Rittal CMC III Processing Unit Compact Installation Manual And Short User's Manual

Taper
Installation Manual And Short User's Manual

Ce manuel convient également à

CMC III Processing Unit
CMC III Processing Unit Compact
Unité centrale CMC III
Unité centrale compacte CMC III
7030.000
7030.010
Installationsanleitung und Kurz-Bedienungsanleitung
Installation Guide and Short User’s Guide
Notice d'installation et notice d'utilisation succincte
2 Rittal CMC III Processing Unit (Compact) / Unité centrale (compacte)
Abb./Fig./Fig. 1: Beigelegtes Zubehör / Accessories provided / Accessoires joints
Abb./Fig./Fig. 2: Montage / Assembly / Montage
Abb./Fig./Fig. 3: Bedienfeld, Stecker und Anschlüsse / Operator panel, plugs and connectors / Panneau
de commande, fiches et raccordements
Abbildungen /
Figures / Figu-
res
Abbildungen / Figures / Figures
Rittal CMC III Processing Unit (Compact) / Unité centrale (compacte) 3
Abb./Fig./Fig. 4: Website Netzwerkeinstellungen / Network settings web site / Interface WEB pour les
réglages réseau
Abbildungen / Figures / Figures
DE
4 Rittal CMC III Processing Unit / CMC III Processing Unit Compact
1 Hinweise zur Dokumentation
Diese Installations- und Kurz-Bedienungsanleitung richtet sich an versiertes Fachpersonal und ent-
hält nur die wichtigsten Informationen zur Montage, Installation und Funktion der
CMC III Processing Unit /CMC III Processing Unit Compact (nachfolgend CMC III PU genannt).
1.1 Mitgeltende Unterlagen
Montage-, Installations- und Bedienungsanleitung
CMC III Processing Unit / CMC III Processing Unit Compact.
Sie ist unter www.rittal.de verfügbar und enthält die vollständigen anwendungsrelevanten Informa-
tionen und technischen Daten zur CMC III PU in Hinblick auf:
Weitere Montagemöglichkeiten
Details zum elektrischen Anschluss
Funktionen und Services
Konfigurationsmöglichkeiten
Detaillierte Bedienungsanweisungen
Fehlerbehebung
2 Sicherheitshinweise
Montage und Installation des Geräts dürfen nur durch versiertes Fachpersonal erfolgen.
Ein Netzspannungsanschluss bzw. eine Netzspannungsverkabelung im Rahmen der
CMC III PU-Verkabelung darf nur durch eine versierte Elektrofachkraft erfolgen.
Das Gehäuse der CMC III PU darf nicht geöffnet werden.
Die CMC III PU darf nicht in Kontakt mit Wasser, aggressiven oder entzündbaren Gasen und
Dämpfen kommen.
Die CMC III PU darf nur innerhalb der spezifizierten Umgebungsbedingungen betrieben werden
(vgl. Abschnitt 3.4).
3 Produktbeschreibung
3.1 Funktionsbeschreibung
Die CMC III PU ist das Kernprodukt des Rittal Schaltschrank-Überwachungs- und -Steuerungssys-
tems zur elektronischen Überwachung von Schaltschränken und Server-Racks. Sie beinhaltet eine
Ethernet-LAN-Schnittstelle in Verbindung mit einer Website zur Benutzerkommunikation. Neben
den eingebauten Sensoren kann über eine CAN-Bus-Schnittstelle eine breite Palette von Sensoren,
Aktoren und Systemen zur Zugangsüberwachung angeschlossen werden. Alle Sensoren initialisie-
ren sich automatisch nach dem Anschluss an das CAN-Bus-System.
3.2 Bestimmungsgemäße Verwendung
Die CMC III PU dient ausschließlich als Schaltschrank-Überwachungssystem und zur Administrie-
rung verschiedener Schaltschrank-Parameter. Eine andere Verwendung ist nicht bestimmungsge-
mäß.
