discharge on the Ducted unit. (This number may
vary.)
The Ducted unit comes with a grey connection hose
and clamp. This hose is connected to the Ducted
unit condensate discharge hose port. The other end
of the hose is sized to accept 3/4 inch PVC piping.
Recommended condensate piping configurations are
shown here:
Electrical Power
Follow all local codes and regulations when installing
electrical wiring.
Route required electrical power to area where the
Ducted unit is to be located. Maintain at least a 10 foot
separation between TV, Radio or any communication
wiring and the power to the indoor unit.
14 Gauge stranded copper wire should be used to
make the electrical connection and communication link
between indoor and outdoor units.
The wiring is connected at the indoor unit electrical
terminal blocks screws 1, 2, 3 and ground. There
should be no splices in the wires between the indoor
and outdoor units as these serve as communication
signal wires and electrical power connections. Any
accessory added to shut off power to the indoor
section should break the Number 2 terminal only.
Air Delivery Clearances
Make certain to maintain proper clearances around the
Ducted unit.
Inadequate clearances can cause system freezing and
temperature control problems.
Service and Maintenance Clearances
Make sure there are adequate clearances for future
maintenance and service. Allow enough room to
access the condensate pump assembly and the
electrical control box.
12 in. below
3-5 ft.
11 in. under
8.6 in.
8.6 in.
19.6 in. below
31-5000099 9
MINIMUM CLEARANCES (Appearance may vary)
This picture is for reference only. Your product may look different.
Installation Instructions
Step 1 - Preparation
A. Procedure for selecting the location:
• Place above the ceiling or in soffit area where you
have enough space to position the unit.
• Place where the drainage pipe can be properly
positioned.
• Place where the inlet and outlet air of the indoor unit
will not be blocked.
• Do not install the unit in a place with heavy oil or
moisture (e.g. - kitchens and workshops)
• Do not install in a location with destructive gas (such
as sulfuric acid gas) or pungent gas (thinner and
gasoline) are used or stored.
• Choose a place solid enough to bear the weight and
vibration of the unit and where the operation noise will
not be amplified.
• The unit in a location which will not adversely
affect occupants, building components, or valuable
possessions.
• Leave enough space for maintenance.
• Install at least 3 ft. away from sources that may create
electronic interference.
NOTES:
R-410A refrigerant is a safe, nontoxic and
nonflammable refrigerant. However, if there is a
concern about refrigerant concentration in the case
of leakage, add extra ventilation.
B. Rod Mounting Information:
The Ducted unit should be mounted to the building
structure using threaded rods. The threaded rods
should have washers and nuts to allow the height
and level of the Ducted unit to be adjusted.
The threaded rods and attachment brackets are field
supplied items. The materials required for mounting
to the brackets on the Ducted unit include:
4- 3/8” Threaded Rods
4- Mounting Brackets
Washers
Nuts (Double shown in step 2C)
Model A - Inches (mm) B - Inches (mm)
AD07SL2VHA 35 1/8 (892) 14 1/2 (369)
AD07SL2VHB 35 1/8 (892) 14 1/2 (369)
AD09SL2VHA 35 1/8 (892) 14 1/2 (369)
AD09SL2VHB 35 1/8 (892) 14 1/2 (369)
AD12SL2VHA 35 1/8 (892) 14 1/2 (369)
AD12SL2VHB 35 1/8 (892) 14 1/2 (369)
AD18SL2VHA 47 3/4 (1213) 14 1/2 (369)
AD18SL2VHB 47 3/4 (1213) 14 1/2 (369)
AM24LP2VHA 39 (990) 23 1/2 (595)
AM36LP2VHA 61 1/4 (1556) 25 3/4 (653)
AM48LP2VHA 61 1/4 (1556) 25 3/4 (653)
Air Flow
> 12 in
> 12 in
> 12 in
> 6 in
B
A
10
31-5000099
Installation Instructions
F. Connect the grey flexible drain hose supplied with
the Ducted unit to the condensate pump discharge
pipe of the Ducted unit. Tighten the clamp securely.
Using 3/4 “ PVC, connect the flexible hose to the
building’s condensate drain system.
Step 2 - Installation of the Slim Duct Unit
A. Determine and mark the position of where the
Ducted unit is to be installed. Install the hardware
necessary to mount the threaded rods. Always
select a location strong enough to support the Slim
Duct unit.
B. Install threaded rods to the hardware attached to
the structure.
D. Using a level, adjust the nuts on the threaded rods
to obtain level readings both side to side and front
to back on the Ducted unit.
