Simplicity 040486-00 Manuel utilisateur

Catégorie
Groupes électrogènes
Taper
Manuel utilisateur
16 Circuit 100 Amp
Automatic Transfer Switch
with AC Control Module™
Installation and Operator’s Manual
Copyright © Briggs & Stratton Corporation
Milwaukee, WI USA. All Rights Reserved.
209963
Revision E
2 BRIGGSandSTRATTON.COM
Thank you for your purchase of this Briggs & Stratton® automatic transfer switch. This product is designed for use with
specific home standby generators and may not function with generators produced by other manufacturers. Seek a qualified
electrical professional to determine applicability of this equipment to generators manufactured by others. When operated
and maintained according to the instructions in this manual, your power management system will provide many years of
dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with this system and how to
avoid them. We have made every effort to provide for a safe, streamlined and cost-effective installation. As each installation
is unique, it is impossible to know of and advise of all conceivable procedures and methods by which installation might be
achieved. We do not know all possible hazards and/or the results of each possible method or procedure. It is important that
you read and understand these instructions thoroughly before attempting to install or operate this equipment. Save these
instructions for future reference.
This transfer switch requires professional installation before use. Refer to the Installation section of this manual for
instructions on installation procedures. Only licensed electrical contractors should install transfer switches. Installations must
strictly comply with all applicable federal, state and local codes, standards and regulations. Your installer should follow the
instructions completely.
Where to Find Us
You never have to look far to find Briggs & Stratton support and service for your system. Consult your Yellow Pages.
There are many authorized service dealers who provide quality service. You can also contact Technical Service by phone at
800743-4115 between 8:00 AM and 5:00 PM CT, or use the Service Center Locator at BRIGGSandSTRATTON.COM, which
provides a list of authorized dealers.
For Future Reference
Please fill out the information below and keep with your receipt to assist in unit identification for future purchase issues.
Transfer Switch
Model Number
Revision
Serial Number
Date Purchased
33
Table of Contents
Important Safety Instructions........................4
Installation ....................................5
Owner Orientation ............................................5
Installing Dealer/Contractor Responsibilities ........................5
Essential Circuit Identification ...................................6
Mounting Guidelines ..........................................7
System Setup...............................................10
Controls ..................................... 11
Operation .................................... 11
Testing the Automatic Transfer Switch ...........................12
Maintenance .................................. 13
Troubleshooting................................ 14
Schematic Diagram ..........................................15
Wiring Diagram .............................................16
Product Specifications ........................... 17
4 BRIGGSandSTRATTON.COM
Important Safety Instructions
SAVE THESE INSTRUCTIONS - This manual contains
important instructions that should be followed during
installation and maintenance of the equipment.
Safety Symbols and Meanings
The safety alert symbol indicates a potential personal
injury hazard. A signal word (DANGER, WARNING, or
CAUTION) is used with the alert symbol to designate a
degree or level of hazard seriousness. A safety symbol
may be used to represent the type of hazard. The signal
word NOTICE is used to address practices not related to
personal injury.
DANGER indicates a hazard which, if not avoided, will
result in death or serious injury.
WARNING indicates a hazard which, if not avoided, could
result in death or serious injury.
CAUTION indicates a hazard which, if not avoided, could
result in minor or moderate injury.
NOTICE addresses practices not related to personal injury.
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard. The warnings in
this manual, and the tags and decals affixed to the unit are,
therefore, not all-inclusive. If you use a procedure, work
method or operating technique that the manufacturer does
not specifically recommend, you must satisfy yourself that
it is safe for you and others. You must also make sure that
the procedure, work method or operating technique that you
choose does not render the equipment unsafe.
Electrical Shock Read Manual
Save These Instructions
WARNING Only qualified electricians should attempt
installation of this equipment, which must strictly comply
with applicable codes, standards and regulations.
WARNING Certain components in this product and
related accessories contain chemicals known to the State
of California to cause cancer, birth defects, or other
reproductive harm. Wash hands after handling.
WARNING Low voltage wire cannot be installed in
same conduit as power voltage wiring.
Failure to follow above warning could cause personal
injury, damage and/or malfunction of equipment.
WARNING Failure to properly ground equipment can
result in electrocution.
Do not touch bare wires.
