Maytag MDG17PD Installation Instructions Manual

Taper
Installation Instructions Manual

Ce manuel convient également à

INSTALLATION INSTRUCTIONS
COMMERCIAL STACKED DRYER
Gas (120-Volt, 60-Hz) or Electric (120/240-Volt, 60-Hz)
www.maytag.com
Actual unit may or may not
contain doors with windows,
depending on model
W10135153B
W10135158A - SP
INSTRUCTIONS POUR L’INSTALLATION D’UNE
SÉCHEUSE COMMERCIALE SUPERPOSÉE
à gaz (120 Volts, 60 Hz) ou électrique (120/240 Volts, 60 Hz)
Selon le modèle, le présent
appareil n’offre peut-être pas
de hublot de porte.
Table of Contents/Table des matières . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2
TABLE OF CONTENTS
DRYER SAFETY............................................................................ 2
I
NSTALLATION REQUIREMENTS .............................................. 4
Tools and Parts .......................................................................... 4
Location Requirements.............................................................. 4
Electrical Requirements - Gas Dryer ........................................ 6
Electrical Requirements - Electric Dryer (U.S. only) ................ 6
Gas Supply Requirements ........................................................ 7
Venting Requirements .............................................................. 8
INSTALLATION INSTRUCTIONS GAS DRYER .................. 10
Make Gas Connection..............................................................10
C
onnect Vent ............................................................................10
Complete Installation ..............................................................10
INSTALLATION INSTRUCTIONS ELECTRIC DRYER........ 11
Make Electrical Connection......................................................11
Connect Vent ............................................................................15
Complete Installation ..............................................................15
ELECTRONIC CONTROL SETUP ...........................................15
MAINTENANCE INSTRUCTIONS ..........................................15
DRYER SAFETY
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
It is recommended that the owner post, in a prominent location, instructions for the customer’s use in the event the customer smells
gas. This information should be obtained from your gas supplier.
Post the following warning in a prominent location.
TABLE DES MATIÈRES
S
ÉCURITÉ DE LA SÉCHEUSE ..............................................17
EXIGENCES D’INSTALLATION................................................19
Outillage et pièces ....................................................................19
Exigences d'emplacement ......................................................19
Spécifications électriques - sécheuse à gaz ...........................21
Spécifications électriques - sécheuse électrique
(É.-U. seulement) .....................................................................21
Spécifications de l’alimentation en gaz ..................................22
Exigences concernant l'évacuation..........................................23
I
NSTRUCTIONS D’INSTALLATION SÉCHEUSE À GAZ ....25
Raccordement à la canalisation de gaz ......................................25
Raccordement du conduit d'évacuation ................................25
Achever l’installation ................................................................26
INSTRUCTIONS D’INSTALLATION SÉCHEUSE
ÉLECTRIQUE............................................................................26
Raccordement électrique ........................................................26
Raccordement du conduit d'évacuation ................................31
Achever l’installation ................................................................31
RÉGLAGE DE LA COMMANDE ÉLECTRONIQUE .............. 31
INSTRUCTIONS D’ENTRETIEN ..............................................31
3
WARNING: For your safety, the information in this manual must be followed to minimize
the risk of fire or explosion, or to prevent property damage, personal injury, or death.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this
or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's
instructions.
If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or
the gas supplier.
Clear the room, building, or area of all occupants.
In the State of Massachusetts, the following installation instructions apply:
Installations and repairs must be performed by a qualified or licensed contractor, plumber, or gasfitter qualified or licensed by
the State of Massachusetts.
If using a ball valve, it shall be a T-handle type.
A flexible gas connector, when used, must not exceed 3 feet.
WARNING: Gas leaks cannot always be detected by smell.
Gas suppliers recommend that you use a gas detector approved by UL or CSA.
For more information, contact your gas supplier.
If a gas leak is detected, follow the “What to do if you smell gas” instructions.
4
Location Requirements
If installing a gas dryer:
IMPORTANT: Observe all governing codes and ordinances.
Check code requirements: Some codes limit or do not permit
installation of clothes dryers in closets or sleeping quarters.
Contact your local building inspector.
Make sure that lower edges of the cabinet, plus the back and
bottom sides of the dryer, are free of obstructions to permit
adequate clearance of air openings for combustion air. See
“Recessed Area Installation Instructions below for minimum
spacing requirements.
NOTE:
The dryer must not be installed in an area where it will be
exposed to water and/or weather.
This dryer must not be installed in a closet with a door.
Recessed Area Installation Instructions
This dryer may be installed in a recessed area. Minimum
installation clearances can be found on the rear of the dryer.
The dryer must be exhausted outdoors.
INSTALLATION REQUIREMENTS
Tools and Parts
Gather the required tools and parts before starting installation.
Read and follow the instructions provided with any tools listed
here.
Tools needed
8" or 10" pipe wrench
8" or 10" adjustable wrench
Flat-blade screwdriver
Phillips screwdriver
Adjustable wrench that opens to 1" (2.5 cm) or 1" (25 mm)
hex-head socket wrench
Security T-20 TORX
®†
driver
Level
5/16" open-end wrench
Vent clamps
Pipe-joint compound resistant to LP gas
Caulk gun and caulk (for installing new exhaust vent)
Pliers
Putty knife
Parts supplied
Remove parts bag from dryer drum. Check that all parts were
included.
10-32 x 5/16" serrated screw (4)
Security cotter pin (2)
IMPORTANT: The gas installation must conform with local codes, or in the absence of local codes, with the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the Canadian Natural Gas and Propane Installation Code, CSA B149.1.
The dryer must be electrically grounded in accordance with local codes, or in the absence of local codes, with the National
Electrical Code, ANSI/NFPA 70 or Canadian Electrical Code, CSA C22.1.
†® TORX is a registered trademark of Textron Innovations, Inc.
