Kozyheat Bellingham 44 Le manuel du propriétaire

Catégorie
Cheminées
Taper
Le manuel du propriétaire
HUSSONG MANUFACTURING CO., INC.
READ ALL THESE STEPS
BEFORE STARTING INSTALLATION.
LEAVE THESE INSTRUCTIONS WITH THE
APPLIANCE.
This kit must be installed by a qualied installer,
service agency, or gas supplier at the time of
the heater installation. These instructions must
be used in conjunction with the installation and
operation manual provided with the appliance.
Please read the appliance owner’s manual
completely before performing any procedures in
these instructions.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
INTERIOR HEAT
TRANSFER KIT
#HTK-INT
English and French installation manuals are available through your
local dealer. Visit our website www.kozyheat.com.
Les manuels d’installation en français et en anglais sont disponibles
chez votre détaillant local. Visitez
www.kozyheat.com
.
Hussong Manufacturing Co., Inc.
P.O. Box 577, 204 Industrial Park Drive
Lakeeld, MN 56150-0577, USA
Heat Transfer Kit - Interior #HTK-INT
Rev. 8, 10/20
1.0 INTRODUCTION .......................................................................3
1.1 Introduction ......................................................................................... 3
1.2 Installation ............................................................................................ 3
1.3 Replacement Parts .............................................................................4
1.4 Dimensions and Clearances ...........................................................5
2.0 INSTALLATION .........................................................................9
2.1 Duct Installation ................................................................................. 9
2.2 Fan Installation ..................................................................................10
2.3 Operation ............................................................................................11
2.4 Maintenance ......................................................................................11
3.0 ELECTRICAL INFORMATION ................................................12
3.1 Electrical Requirements ................................................................12
3.2 Electrical Wiring ................................................................................12
For use with models #ABY, #BHM-44, #BHM-52,
#ALP-36S, #CLW-40, #CLW-50, #CLW-72, #SFD-
36, & Z42
Heat Transfer Kit #HTK-INT R.8 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces 3
1.1 Introduction
The Kozy Heat #HTK-INT Heat Transfer Kit - Interior is designed to
mount inside of the house and transfer heat to dierent rooms, or
locations within a room.
The following model(s) allow a maximum installation of two heat
transfer kits: #ABY, #ALP-36S, #BHM-44, #BHM-52, #CLW-40, #CLW-50,
#CLW-72, #SFD-36, & #Z42
Fan assembly must be installed on interior walls or ceiling only.
Installation in the oor is not recommended.
Fan wheel must be installed in the horizontal plane. Do not
install with fan axis mounted vertically.
Amount of heat delivered depends on many factors such as:
Length, type, and location of pipe (avoid running pipe
through unheated areas—insulate pipe if doing so)
Number of elbows
Duration of replace operation
Elevation of fan relative to heater (note: using the remote fan
will aect the heat output at the replace)
1.2 Installation
1.2.1 Installation Precautions
This device must be installed by a qualied installer in accordance
with these instructions and in accordance with local codes, if any, and
with National Electrical Code ANSI/NFPA 70, current edition.
The #HTK-INT fan will generate sound during operation. The eects
of the increased sound level can be minimized with careful planning
during installation of the system.
CAUTION: Wear protective gloves and safety glasses during
installation. Sheet metal edges are sharp.
Disconnect electrical power supply before performing any
maintenance, repair, or electrical wiring.
WARNING: Failure to install, operate, and maintain the heat transfer
system - interior in accordance with manufacturer's instructions will
result in conditions which may produce bodily injury and/or property
damage.
1.2.2 Installation Guidelines
NOTE: Support duct at intervals of no greater than 4 feet, with no
more than 1/2" sag between supports as required by local code.
Do not substitute any other duct work as a replacement for the
provided insulated exible duct.
Minimum Duct Run Length for #ALP-36S, #BHM-
44, #BHM-52, #CLW-40, #CLW-50, #CLW-72, &
#SFD-36
3 ft (914mm)
Minimum Duct Run Length for #ABY & Z42 8 ft (2.4m)
Maximum Duct Run Length 25 ft (7.8m)
Clearance to exible duct 0 in
IMPORTANT: The insulated exible pipe is zero clearance to
combustibles but CANNOT be compressed into a smaller diameter.
