APT XM Series Installation, Operation & Maintenance Manual

Taper
Installation, Operation & Maintenance Manual
Thank you for choosing an APT Surge
Protective Device (SPD). The XM is a high quality,
high energy surge suppressor designed to protect
sensitive equipment from damaging transient
overvoltages. The SPD is parallel connected
such that circuit ampacity is unlimited. Proper
installation is important to maximize performance.
Please follow steps outlined herein. These
instructions are not intended to replace national or
local codes. Follow all applicable electrical codes
to ensure compliance.
XM complies with latest regulatory actions and is
UL 1449 Listed (VZCA.E321351). See National
Electrical Code (NEC
®
) Article 285 regarding SPDs.
XM is a Type 2 SPD, intended for installation
on the load-side of the service disconnect. We
recommend connecting via a 20-30A circuit breaker
due to 10 AWG conductors. UL 1449 safety and
performance evaluations were performed with a
30A circuit breaker. The circuit breaker serves as
a disconnect switch and provides NEC
®
imposed
short circuit protection to the conductors in Type
2 applications.
Simplied Explanation of Operation
SPDs sense overvoltage and create a momentary
short circuit to redirect harmful surge energy to
earth ground. They reset automatically and wait
for the next surge. This is similar to the pressure
relief valve on a water heater: pressure goes up,
valve opens to relieve pressure and then resets. In
an electrical system, an SPD senses overvoltage,
shorts temporarily sending energy to ground and
then resets. SPDs are capable of repeating this
function thousands of times.
Parts List:
1 – XM suppressor including 3’ (~1m) conductors
1 - Data Sheet
1 - Installation Sheet (this document)
Specications
Temperature Operating -40
o
C (-40
o
F) to +85
o
C (+140
o
F)
Temperature Storage -55
o
C (-67
o
F) to +85
o
C (+149
o
F)
Wire Size & Installation Torque 10 AWG; 18 inch-pounds
Appropriate Circuit Breaker
20-30A
NEMA 250 Enclosure Rating
Type 4X with appropriate
sealing and sealing condulets
Only qualied licensed electricians should install or
service SPDs
SPDs should never be installed or serviced when
energized or during electrical storms
Use appropriate safety precautions including
Personal Protection Equipment
Failure to follow these instructions can result in
death, serious injury, and/or equipment damage
When used in outdoor applications, customer must
seal the conduit nipple using watertight ttings (not
included) to ensure a watertight connection
Read this manual in its entirety prior to installing
WARNING
Risk of Electric Shock
Installation, Operation
& Maintenance Manual
(800) 237-4567
·
(727) 535-6339
·
Fax (727) 539-8955
Advanced Protection Technologies
www.aptsurge.com
·
14550 58th Street North
·
Clearwater, Florida 33760
UL is a registered trademark of Underwriters Laboratories, NEC
®
and National Electrical Code are
registered trademarks of National Fire Protection Association, C62.41.1-2002, C62.41.2-2002,
C62.45-2002, C62.72-2007 are registered trademarks of IEEE.
European Authorized Representative
Obelis s.a.
Boulevard Général Wahis 53
1030 Brussels, BELGIUM
Tel: +(32) 2. 732.59.54
Fax: +(32) 2. 732.60.03
XM Series
Surge Protective Device (SPD)
INSTALLATION
Pre-Plan your installation. You need to accomplish the following:
Meet all National and Local codes. (NEC
®
Article 285 and UL 1449 address SPDs).
Conrm System voltage to SPD voltage. (120V SPD will fail instantly on 240V, 277V, etc.).
Verify that the SPD’s 100kA SCCR is greater than or equal to the available fault current.
(NEC
®
Article 285.6 compliance).
A 20-30A circuit breaker is required, having a kAIC rating equal to or greater than the
available fault current is required.
Mount SPD as close to panel or equipment as possible to keep leads short. (long leads hurt
performance).
Ensure leads are as short and straight as possible, including neutral and ground. If using a
breaker, use a breaker position that is close to the SPD and the panel’s neutral and ground.
Make sure system is grounded per NEC
®
and clear of faults before energizing SPD.
(inadvertent system problem may fail SPD).
Never Hi-Pot test Any SPD. (will prematurely fail SPD).
Do Not Install the XM through the bottom of a NEMA 3R panel. Dripping water into the hub
& wire entry area will prematurely fail the SPD. If installing in the bottom of a 3R panel,
install threaded and watertight hardware into the SPD such that it rises above the panel’s
standing-water line.
1. Use voltmeter to check voltages and ensure correct SPD. See Data Sheet for specs & wire-outs.
2. Ensure SPD SCCR and circuit breaker kAIC ratings are equal to or greater than the available
fault current.