Vor Einsatz eines angeschlossenen Sensors außerhalb eines Schaltschranks muss Rücksprache
mit Fa. Rittal gehalten werden.
3.3 Lieferumfang
CMC III Processing Unit oder CMC III Processing Unit Compact
Beigelegtes Zubehör (Abb. 1)
Installations- und Kurz-Bedienungsanleitung
DE
Hinweise zur Dokumentation, Sicherheitshinweise, Produktbeschreibung
Rittal CMC III Processing Unit / CMC III Processing Unit Compact 5
DE
3.4 Betriebsbedingungen
Die CMC III PU darf nur unter folgenden Betriebsbedingungen betrieben werden:
4 Montage
4.1 Montageanweisung
Die Montage der CMC III PU erfolgt gemäß Abb. 2.
Bringen Sie die CMC III PU so an, dass die Front mit Sender und Empfänger zu der zu überwa-
chenden Tür hin zeigt.
Kleben Sie die beigelegte Reflexfolie exakt an die dem Infrarot-Zugangssensor gegenüberlie-
gende Position an der Tür bzw. der Seitenwand.
5 Installation und Bedienung
5.1 Bedien- und Anzeigeelemente
Die Bedien- und Anzeigeelemente sind in Abb. 3 dargestellt.
Legende zu Abb. 3
1 „C“-Taste zur Quittierung von Meldungen
2 Versteckte Reset-Taste
3 Multi-LED zur Statusanzeige
4 SD-Card Einschub (nicht bei Ausführung „Compact“)
5 Integrierter Infrarot-Zugangssensor
6 Mini USB-Anschluss zur Konfiguration
7 Digitale Eingänge (2 Stück), je 24 V , 10 mA
8 USB Master-Anschluss (nicht bei Ausführung „Compact“)
9 Anschluss externer Temperaturfühler
Temperatur-Einsatzbereich +0°C…+45°C
Feuchtigkeits-Einsatzbereich 5 %…95 % relative Feuchte, nicht kondensierend
Schutzart IP 30 nach IEC 60 529
Hinweis:
Es wird empfohlen, vor dem Einbau des Geräts die Netzwerkeinstellungen anzupas-
sen (vgl. Abschnitt 6).
Hinweis:
Zur genauen Temperaturmessung mit dem internen Temperatursensor muss eine
ausreichende Luftzirkulation im Schaltschrank bzw. Serverschrank gegeben und die
CMC PU III so angeordnet sein, dass sie ausreichend gut mit Luft durchströmt wird
und die Lüftungsschlitze nicht verdeckt werden.
Sollte dies nicht realisiert werden können, muss anstelle des internen Temperatursen-
sors der externe Temperaturfühler aus dem Lieferumfang verwendet werden.
Hinweis:
Der Abstand zwischen dem Infrarot-Zugangssensor in der CMC III PU und der Re-
flexfolie darf maximal 15 cm betragen. Korrigieren Sie ggf. den Montageort der
CMC III PU entsprechend.
Montage, Installation und Bedienung
DE
6 Rittal CMC III Processing Unit / CMC III Processing Unit Compact
10 Anschluss für Display-, GSM- oder ISDN-Unit Module RJ 12/RS 232, 24 V , 500 mA
11 Ethernet-Schnittstelle RJ 45 mit PoE
12 CAN-Bus-Anschluss (Daisy Chain) für CMC III Sensoren und Steuereinheiten, 24 V ,1 A
13 Zweiter CAN-Bus-Anschluss (nicht bei Ausführung „Compact“), 24 V ,1 A
14 Spannungsversorgung 24 V (Netzteilanschluss)
15 Spannungsversorgung 24 V (Direktanschluss)
16 Alarm-Relaisausgang (potenzialfreier Kontakt, max. 24 V ,1 A)
Des Weiteren ist in der CMC III PU die Sicherung F5 mit folgender Spezifikation verbaut:
450 V , 3,15 A, träge, Typ 09773.15MXP Littelfuse.
5.2 Installation
Stecken Sie ggf. den externen Temperaturfühler hinten am Anschluss der CMC III PU (Abb. 1,
Pos. 9) an und führen Sie den Messfühler zur gewünschten Messstelle.