Do not use equipment with worn, frayed, bare or
otherwise damaged wiring.
Do not handle electrical cords while standing in water,
while barefoot, or while hands or feet are wet.
If you must work around a unit while it is operating, stand
on an insulated dry surface to reduce shock hazard.
Do not allow unqualified persons or children to operate or
service equipment.
In case of an accident caused by electrical shock,
immediately shut down all sources of electrical power
and contact local authorities. Avoid direct contact with
the victim.
WARNING Equipment contains high voltage that can
cause personal injury or death.
Despite the safe design of the system, operating this
equipment imprudently, neglecting its maintenance or
being careless can cause possible injury or death.
NOTICE Improper treatment of equipment can damage it
and shorten its life.
Use equipment only for intended uses.
If you have questions about intended use, ask dealer or
contact Briggs & Stratton Power Products.
Do not expose equipment to excessive moisture, dust,
dirt, or corrosive vapors.
Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
If connected devices overheat, turn them off and turn off
their circuit breaker/fuse.
5
Installation
We sincerely appreciate your patronage. For this reason,
we have made significant effort to provide for a safe,
streamlined and cost-effective installation. Because each
installation is unique, it is impossible to know of and advise
the trade of all conceivable procedures and methods by
which installation might be achieved. Neither could we know
of possible hazards and/or the results of each method or
procedure. For these reasons,
Only current licensed electrical professionals should
attempt system installations. Installations must strictly
comply with all applicable codes, industry standards
andregulations.
Your equipment is supplied with this combined “Installation
and Operator’s Manual”. This is an important document and
should be retained by the owner after the installation has
been completed.
Every effort has been made to make sure that the information
in this manual is both accurate and current. However, the
manufacturer reserves the right to change, alter or otherwise
improve the system at any time without prior notice.
Home Owner Responsibilities
To help you make informed choices and communicate
effectively with your installation contractor(s),
Read and understand Owner Orientation before contracting
or starting your equipment installation.
To arrange for proper installation, contact the store at which
you purchased your equipment, your dealer, or your utility
power provider.
The equipment warranty is VOID unless the system is
installed by licensed electrical professionals.
Owner Orientation
The illustrations provided are for typical circumstances and
are meant to familiarize you with the installation options
available with your system.
Local codes, appearance, and distances are the factors that
must be considered when negotiating with an installation
professional. As the distance from the existing electrical
service increases, compensation in wiring materials must
be allowed for. This is necessary to comply with local codes
and overcome electrical voltage drops.
These factors will have a direct effect on the overall price
of your equipment installation.
Your installer must check local codes AND obtain permits
before installing the system.
Read and follow the instructions given in this manual.
Follow a regular schedule in caring for and using your
equipment, as specified in this manual.
Installing Dealer/Contractor Responsibilities
Read and observe the safety rules.
Read and follow the instructions given in this manual.
Consult with home generator owner(s) to discuss their
selection of “Essential Circuits”.
The installer may need to provide appropriate rated
contactors based on loads to be controlled.
Check federal, state and local codes and authority
having jurisdiction, for questions on installation.
Ensure generator is not overloaded with selected loads.
If you need more information about the transfer switch, call
800743-4115, between 8:00 AM and 5:00 PM CT.
Equipment Description
The transfer switch is designed to transfer the selected loads
found in normal residential installations when used with the
supervisory contacts provided. The load is connected either
to utility power (normal) or home standby power (generator).
The transfer switch monitors utility and generator voltages
and will automatically connect to the appropriate source
ofpower.
This switch makes it easy for a licensed electrician to
complete a home standby installation. The transfer switch
contains an automatic transfer switch and control circuitry,
and up to 16 essential branch circuit breakers, all in
oneenclosure.
Major components of the transfer switch are a 2 pole
double throw transfer switch, control circuit board, fused
utility terminals, branch circuit breakers and bus, and
interconnecting wiring. The control board also has two
inputs for current transformers that sense generator current.
These components are housed in a NEMA 3R enclosure that
is suitable for both indoor and outdoor installations.
The transfer switch is solenoid-operated from utility or
generator inputs and contain suitable mechanical and
electrical interlock switches to eliminate the possibility of
connecting the utility service to the generator output. It
has ratings capable of switching full utility power into the
essential circuits. In addition, a manual override lever is
provided for the transfer function.