5
Product Dimensions
Recessed
front view
Recessed
side view
M
inimum Installation Clearances
Additional clearances for wall, door, and floor moldings may be required
or if external exhaust elbow is used.
2
" (5 cm)
0" (0 cm)
1
2"
(
30 cm)
0" (0 cm)
0
"
(0 cm)
B
ack Sides Top Front
Recessed 2 in 0 in 12 in
(
5 cm) (0 cm) (30 cm)
Back View
29-1/4"
(74.3 cm)
approx. 1"
(2.5 cm)
23-3/4"
(60.3 cm)
door
t
op dryer
e
xhaust
bottom
dryer
exhaust
41"
(
104.1 cm)
76-3/4"
(195 cm)
1
3-1/2"
(34.3 cm)
Side View
27" (68.6 cm)
37"
(94.0 cm)
5-1/2" (14.0 cm)
10-1/2"
(26.7 cm)
3-1/8"
(7.9 cm)
7-1/2"
(19.1 cm)
5-3/8"
(13.7 cm)
top dryer
gas line
bottom
dryer
gas line
5-3/8"
(13.7 cm)
NOTE: Gas lines
located 1-1/2"
inward from
adjacent side.
6
Electrical Requirements Gas Dryer
IMPORTANT: The dryer must be electrically grounded in
accordance with local codes and ordinances or, in the absence
of local codes, with the National Electrical Code, ANSI/NFPA 70,
latest edition.
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrical installer determine that
the ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park, Quincy, MA 02269
A 120 volt, 60 Hz, AC only, 15-amp, fused electrical circuit
is required. A time-delay fuse or circuit breaker is also
recommended. It is recommended that a separate circuit
serving only this dryer be provided.
Recommended Ground Method
The dryer, when installed, must be electrically grounded in
accordance with local codes or, in the absence of local codes,
with the National Electrical Code, ANSI/NFPA 70, latest edition.
Electrical Requirements Electric Dryer
(U.S. Only)
IMPORTANT: The dryer must be electrically grounded in
accordance with local codes and ordinances or, in the absence
of local codes, with the National Electrical Code, ANSI/NFPA 70,
latest edition.
The National Electrical Code requires a 4-wire supply connection
for homes built after 1996, dryer circuits involved in remodeling
after 1996, and all mobile home installations.
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrical installer determine
that the ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park, Quincy, MA 02269
A four-wire or three-wire, single-phase, 120/240 volt, 60 Hz,
AC only electrical supply (or four-wire or three-wire,
120/208 volt, if specified on the model/serial rating plate) is
required on a separate, 30-amp circuit, fused on both sides of
the line. A time-delay fuse or circuit breaker is recommended.
Recommended Ground Method
It is your responsibility to contact a qualified electrical installer
to ensure that the electrical installation is adequate and in
conformity with the National Electrical Code, ANSI/NFPA 70,
latest edition, and all local codes and ordinances.
GROUNDING INSTRUCTIONS
SAVE THESE INSTRUCTIONS
For a grounded, cord-connected dryer:
This dryer must be grounded. In the event of a malfunction or
breakdown, grounding will reduce the risk of electric shock
by providing a path of least resistance for electric current.
This dryer is equipped with a cord having an equipment-
grounding conductor and a grounding plug. The plug must be
plugged into an appropriate outlet that is properly installed
and grounded in accordance with all local codes and
ordinances.
WARNING: Improper connection of the equipment-
grounding conductor can result in a risk of electric shock.
Check with a qualified electrician or service representative or
personnel if you are in doubt as to whether the dryer is
properly grounded. Do not modify the plug provided with the
dryer: if it will not fit the outlet, have a proper outlet installed
by a qualified electrician.
GROUNDING INSTRUCTIONS
SAVE THESE INSTRUCTIONS
For a grounded, cord-connected dryer:
This dryer must be grounded. In the event of a malfunction or
breakdown, grounding will reduce the risk of electric shock
by providing a path of least resistance for electric current.
This dryer uses a cord having an equipment-grounding
conductor and a grounding plug. The plug must be plugged
into an appropriate outlet that is properly installed and
grounded in accordance with all local codes and ordinances.
For a permanently connected dryer:
This dryer must be connected to a grounded metal,
permanent wiring system, or an equipment-grounding
conductor must be run with the circuit conductors and
connected to the equipment-grounding terminal or lead on
the dryer.
WARNING: Improper connection of the equipment-
grounding conductor can result in a risk of electric shock.
Check with a qualified electrician or service representative or
personnel if you are in doubt as to whether the dryer is
properly grounded. Do not modify the plug on the power
supply cord: if it will not fit the outlet, have a proper outlet
installed by a qualified electrician.
7
Flexible metal appliance connector
It is recommended that a new flexible stainless steel gas line,
design-certified by CSA International, be used for connecting
the dryer to the gas supply line. (The gas pipe which extends
through the lower rear of the dryer is provided with
3
8" male
pipe thread.)
Do not kink or damage the flexible stainless steel gas line
when moving the dryer.
Rigid pipe connection
The rigid pipe connection requires a combination of pipe fittings
to obtain an in-line connection to the dryer.
Must include a shutoff valve:
The supply line must be equipped with a manual shutoff
valve. In the U.S., the valve must be installed within 6 ft. (1.8
m) of dryer in accordance
with National Fuel Gas
Code, ANSI Z223.1. In
Canada, an individual
manual shutoff valve must
be installed in accordance
with the B149 installation
codes CAN/CGA B149.1
and CAN/CGA B149.2.
This valve should be
located in the same room
as the dryer. It should be in
a location that allows ease of opening and closing. Do not
block access to shutoff valve. The valve is for turning on or
shutting off gas to the dryer.
Installed in a confined area:
If the dryer is installed in a confined area such as a bathroom,
provision must be made for enough air for combustion and
ventilation. Check governing codes and ordinances or refer to
the “Recessed Area Installation Instructions” in the “Location
Requirements” section.