Schließen Sie das externe Netzteil (7030.060) an den Anschluss der 24 V-Spannungsversorgung
an (Abb. 3, Pos. 14).
Der Start des Geräts dauert ca. 1 Minute. Während dieser Zeit blinkt die Statusanzeige in unre-
gelmäßigen Abständen blau (Abb. 3, Pos. 3).
Das Gerät ist betriebsbereit, wenn die Statusanzeige dauerhaft grün leuchtet.
Falls die Statusanzeige nach Abschluss des Einschaltvorgangs rot-blau blinkt, drücken und hal-
ten Sie die „C“-Taste zur Quittierung von anstehenden Meldungen (Abb. 3, Pos. 1).
Anschließend leuchtet die Statusanzeige dauerhaft grün und das Gerät ist betriebsbereit.
Bei nicht erfolgreicher Installation: vgl. Abschnitt 1.1.
Hinweis:
Die Spannungsquellen an Pos. 7, 10, 12, 13 sowie 16 (Abb. 3) müssen den Limited
Power Source (LPS)-Anforderungen nach UL 60950 genügen und die o.g. Grenzwer-
te einhalten.
Hinweis:
Das Gerät ist erst nach Trennung von allen Spannungsquellen spannungsfrei!
Hinweis:
Wenn der externe Temperaturfühler eingesteckt ist, wird der interne Temperatursen-
sor abgeschaltet.
Hinweis:
Der externe Temperaturfühler muss vor dem Start der CMC III PU angeschlossen
werden.
Wird der externe Temperaturfühler im laufenden Betrieb angeschlossen, muss die
CMC III PU zunächst neu gestartet werden, damit der externe Temperaturfühler er-
kannt und verwendet wird.
Installation und Bedienung
Rittal CMC III Processing Unit / CMC III Processing Unit Compact 7
DE
6 Netzwerkeinstellungen
Schließen Sie das Gerät mit einem Netzwerkkabel über die Ethernet-Schnittstelle an Ihren Com-
puter an (Abb. 3, Pos. 11).
Ändern Sie die IP-Adresse Ihres Computers auf eine beliebige Adresse im Bereich
192.168.0.xxx, z. B. 192.168.0.191. Nicht zulässig ist die voreingestellte Adresse 192.168.0.190
des Geräts.
Stellen Sie die Subnetzmaske auf den Wert 255.255.255.0.
Schalten Sie ggf. den Proxyserver im Browser ab, um eine direkte Verbindung zum Gerät zu er-
möglichen.
Geben Sie im Browser die Adresse http://192.168.0.190 ein (Abb. 4, Pos. 1). Es wird der Anmel-
dedialog zur Anmeldung am Gerät angezeigt.
Melden Sie sich als Benutzer admin mit dem Kennwort admin an (Abb. 4, Pos. 2).
Klicken Sie im linken Teilbereich des Übersichtsfensters (Navigationsbereich) den Eintrag Pro-
cessing Unit an (Abb. 4, Pos. 3) und im rechten Teilbereich (Konfigurationsbereich) die Regis-
terkarte Configuration (Abb. 4, Pos. 4).
Klicken Sie im Gruppenrahmen Network die Schaltfläche TCP/IP an (Abb. 4, Pos. 5).
Ändern Sie im Fenster TCP/IP Configuration im Gruppenrahmen IPv4 Configuration die IP-
Adresse des Geräts auf eine im Netzwerk erlaubte Adresse ab (Abb. 4, Pos. 6).
Stellen Sie ggf. die Netmask und das Gateway korrekt ein.
Wählen Sie alternativ die Einstellung „DHCPv4“ statt „Manual“ für eine automatische IP-Vergabe.
Klicken Sie auf die Schaltfläche Save, um die Einstellungen zu speichern.