The control board has active circuits sensing utility and
generator voltages. It creates a signal for generator start-up,
switch transfer and retransfer when utility is restored. The
control board also contains red and green LED’s indicating
the power sources available and two relay operated contacts
that provide supervisory control of external loads.
6 BRIGGSandSTRATTON.COM
Delivery Inspection
After opening the carton, carefully inspect the transfer
switch components for any damage that may have occurred
duringshipment.
If loss or damage is noted at time of delivery, have the
person(s) making delivery note all damage on the freight bill
and affix his signature under the consignor’s memo of loss
or damage. If loss or damage is noted after delivery, contact
the carrier for claim procedures. Missing or damaged parts
are not warranted.
Shipment contents
Automatic transfer switch (1)
Full complement of branch circuit breakers
Installation and operator’s manual (1)
Current transformers (2)
To be supplied by installer:
Connecting wire and conduit
Various specialty tools/equipment
Essential Circuit Identification
Essential electrical loads are loads that will be powered by
the home generator. Essential loads are grouped together
and wired into the transfer switch.
TO THE INSTALLER: Consult with home generator owner(s)
to discuss their selection of “Essential Circuits”, as described
in the generator operator’s manual.
Ensure that the total of the selected load circuits fed by this
transfer switch are within the generator’s rated capacity.
The following requirements apply to this type of
isolationsystem:
The automatic transfer switch is installed after the main
distribution panel.
The automatic transfer switch has a load rating of
100Amps. This is the maximum load rating of the total
essential load.
All wiring must conform to national, state and
localcodes.
The illustration below depicts a typical system installation
and assumes the utility is supplying 120/240 Volt, single-
phase electrical service.
Typical
Main
Distribution
Panel
Transfer
Switch
Hot
Water
Heater
Air
Conditioner
Contactor
Generator
Watt -
Hourmeter
Essential Branch Circuits
— — — — — — Control Wiring
Disconnect Switch
Branch Circuits
7
Mounting Guidelines
The system circuitry is enclosed in a NEMA Type 3R
enclosure suitable for indoor/outdoor use. Guidelines for
mounting the enclosure include:
Install enclosure on a firm, sturdy supporting structure.
The enclosure must be installed with minimum
NEMA3R hardware for conduit connections.
To prevent switch contact distortion, level and plumb
the enclosure. This can be done by placing washers
between the enclosure and the mounting surface.
NEVER install the switch where any corrosive
substance might drip onto the enclosure.
Protect the switch at all times against excessive
moisture, dust, dirt, lint, construction grit and
corrosivevapors.
It is best if the transfer switch is mounted near the utility
meter, either inside or outside. Discuss layout suggestions/
changes with the owner before beginning the system
installation process.
NOTICE Before drilling conduit entry holes, or any
other holes, cover and protect the switch and electronics
to prevent dirt and metal fragments from entering the
mechanical and electrical components. Failure to do so may
result in damage or malfunction of the switch.
NOTICE Use a vacuum to clean any dirt or metal
shavings inside the transfer switch. Do not use a blower or
compressed air to clean the inside of the transfer switch
because debris may become lodged in the electrical and
mechanical components causing damage or malfunction.
Power Wiring Interconnections
Utility and generator conduits must enter enclosure above
circuit breaker bus in transfer switch. No conductors shall
pass over top of control board. Branch circuit conduits
must enter sides or bottom of enclosure adjacent to circuit
breaker terminals. Do Not use large knockouts in bottom
ofenclosure.
All wiring must be the proper size, properly supported
and protected by conduit. All wiring should be done per
applicable federal, state and local codes, standards and
regulations. Obey wire type and torque specifications printed
on the terminal blocks and neutral/ground connector.
Approved for copper and aluminum conductors.
Complete the following connections between the transfer
switch, main distribution panel and generator. Use installer-
supplied 300VAC or greater wire that complies with Table
310.16 in the National Electric Code. Apply the necessary
correction factors and wire size calculations.
1. Set generator’s circuit breaker to OFF (open) position.
2. Set generator’s system switch to OFF position and
remove 15 Amp fuse from system control panel.
3. Turn off utility power to the standby generator and
transfer switch.