Gas Supply Requirements
IMPORTANT: Observe all governing codes and ordinances.
This installation must conform with all local codes and
ordinances. In the absence of local codes, installation must
conform with American National Standard, National Fuel Gas
Code ANSI Z223.1/NFPA 54.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park, Quincy, MA 02269
The design of this dryer has been certified by CSA International
for use at altitudes up to 10,000 feet (3048 m) above sea level at
the B.T.U. rating indicated on the model/serial plate. Burner input
adjustments are not required when the dryer is operated up to
this elevation.
When installed above 10,000 feet (3048 m), a four percent (4%)
reduction of the burner B.T.U. rating shown on the model/serial
plate is required for each 1,000 foot (305 m) increase in elevation.
For assistance when converting to other gas types and/or
installing above 10,000 feet (3048 m) elevation, contact your
local service company.
Type of Gas
This dryer is equipped for use with natural gas. It is design-
certified by CSA International for L.P. (propane and butane) gases
with appropriate conversion. No attempt shall be made to convert
the dryer from the gas specified on the serial/rating plate for use
with a different gas without consulting the serving gas supplier.
Conversion must be done by a qualified service technician.
Gas conversion kit part numbers are listed on the gas valve
burner base.
WARNING
Explosion Hazard
Use a new CSA International approved gas supply line.
Install a shut-off valve.
S
ecurely tighten all gas connections.
If connected to LP, have a qualified person make sure
gas pressure does not exceed 13" (33 cm) water
column.
Examples of a qualified person include:
licensed heating personnel,
authorized gas company personnel, and
authorized service personnel.
Failure to do so can result in death, explosion, or fire.
Gas Supply Line
Recommended method
Provide a gas supply line of
1
2" rigid (IPS) pipe to the dryer
location. Pipe joint compounds that resist the action of LP gas
must be used. Do not use TEFLON
®†
tape. With LP gas,
piping or tubing size can be
1
2" minimum. Usually, LP gas
suppliers determine the size and materials used in the system.
Alternate method
The gas supply may also be connected using
3
8" approved
copper or aluminum tubing. If the total length of the supply
l
ine is more than 20 feet (6.1 m), larger tubing will be required.
If using natural gas, do not use copper tubing. Pipe joint
compounds that resist the action of LP gas must be used.
†®TEFLON is a registered trademark of E.I. Du Pont De Nemours and Company.
D
B
C
A
A. Gas supply line
B. Shutoff valve in “open” position
C. To dryer
D. NPT 1/8” min. plugged tapping
Plan installation to use the fewest number of elbows and turns.
Allow as much room as possible when using elbows or making
turns. Bend vent gradually to avoid kinking.
Vent outlet is located at the center of the bottom dryer back.
The vent can be routed up, down, left, right, behind the dryer,
or straight out the back of the dryer.
Vent System Length
Maximum length of vent system depends upon the type of vent
used, number of elbows, and type of exhaust hood. The
maximum length for rigid vent is shown in the chart.
For vent systems not covered by the vent specification chart,
see your parts distributor.
If dryer is installed in a confined area, such as a bedroom
or bathroom, provision must be made for enough air
for combustion and ventilation. (Check governing codes and
ordinances.) See “Recessed Area Installation Instructions” in the
“Location Requirements” section.
8
Gas Supply Pressure Testing
A
1
8" NPT minimum plugged tapping, accessible for gauge
t
esting, must be installed immediately upstream of the installed
shut-off valve to the dryer.
The dryer must be disconnected from the gas supply piping
system during any pressure testing of the system at test
pressures in excess of
1
2 psig.
Venting Requirements
WARNING: To reduce the risk of fire, this dryer MUST BE
EXHAUSTED OUTDOORS.
The dryer vent must not be connected into any gas vent,
chimney, wall, ceiling, or a concealed space of a building.
Do not use an exhaust hood with a magnetic latch.
Do not install flexible metal vent in enclosed walls, ceilings,
or floors.
4" (10.2 cm) heavy metal vent and clamps must be used.
Use clamps to seal all joints. Vent must not be connected or
secured to the dryer with screws. Do not use duct tape.
IMPORTANT: Observe all governing codes and ordinances.
Use a heavy metal vent. Do not use plastic or metal foil vent.
Rigid metal vent is recommended to prevent crushing and
kinking.
Flexible metal vent must be fully extended and supported when
the dryer is in its final position. Remove excess flexible metal vent
to avoid sagging and kinking that may result in reduced airflow
and poor performance.
An exhaust hood should cap the vent to prevent rodents and
insects from entering the home or business.
Exhaust hood must be at least 12" (30.5 cm) from the ground
or any object that may be in the path of the exhaust (such as
flowers, rocks, or bushes).
If using an existing vent system, clean lint from the entire length
of the system and make sure exhaust hood is not plugged with
lint. Replace any plastic or metal foil vent with rigid metal vent.
WARNING
Fire Hazard
Use a heavy metal vent.
Do not use a plastic vent.
Do not use a metal foil vent.
Failure to follow these instructions can result in death
or fire.
A
B
Exhaust Air Flow
A. Good
B. Better
Rigid Metal Vent
No. of 90° turns
4" (10.2 cm) Diameter Exhaust Hoods
Maximum Vent Length
130 ft. (39.6 m)
125 ft. (38.1 m)
115 ft. (35.1 m)
106 ft. (32.3 m)
98 ft. (29.9 m)
0
1
2
3
4
129 ft. (39.3 m)
119 ft. (36.3 m)
109 ft. (33.2 m)
100 ft. (30.5 m)
92 ft. (28.0 m)
Box Hood and Louvered Style Angled Hood Style
If an exhaust hood cannot be used:
The outside end of the main vent should have a sweep elbow
directed downward. If the main vent travels vertically through the
roof, rather than through the wall, install a 180° sweep elbow on
the end of the vent at least 2 feet (61 cm) above the highest part
of the building. The opening in the wall or roof shall have a
diameter 1/2" (1.3 cm) larger than the vent diameter. The vent
should be centered in the opening.