Ändern Sie die Netzwerkeinstellungen Ihres Computers auf die ursprünglichen Werte der IP-
Adresse sowie der Subnetzmaske ab.
Trennen Sie das Netzwerkkabel zu Ihrem Computer.
Verbinden Sie die CMC III PU mit einem Netzwerkkabel mit Ihrem Ethernet-LAN (Abb. 3,
Pos. 11).
Eventuell notwendige Softwareupdates: siehe www.rittal.de oder Anfrage bei Rittal Service (vgl.
Abschnitt 7).
7 Service
Zu technischen Fragen wenden Sie sich bitte an:
Tel.: +49(0)2772 505-9052
Homepage: www.rittal.de
Bei Reklamationen oder Servicebedarf wenden Sie sich bitte an:
Tel.: +49(0)2772 505-1855
Hinweis:
Eventuell müssen Sie hierfür ein Crossoverkabel nutzen.
Hinweis:
Im Folgenden wird die Einstellung für das IPv4-Protokoll detailliert beschrieben. Wei-
terführende Hinweise zur TCP/IP-Konfiguration: vgl. Abschnitt 1.1.
Netzwerkeinstellungen, Service
EN
8 Rittal CMC III Processing Unit / CMC III Processing Unit Compact
1 Notes on documentation
This installation and short user’s guide is intended for experienced trained specialists and contains
only the most important information concerning the assembly, installation and function of the
CMC III Processing Unit / CMC III Processing Unit Compact (subsequently called CMC III PU).
1.1 Associated documents
Assembly, installation and user’s guide CMC III Processing Unit / CMC III Processing Unit Com-
pact.
It is available at www.rittal.com and contains the complete application-relevant information and
technical data for the CMC III PU with regard to:
Further assembly possibilities
Details concerning the electrical connection
Functions and services
Configuration possibilities
Detailed operating instructions
Troubleshooting
2 Safety instructions
Assembly and installation of the device may only be performed by experienced trained special-
ists.
A mains power connection or mains power wiring as part of the CMC III PU wiring may only be
performed by an experienced electrician.
The CMC III PU housing must not be opened.
The CMC III PU may not come in contact with water, aggressive or inflammable gases and va-
pours.
The CMC III PU may only be operated within the specified environmental conditions (see
section 3.4).
3 Product description
3.1 Functional description
The CMC III PU is the central product of the Rittal enclosure monitoring and control system for the
electronic monitoring of enclosures and server racks. It provides an Ethernet LAN interface in con-
junction with a web site for user communication. In addition to the integrated sensors, the CAN bus
interface allows a wide range of sensors, actuators and systems for access monitoring to be con-
nected. All sensors initialise themselves automatically after connection to the CAN bus system.
3.2 Proper use
The CMC III PU is used only as an enclosure monitoring system and for the administration of the
various enclosure parameters. Any other use is not permitted.
Rittal must be contacted before using a sensor connected outside of an enclosure.
3.3 Scope of delivery
CMC III Processing Unit or CMC III Processing Unit Compact
Accessories provided (fig. 1)
Installation and Short User’s Guide
Notes on documentation, Safety instructions, Product description
EN
Rittal CMC III Processing Unit / CMC III Processing Unit Compact 9
EN
3.4 Operating conditions
The CMC III PU may only be operated under the following operating conditions:
4 Assembly
4.1 Assembly instructions
The assembly of the CMC III PU is made as shown in fig. 2.
Mount the CMC III PU so that the front with the transmitter and receiver is pointing to the moni-
tored door.
Stick the enclosed reflecting foil on the door and the side wall exactly opposite of the integrated
infrared access sensor.
5 Installation and operation
5.1 Operating and display elements
The operating and display elements are shown in fig. 3.