4. Using installer supplied 300VAC or greater conductor,
connect utility source from an installer-supplied 100
Amp two pole “essential circuit breaker” installed in
main distribution panel to transfer switch contactor
terminals marked “UTILITY”. Ensure circuit breaker is
turned OFF.
5. Using installer supplied 300VAC or greater conductor,
connect main distribution panel ground to transfer
switch GROUND bus.
6. Using installer supplied 300VAC or greater conductor,
connect main distribution panel neutral to transfer
switch NEUTRAL bus.
WARNING Low voltage wire cannot be installed in
same conduit as power voltage wiring.
Failure to follow above warning could cause personal
injury, damage and/or malfunction of equipment.
NOTICE Improper installation can cause damage to the
circuit boards and shorten their life. Installing circuit
boards in live circuits will damage the board and is not
covered by warranty. ALWAYS disconnect ALL sources of
power prior to servicing.
Remove all power prior to installing this equipment.
Failure to do so could cause internal damage to the board
when making electrical connections.
Turn generator to OFF position.
Turn off utility power to the standby generator and
transfer switch.
8 BRIGGSandSTRATTON.COM
7. Connect all essential branch circuit wiring to
appropriate circuit breakers in transfer switch.
8. Connect essential branch circuit Neutral conductors to
transfer switch NEUTRAL bus.
9. Connect essential branch ground conductors to transfer
switch GROUND bus.
10. Connect feeder conductors from transfer switch
contactor “GENERATOR” terminals to generator circuit
breaker LINE1 and LINE2 terminals. Each conductor
must pass through hole of current transformer before
making connection.
11. Plug current transformer leads into “CT1” and “CT2”
connectors on transfer switch control board.
12. Connect conductor from transfer switch NEUTRAL bus
to generator NEUTRAL terminal. Observe generator
control panel labeling for terminalidentification.
13. Connect conductor from transfer switch GROUND bus
to generator control panel GROUNDterminal.
Assure generator and transfer switch equipment grounding
conductor is connected per applicable federal, state and local
codes, standards and regulations.
14. Connect the transfer switch “UTILITY 240 VAC”
terminals to generator’s “240 VAC” terminals using
installer supplied 300VAC or greater wire, minimum
#14 AWG conductors via two-pin connector supplied
with generator.
15. Connect “T/R” and “GND” terminals on transfer switch
control board (J) to the generator’s control panel (X)
“TxRx” and “TxRx GND” terminals using #18 AWG
twisted pair conductors, no greater than 200ft in
length, 300 volt 75°C-90°C via ten-pin connector
supplied with generator.
16. Tighten all wire connections/fasteners to proper
torque. See label inside transfer switch enclosure
for proper torque values. If removed, replace all
protectivebarriers.
The illustration on the facing page shows a typical completed
installation - your actual layout will vary. Illustration
calloutsare:
A - NEUTRAL bus
B - Utility source
C - GROUND bus
D - Main distribution panel
E - Current transformers
F - GENERATOR terminals
G - UTILITY terminals
H - Transfer switch assembly
J - T/R and GND to generator
K - Transfer switch control board
L - CT1 and CT2 connectors
M - Supervisory contacts
N - UTILITY 240VAC to generator
P - Essential branch circuit loads
R - Essential branch circuit breakers
S - Generator NEUTRAL terminal
T - Generator GROUND terminal
V - Generator circuit breaker
W - Two-pin connector
X - Ten-pin connector
33
240V
11
22
44
11
22
44
120V
120V
0
Neutral
Ground
To Transfer Switch
Line 1 Neutral
Ground
Line 2
Circuit
Breaker
X
J
9
G
LINE2
LINE1
N
240
VAC
L
1
L
2
N
G
L1
L2
N
A
A
D E F H
T
J
N
R
PP
L
W
K
V
G
S
C
C
B
M
X
10 BRIGGSandSTRATTON.COM
Supervisory Control Wiring
An air conditioner can be used with the supervisory contacts
on either terminals A-A or B-B. Terminals A-A can only be
used with supervisory control. Large loads can only be used
with contactor control on terminals B-B. Examples of each
system are described below.
1. The terminal strip on the transfer switch control board
has four connections for customer use. There are two
sets of “Normally Closed” contacts available. They will
be activated when generator power is required. These
can be used for supervisory control of large connected
loads on generator. Loads will be allowed to operate if
there is enough generator poweravailable.