Do not install screening or cap over the end of the vent.
Multiple Dryer Venting
A main vent can be used for venting a group of dryers. The
main vent should be sized to remove 200 CFM of air per dryer
(min. static pressure of 0.06 inch water column TOTAL).
Large-capacity lint screens of proper design may be used in
the main vent if checked and cleaned frequently. The room
where the dryers are located should have make-up air equal
to or greater than the CFM of all the dryers in the room.
Back-draft Damper Kits, Part No. 3391910, are available from
y
our dealer or distributor and should be installed in the vent of
each dryer to prevent exhausted air from returning into the
dryers and to keep the exhaust in balance within the main
v
ent. Unobstructed air openings are required.
Each vent should enter the main vent at an angle pointing in the
direction of the airflow. Vents entering from the opposite side
should be staggered to reduce the exhausted air from interfering
with the other vents.
The maximum angle of each vent entering the main vent should
be no more than 30°.
Keep air openings free of dry cleaning fluid fumes. Fumes create
acids which, when drawn through the dryer heating units, can
damage dryers and loads being dried.
A clean-out cover should be located on the main vent for periodic
cleaning of the vent system.
9
A. Individual dryer vent
B. Main vent
air flow
3
max.
A
B
A
A. Exhaust hood or elbow
B. Wall
C. Main collector vent
D. Horizontal vent
E. 180° sweep elbow
F. Vertical vent
G. Roof
E
B
G
C
D
2
ft. (61 cm) min.
a
bove highest
point of building
F
C
M
in. 12
"
(30 cm) clearance
a
bove any accumulation
o
f snow, ice, or debris such
a
s leaves.
10
INSTALLATION INSTRUCTIONS GAS DRYER
Make Gas Connection
1. Remove red cap from gas pipe.
2. Connect gas supply to dryer. Use pipe-joint compound
resistant to the action of L.P. gas for gas connections. If
flexible metal tubing is used, be certain there are no kinks.
If necessary for service, open the toe panel. Use a putty knife
to press on the toe panel locks located at the upper corners
of the toe panel. Pull downward on the toe panel to open. Toe
panel is hinged at the bottom.
3. Open the shutoff valve in the gas supply line.
4. Test all connections by brushing on an approved noncorrosive
leak-detection solution. Bubbles will show a leak. Correct any
leak found.
Connect Vent
1. Using a 4" (10.2 cm) clamp, connect vent to exhaust outlet
on rear of dryer. If connecting to existing vent, make sure the
vent is clean. The dryer vent must fit over the dryer exhaust
outlet and inside the exhaust hood. Make sure the vent is
secured to exhaust hood with a 4" (10.2 cm) clamp.
2. Using two or more people, move dryer to desired installation
location. Do not crush or kink vent. Make sure dryer is level.
3. Check that there are no kinks in the flexible gas line.
Complete Installation
1. With dryer in final position, place level on top of the dryer, first
side to side; then front to back. If the dryer is not level, adjust
the legs of the dryer up or down until the dryer is level.
2. Using a Torx T20 security driver, open the control panel and
rest it on the bottom edge of the opening.
3. For added security between the upper dryer and the collar,
insert the cotter hair pin through the connecting bolt.
4. Close the control panel.
5. Plug into a grounded 3 prong outlet.
6. Check dryer operation.
Select a full heat cycle, let the dryer run for at least five
minutes. Dryer will stop when time is used up.
NOTE: Dryer door must be closed for dryer to operate. When
door is opened, dryer stops, but time continues to count
down. To restart dryer, close door and reselect cycle.
7. If the burner does not ignite and you can feel no heat inside
the dryer, shut off dryer for five minutes. Check that all supply
valve controls are in “ON” position and that the electrical cord
is plugged in. Repeat five-minute test.
INSTALLATION INSTRUCTIONS ELECTRIC DRYER
Make Electrical Connection
Power Supply Cord Method U.S. Only
This dryer is manufactured ready to install with a 3-wire
electrical supply connection. The neutral ground conductor is
permanently connected to the neutral conductor (white wire)
within the dryer. If the dryer is installed with a 4-wire electrical
supply connection, the neutral ground conductor must be
removed from the external ground connector (green screw), and
secured under the neutral terminal (center or white wire) of the
terminal block. When the neutral ground conductor is secured
under the neutral terminal (center or white wire) of the terminal
block, the dryer cabinet is isolated from the neutral conductor.
1. Disconnect power.
2. Remove hold-down screw and the terminal block cover.
3. Assemble
3
4" UL-listed strain relief (UL marking on strain
relief) into the hole below the terminal block opening. Tighten
strain relief screws just enough to hold the two clamp
sections together. Install power supply cord through the
strain relief.
4. Complete installation following instructions for your type of
electrical connection:
Four-wire (recommended method)
Three-wire (if four-wire is not available)
11
B
C
A
A. Strain relief clamp sections
B. Dryer cabinet
C. Strain relief screws
5. Remove the center terminal block screw.
6. Remove the appliance neutral ground wire
from the external ground conductor screw.
Fasten under center, silver-colored
terminal block screw.
7. Connect the ground wire of the power
supply cord to the external ground
conductor screw. Tighten screw.
8. Connect the neutral wire (white or center)
of the power supply cord under the center
screw of the terminal block. Tighten
screw.
9. Connect the other wires to outer terminal
block screws. Tighten screws.
10. Tighten strain relief screws.
11. Insert tab of the terminal block cover into
slot of the dryer rear panel. Secure cover
with hold-down screw.
Four-wire power supply cord must have four, No. 10 copper wires and match a four-wire
receptacle of NEMA Type 14-30R. The fourth wire (ground conductor) must be identified
by a green cover and the neutral conductor by a white cover.