1.2.3 Painting Requirements
The #HTK-INT air grille may be painted to a desired color, as long as
the paint selected has sucient temperature and environmental
ratings.
Thoroughly sand the existing coating prior to painting with
sandpaper or steel wool.
The front of the air grille may be eld-painted and cured up to
250 degrees Fahrenheit (121° C).
1.0 INTRODUCTION
4 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Heat Transfer Kit #HTK-INT R.8
Figure 1.1, Kit Components
REPLACEMENT PARTS (not shown)
6" Insulated Flex Pipe #HTK-INT-105
Band Clamp #HTK-INT-106
FAN ASSEMBLY
#HTK-INT-101
FAN COVER PLATE
#HTK-INT-102
AIR GRILLE
#HTK-INT-103
3.25” x 10” x 6” BOOT
#HTK-INT-104
HTK 6” COLLAR
#HTK-INT-107
HTK AIR CHUTE (required for #HTK-INT)
Figure 1.2, HTK Air Chute and 6" Collar
1.3 Replacement Parts
See Figures 1.1 and 1.2 below.
1.3.1 Additional Components Required
Sheet metal screws to match number of joints
Variable speed control, switch, electrical wire, electrical boxes,
wall plate as required. See Section 3.1 Electrical Requirements on
page 12 for speed control or switch requirements.
Optional 3.25" x 10" x 6" diameter right angle boot (for adapting
to wall stack)
Optional 3.25" x 10" rectangular wall stack and S drive cleats
when required
1.3.2 Heat Transfer Kit Air Chute
The HTK air chute is required when installing a #HTK-INT.
(1) air chute is needed per heat transfer kit.
Order model specic air chute. Yours may look dierent than
what is shown in Figure 1.2.
Heat Transfer Kit #HTK-INT R.8 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces 5
1.4 Dimensions and Clearances
Model #SFD-36 corner installations have dierent minimum
dimensions to allow space for the SFD-HTK air chute. See appliance
installation and operation manual for more information.
Figure 1.3 shows the dimension of the air discharge box with the
boot attached.
Figure 1.4 shows the depth of the boot.
Figure 1.5 shows the 4" (102mm) clearance between the air
discharge box and the framing of the oor or the ceiling.
Figure 1.6 shows an optional installation method of using 3.25"
x 10" wall stack with S cleats attached to the air discharge box.
The gure also shows an angled 3.25" x 10" x 6" boot that may be
needed for certain installations. The wall stack application has to
start after achieving the minimum 3' (914mm) run of insulated
ex pipe to the boot. The wall stack is 0" (0mm) clearance to
combustibles. The wall stack and angled boot are not provided.
Figure 1.7 on the following page shows nishing clearances.
6” (152mm) dia.
5
½
(140mm)
15
½
(394mm)
11
⁄
(290mm)
3
¼
(83mm)
4”
(102mm)
Figure 1.3, HTK-INT Dimensions
14½
(368mm)
24”
(610mm)
4”
(102mm)
Figure 1.4, HTK-INT Dimensions - Side View
Figure 1.5, HTK-INT Ceiling and Floor Clearances
65⁄8
(169mm)
Figure 1.6, HTK-INT Wall Stack (optional installation)
3.25” x 10”
WALL STACK
(not provided)
3.25” x 10” x 6”
ANGLED BOOT
(not provided)
#HTK-INT
THIS OPTIONAL APPLICATION HAS TO START
AFTER ACHIEVING THE MINIMUM 3’ (914mm)
RUN OF INSULATED FLEX PIPE TO THE BOOT
6 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Heat Transfer Kit #HTK-INT R.8
1.4.1 Finishing Dimensions
15½
(394mm)
5
½
(140mm)
Figure 1.7, Finishing Material Dimensions
Heat Transfer Kit #HTK-INT R.8 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces 7
6” dia. piping
MIN:
36” (914mm)
MAX:
25’ (7.6m)
Figure 1.8, Piping Dimensions
1.4.2 Piping Dimensions
Pipe diameter: 6 in (152mm)
Minimum vent run: 3 ft (914mm)
Maximum vent run: 25 ft (7.8m)
8 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Heat Transfer Kit #HTK-INT R.8
2”
(51mm)
12”
(305mm)
18”
(457mm)
18”
(457mm)
MAX
2”
(51mm)
For models ABY, BHM-44, BHM-52,
CLW-40, CLW-50, CLW-72, SFD-36, Z42
MIN
MIN
MIN
MIN
1.4.3 Shelf Requirements
WARNING: LEAVE THIS SPACE CLEAR OF CONTENTS!