3. Determine Mounting method – weather resistant equipment may be required.
4. If SPD has optional Dry Contact or Flush Mount Kit, pre-plan their installation.
5. Remove power from panel/source. Conrm panel/source is deenergized.
6. Identify breaker location and SPD location. Position SPD such that LEDs are most visible.
7. Remove an appropriately sized knockout from panel.
8. Mount SPD – weather resistant applications require additional sealing, o-rings, etc. (not included).
9. Connect conductors as appropriate – short and straight as possible. (Hi-Legs are Phase B).
10. Label or mark conductors as appropriate. (neutral: white, ground: green, energized: black,
hi-leg: orange).
11. Make sure system is bonded per NEC
®
and is clear of hazards or faults before energizing.
(N-G bonding not per NEC
®
will fail SPDs: #1 cause of SPD failures).
12. Energize and conrm proper operation of green LED indicators and/or options.
2
Figure 2
A
BC
GN
BREAKER
Figure 1
(Individual equipment installations may vary)
Use closest breaker
to SPD
Locate SPD close to
intended breaker
Keep Leads Short
as Possible
Avoid Sharp Bends
Rotate SPD such
that LED indicators
are most visible
Outdoor installation requires appropriate weather
sealing at hub (o-ring, gasket, sealing condulet, etc.)
To Protected Loads
LEADS SHORT & STRAIGHT
Cut off
Excess
Length
Do Not
Loop or
Coil
Short and
Straight
Figure 3
TYPICAL PANEL
INSTALLATION
X
NOT
GOOD
GOOD
SPD
Hex Standoff
(4 Provided)
Mounting Surface
Mounting Screws
(4 Places, Not Provided)
Flush Mount Kit Screws
(8 Provided)
Phase,Ground,
Neutral Wires
Flush Mount Plate
Removed Material
Safety Disconnectors
XMs have demonstrated 100kA Short Circuit
Current Ratings (SCCR). (See UL Label markings
on each SPD or see Data Sheet for specs.) A
20-30A circuit breaker is required as overcurrent
protection for this SPD. Follow applicable codes.
This device features internal overtemperature
protection that will disconnect effected surge
suppression components at the end of their useful
life, but will maintain power to the load – now
unprotected. If this situation is undesirable for the
application, follow these instructions for replacing
the device. The XM is ultrasonically welded closed
and contains no user serviceable parts.
Voltage Rating & Application
Before installing SPD, verify by nameplate voltage
or model number that it has the same voltage
rating as the power distribution system. See
attached Data Sheet or call APT Tech Support at
(800) 237-4567 as appropriate. The SPD’s specier
or user should be familiar with the conguration and
arrangement of the power distribution system. The
system is dened by how the secondary windings
of the transformer supplying the service entrance
main or load are congured. This includes whether
or not the transformer windings are referenced
to earth via a grounding conductor. The system
conguration is not based on how any specic load
or equipment is connected to a particular power
distribution system. SPDs should be installed per
the distribution system, not per a load or motors
wiring connection.
For example, suppose a 480V three phase motor
appears to be connected as a 480V Delta. In
actuality, the serving distribution system might
be a 480Y/277V grounded Wye, with or without a
neutral pulled to the motor or MCC. The system
is still a 480Y/277V Wye, even though the load
is connected as a Delta. A grounded Wye has a
dened reference to ground (i.e., neutral is bonded
to ground). In contrast, some Delta systems are
ungrounded, which have no reference to ground.
SPDs on Ungrounded Systems
Caution: Ungrounded systems are inherently
unstable and can produce excessively high
line-to-ground voltages during certain fault
conditions. During these fault conditions, any
electrical equipment including an SPD, may be
subjected to voltages which exceed their designed
ratings. This information is being provided to the
user so that an informed decision can be made
before installing any electrical equipment on an
ungrounded power system.
Attention: Les systèmes non mis à la terre sont
fondamentalement instables et peuvent produire
des tensions excessives entre la ligne haute
tension et la mise à la terre lors de certaines
conditions de défaut. Durant ces conditions de
défaut, tout appareil électrique, y compris un SPD,
peut être soumis à des tensions dépassant leurs
spécications nominales. Ces renseignements
sont fournis à l’utilisateur an qu’il puisse prendre
une décision informée avant d’installer un appareil
électrique sur un système d’alimentation qui n’est
pas mis à la terre.
Connecting Optional Form C Dry Contact
Three (3) 3’ (~1m) 18 AWG wires are included
through the hub with this option. (These are
smaller than the 10 AWG SPD conductors.) Gray
is Common, red is Normally Open and blue is
Normally Closed. (We generally recommend the
Normally Closed conguration because it detects
disconnected or failed wiring whereas Normally
Open does not.) Dry Contact wires to be connected
to Class 1 circuits only.
The contact is rated 250V, 5A. Higher energy
applications require supplemental relaying. This
option monitors suppression element condition
and is not intended for use as phase loss or phase
detection monitoring.
