3
IS-0625 – Rev. 2
First select the room, then click on Vantage Objects in the Object Explorer and expand Stations, WireLink. From the list of
stations double click on the Power Station to place it in the room. In the Object Editor name the station, select the correct model and
make sure it is on the correct Station Bus port.
CONFIGURING
If using the conguration install method number “2” above, the station should not be congured. For method “1” above, the serial
number may be manually typed in the project le. Traditional conguration: When the Power Station is rst connected to the
Station Bus, the diagnostic LED will blink twice followed by a pause. This means the Power Station is connected correctly but is not
congured. It is congured like any other station. From Design Center, click on the Congure Stations button on the toolbar. To nish,
press the congure button on the front of the station. Once congured the diagnostic LED will blink evenly.
DIAGNOSTIC INFORMATION
The Diagnostic LED blinks 1 time evenly or 2, 3, 4, or 5 blinks followed by a pause.
One Even Blink: The Power Station is operating correctly and is congured.
Two Blinks: The Power Station is operating correctly but is not congured.
Three Blinks: The Power Station is not communicating with the Main Controller. Check the Station Bus connection.
Four Blinks: Factory problem. Please contact the factory.
Five Blinks: The Power Station is waiting to be congured.
PROPER TORQUE and WIRE
RESET
The power booster station operates as a standalone or as a high power load on the system. To reset, turn OFF power to LINE. With
the power OFF, hold in the Congure/Toggle button on the front while power is restored to LINE. Continue holding the button in for
about two (2) seconds to make sure the station reset happens.
NOTE: If the Station Load was changed to RELAY this Process will change it back to DIM. Make sure it is back on line with the Main
Controller before testing button or load operation.
DEFAULT BUTTON OPERATION
Action Load Operation
Single Press The load toggles between off and the learned level. The turn on ramp
time is 1.5 seconds and the turn off fade time is 5 seconds.
Double Press The load ramps to 100% in 1.5 seconds. The second press must be
within 1 second of the rst press.
Press and Hold After a one second delay the load will ramp in the opposite direction
from the last press and hold. If the load reaches 0 or 100% it will reverse
direction. When the button is released the current load level will be saved
as the new learned level for that button. The cycle time is 5 seconds from
0-100%.
Relay Mode The load turns on with the rst press and release and OFF with the
second press and release.
SETUP IN DESIGN CENTER
Connector Torque Wire Range
LINE/LOAD WIRING 20 INCH POUNDS 14-10 AWG (Must match breaker wire gauge)
LED DIMMING
• Legrand is leading the way in LED lighting control through innovations of new hardware and software products;
however, industry standards are still undened for dimming LED lamps and xtures. Dimming performance of
LED lighting cannot be guaranteed, even when applying the correct dimming technology specied by the LED
manufacturer. While Legrand may be consulted when performance issues are present, Legrand will not be liable for
on-site performance issues.
• There are many factors that may contribute to unsatisfactory results within a specic installation, including, but not
limited to:
- Line noise originating from electrical equipment within the premises
- Line noise from the source (particularly with local generators or inverters)
- Interference between dimmed LED products
- Wiring conditions (i.e. shared neutrals, loose neutrals, incorrectly bonded neutral, or grounding issues)
- LED product variances, including:
• Unintended batch-related variances
• Product revisions