B
D
C
G
F
E
A
A. Spade terminals with
upturned ends
B. Neutral
C.
3
4" UL-listed strain
relief
D. Neutral (white)
E. Ring terminals
F. Ground wire
G. Ground prong
A. External ground conductor screw
B. Appliance neutral ground wire
C. Center terminal block screw
D. Outer terminal block screws
E. Strain relief screw
F. Neutral (center wire)
G. Ground wire
Power Supply Cord,
Four-wire electrical connection:
C
B
A
F
G
E
D
Power Supply Cord Method U.S. Only
If local codes do not permit the connection of a neutral ground
wire to the neutral wire, see “Optional 3-wire connection”
section.
A 4-wire power supply connection must be used when the
appliance is installed in a location where grounding through the
neutral conductor is prohibited. Grounding through the neutral
i
s prohibited for (1) new branch-circuit installations, (2) mobile
homes, (3) recreational vehicles, and (4) areas where local
codes prohibit grounding through the neutral conductors.
C
D
B
A
A. External ground conductor screw
B. Tab
C. Terminal block cover
D. Hold-down screw
12
A. Spade terminals with upturned ends
B. Ring terminals
C. Neutral (white or center)
D.
3
4" UL-listed strain relief
E. Neutral
A. External ground conductor screw
B. Center terminal block screw
C. Outer terminal block screws
D. Strain relief screw
E. Neutral (center wire)
F. Appliance neutral ground wire
A. Separate copper ground wire
B. External ground conductor screw
C. Appliance neutral ground wire
D. Center terminal block screw
E. Outer terminal block screws
F. Strain relief screw
G. Neutral (center wire)
G
F
E
Power Supply Cord,
Three-wire electrical connection:
B
A
E
F
D
C
Three-wire power supply cord must
have three, No. 10 copper wires and
match a three-wire receptacle of NEMA
Type 10-30R.
E
C
D
T
his blade connected to
t
his conductor.
B
A
5. Loosen or remove the center terminal
block screw.
6. Connect the neutral wire (white or center)
of the power supply cord to the center,
silver-colored terminal screw of the
terminal block. Tighten screw.
7
. Connect the other wires to outer terminal
block screws. Tighten screws.
8. Tighten strain relief screws.
9. Insert tab of the terminal block cover into
slot of the dryer rear panel. Secure cover
with hold-down screw.
D
A
C
B
5. Remove the center terminal block screw.
6. Remove the appliance neutral ground wire
from the external ground conductor
screw. Connect the appliance neutral
ground wire and the neutral wire (white or
center) of the power supply cord under
the center, silver-colored terminal block
screw. Tighten screw.
7. Connect the other wires to outer terminal
block screws. Tighten screws.
8. Tighten strain relief screws.
9. Insert tab of the terminal block cover into
slot of the dryer rear panel. Secure cover
with hold-down screw.
10. After reattaching the terminal cover,
connect a separate copper ground wire
from the external ground conductor screw
to an adequate ground.
If codes permit and a separate ground wire is
used, it is recommended that a qualified
electrician determine that the ground path is
adequate.
Use this method where local codes permit connecting
neutral ground wire to neutral wire:
Use this method where local codes do not permit
connecting neutral ground wire to neutral wire:
13
Direct Wire Method U.S. Only
Direct wire cable must match power supply (4-wire or 3-wire)
and be:
Flexible armored cable or nonmetallic sheathed copper cable
(with ground wire), protected with flexible metallic conduit.
All current-carrying wires must be insulated.
10-gauge solid copper wire (do not use aluminum).
At least 5 ft. (1.52 m) long.
1. Disconnect power.
2. Remove hold-down screw and terminal block cover.
3. Install
3
4" conduit connector into the hole below the terminal
block opening. Connect flexible metallic conduit and tighten
connector screw. Install direct wire cable through the flexible
metallic conduit.
4. Complete installation following instructions for your type of
electrical connection:
Four-wire (recommended method)
Three-wire (if four-wire is not available)
C
D
B
A
A. External ground conductor screw
B. Tab
C. Terminal block cover
D. Hold-down screw
A
to
disconnect
box
B
D
5" (12.7 cm)
3
1
2
" (8.9 cm)
1" (2.5 cm)
of wires
stripped of
insulation
C
Strip 5" (12.7 cm) of outer covering
from end of cable. Leave green or bare
ground wire at 5" (12.7 cm). Cut 1
1
2
"
(3.8 cm) from 3 remaining wires. Strip
insulation back 1" (2.5 cm).
Shape ends
of wires into
a hook.
C
B
A
E
D
F
5. Remove the center terminal block screw.
6. Remove the appliance neutral ground
wire from the external ground conductor
screw. Fasten under center, silver-
colored terminal block screw.
7. Connect the ground wire (green or bare)
of the direct wire cable to the external
ground conductor screw. Tighten screw.
8. Place the hooked end of the neutral wire
(white or center) of the direct wire cable
under the center screw of the terminal
block (hook facing right). Squeeze hook
end together. Tighten screw.
9. Place the hooked ends of the other
direct wire cable wires under the outer
terminal block screws (hook facing right).
Squeeze hooked ends together. Tighten
screws.
10. Insert tab of the terminal block cover into
slot of the dryer rear panel. Secure cover
with hold-down screw.
Direct Wire,
Four-wire electrical connection:
A.
3
4" conduit connector
B. Neutral (white or center)
C. Ground wire (green or bare)
D. 10-gauge, 3 wire with ground wire
in flexible metallic conduit0
A. External ground conductor screw
B. Appliance neutral ground wire
C. Center terminal block screw
D. Outer terminal block screws
E. Neutral (center wire)
F. Green or bare ground wire
B
C
A
A. Conduit connector
B. Dryer cabinet
C. Connector screw
14
A.
