15
Initial Start-up (No Load)
Before operating the home generator or placing it into
service, inspect the entire installation carefully.
Then begin testing the system without any electrical loads
connected, as follows:
1. Set generator’s main circuit breaker to its ON (closed)
position.
2. Install 15 Amp fuse in control panel.
3. Set generator’s system switch to AUTO.
4. Push MANUAL OVER-RIDE button on control panel.
NOTE: When the home generator is started for the very
first time, it will require that air in the gaseous fuel lines be
purged. This may take a few minutes.
5. DO NOT crank engine for more than 10 seconds, then
pause for 10 seconds to reduce heat in the starter.
6. Repeat process until engine starts.
7. Listen for unusual noises, vibration or other indications of
abnormal operation. Check for oil leaks while engine runs.
8. Let engine warm up for about five minutes to allow
internal temperatures to stabilize.
9. Connect an accurate AC voltmeter and a frequency
meter to check generator output at load side of circuit
breaker. Voltage should be 239-262 Volts, frequency
should be 62.0 - 62.5 Hz.
NOTE: If either parameter is outside these ranges, perform
the Engine Adjustments described below.
10. Check generator output between one of the generator
connection lugs and the neutral lug, then between the
other generator connection lug and the neutral lug.
In both cases, voltage reading should be between
119-131 Volts.
11. Push and hold MANUAL OVER-RIDE button on control
panel again until engine stops.
IMPORTANT: DO NOT proceed until you are certain that
generator AC voltage and frequency are correct and within
the stated limits. To obtain the proper generator frequency,
see Engine Adjustments.
Engine Adjustment
There are regional variances in the composition of natural
gas. Each home generator unit leaves the factory set for
NG operation. If the generator output voltage or frequency
measured during Initial Start-Up (paragraph #9) is outside
the listed ranges, the combustibility of the gas supplied at
the installation site may be substantially different from the
fuel used at the factory.
To adjust the engine for this difference, proceed as follows.
1. Remove the oil drain and control panel access covers.
2. Connect an accurate frequency meter to the line side of
the generator’s main circuit breaker.
3. Ensure that the 15 Amp fuse is installed.
4. Set the generator’s main circuit breaker ON.
5. Set the generator’s system switch to AUTO.
6. Push MANUAL OVER-RIDE button on control panel.
When the engine starts, allow it to warm up for five
minutes.
7. Normal no load frequency is 62.0 to 62.5 Hz. If
adjustment is needed at no load, slowly rotate
the governor adjustment nut (A) clockwise and/or
counterclockwise until frequency is 62.0 to 62.5 Hz.
8. Push and hold MANUAL OVER-RIDE button on control
panel again until engine stops.
9. Turn the service disconnect to the transfer switch off.
After a short time delay, the transfer switch will connect
to the generator.
10. Load generator to full load.
11. Connect an accurate frequency meter to the load side of
the generator’s main circuit breaker. Frequency should
be above 57.0 Hz.
12. If frequency is below 57.0 Hz, slowly rotate the
governor adjustment nut or screw clockwise and/or
counterclockwise until frequency is above 57.0 Hz.
13. Turn the service disconnect to the transfer switch on.
The transfer switch will connect to the utility after five
minutes.
14. After the engine has stopped running,
• If an adjustment was made in step 12, repeat steps
3 through 8.
• If an adjustment was not made in step 12, proceed
to step 15.
IMPORTANT: If the no load frequency falls out of the no
load parameter after full load adjustment is made, contact an
authorized service center.
15. Install the oil drain and control panel access covers.
A