Figure 1.9 shows the shelf requirements for models ABY, BHM-44,
BHM-52, CLW-40, CLW-50, CLW-72, SFD-36, and Z42 when the air
discharge opening is located in a shelf or a built-in cabinet.
Figure 1.10 shows the shelf requirements for model ALP-36S when
the air discharge opening is located in a shelf or a built-in cabinet.
Figure 1.9, Shelf Requirements for ABY, BHM-44, BHM-52, CLW-40, CLW-50,
CLW-72, SFD-36, Z42
Figure 1.10, Shelf Requirements for ALP-36S
10”
(254mm)
24”
(610mm)
18”
(457mm)
MAX
6
½
(165mm)
18”
(457mm)
MIN
MIN
MIN
MIN
For model ALP-36
Heat Transfer Kit #HTK-INT R.8 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces 9
2.0 INSTALLATION
2.1 Duct Installation
NOTE: The fan assembly can be installed on the wall, minimum 4"
(102mm) from the oor or the ceiling. It can also be installed on the
ceiling.
1. The outer shell of your replace will have cover plate(s) for use
with heat transfer kits. Reference the replace manual for the
location of your heat transfer kit cover plates. See Figure 2.1.
2. Remove screws securing cover plate(s) on the outer shell of the
replace.
3. Remove the damper from the heat transfer kit air chute by
pushing the metal tab through the hole and pulling the damper
out of the air chute. NOTE: Air chutes for models #ABY & #Z42
do not have a damper. See Figure 2.2. Your air chute may look
dierent than the one shown. Attach the HTK air chute to the
replace as per instructions included with HTK air chute.
4. Use the nailing anges attached to the air discharge box to
secure it to the framed opening at the desired location for air
discharge.
5. Attach and secure the 3.25" x 10" x 6" boot to the top of the air
discharge box using sheet metal screws.
6. Cut the insulated exible duct to necessary length.
7. Place the band clamp over the HTK air chute collar. Screw the
inner liner of the exible duct to the collar with (3) sheet metal
screws. See Figure 2.3.
8. Use the band clamp to secure the outer exible pipe insulation
to the inner pipe and collar. See Figure 2.4.
9. Repeat Steps 7 and 8 to attach and secure the exible pipe to the
duct boot on the air discharge box.
NOTE: If you choose to attach the air discharge box to a wall stack
with S cleats, your installation steps may vary. A right angle boot may
be needed instead of the provided straight boot. Attach the insulated
exible pipe from the HTK air chute to the boot on the wall stack that
would connect to the air discharge box.
Figure 2.1, HTK Square Cover Plate Removal (1) Shown
Figure 2.2, Damper Removal
Figure 2.3, Band Clamp over HTK Air Chute Collar
Figure 2.4, Band Clamp Securing Outer Insulation to Inner Pipe and Collar
Air chute with damper removed
Holes
Discard damper
Push tabs through
holes to remove damper
Tabs
Remove damper for HTK-INT installations
10 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Heat Transfer Kit #HTK-INT R.8
i ii
iii
iv
v vi
2.2 Fan Installation
1. Install the fan housing according to the minimum dimensions for
your appliance listed in Section 1.4 on page 5. See (i) below.
2. Attach the duct boot or wall stack to fan housing using the (4)
provided self-tapping screws . The screws must be fastened on
the sides of the duct boot or wall stack for proper nishing. See
(i) below.
3. Secure the fan housing and duct boot/wall stack to the wall
studs with (4) provided black wood screws. See (ii) below.
4. Finish the wall around the fan housing.
5. Attach the fan cover plate to the fan housing using (4) screws.
See (iii) and (iv) below.
6. Fit the air grille to the frame through the brackets with (2) screws
provided. See (v) and (vi) below.