3
4" conduit connector
B. Neutral (white or center)
C. 10-gauge, 3 wire with ground wire
in flexible metallic conduit
A. External ground conductor screw
B. Center terminal block screw
C. Outer terminal block screws
D. Neutral (center wire)
E. Appliance neutral ground wire
Shape ends
of wires into
a hook.
Strip 3
1
2
" (8.9 cm) of outer
covering from end of cable. Strip
insulation back 1" (2.5 cm). If using
3 wire cable with ground wire, cut
green or bare wire even with outer
covering.
T
hree wire with ground wire: green or bare
wire cut short. Wire is not used. Dryer is
grounded through neutral conductor.
t
o
d
isconnect
b
ox
1" (2.5 cm)
of wires
stripped of
insulation
3
1
2" (8.9 cm)
5. Loosen or remove the center terminal
block screw.
6. Place the hooked end of the neutral wire
(white or center) of the direct wire cable
under the center screw of the terminal
block (hook facing right). Squeeze
hooked end together. Tighten screw.
7. Place the hooked ends of the other
direct wire cable wires under the outer
terminal block screws (hook facing right).
Squeeze hooked ends together. Tighten
screws.
8. Insert tab of the terminal block cover into
slot of the dryer rear panel. Secure cover
with hold-down screw.
5. Remove the center terminal block screw.
6. Remove the appliance neutral ground wire
from the external ground conductor screw.
Connect the appliance neutral ground wire
and the neutral wire (white or center) of the
direct wire cable under the center, silver-
colored terminal block screw. Tighten
screw.
7. Connect the other wires to outer terminal
block screws. Tighten screws.
8. Insert tab of the terminal block cover into
slot of the dryer rear panel. Secure cover
with hold-down screw.
9. After reattaching the terminal cover,
connect a separate copper ground wire
from the external ground connector screw
to an adequate ground.
If codes permit and a separate ground wire
is used, it is recommended that a qualified
electrician determine that the ground path
is adequate.
D
irect Wire,
Three-wire electrical connection:
Use this method where local codes permit
c
onnecting neutral ground wire to
neutral wire:
Use this method where local codes do
not permit connecting neutral ground
wire to neutral wire:
A
B
C
A
B
C
D
E
A. Separate copper ground wire
B. External ground conductor screw
C. Appliance neutral ground wire
D. Center terminal block screw
E. Outer terminal block screws
F. Neutral (center wire)
F
E
D
A
C
B
15
Connect Vent
1. Using a 4" (10.2 cm) clamp, connect vent to exhaust outlet
in dryer. If connecting to existing vent, make sure the vent is
clean. The dryer vent must fit over the dryer exhaust outlet
and inside the exhaust hood. Make sure the vent is secured
to exhaust hood with a 4" (10.2 cm) clamp.
2. Using two or more people, move dryer to desired installation
location. Do not crush or kink vent. Make sure dryer is level.
Complete Installation
1. With dryer in final position, place level on top of the dryer, first
side to side; then front to back. If the dryer is not level, adjust
the legs of the dryer up or down until the dryer is level.
2. Using a Torx T20 security driver, open the control panel and
rest it on the bottom edge of the opening.
3. For added security between the upper dryer and the collar,
insert the cotter hair pin through the connecting bolt.
4. Close the control panel.
5. Plug in dryer or reconnect power.
6 Check dryer operation.
Select a full heat cycle, let the dryer run for at least five
minutes. Dryer will stop when time is used up.
NOTE: Dryer door must be closed for dryer to operate. When
door is opened, dryer stops, but time continues to count
d
own. To restart dryer, close door and reselect cycle.
7. Now start the dryer and allow it to complete a full heat cycle
to make sure it is working properly.
ELECTRONIC CONTROL SETUP
See Tech Sheet for information on setup.
Maintenance instructions:
Clean lint screen after each cycle.
Removing accumulated lint:
From inside the dryer cabinet:
Lint should be removed every 2 years or more often,
depending on dryer usage. Cleaning should be done
by a qualified person.
From the exhaust vent:
Lint should be removed every 2 years, or more often,
depending on dryer usage.
Keep area around dryer clear and free from combustible
materials, gasoline and other flammable vapors and liquids.
Keep dryer area clear and free from items that would obstruct
the flow of combustion and ventilation air.
If dryer does not operate, check the following:
Electrical supply is connected.
Circuit breaker is not tripped or house fuse is not blown.
Door is closed.
Controls are set in a running or “ON” position.
Cycle has been selected.
For gas dryers, check that gas supply shutoff valves are set
in open position.
If you need assistance:
The Commercial Laundry Support Center will answer any
questions about operating or maintaining your dryer not covered
in the Installation Instructions. Just dial 1-800 NO BELTS
(1-800-662-3587) the call is toll free.
When you call, you will need the dryer model number and serial
number. Both numbers can be found on the serial-rating plate
located in the dryer door well.
MAINTENANCE INSTRUCTIONS
MAYTAG COMMERCIAL WASHER, DRYER, STACKED DRYER/
DRYER, COMMERCIAL STACK LAUNDRY, AND MULTI-LOAD
COIN OPERATED COMMERCIAL WASHERS AND DRYERS
WARRANTY
LIMITED WARRANTY ON PARTS
For the first five years from the date of purchase, when this commercial appliance is installed, maintained and operated according to the
instructions attached to or furnished with the product, Maytag brand of Whirlpool Corporation (thereafter “Maytag”) will pay for factory
specified parts or original equipment manufacturer parts to correct defects in materials or workmanship. Proof of original purchase date
is required to obtain service under this warranty.
ITEMS MAYTAG WILL NOT PAY FOR
1. All other costs including labor, transportation, or custom duties.
2. Service calls to correct the installation of your commercial appliance, to instruct you how to use your commercial appliance, to
replace or repair fuses, or to correct external wiring or plumbing.