2. Terminals “A-A” on transfer switch control board
are rated for 24VAC. Connect these contacts in
series between air conditioner thermostat and air
conditionercontactor.
3. Terminals “B-B” on transfer switch control board are
rated for 1 Amp 125 VAC. When connected with an
installer supplied contactor, it can be used to control
a large load, such as an electric hot water heater.
Contacts are connected in series with the contactor
control circuit.
4. Tighten all wire connections/fasteners to proper torque.
See label inside transfer switch enclosure for proper
torquevalues.
System Setup
You must perform the following before operating the system:
If generator is installed in an area regularly subjected
to temperatures below 40°F (4°C), select a 50 second
warm up time by moving jumper JP2 installed on
transfer switch control board from ‘20’ position to
‘50’position.
Set the DPSW1 and DPSW2 dipswitches on the
transfer switch control board to match the kW rating
of the home standby generator, as described in
SettingDipswitches.
System Setup
You must perform the following before operating the system:
• If generator is installed in an area regularly subjected to
temperatures below 40°F (4°C), select a 50 second warm up
time by moving jumper JP2 (C) installed on transfer switch
control board from ‘20’ position to ‘50’position.
• Set the DPSW1 (A) and DPSW2 (B) dipswitches on the
transfer switch control board to match the kW rating of the
standby generator, as described in SettingDipswitches.
Setting Dipswitches
Dipswitches are used to adjust control board operation based
on generator capacity. DPSW1 and DPSW2 switches are set to
correspond to total system kW rating. Dipswitch DPSW1 (A) has
units of 1,000 watts; Dipswitch DPSW2 (B) has units of
10,000 watts.
Set dipswitches with utility and generator power removed from
the transfer switch to ensure proper control system operation.
If dipswitches are set when power is present at transfer switch,
a power reset needs to be performed before the new dipswitch
settings will take effect. Power reset is when all power is removed
from the transfer switch and then reintroduced after 30 seconds.
NOTICE An FC_8 will occur on standby generator control board if
dipswitches are not properly established as noted above.
NOTICE Use extreme caution when setting dipswitches or
damage to control board will result.
Use a pencil or small piece of plastic to set the dipswitch.
NEVER use a screwdriver or any type of metal object to
set dipswitches.
B
B
Contactor
Neutral
120 VAC
A
A
To air conditioner contactor
From air conditioner thermostat (yellow?)
24 VAC
DPSW
1
DPSW2
JP2
A
B
C
11
The “On” position for the dipswitches is the switch number ON
THE TRANSFER SWITCH CONTROL BOARD, not on the switch. For
example, for an 18,000 watt generator, set DPSW2 dipswitch 10 to
“On” position. Set DPSW1 dipswitch 8 to “On” position. 10,000 plus
8000 equals 18,000 watts.
Set only one switch to “On” position
on DPSW1 andDPSW2.
Refer to following chart for proper switch selection(s).
NOTICE
Air density is less at high altitudes, resulting in less
available engine power. Specifically, engine power will decrease 3.5%
for each 1,000 feet (300 meters) above sea level and 1% for each 10°
F (5.6°C) above 77°F (25°C). Generators located in these conditions
must have the transfer switch programmed appropriately for this
power decrease.
System Test
With the generator system switch in AUTO, turn the
100Amp circuit breaker feeding the transfer switch to the
OFF position. After a few minutes the generator will start
and the transfer switch will transfer essential loads to
generatorpower.
To return to utility power, turn the 100 Amp circuit breaker
feeding the transfer switch ON.
Controls
Other than a Manual Override lever, there are no operator
controls because this is an automatic transfer switch. The
manual override is to be used only by licensed professionals.
Information on handle use can be obtained by calling
Technical Service at 800743-4115.
Operation
To select automatic transfer operation, do the following:
1. In main distribution panel, set 100 Amp circuit
breaker that sends utility power to transfer switch to
ON”position.
2. Install 15 Amp fuse in generator’s control panel.
3. Set generator’s circuit breaker to “ON” position.
4. Set generator’s system switch to “AUTO” position.
The system will now be in automatic operation mode.