7. Complete wiring. Refer to Section 3.0 on page 12.
Figure 2.5, Fan Assembly Installation
Heat Transfer Kit #HTK-INT R.8 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces 11
2.3 Operation
Turn the replace on and let it warm up.
Fan operation may vary based on the on/o switch and/or fan
speed control you have chosen to use. See Section 3.0 on page
12.
2.4 Maintenance
The #HTK-INT must occasionally be cleaned to maintain its
performance. To clean:
1. Turn o the fan.
2. Remove the air grille and vacuum it.
3. Remove (6) screws securing the fan cover plate.
4. Unplug the fan from the receptacle.
5. Vacuum the fan and the housing to remove dust and lint.
6. Plug the fan back into the receptacle.
7. Reattach the fan cover plate using (6) screws previously
removed.
8. Reattach the air grille using (2) screws previously removed.
12 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Heat Transfer Kit #HTK-INT R.8
3.0 ELECTRICAL INFORMATION
POWER SOURCE
ON/OFF
SWITCH
FAN SPEED
CONTROL
GROUND
BLACK
WHITE
WIRE NUTS
Figure 3.1, HTK-INT Wiring Diagram
3.1 Electrical Requirements
#HTK-INT operates on 120VAC, 60Hz electrical service
Disconnect electrical service before servicing.
The on/o switch and/or fan speed control must be able to
handle a rating of 0.5 amps
3.2 Electrical Wiring
ITEMS SUPPLIED: Wiring leads from the fan, wiring nuts, and a
green ground screw will be attached to the air discharge box.
NOTE: Wiring and switches/speed control are not supplied.
Figure 3.1 illustrates a typical wiring installation. Hard wire the
fan to the electrical system.
It is easier to access the ground screw if you remove the (2)
ange nuts securing fan to the assembly and slide the fan
forward.
Secure grounding wire to the grounding screw installed in fan
assembly housing.
Connect the fan to the speed controller and test the fan
operation.
GROUND WIRE
GROUND SCREW
HUSSONG MANUFACTURING CO., INC.
LISEZ TOUTES CES ÉTAPES
AVANT DE COMMENCER L’INSTALLATION.
LAISSEZ CE MANUEL AVEC L APPAREIL.
Ce kit doit être installé par un centre de service
ou un installateur qualié, ou par le fournisseur
de gaz, au moment d’installer l’appareil de
chauage. Ces instructions doivent être utilisées
conjointement avec le manuel d’installation
et d’utilisation fourni avec l’appareil. Veuillez
lire complètement le manuel d’installation de
l’appareil avant de commencer les procédures
de ce manuel d’instructions.
INSTALLATEUR : Laissez ce maneuel avec l’appareil.
PROPRIÉTAIRE : Conservez ce manuel pour le consulter.
KIT DE TRANSFERT DE
CHALEUR INTÉRIEUR
nº HTK-INT
English and French installation manuals are available through your
local dealer. Visit our website www.kozyheat.com.
Les manuels d’installation en français et en anglais sont disponibles
chez votre détaillant local. Visitez
www.kozyheat.com
.
Hussong Manufacturing Co., Inc.
P.O. Box 577, 204 Industrial Park Drive
Lakeeld, MN 56150-0577, USA
Kit de transfert de chaleur - Intérieur nº HTK-INT
Rév. 8, 10/20
1.0 INTRODUCTION .......................................................................3
1.1 Introduction ......................................................................................... 3
1.2 Installation ............................................................................................ 3
1.3 Pièces de rechange............................................................................4
1.4 Dimensions et dégagements ........................................................5
2.0 INSTALLATION .........................................................................9
2.1 Installation des conduits ................................................................. 9
2.2 Installation du ventilateur .............................................................10
2.3 Utilisation ............................................................................................ 11
2.4 Entretien ..............................................................................................11
3.0 INSTALLATION ÉLECTRIQUE ................................................ 12
3.1 Alimentation électrique ...............................................................12
3.2 Câblage électrique ..........................................................................12
Pour utilisation avec modèles ABY, ALP-36S, BHM-
44, BHM-52, CLW-40, CLW-50, CLW-72, SFD-36 et
Z42
Kit de transfert de chaleur - Intérieur n HTK-INT R.8 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces 3
1.1 Introduction
Le Kit de transfert de chaleur intérieur HTK-INT de Kozy Heat est
conçu pour être installé à l’intérieur de la maison et transférer la
chaleur à diérentes pièces ou à diérents endroits à l’intérieur d’une
même pièce.