C.
Lift the Ducted unit and position the threaded rods
into the 4 mounting clips, one located on each corner
of the unit.
E.
Ream both inside and outside of the refrigerant
tubing where a cut has been made. Use every
precaution to ensure reamed copper chips not to
lodge inside the tubing.
Install the factory-supplied flare nuts on the
refrigerant tubing using an R-410A flaring tool
ONLY. Apply a small amount of refrigerant oil to
the back of the flare and threads.
Tighten the flares with a torque wrench and back-
up wrench to the specifications found in the outdoor
unit Installation Manual.
31-5000099 11
Step 2 - Installation of the Slim Duct Unit (Cont.)
G. Route the 14AWG stranded 4 conductor power/
communication cable and the wired remote
cable to the air handler. Use reducing washers
and appropriate connector to attach the power/
communication cable to the unit. The wired remote
cable will enter the unit through a rubber grommet.
The 4 conductor cable connects to the terminal block
at terminals 1, 2, 3, and ground. The wired remote
cable connects to the air handler main board at
connector CN1. Re-install electrical box cover.
Installation Instructions
H. The unit is now ready for connection to the
ductwork. The return air duct can be configured
as either a rear inlet or bottom inlet.
Rear side air inlet
Bottom side air inlet
Diffuser
Return Duct
Diffuser
Return Duct
12
31-5000099
Installation Instructions
Step 3 - Electrical Connections
Step 4 - Leak Testing and Evacuation
Electrical Connections Indoor and Outdoor Units
14AWG stranded copper wire only. (Central Controller Not Used)
Maintain 10 feet of distance from TV, Radio or any communication wiring.
NOTE: The Slim Duct unit ships with the YR-E17 wired controller. SeeWired Controller
manual for more information..
Refer to the outdoor section Installation Manual for the recommended procedure.
Outdoor unit
3
2
Power
Wiring
1
)
(
N
)
(L
)
(
C
3
2
1
)
(
N
)
(
L
)
(
C
Indoor unit
3wire 14AWG
Control Wiring
31-5000099 13
Limited Warranty
Staple your receipt here. Proof of the original purchase
date is needed to obtain service under the warranty.
Damage from improper installation.
Damage in shipping.
Defects other than from manufacturing (i.e.,
workmanship or materials).
Damage from misuse, abuse, accident, alteration, lack
of proper care and/or regular maintenance, or incorrect
electrical voltage or current.
Damage resulting from floods, fires, wind, lightning,
accidents or similar conditions.
Damage from installation or other services performed
by other than a licensed HVAC technician.
Labor and related services for repair or installation of
the Product.
A Product purchased from an online retailer.
Damage as a result of subjecting Product to an
atmosphere with corrosives or high levels of
particulates (such as soot, aerosols, fumes, grease).
A Product sold and/or installed outside of the 50 United
States, the District of Columbia, or Canada.
Batteries for the controller and other accessories
provided with the Product for installation (e.g., plastic
hose).
Normal maintenance, such as cleaning of coils, cleaning
filters, and lubrication.
For Product installed in non-owner occupied
applications, Product that has not been maintained
annually by a licensed HVAC technician (proof required).
For The Period Of: GE Appliances, a Haier company Will Replace:
5 year limited parts
warranty
From the date of the
original purchase
This limited warranty cover all defects in workmanship or material for the mechanical and
electrical parts contained in the Product (“Defective Parts”) for a period of 5 years from the
Date of Purchase. Haier will provide new or refurbished parts, or a replacement for all or part
of the unit, at its sole discretion, to your licensed HVAC technician installer. This warranty also
covers all defects in workmanship or material for the unit controller for a period of 1 year. The
remote controller is covered by 1-year accessory warranty. The ductless system is covered
by standard warranty. Haier will provide a new or refurbished controller, at its sole discretion.
7 year compressor
warranty
from the date
of the original purchase
The compressor contained in this product is warrantied for a period of 7 years from the Date
of Purchase. Haier will provide a new or refurbished compressor, or a replacement for all or
part of the unit, at its sole discretion, to your licensed HVAC technician installer.
For the product models listed on Attachment 1 (the “Product”), this Standard Limited Warranty is provided to the Original
Owner of the Product:
WHAT IS THE DATE OF PURCHASE
WHO IS COVERED
HOW CAN YOU GET SERVICE
THIS WARRANTY DOES NOT COVER
The “Date of Purchase” is the date that the original installation is complete and all product start-up procedures have
been properly completed and verified by the installer’s invoice. If the installation date cannot be verified, then the
Date of Purchase will be sixty (60) days after the manufacture date, as determined by the Product’s serial number. You
should keep and be able to provide your original sales receipt from the installer as proof of the Date of Purchase. In new
construction, the Date of Purchase will be the date the owner purchased the residence from the builder.