When the generator is providing power to the transfer
switch, the transfer switch control board is constantly
monitoring generator power. If the air conditioner is called
to run, and there is sufficient generator power available,
the controller will close contacts “A-A” to air conditioner
contactor. Contacts “B B” will open before contacts A-A
close. If loads are too great for the generator, contacts A-A
and/or B-B will open. When air conditioning is not needed,
A-A will open. If enough power is available, B-B will close.
kW Rating
of
Generator
DPSW
#1 “ON”
Position
DPSW
#2 “ON”
Position
7kW 7 0
8kW 8 0
9kW 9 0
10kW* 0 10
11kW* 1 10
12kW 2 10
13kW* 3 10
14kW 4 10
15kW 5 10
16kW 6 10
17kW 7 10
18kW 8 10
19kW 9 10
20kW 0 20
30kW 0 30
45kW 5 40
48kW 8 40
50kW 0 50
60kW 0 60
* For generators with a rating that includes 500 Watts, round
down to next lowest rating
(example: 13.5 kW set to 13kW)
12 BRIGGSandSTRATTON.COM
Enclosure Door
To open door, press the spring-load door lock to the right
and pull down on the door.
To close and latch door, push door closed against enclosure.
While in this position, push door upwards. This will cause
spring-load door lock to engage and latch door in place.
Enclosure door MUST be closed and latched at all times
except when system is being serviced.
Testing the Automatic Transfer Switch
Turn the main distribution panel circuit breaker feeding the
transfer switch to the “OFF” position. The system’s automatic
sequence will initiate. To return to utility power, turn the
main distribution panel circuit breaker to the “ON”position.
Utility Fail
The generator senses when utility voltage is below
70percent of nominal. Engine start sequence is initiated
after 6 second time delay.
Engine Warm-Up
Time delay to allow for engine warm-up before transfer. Use
jumper on transfer switch control board to select delay of
20seconds or 50seconds.
Transfer
Transfer from utility to generator supply occurs after voltage
is above set levels. Minimum engine run time is 5 minutes
after transfer.
Utility Pickup
Voltage pickup level is 80 percent of nominal voltage.
Retransfer
Retransfer from generator to utility power is approximately
10 seconds after utility voltage supply is above pickup level
and minimum run time is completed.
Engine Cool Down
Engine will run for 60 seconds after retransfer.
13
Maintenance
The transfer switch is designed to be maintenance free under
normal usage. However, inspection and maintenance checks
should be made on a regular basis. Maintenance will consist
mainly of keeping the transfer switch clean.
Visual inspections should be done at least once a month.
Access to transfer switch must not be obstructed. Keep
3feet (92 cm) clearance around transfer switch. Check
for an accumulation of dirt, moisture and/or corrosion
on and around the enclosure, loose parts/hardware,
cracks and/or discoloration to insulation, and damaged or
discoloredcomponents.
Exercise the transfer switch at least once every three months
as described in Testing the Automatic Transfer Switch unless
a power outage occurs and home generator system has gone
through an automatic sequence. Allow generator to run for at
least 30 minutes.
Contact a licensed electrical professional to inspect and clean
the inside of the enclosure and other components of your
home generator system at least once a year.
When Calling for Assistance
You must have the Model Number and Serial Number from
the unit ID label at hand if it is necessary to contact a local
service center regarding service or repair of this unit. Obtain
this information from the unit ID label located on or inside
the enclosure.
To contact Briggs & Stratton call 800743-4115, between
8:00 AM and 5:00 PM CT.
Installation Inspection
Before placing the system into service, inspect the entire
installation carefully.
14 BRIGGSandSTRATTON.COM
Troubleshooting
Problem Cause Correction
Au tomatic transfer switch does not
transfer to generator
1. Generator breaker open.
2. Generator voltage not acceptable.
1. Reset generator circuit breaker.
2. Refer to generator manual.
Au tomatic transfer switch does not
transfer to utility
1. Main distribution panel circuit
breaker open.
2. Utility voltage not acceptable.
1. Reset circuit breaker in main
distribution panel.
2. Wait for utility voltage to return
tonormal.
Ge nerator is still running after switch
transfers to utility power
Engine cool down period. Engine should stop after 1 minute.
Ge nerator or supervised loads (air
conditioner, etc.) are operating
improperly when generator is
supplyingpower
1. A-A or B-B contacts not
operatingcorrectly.