Le modèle de foyer suivant permet d’installer un maximum de deux
kits de transfert de chaleur : ABY, ALP-36S, BHM-44, BHM-52, CLW-40,
CLW-50, CLW-72, SFD-36 et Z42.
Le ventilateur doit être installé seulement sur un mur intérieur ou au
plafond. Linstallation dans un plancher est déconseillée.
Le ventilateur doit être installé à l’horizontale. Ne l’installez pas à
la verticale.
La quantité de chaleur fournie dépend de plusieurs facteurs :
Longueur, type et trajet des conduits (évitez de passer les
conduits à travers les zones non chauées, sinon isolez-les)
Nombre de coudes
Durée de chauage du foyer
Hauteur du ventilateur par rapport au foyer (Note: l’utilisation
du ventilateur de transfert de chaleur aectera la puissance
thermique à l’emplacement du foyer)
1.2 Installation
1.2.1 Précautions d’installation
Ce système doit être installé par un installateur qualié selon ces
instructions et les codes locaux, et le Code canadien de l’électricité
CSA C22.1 (ou le National Electrical Code ANSI/NFPA 70, aux É.-U.).
Le ventilateur du HTK-INT fera du bruit, une fois en marche. Les eets
du niveau sonore accru peuvent être minimisés en planiant avec
soin l’installation du système.
ATTENTION: Porter des gants protecteurs et lunettes de sécurité pour
l’installation. Les bords en tôle métallique sont coupants.
Débranchez l’alimentation électrique avant d’eectuer tout entretien,
réparation ou câblage électrique.
AVERTISSEMENT: Le non-respect des instructions d’installation,
d’utilisation et d’entretien de ce système de transfert de chaleur
intérieur pourrait créer des conditions dangereuses avec risques de
blessures et de dommages matériels.
1.2.2 Directives d’installation
NOTE: Le conduit doit être supporté à des intervalles ne dépassant
pas 4 pieds (122 cm), avec pas plus de 1/2 po (13 mm) de déexion
entre les supports, tel quexigé par les codes locaux. Ne remplacez pas
le conduit exible isolé fourni par aucun autre type de conduit.
Longueur de conduit minimale ALP-36S,
BHM-44, BHM-52, CLW-40, CLW-50, CLW-72
et SFD-36 :
3 pieds (914 mm)
Longueur de conduit minimale ABY et Z42 : 8 pieds (2,4 m)
Longueur de conduit maximale : 25 pieds (7,6 m)
Dégagement au conduit exible : 0 pouce (0 mm)
IMPORTANT: Le conduit exible isolé est à dégagement zéro aux
matériaux combustibles mais NE PEUT PAS être comprimé à un
diamètre inférieur.
1.2.3 Exigences de peinturage
Le devant de la grille de sortie d’air du HTK-INT peut être peinturé à
la couleur désirée, pourvu que la peinture choisie ait une résistance
susante aux températures et conditions ambiantes.
Avec du papier sablé ou de la laine d’acier, sablez bien le
revêtement existant, avant d’appliquer la peinture.
Le devant de la grille de sortie d’air peut être peinturé sur place
en faisant sécher la peinture à 250°F (121°C).
1.0 INTRODUCTION
4 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Kit de transfert de chaleur - Intérieur n HTK-INT R.8
Figure 1.1, Composants du kit
PIÈCES DE RECHANGE (non-montrées)
Conduit ex. isolé 6 po HTK-INT-105
Collier de serrage HTK-INT-106
VENTILATEUR
HTK-INT-101
COUVERCLE DU VENTILATEUR
HTK-INT-102
GRILLE D’AIR
#HTK-INT-103
RACCORD DE CONDUIT
3.25” x 10” x 6” dia.
HTK-INT-104
COLLET de 6 po du HTK
HTK-INT-107
CHUTE D’AIR DU HTK (requise pour HTK-INT)
Figure 1.2, , Chute d’air du HTK et collet de 6 po
1.3 Pièces de rechange
Voir les Figures 1.1 et 1.2 ci-dessous.