Figure 4
DIMENSIONS & WEIGHT
LH
XM SERIES
ENCLOSURE
10.7.13
10.7.13
10.7.13
LF
DMP
XM
8609
05A8609 -
8.28
(210.31)
3.67
(93.22)
3.00
(76.20)
2.21
(56.13)
7.41
(188.21)
0.19
(4.83)
3
V
WARNING
Conrm XO N-G Bonding at Upstream Transformer
Do Not Hi-Pot Test SPD
Resulting Damage is not Covered Under Warranty
Dry Contact
Leads
(18 AWG)
Power
Leads
(10 AWG)
Blue
Gray
Red
Figure 5
Normally Closed
(suggested):
Use Gray
and Blue
Normally Open:
Use Gray and Red
LEADS
NORMAL OPERATION
Green LED Indicators – The SPD includes two
green LED indicators per phase for redundancy
purposes. Full Protection is indicated when
both LEDs for every phase are illuminated. If
only one LED per phase is illuminated, then the
SPD is providing partial protection. If no LEDs
are illuminated, then the SPD is providing no
protection, or there is no power to the affected
phase(s).
Form C Dry Contact
Similar to the green LED above, the Dry Contact
will change state upon internal SPD failure.
UL 1283 required language concerning the
installation of EMI Filters
a) An insulated grounding conductor that is
identical in size and insulation material and
thickness to the grounded and ungrounded circuit
supply conductors, except that it is green with
or without one or more yellow stripes, is to be
installed as part of the circuit that supplies the lter.
Reference should be made to Table 250-122 of the
National Electrical Code regarding the appropriate
size of the grounding conductor.
b) The grounding conductor mentioned in item a is
to be grounded to earth at the service equipment
or other acceptable building earth ground such as
the building frame in the case of a high-rise steel-
frame structure.
c) Any attachment-plug receptacles in the vicinity
of the lter are to be of a grounding type, and the
grounding conductors serving these receptacles
are to be connected to earth ground at the service
equipment or other acceptable building earth
ground such as the building frame in the case of a
high-rise steel-frame structure.
d) Pressure terminal or pressure splicing connectors
and soldering lugs used in the installation of the
lter shall be identied as being suitable for the
material of the conductors. Conductors of dissimilar
metals shall not be intermixed in a terminal or
splicing connector where physical contact occurs
between dissimilar conductors unless the device
is identied for the purpose and conditions of use.
Maintenance
SPDs require minimal maintenance. We
recommend periodic inspection of diagnostic
indicators to ensure proper operation. We also
recommend keeping the SPD clean as appropriate.
Troubleshooting & Service
Please contact us for any service related issues.
We want to take care of any problems.
Quality SPDs withstand severe duty and attempt to
protect their load until failure. There are electrical
anomalies that SPDs cannot protect against. These
are generally Sustained Overvoltages also known
as Temporary Overvoltages (TOVs). In this context,
Sustained Overvoltages may be only a few cycles.
Failed SPDs tend to be symptoms, not root causes.
We suggest treating a failed SPD as a ‘canary in the
coalmine’ as there may be larger issues at play. As
a generalization, the single largest ‘killer of SPDs
is reference to ground issues. If the SPD shows
problems on startup, there is reasonable chance
of bonding/grounding/misapplication issue. This
permanently damages the unit. If not corrected, it
will happen again.
Any returns need a
Return Authorization (RA) number.
V
WARNING
Conrm XO N-G Bonding at Upstream Transformer
Do Not Hi-Pot Test SPD
Resulting Damage is not Covered Under Warranty
V
WARNING
VERIFY THAT ALL POWER CIRCUITS ARE
DEENERGIZED BEFORE MAKING CONNECTIONS
All electrical connections should be performed by a qualied
(licensed) electrician or technician. All wiring must comply with the
National Electrical Code (NEC
®
) and applicable local codes.
(800) 237-4567
·
(727) 535-6339
·
Fax (727) 539-8955
Advanced Protection Technologies
www.aptsurge.com
·
14550 58th Street North
·
Clearwater, Florida 33760
UL is a registered trademark of Underwriters Laboratories, NEC
®
and National Electrical Code are
registered trademarks of National Fire Protection Association, C62.41.1-2002, C62.41.2-2002,
C62.45-2002, C62.72-2007 are registered trademarks of IEEE.
12.30.14.lh.RevA #8962
European Authorized Representative
Obelis s.a.
Boulevard Général Wahis 53
1030 Brussels, BELGIUM
Tel: +(32) 2. 732.59.54
Fax: +(32) 2. 732.60.03
Pending
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

APT XM Series Installation, Operation & Maintenance Manual

Taper
Installation, Operation & Maintenance Manual

dans d''autres langues