2. Too much load on generator.
3. Current transformer not connected.
4. Broken current transformer.
1. Contact local authorized
servicecenter.
2. Decrease load to generator.
3. Contact local authorized
servicecenter.
4. Contact local authorized
servicecenter.
Ge nerator is still running after utility
power is restored
1. Minimum engine run time has
notelapsed.
2. Transfer switch fuse(s) defective.
1. Wait five minutes for transfer switch
to retransfer to utility power.
2. Contact local authorized
servicecenter.
15
Schematic Diagram
16 BRIGGSandSTRATTON.COM
Wiring Diagram
Dashed lines show customer (field) connections
17
Automatic Transfer Switch
Product Specifications
Rated Maximum Load Current (at 25°C/77°F) ........................................................................ 100 Amps
Rated AC Voltage .....................................................................................................................250 Volts
Poles ..................................................................................................................................................... 2
Frequency ......................................................................................................................................60 Hz
Fault Current Rating ........................................................................22,000 RMS Symmetrical Amperes
Supervisory Contacts Rating:
A-A Terminals ...................................................................................................................24 Volt AC
B-B Terminals ...................................................................................1 Amp, 125 Volt AC, Pilot Duty
Normal Operating Range .....................................................................-20°F (-28.8°C) to 104°F (40°C)
Weight .............................................................................................................................44 lbs. (20 kg)
* This transfer switch is certified in accordance with UL (Underwriters Laboratories) 1008 (transfer switch equipment).
18 BRIGGSandSTRATTON.COM
Circuito 16
interruptor de transferencia automática
de 100 amperios
con módulo de control de energía eléctrica de CA™
Manual de instalación ydeloperario
Copyright © Briggs & Stratton Corproation
Milwaukee, WI, USA. Reservados todos los derechos.
2 BRIGGSandSTRATTON.COM
Gracias por comprar este conectador automático de Briggs & Stratton® Power Products. Este producto está diseñado para
utilizarse con generadores de reserva domésticos específicos y puede no funcionar con generadores producidos por otros
fabricantes. Recurra a un electricista profesional cualificado para determinar la aplicabilidad de este equipo en generadores
fabricados por terceros. Si se utiliza y mantiene de acuerdo con las instrucciones de este manual, su sistema le proporcionará
muchos años de funcionamiento fiable.
Este manual contiene información de seguridad para que usted conozca los peligros y riesgos propios de este sistema y
cómo evitarlos. Se ha realizado el máximo esfuerzo para que la instalación resulte segura, sencilla y económica. Debido a que
cada instalación es única, es imposible conocer y recomendar todos los procedimientos y métodos posibles para efectuarla.
No conocemos todos los riesgos y/o resultados posibles de cada método o procedimiento existente. Es importante que lea
y comprenda perfectamente estas instrucciones antes de intentar instalar o utilizar este equipo. Guarde estas instrucciones
para futuras consultas.
Este el conectador requiere instalación profesional antes de utilizarse. Consulte las instrucciones sobre los procedimientos
de instalación en la sección Instalación del presente manual. Los conectador sólo deben ser instalados por electricistas con
licencia. Las instalaciones deben cumplir estrictamente la totalidad de los códigos, estándares y regulaciones federales,
estatales y locales vigentes. El instalador debe seguir las instrucciones detalladamente.
Dónde encontrarnos
Nunca debe ir demasiado lejos para encontrar el soporte y servicio de Briggs & Stratton para su sistema. Consulte las
Páginas Amarillas. Existen múltiples distribuidores de servicio autorizados que ofrecen un servicio de calidad. También
puede comunicarse con el Servicio técnico por teléfono al 800743-4115 de 8:00 a. m. a 5:00 p. m. Hora del Centro, o
utilizar el buscador de centros de servicio técnico de BRIGGSandSTRATTON.COM, que ofrece la lista de los distribuidores de
servicioautorizados.
Para futuras consultas
Llene la siguiente información y conserve su factura para facilitar la identificación de la unidad en caso de que surjan
problemas relacionados con la compra en el futuro.
Conectador automático
Número de modelo
Versión
Número de serie
Fecha de compra
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

Simplicity 040486-00 Manuel utilisateur

Catégorie
Groupes électrogènes
Taper
Manuel utilisateur