1.3.1 Composants additionnels requis
Vis à tôle en quantité susante selon le nombre de joints
Contrôle à vitesse variable, interrupteur, ls électriques, boîtes
électriques, plaque murale selon l’installation. Voir Section 3.1,
Alimentation électrique (page 11) pour les spécications du
contrôle de vitesse ou de l’interrupteur.
Optionnel: Raccord de conduit à angle droit de 3,25 po x 10 po x
6 po de diamètre (pour s’adapter à un conduit de colonne)
Optionnel: Conduit de colonne rectangulaire de 3,25 po x 10 po
et taquets de xation en S au besoin (selon l’installation).
1.3.2 Chute d’air du kit de transfert de chaleur
La chute d’air du HTK est requise pour installer le kit HTK-INT.
(1) chute d’air est requise pour chaque kit de transfert de chaleur.
Commandez la chute d’air spécique au modèle. La vôtre peut
être diérente de la chute d’air illustrée à la Figure 1.2.
Kit de transfert de chaleur - Intérieur n HTK-INT R.8 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces 5
1.4 Dimensions et dégagements
Modèle SFD-36 avoir des dimensions minimales diérentes pour les
installations du coin pour permettre l'espace pour l'installation de
chute d'air du htk. Voir le manuel d'appareil.
La Figure 1.3 montre la dimension de la boîte de sortie d’air xée
au raccord de conduit.
La Figure 1.4 montre la profondeur du raccord de conduit.
La Figure 1.5 montre le dégagement de 4 po (102 mm) entre la
boîte de sortie d’air et l’encadrement près du plancher ou du
plafond.
La Figure 1.6 montre une méthode d’installation optionnelle
utilisant le conduit de colonne de 3,25 po x 10 po avec les
taquets en S xés à la boîte de sortie d’air. Cette gure montre
aussi un raccord à angle de 3,25 po x 10 po x 6 po dia. qui
peut être nécessaire pour certaines installations. Le conduit
de colonne peut commencer seulement après avoir atteint la
course minimale de 3 pieds (914 mm) de conduit exible isolé
au raccord de conduit. Le conduit de colonne est à dégagement
zéro (0 po/0 mm) aux matériaux combustibles. Le conduit de
colonne et le raccord à angle ne sont pas fournis.
6” (152mm) dia.
5
½
(140mm)
15
½
(394mm)
11
⁄
(290mm)
3
¼
(83mm)
4”
(102mm)
Figure 1.3, Dimensions du HTK-INT
14½
(368mm)
24”
(610mm)
4”
(102mm)
Figure 1.4, Profondeur du HTK-INT avec raccord de conduit (Vue de côté)
Figure 1.5, Dégagements du HTK-INT au plafond et au plancher
65⁄8
(169mm)
Figure 1.6, HTK-INT avec conduit de colonne (installation optionnelle)
CONDUIT DE COLONNE
3,25 po x 10 po
(non fourni)
RACCORD À ANGLE
3,25 po x 10 po x 6 po dia.
(non fourni)
Ventilateur du HTK-INT
CETTE APPLICATION OPTIONNELLE DOIT COMMENCER
APRÈS AVOIR ATTEINT LA COURSE MINIMALE DE 3 pieds (914 mm)
DE CONDUIT FLEXIBLE ISOLÉ AU RACCORD
6 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Kit de transfert de chaleur - Intérieur n HTK-INT R.8
1.4.1 Exigences de façade
15½
(394mm)
5
½
(140mm)
Figure 1.7, Exigences de façade
Kit de transfert de chaleur - Intérieur n HTK-INT R.8 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces 7
Conduit de 6 po
de diamètre
MIN:
36 pouces (914mm)
MAX:
25 pieds (7,6m)
Figure 1.8, Dimensions du conduit
1.4.2 Dimensions de conduit
Diamètre de conduit : 6 pouces (152 mm)
Longueur de conduit minimale : 3 pieds (914 mm)
Longueur de conduit maximale : 25 pieds (7,6 m)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26

Kozyheat Bellingham 44 Le manuel du propriétaire

Catégorie
Cheminées
Taper
Le manuel du propriétaire

dans d''autres langues