Key for fig. 3
1 "C" key to acknowledge messages
2 Hidden reset key
3 Multi-LED for the status display
4 SD card slot (not for the "Compact" variant)
5 Integrated infrared access sensor
6 Mini USB connection for configuring
7 Digital inputs (two), per 24 V , 10 mA
8 USB master connection (not for the "Compact" variant)
9 Connection of an external temperature sensor
Temperature operational range +0°C…+45°C
Humidity operational range 5%…95% relative humidity, non-condensing
Protection category IP 30 according to IEC 60 529
Note:
We recommend that the network settings are changed before the device is installed
(see section 6).
Note:
To permit the exact temperature measurement with the internal temperature sensor,
an adequate air circulation in the enclosure or server enclosure must be provided,
and the CMC PU III located so that it is adequately supplied with air, and the vent slots
not covered.
If this cannot be implemented, the external temperature sensor from the scope of sup-
ply must be used instead of the internal temperature sensor.
Note:
The separation between the infrared access sensor in the CMC III PU and the reflect-
ing foil must not exceed 15 cm. If necessary, correct the CMC III PU installation loca-
tion appropriately.
Assembly, Installation and operation
EN
10 Rittal CMC III Processing Unit / CMC III Processing Unit Compact
10 Connection for display, GSM or ISDN unit module, RJ 12/RS 232, 24 V , 500 mA
11 Ethernet interface, RJ 45 with PoE
12 CAN bus connection (daisy chain) for CMC III sensors and control units, 24 V ,1 A
13 Second CAN bus connection (not for the "Compact" variant), 24 V ,1 A
14 24 V power supply (power pack connection)
15 24 V power supply (direct connection)
16 Alarm relay output (floating contact, max. 24 V , 1 A)
The F5 fuse with the following specification – 450 V , 3.15 A, slow fuse, type 09773.15MXP
Littlefuse – is also installed in CMC III PU.
5.2 Installation
Insert the external temperature sensor at the rear on the CMC III PU connection (fig. 1, item 9)
and route the measuring sensor to the required measuring point.
Connect the external power pack (7030.060) to the 24 V power supply connection (fig. 3,
item 14).
The device start takes approx. 1 minute. During this time, the status display flashes blue in irreg-
ular intervals (fig. 3, item 3).
The device is operational when the status display lights green continually.
If, after completion of the switch-on process, the status display flashes red-blue, keep the "C" key
pressed to acknowledge pending messages (fig. 3, item 1).
The status display then lights green continually and the device is operational.
If the installation is not successful: see section 1.1.
Note:
The voltage sources at positions 7, 10, 12, 13 and 16 (fig. 3) must satisfy the Limited
Power Source (LPS) requirements in accordance with UL 60950 and observe the limit
values mentioned above.
Note:
The unit is free from power only after all power sources have been disconnected!
Note:
The internal temperature sensor will be disabled when the external temperature sen-
sor is inserted.
Note:
The external temperature sensor must be connected before the CMC III PU is started.
If the external temperature sensor is connected during running operations, the
CMC III PU must be restarted so that the external temperature sensor is detected and
used.
Installation and operation
Rittal CMC III Processing Unit / CMC III Processing Unit Compact 11
EN
6 Network settings
Connect the device with a network cable using the Ethernet interface to your computer (fig. 3,
item 11).
Change the IP address of your computer to any address in the range 192.168.0.xxx, e.g.
192.168.0.191. The default address 192.168.0.190 of the device may not be used.
Set the subnet mask to the value 255.255.255.0.
If necessary, switch off the proxy server in the browser in order to permit a direct connection to
the device.
Enter the http://192.168.0.190 address in the browser (fig. 4, item 1). The login dialogue to log
in to the device will be displayed.
Login as admin user with password admin (fig. 4, item 2).
Click the Processing Unit entry (fig. 4, item 3) in the left-hand subarea of the overview window
(configuration area) and the Configuration tab (fig. 4, item 4) in the right-hand subarea (naviga-
tion area).
Click the TCP/IP button in the Network group frame (fig. 4, item 5).
Change the IP address of the device in the TCP/IP Configuration window in the IPv4 Configu-
ration group frame to an address permitted in the network (fig. 4, item 6).
If necessary, correct the settings for the net mask and the gateway.