Contact your licensed HVAC technician installer. All installation and service must be performed by a licensed HVAC
technician. Failure to use a licensed HVAC technician for installation of this Product voids all warranty on this Product..
Owner occupied: The “Original Owner” of this product, which means the original owner (and his or her spouse) of the
residence where the Product was originally installed. Subject to the law of the state or province where the Product is
installed, this warranty is not transferable to subsequent owners or if the product is moved to a different residence after
the initial installation. Non-owner occupied: This limited warranty is provided for product 1) installed in a) single family
or multi-family non-owner occupied residential buildings, or b) non-industrial commercial applications, (such as office
buildings, retail establishments, hotels/motels) where the product is not subjected to an atmosphere with corrosives or
high levels of particulates (such as soot, aerosols, fumes, grease), and 2) if the product is maintained annually by a licensed
HVAC technician (proof of annual maintenance is required). The “Original Owner” of the product, means the original
owner of the building where the product was originally installed. For new construction, the purchaser of the building
from the builder will also be considered an original owner. This warranty is not transferable to subsequent owners or if the
product is moved to a different location after the initial installation.
14
31-5000099
10 YEAR STANDARD REGISTERED LIMITED WARRANTY
ATTACHMENT 1
THIS LIMITED WARRANTY IS GIVEN IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING
THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
All “Indoor and Outdoor Products,” identified in Attachment 1, registered by the installer or the Original Owner within 60
days of the Date of Purchase shall receive a Standard Registered Limited Warranty, which shall be identical to the Standard
Base Warranty, except that the Limited Parts Warranty shall be for a term of 10 Years and the Limited Compressor Warranty
shall be for a term of 10 years. All Product not registered within 60 days of the Date of Purchase shall be subject to the
Standard Base Warranty. Some states and provinces do not allow warranty terms to be subject to registration; in those
states and provinces the longer terms for Limited Parts Warranty and the Limited Compressor Warranty apply.
The remedy provided in this warranty is exclusive and is granted in lieu of all other remedies. This warranty does not cover
incidental or consequential damages. Some states and provinces do not allow the exclusion of incidental or consequential
damages, so this limitation may not apply to you. Some states and provinces do not allow limitations on how long an implied
warranty lasts, so this limitation may not apply to you. This warranty gives you specific legal rights and you may also have
other rights which vary by state and province. This warranty covers units within the 50 United States, the District of Columbia
and Canada. This warranty it provided by GE Appliances a Haier company, Louisville, KY 40225.
The “Product” is defined as Haier brand Ductless Split Units. The “Product” contains 2 sub-categories of goods: “Indoor and
Outdoor Products” and “Selected Installation Products,” which are further defined below: “Indoor and Outdoor Products”
can further be identified by the following model number descriptions: 1U*, 2U*, 3U*, 4U*, AB*, AD*, AL*, AM*, AW*, AF*,
MVA* MVH* “Selected Installation Products,” identified by the following model number descriptions: PB-* FQG-*, AH1-*,
MS1-* and MS3-*
Limited Warranty
31-5000099 15
Table des matières
CONSIGNES DE SÉCURITÉ IMPORTANTES ...................................................... 22
INSTRUCTIONS D’INSTALLATION .............................................................. 23
Étape 1 ................................................................................. 27
Étape 2 ................................................................................. 28
Étape 3 ................................................................................. 31
Étape 4 ................................................................................ 34
GARANTIE LIMITÉE .......................................................................... 35
16
31-5000099
CONSIGNES DE SÉCURITÉ IMPORTANTES
LISEZ TOUTES LES INSTRUCTIONS AVANT D’UTILISER L’APPAREIL
AVERTISSEMENT
Pour votre sécurité, les renseignements dans ce manuel doivent être observés afin de
minimiser le risque d’incendie, de décharge électrique ou de blessure.
Utilisez cet équipement uniquement aux fins auxquelles il
est fait mention dans ce manuel d’utilisation.
Avant son utilisation, ce climatiseur doit être installé
correctement en conformité avec les instructions
d’installation.
Tout le câblage doit présenter des valeurs nominales
compatibles avec l’alimentation électrique spécifiée sur la
plaque signalétique. Utilisez seulement du fil de cuivre.