3. Repairs when your commercial appliance is used for other than normal, commercial use.
4. Damage resulting from improper handling of product during delivery, theft, accident, alteration, misuse, abuse, fire, flood, acts of
God, improper installation, installation not in accordance with local electrical or plumbing codes, or use of products not approved
by Maytag.
5. Pickup and Delivery. This commercial appliance is designed to be repaired on location.
6. Repairs to parts or systems resulting from unauthorized modifications made to the commercial appliance.
7. The removal and reinstallation of your commercial appliance if it is installed in an inaccessible location or is not installed in
accordance with published installation instructions.
8. Chemical damage is excluded from all warranty coverage.
9. Changes to the building, room, or location needed in order to make the commercial appliance operate correctly.
DISCLAIMER OF IMPLIED WARRANTIES; LIMITATIONS OF REMEDIES
CUSTOMER'S SOLE AND EXCLUSIVE REMEDY UNDER THIS LIMITED WARRANTY SHALL BE PRODUCT REPAIR AS PROVIDED
HEREIN. IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE,
ARE LIMITED TO ONE YEAR OR THE SHORTEST PERIOD ALLOWED BY LAW. WHIRLPOOL SHALL NOT BE LIABLE FOR
INCIDENTAL OR CONSEQUENTIAL DAMAGES. SOME STATES AND PROVINCES DO NOT ALLOW THE EXCLUSION OR LIMITATION
OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, OR LIMITATIONS ON THE DURATION OF IMPLIED WARRANTIES OF
MERCHANTABILITY OR FITNESS, SO THESE EXCLUSIONS OR LIMITATIONS MAY NOT APPLY TO YOU. THIS WARRANTY GIVES
YOU SPECIFIC LEGAL RIGHTS AND YOU MAY ALSO HAVE OTHER RIGHTS, WHICH VARY FROM STATE TO STATE OR PROVINCE
TO PROVINCE.
If you need service, please contact your authorized Maytag Commercial Laundry distributor. To locate your authorized Maytag
Commercial Laundry distributor, or for web inquiries, visit www.MaytagCommercialLaundry.com.
9/07
For written correspondence:
Maytag Commercial Laundry Service Department
2000 M-63 North
Benton Harbor, Michigan 49085 USA
16
17
SÉCURITÉ DE LA SÉCHEUSE
Risque possible de décès ou de blessure grave si vous ne 
suivez pas immédiatement les instructions.
Risque possible de décès ou de blessure grave si vous 
ne suivez pas les instructions.
Tous les messages de sécurité vous diront quel est le danger potentiel et vous disent comment réduire le risque de blessure et 
ce qui peut se produire en cas de non-respect des instructions.
Votre sécurité et celle des autres est très importante.
Nous donnons de nombreux messages de sécurité importants dans ce manuel et sur votre appareil ménager. Assurez-vous de 
toujours lire tous les messages de sécurité et de vous y conformer.
AVERTISSEMENT
DANGER
V
oici le symbole d’alerte de sécurité.
Ce symbole d’alerte de sécurité vous signale les dangers potentiels de décès et de blessures graves à vous 
et à d’autres.
Tous les messages de sécurité suivront le symbole d’alerte de sécurité et le mot “DANGER” ou
“AVERTISSEMENT”. Ces mots signifient :
POUR VOTRE SÉCURITÉ
Ne pas entreposer ni utiliser de l'essence ou d'autres produits liquides ou gazeux inflammables à proximité de cet appareil ou de
tout autre appareil électroménager.
On recommande que le propriétaire place les instructions à l'usage du client à un endroit bien visible, pour le cas le client
percevrait une odeur de gaz. Ces renseignements doivent être obtenus auprès de votre fournisseur de gaz.
Placer l'avertissement qui suit à un endroit bien visible.
AVERTISSEMENT : Pour votre sécurité, les renseignements dans ce manuel doivent
être observés pour réduire au minimum les risques d’incendie ou d’explosion ou pour
éviter des dommages au produit, des blessures ou un décès.
Ne pas entreposer ou utiliser de l’essence ou d’autres vapeurs ou liquides
inflammables à proximité de cet appareil ou de tout autre appareil électroménager.
QUE FAIRE DANS LE CAS D’UNE ODEUR DE GAZ :
Ne pas tenter d’allumer un appareil.
Ne pas toucher à un commutateur électrique; ne pas utiliser le téléphone se trouvant
sur les lieux.
Évacuer tous les gens de la pièce, de l’édifice ou du quartier.
Appeler immédiatement le fournisseur de gaz d’un téléphone voisin. Suivre ses
instructions.
À défaut de joindre votre fournisseur de gaz, appeler les pompiers.
L’installation et l’entretien doivent être effectués par un installateur qualifié, une
agence de service ou le fournisseur de gaz.
18
IMPORTANTES INSTRUCTIONS DE SÉCURITÉ
Pour réduire le risque d'incendie, de choc électrique ou de blessure lors de l'utilisation de
l
a sécheuse, il convient d'observer certaines précautions élémentaires dont les suivantes :
AVERTISSEMENT :
I L
ire toutes les instructions avant d'utiliser la sécheuse.
I Ne pas placer des articles exposés aux huiles de cuisson
dans votre sécheuse. Les articles contaminés par des
huiles de cuisson peuvent contribuer à une réaction
chimique qui pourrait causer à la charge de s'enflammer.
I Ne pas faire sécher dans la machine des articles qui ont
déjà été nettoyés, lavés, imbibés, ou tachés d'essence,
de solvants pour nettoyage à sec, d'autres substances
inflammables, ou de substances explosives puisqu'elles
dégagent des vapeurs qui peuvent provoquer un
incendie ou une explosion.
I Ne pas permettre à des enfants de jouer sur ou à
l'intérieur de la sécheuse. Une surveillance étroite est
nécessaire lorsque la sécheuse est utilisée près d'eux.