Alternatively, select the "DHCPv4" setting instead of "Manual" for an automatic IP allocation.
Click the Save button to save the settings.
Change the network settings of your computer to their original values of the IP address and the
subnet mask.
Disconnect the network cable to your computer.
Connect the CMC III PU with a network cable with your Ethernet LAN (fig. 3, item 11).
To determine whether any software updates are required: see www.rittal.com or contact Rittal Serv-
ice (see section 7).
7 Service
For technical questions, please contact:
Tel.: +49(0)2772 505-9052
Homepage: www.rittal.com
For complaints or service requests, please contact:
Tel.: +49(0)2772 505-1855
Note:
You may need to use a cross-over cable for this purpose.
Note:
The settings for the IPv4 protocol are described below in detail. For further information
on TCP/IP configuration, please see section 1.1.
Network settings, Service
FR
12 Unité centrale CMC III / Unité centrale compacte CMC III
1 Remarques relatives à la documentation
Cette notice d’installation et d’utilisation succincte s’adresse à du personnel qualifié et chevronné
et contient uniquement les informations essentielles pour le montage, l’installation et le fonctionne-
ment de l’unité centrale CMC III / de l’unité centrale compacte CMC III (nommée UC CMC III par la
suite).
1.1 Autres documents applicables
Notice de montage, d’installation et d’utilisation
Unité centrale CMC III / Unité centrale compacte CMC III.
Elle est disponible sous www.rittal.com et contient les informations complètes relatives à la mise en
œuvre et les caractéristiques techniques de l’UC CMC III dans les domaines suivants :
Autres possibilités de montage
Détails des raccordements électriques
Fonctionnement et services
Possibilités de configuration
Instructions d’utilisation détaillées
Dépannage
2 Consignes de sécurité
Le montage et l’installation de l’appareil doivent être réalisés uniquement par du personnel qua-
lifié et chevronné.
Le raccordement au réseau électrique ou le câblage du réseau électrique dans le cadre de l’ali-
mentation de l’UC CMC III, doit être réalisé uniquement par un électricien qualifié et chevronné.
Ne jamais ouvrir le boîtier de l’UC CMC III.
L’UC CMC III ne doit pas se trouver en contact d’eau, de gaz et de vapeurs agressifs ou inflam-
mables.
L’UC CMC III doit être mise en œuvre uniquement dans les conditions ambiantes spécifiées (voir
paragraphe 3.4).
3 Description du produit
3.1 Principe de fonctionnement
L’UC CMC III constitue l’élément central du système Rittal de surveillance et de commande pour la
surveillance électronique des armoires électriques et des baies serveurs. Elle contient une interfa-
ce Ethernet LAN pour la communication utilisateur avec une interface WEB. En complément des
détecteurs installés, il est possible de raccorder une large palette de détecteurs, d’actionneurs et
de systèmes pour le contrôle d’accès par l’intermédiaire d’une interface CAN-Bus. Tous les détec-
teurs s’initialisent automatiquement après le raccordement au système CAN-Bus.
3.2 Utilisation conforme de l’appareil
L’UC CMC III est utilisée exclusivement comme système de surveillance des armoires électriques
et baies serveurs et pour la gestion de différents paramètres des armoires électriques et baies ser-
veurs. Toute autre utilisation est non conforme.
Prière de contacter Rittal avant toute utilisation d’un capteur raccordé à l’extérieur de l’armoire ou
la baie.
Remarques relatives à la documentation, Consignes de sécurité, Description du produit
FR
Unité centrale CMC III / Unité centrale compacte CMC III 13
FR
3.3 Composition de la livraison
Unité centrale CMC III ou unité centrale compacte CMC III
Accessoires joints (fig. 1)
Notice d’installation et d’utilisation succincte
3.4 Conditions de fonctionnement
L’UC CMC III doit être mise en œuvre uniquement dans les conditions de fonctionnement
suivantes :
4 Montage
4.1 Instruction de montage
Le montage de l’UC CMC III est réalisé conformément à la fig. 2.