Toute la partie électrique de l’installation doit être exécutée
par un électricien agréé selon les codes de l’électricité local
et national.
Toute réparation doit être effectuée par une personne
qualifiée.
Tous les climatiseurs contiennent un frigorigène qu’il
faut retirer avant de disposer du produit en vertu de la
loi fédérale. Si vous vous débarrassez d’un produit qui
contient un frigorigène, informez-vous auprès de l’organisme
responsable d’en disposer.
Ces systèmes de climatisation R-410A exigent que les
entrepreneurs et les techniciens utilisent des outils, des
équipements et des normes de sécurité approuvés pour ce
type de frigorigène. N’utilisez PAS un équipement certifié
pour le frigorigène R22 seulement.
AVERTISSEMENT
RISQUE DE CHOC ÉLECTRIQUE. Peut occasionner une blessure ou la mort.
Une mise à la terre est essentielle avant de brancher
l’alimentation électrique.
Coupez l’alimentation électrique à la source avant de
procéder à une réparation ou un entretien.
Réparez ou remplacez immédiatement tout câblage électrique
usé ou autrement endommagé. N’utilisez pas un câblage
qui présente des fissures ou des marques d’abrasion sur sa
longueur ou l’une de ses extrémités.
AVERTISSEMENT
RISQUE D’INCENDIE. Peut occasionner une blessure ou la mort.
Abstenez-vous d’entreposer ou d’utiliser des matières
combustibles, de l’essence ou d’autres vapeurs ou liquides
inflammables à proximité de cet appareil ou de tout autre.
LISEZ ET CONSERVEZ CES INSTRUCTIONS
Si une réparation exige de pénétrer dans le
système de frigorigène étanche, la réglementation
fédérale impose de faire réaliser le travail par
un technicien de Classe II ou détenant une
certification universelle.
31-5000099 17
Instructions d’installation
POUR OBTENIR DE L’AIDE SUPPLÉMENTAIRE, VISITEZ HAIERAPPLIANCES.COM/DUCTLESS OU
GEAPPLIANCES.COM/DUCTLESS
AVANT DE COMMENCER
Veuillez lire toutes ces instructions attentivement.
IMPORTANT – Conservez ces
instructions à l’usage de l’inspecteur local.
IMPORTANT – Observez tous les
codes et ordonnances en vigueur.
Note à l’installateur – Assurez-vous de laisser ces
instructions au propriétaire.
Note au consommateur - Conservez ces instructions
pour référence ultérieure.
Niveau de compétence – Un technicien (pour manipuler
le frigorigène R-410A, récupération, etc.) et un électricien
agréés sont requis pour l’installation y servicio de ce
climatiseur à deux blocs.
Utilisez le lève-personne pour monter l’unité canalisée
L’exactitude de l’installation est la responsabilité de
l’installateur.
La garantie ne couvre pas les défectuosités du produit
causées par une installation inadéquate.
Pour votre sécurité, ce produit doit être correctement mis
à la terre.
Les dispositifs de protection (fusibles ou disjoncteurs)
admissibles pour l’installation sont spécifiés sur la plaque
signalétique de chaque unité.
. • Si une réparation exige de pénétrer dans le système de
frigorigène étanche, la réglementation fédérale impose
de faire réaliser le travail par un technicien de Classe II
ou détenant une certification universelle.
ATTENTION
N’utilisez pas un cordon de rallonge avec ce système.
Le câblage de bâtiment en aluminium peut présenter
des problèmes particuliers, veuillez consulter un
électricien agréé.
18
31-5000099
Instructions d’installation: Liste du matériel
Outils nécessaires pour l’installation
Fourni avec l’appareil
Fourni par l’installateur
• Clé 17 mm, 22 mm, 26 mm ou clé réglable
• Tournevis à tête cruciforme no 2
• Perceuse
• Outil à évaser approuvé pour R-410A
• Clé hexagonale
• Scie-cloche 2 1/4 po
• Niveau
• Manomètre de pression d’admission
• Ruban à mesurer
• Microvacuomètre
• Adaptateur « mini-split » (5/16 po F à 1/4 po M)
• Azote*
• Coupe-tube
• Couteau utilitaire
• Alésoir
• Scellant, non expansif (pour trou de tubulure)
• Solution d’eau savonneuse ou détecteur de fuite de
gaz
• Localisateur de montants
• Clé dynamométrique et clé d’appoint
• Pompe à vide
• Pinces à dénuder
• Balance de réfrigérant
• Outils manuels habituels en CVC
• Tube de raccord pour condensat
• Bride
• Raccords coniques (2)
• Commande câblée YR-E17
• Câble 15 pi (4,6 m)
• Isolant
• Tuyau de cuivre isolé • Câble toronné 14/4 (calibre 14 – 4 conducteurs)
• PVC 3/4 po pour condensat
• Isolant pour drain à condensat
• Tige filetée 3/8, rondelles et écrous
• Frigorigène 410A
Modèle Liquide (po) Vapeur (po)
AD07SL2VH(A)/(B) 1/4 3/8
AD09SL2VH(A)/(B) 1/4 3/8
AD12SL2VH(A)/(B) 1/4 3/8
AD18SL2VH(A)/(B) 1/4 1/2
AM24LP2VHA 3/8 5/8
AM36LP2VHA 3/8 5/8
AM48LP2VHA 3/8 5/8
31-5000099 19
Instructions d’installation:
Introduction et vue d’ensemble
Informations sur le produit à conduits
L’unité intérieure à conduits est livrée avec une
commande à distance câblée.