I Avant d'enlever la sécheuse du service ou la jeter, enlever
la porte du compartiment de séchage.
I
Ne pas mettre la main dans la sécheuse si le tambour est
en mouvement.
I N
e pas réparer ni remplacer une pièce de la sécheuse ou
essayer d'en faire l'entretien à moins d'une recommandation
spécifique dans le guide d'utlilisation et d'entretien, ou
p
ubliée dans les instructions de réparation par l'utilisateur
que vous comprenez et pouvez exécuter avec compétence.
CONSERVEZ CES INSTRUCTIONS
I
Ne pas installer ni entreposer la sécheuse où elle sera
exposée aux intempéries.
I Ne pas jouer avec les commandes.
I Ne pas utiliser un produit assouplissant de tissu ou des
produits pour éliminer la statique à moins qu'ils ne soient
recommandés par le fabricant du produit assouplissant de
tissu ou du produit.
I Ne pas utiliser la chaleur pour faire sécher des articles
fabriqués avec du caoutchouc mousse ou des matériaux
semblables.
I Nettoyer le filtre à charpie avant et après chaque charge.
I Ne pas laisser la charpie, la poussière, ou la saleté
s'accumuler autour du système d'évacuation ou autour de
l'appareil.
I Un nettoyage périodique de l'intérieur de la sécheuse et du
conduit d'évacuation doit être effectué par une personne
qualifiée.
I Voir les instructions d'installation pour les exigences de
liaison de l'appareil à la terre.
A
VERTISSEMENT : L’odorat ne permet pas toujours la détection d’une fuite de gaz.
L
es distributeurs de gaz recommandent l’emploi d’un détecteur de gaz (homologation UL ou CSA).
Pour d’autre information, contacter le fournisseur de gaz local.
En cas de détection d’une fuite de gaz, exécuter les instructions “Que faire dans le cas d’une odeur de gaz”.
19
Exigences d’emplacement
Pour l’installation d’une sécheuse à gaz :
IMPORTANT : Respecter les dispositions de tous les codes
et règlements en vigueur.
Déterminer les exigences des codes : Certains codes limitent
ou prohibent l’installation d’une sécheuse dans un placard ou
une chambre à coucher. Consulter l’inspecteur local des
bâtiments.
EXIGENCES D’INSTALLATION
Veiller à ce que les bords inférieurs de la caisse ainsi que
l’arrière et les côtés inférieurs de la sécheuse soient exempts
d’obstructions, afin de permettre le passage adéquat de l’air
d
e combustion. Voir la section “Instructions pour l’installation
dans un encastrement” pour l’espace de dégagement
minimal.
REMARQUE :
La sécheuse ne doit pas être installée en un endroit elle
serait exposée à de l’eau ou aux intempéries.
Cette sécheuse ne doit pas être installée dan un placard muni
d'une porte.
Instructions pour l’installation dans
un encastrement
Cette sécheuse peut être installée dans un encastrement. Les
distances de séparation minimales sont mentionnées à l'arrière
de la sécheuse.
Le circuit d’évacuation de la sécheuse doit être relié à l’extérieur.
Outillage et pièces
Rassembler les outils et pièces nécessaires avant de commencer
l
’installation. Lire et respecter les instructions d’installation
fournies avec chacun des outils de cette liste.
O
utillage nécessaire
Clé à tube de 8" ou 10"
C
à molette de 8" ou 10"
Tournevis à lame plate
T
ournevis Phillips
Clé à molette avec
ouverture jusqu'à 1"
(2,5 cm) ou clé à douille
hexagonale de 1" (25 mm)
Tournevis de sécurité
TORX
®
T-20
Niveau
Clé à douille de 5/16"
B
rides de fixation
Composé d’étanchéité des
raccords filetés - résistant
au propane
Pistolet à calfeutrage et
composé de calfeutrage
(pour l’installation d’un
nouveau circuit
d’évacuation)
Pince
Couteau à mastic
Pièces fournies
Retirer le sac de pièces du tambour de la sécheuse.
Vérifier la présence de toutes les pièces.
Vis cannelées de 10-32 x
5/16 po (4)
Goupille fendue (2)
†® TORX est une marque déposée de Textron Innovations, Inc.
20
Encastrement,
vue avant
Encastrement,
vue latérale
Distances de séparation minimales
On doit prévoir un espacement additionnel pour tenir compte éventuellement
des moulures du mur, de la porte et du plancher, ou si le circuit d’évacuation
comporte un coude.
2 po (5 cm)
0
po (0 cm)
1
2 po
(
30 cm)
0 po (0 cm)
0
po
(0 cm)
Arrière Côtés Dessus Avant
E
ncastré 2 po 0 po 12 po
(5 cm) (0 cm) (30 cm)
Dimensions du produit
29-1/4 po
(74,3 cm)
approx. 1 po
(2,5 cm)
23-3/4 po
(60,3 cm)
Porte
76-3/4 po
(195 cm)
Vue latérale
27 po (68,6 cm)
5-1/2 po (14,0 cm)
10-1/2 po
(26,7 cm)
Vue arrière
B
ouche de
décharge
supérieure
Bouche de
décharge
inférieure
4
1 po
(
104,1 cm)
13-1/2 po
(34,3 cm)
37 po
(
94,0 cm)
3-1/8 po
(7,9 cm)
5-3/8 po
(
13,7 cm)
canalisation
d
e gaz
s
upérieure
canalisation
d
e gaz
inférieure
5-3/8 po
(
13,7 cm)
7-1/2 po
(19,1 cm)
NOTE : Canalisation
de gaz à 1-1/2 po
(3,8 cm) vers
l’intérieur du
côté adjacent
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32

Maytag MDG17PD Installation Instructions Manual

Taper
Installation Instructions Manual
Ce manuel convient également à

dans d''autres langues