Placer l’UC CMC III de manière à ce que la face avant, avec émetteur et capteur, soit tournée
vers la porte à surveiller.
Fixer le film réflecteur fourni exactement face au détecteur d’accès infrarouge sur la porte ou la
paroi latérale.
5 Installation et utilisation
5.1 Organes de commande et de signalisation
Les organes de commande et de signalisation sont présentés sur la fig. 3.
Légende pour la fig. 3
1 Touche «C» pour l’acquittement des messages
2 Touche Reset cachée
3 LED multiple pour l’affichage d’état
4 Emplacement pour carte SD (pas pour la version «compacte»)
Plage de température tolérée +0°C…+45°C
Plage d’humidité tolérée 5 %…95 % d’humidité relative, sans condensation
Indice de protection IP 30 selon IEC 60 529
Remarque :
Il est conseillé d’adapter les réglages réseau avant le montage de l’appareil (voir
paragraphe 6).
Remarque :
Pour permettre la mesure exacte de la température avec le capteur de température
interne, il faut assurer une circulation d’air adéquate à l’intérieur de la baie, positionner
l’UC CMC III dans le flux d’air et ne pas obturer les ouïes du boîtier.
Si ceci ne peut être réalisé, alors le capteur de température externe doit être utilisé
comme alternative.
Remarque :
La distance entre le détecteur d’accès infrarouge de l’UC CMC III et son réflecteur ne
doit pas dépasser 15 cm. Si nécessaire, modifier l’installation de l’Unité Centrale de
manière appropriée.
Montage, Installation et utilisation
FR
14 Unité centrale CMC III / Unité centrale compacte CMC III
5 Détecteur d’accès infrarouge intégré
6 Mini raccordement USB pour la configuration
7 Entrées numériques (2 unités), par 24 V , 10 mA
8 Raccordement USB maître (pas pour la version «compacte»)
9 Raccordement d’un capteur de température externe
10 Raccordement RJ 12/RS 232 pour modules d’écran, GSM ou RNIS, 24 V , 500 mA
11 Interface Ethernet RJ 45 avec PoE
12 Raccordement CAN-Bus (Daisy Chain) pour détecteurs et unités de commande CMC III,
24 V , 1 A
13 Deuxième raccordement CAN-Bus (pas pour la version «compacte»), 24 V , 1 A
14 Tension d’alimentation 24 V (raccordement au bloc d’alimentation)
15 Tension d’alimentation 24 V (raccordement direct)
16 Sortie de relais pour alarme (contact sec, max. 24 V ,1 A)
L’unité centrale CMC III intègre également un fusible F5 avec les spécifications suivantes :
fusible lent, 450 V , 3,15 A, type 09773.15MXP Littelfuse.
5.2 Installation
En cas d’utilisation, insérer le capteur de température externe dans le connecteur à l’arrière de
l’UC CMC III (fig. 1, pos. 9) et le déployer jusqu’à point de mesure.
Raccorder le bloc d’alimentation externe (7030.060) au raccordement de l’alimentation 24 V
(fig. 3, pos. 14).
Le démarrage de l’appareil dure env. 1 minute. Pendant ce temps, l’affichage d’état clignote en
bleu à une fréquence irrégulière (fig. 3, pos. 3).
L’appareil est prêt à fonctionner lorsque l’affichage d’état est allumé en vert de manière continue.
Remarque :
Les sources d’alimentation aux bornes 7, 10, 12, 13 et 16 (fig. 3) doivent satisfaire aux
exigences des ’sources à puissance limitée’ (LPS) conformément à la Norme
UL 60950 et respecter les valeurs limites spécifiées plus haut.
Remarque :
L’unité centrale n’est plus sous tension à partir du moment où toutes les sources d’ali-
mentation sont déconnectées !
Remarque :
Le capteur de température interne est désactivé dès lors que le capteur externe est
connecté.