L’unité à conduits sera installée au-dessus du plafond
ou dans une zone de soffite. Elle est montée avec des
tiges filetées qui se placent dans des supports situés à
tous les quatre coins de l’assemblage à conduits.
L’unité à conduits étroits comporte une pompe à
condensat intégrée et un interrupteur à flotteur pour
éviter les débordements et maintenir un fonctionnement
fiable. Un raccord pour condensat isolé est inclus dans
la trousse d’accessoires. Ce raccord connecte la sortie
du condensat de l’unité au tuyau de vidange acheté
localement.
Lors de la réalisation des raccordements de la conduite
de réfrigérant, utilisez toujours les raccords coniques
fournis avec cet équipement. Les raccords de la
conduite de réfrigérant doivent être enveloppés du
ruban isolant au niveau de l’unité intérieure à conduits
étroits afin de prévenir le suintement.
Commande câblée YR-E17
Consultez le manuel de la
commande câblée pour des
renseignements supplémentaires.
20
31-5000099
Instructions d’installation:
Introduction et vue d’ensemble
Gestion du condensat
L’unité à conduits comporte une pompe à condensat
intégrée et un interrupteur de sécurité du niveau
d’eau. Elle est aussi dotée de deux orifices facultatifs
pour l’évacuation par gravité. La pompe à condensat
est homologuée pour monter l’eau jusqu’à 27 po (68,6
cm) depuis le point d’évacuation sur l’unité à conduits.
(Ce chiffre peut varier.)
L’unité à conduits est livrée avec un flexible de
raccordement gris et une bride. Ce flexible est
raccordé à l’orifice pour flexible d’évacuation du
condensat de l’unité à conduits. L’autre extrémité du
flexible est dimensionnée pour accepter un tuyau PVC
de 3/4 po.
Les configurations de tuyauterie du condensat
recommandées sont indiquées ici:
Alimentation électrique
Suivez tous les codes et règlements locaux lorsque
vous installez le câblage électrique.
Acheminez l’alimentation électrique requise vers
la zone où l’unité à conduits est située. Maintenir
au moins une séparation de 10 pi (3 m) entre le
câblage de la télévision, la radio ou tout câblage de
communication et l’alimentation à l’unité intérieure.
Un câble toronné en cuivre de calibre 14 doit être
utilisé pour effectuer les connexions électriques et le
lien de communication entre les unités intérieure et
extérieure.
Le câblage est connecté au vis 1, 2, 3 du bornier de
l’unité intérieure et à la terre. Il ne doit pas y avoir
d’épissures dans les fils entre les unités intérieure
et extérieure car ils acheminent les signaux de
communication et l’alimentation électrique. Tout
dispositif ajouté pour couper le courant à la section
intérieure doit couper la borne numéro 2 seulement.
Dégagements pour la circulation d’air
Assurez-vous de maintenir les dégagements
appropriés autour de l’unité à conduits.
Des dégagements inappropriés peuvent causer le
gel du système et des problèmes de contrôle des
températures.
Dégagements pour réparation et entretien
Assurez-vous de procurer les dégagements
appropriés pour l’entretien et les réparations à venir.
Allouez suffisamment d’espace pour accéder à la
pompe de condensat et au boîtier de commandes
électriques.
12 in. below
3-5 ft.
11 in. under
8.6 in.
8.6 in.
19.6 in. below
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38

Haier AD07SL2VHA Installation Instructions Manual

Catégorie
Climatiseurs split-system
Taper
Installation Instructions Manual
Ce manuel convient également à

dans d''autres langues