Remarque :
Le capteur de température externe doit être connecté avant que l’UC CMC III ne soit
alimentée.
Si le capteur externe est connecté après coup, il est alors nécessaire de redémarrer
l’UC CMC III pour que le capteur soit pris en compte et activé.
Installation et utilisation
Unité centrale CMC III / Unité centrale compacte CMC III 15
FR
Actionner et maintenir la touche «C» pour l’acquittement des messages présents (fig. 3, pos. 1)
lorsque l’affichage d’état clignote en rouge-bleu à la fin de la procédure de démarrage.
L’affichage d’état est ensuite allumé en vert de manière continue et l’appareil est prêt à fonction-
ner.
En cas d’échec de l’installation : voir paragraphe 1.1.
6 Configuration réseau
Raccorder l’appareil à votre ordinateur à l’aide d’un câble réseau via l’interface Ethernet (fig. 3,
pos. 11).
Modifier l’adresse IP de votre ordinateur à une adresse quelconque de la plage 192.168.0.xxx,
p. ex. 192.168.0.191. L’adresse présélectionnée 192.168.0.190 de l’appareil n’est pas autorisée.
Configurer le masque de sous-réseau sur la valeur 255.255.255.0.
Déconnecter éventuellement le serveur Proxy dans le navigateur pour avoir une liaison directe
avec l’appareil.
Saisir l’adresse http://192.168.0.190 dans le navigateur (fig. 4, pos. 1). La page d’accueil pour
l’identification est affiché sur l’appareil.
S’identifier comme utilisateur admin avec le mot de passe admin (fig. 4, pos. 2).
Dans la partie gauche de l’écran (zone de configuration), cliquer sur la ligne Processing Unit
(fig. 4, pos. 3) et dans la partie droite (zone de navigation), sur l’onglet Configuration (fig. 4,
pos. 4).
Dans le cadre Network, cliquer sur la fonction TCP/IP (fig. 4, pos. 5).
Remplacer l’adresse IP de l’Unité Centrale par une adresse compatible avec le réseau, dans le
cadre IPv4 Configuration de la fenêtre TCP/IP Configuration (fig. 4, pos. 6).
Si nécessaire, corriger le paramétrage du masque réseau et de la passerelle.
Sinon, sélectionner le paramétrage «DHCPv4» à la place de «Manual» pour une affectation d’IP
automatique.
Cliquer sur le bouton Save pour sauvegarder le paramétrage.
Modifier les réglages réseau de votre ordinateur aux valeurs d’origine de l’adresse IP et du mas-
que de sous-réseau.
Déconnecter le câble réseau du micro ordinateur.
Relier l’UC CMC III au réseau Ethernet via un câble réseau (fig. 3, pos. 11).
Si des mises à jour de logiciel sont éventuellement nécessaires : voir www.rittal.com ou sur deman-
de au service Rittal (voir paragraphe 7).
Remarque :
Il faut éventuellement utiliser un câble croisé pour cela.
Remarque :
Le paramétrage du protocole IPv4 est décrit en détail plus bas. Pour de plus amples
informations sur la configuration TCP/IP, se reporter au paragraphe 1.1.
Configuration réseau
FR
16 Unité centrale CMC III / Unité centrale compacte CMC III
7 Service
Pour toute question technique, veuillez vous adresser à :
Tél. : +49(0)2772 505-9052
Site Internet : www.rittal.com
Pour toute réclamation ou un service, veuillez vous adresser à :
Tél. : +49(0)2772 505-1855
Service
Enclosures
Power Distribution
Climate Control
IT Infrastructure
Software & Services
RITTAL GmbH & Co. KG
Postfach 1662 · D-35726 Herborn
Phone +49(0)2772 505-0 · Fax +49(0)2772 505-2319
E-mail: [email protected] · www.rittal.com
01.2014 / ID no. A45099 05 IT75
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18

Rittal CMC III Processing Unit Compact Installation Manual And Short User's Manual

Taper
Installation Manual And Short User's Manual
Ce manuel convient également à