2112
Fenton
Logistic
Park
Blvd.
Fenton,
MO
63026
USA
P/N
KIL00921505
FORM
NO.
K1505
ECO6-078-21
R11/21
Note: Due to the surge protection provided in the fixture to protect the internal electronics and LEDs, a branch
circuit with
the LED fixture may false fail a megohmmeter test (sometimes referred to as a megger test). If a
megohmmeter test is
required, the LED fixture should be removed from the branch circuit.
This fitting’s driver is protected via thermal foldback sensor which reduces the light output of the fitting to prolong the life of
the driver in high ambient service conditions. When the driver reaches temperatures near the manufacturer’s recommended
limits, the foldback sensor will activate and slightly reduce the light output to decrease the temperature of the fixture. Once
the driver temperature reduces from this level, the fitting will operate at normal levels
Note: Multiple fluorescent or LED fixtures attached to a single Ground Fault Circuit Interrupter (GFCI) may cause
nuisance
tripping of the GFCI. Regulatory agencies allow a small amount of leakage current because of the circuitry
required to mitigate
possible issues with electromagnetic compatibility (reference UL8750 and EN61347). The
summation of these leakage
currents from multiple fixtures may be enough to trip a GFCI.
Note: When fitted with a polycarbonate lens, the polycarbonate lens should not be subjected to sunlight.
NOTE- For Class I, Division 1 / Class II, Division 1 / Class I, Zone 1 Hazardous Locations, use rigid conduit
or
appropriate cable connectors/ glands rated for Class I, Division 1 Groups BCD
NOTE – Pour les endroits dangereux Classe I, Division 1 / Classe II, Division 1 / Classe I, Zone 1 utiliser des Conduits rigides.
KFLX/ARXC INSTALLATION INSTRUCTIONS:
Yoke Mounting:
1.
For convenience, install the yoke bracket to the fixture before mounting the structure.
2.
Loosen bolts - aim the floodlight to the desired spot.
3.
Tighten both bolts securely.
4.
Fasten the yoke bracket to the mounting location using ½” bolts/fasteners.
5.
An “Earthquake Safety Chain” can be looped around the bosses that attach the LED heat sink to the driver box.
IMPORTANT NOTE:
Make sure that the circuit is de-energized at main fuse or at circuit breaker prior to installation.
NOTE IMPRORTANTE:
Mettre le circuit hors tension grace au fusible principal ou le disjoncteur. Open the fixture by loosening the swing bolts. Using the terminal
blocks supplied, run supply wire to fixture through applicable watertight joint
using sealing fittings at appropriate hole. The included hubs are for ¾”-
14NPT. A ½-14NPT reducer is also included. The holes through the cast
metal in the driver compartment are for an M20 cable gland. To use an M20
cable gland, discard the ¾ NPT hubs. he terminal block shown is with battery
back up. Non back up
fixtures will not have the “L2” terminal. Mains wiring
should be
brought into the corresponding marked terminal. Looping
wiring
can be accomplished by using the adjacent connection
port. A small
screwdriver can be inserted in the slot near the
connection port to ease the
force required to insert the wire. The external ground is located next to the
gland/hub opening
where the mains wires exit the fixture.
Reattach the swing bolts. Torque the cover bolts until the cover touches the housing. Approximately 3 N-m (25 in-lbf).
Re-
energized the circuit to verify the fixture is operating properly
IMPORTANT:
Technical information, advice and recommendations contained in these documents are based on information that Killark
believes to be reliable. All the information and advice contained in these documents is intended only for use by persons
having been trained and possessing the requisite skill and know-how and to be used by such persons only at their own
discretion and risk.
The nature of these instructions is informative only and do not cover all of the details, variations or combinations in which this
equipment may be used, its storage, delivery, installation, check out, safe operation, and maintenance. Since conditions of
use of the product are outside of the care, custody and control of Killark, the purchaser should determine the suitability of the
product for its intended use and assumes all risk and liability whatsoever in connection therewith. ATTENTION:
Avant d’installer le luminaire, s’assurer que le luminaire est conforme à la classification des zones, le non- respect de cette
règle risque d’entraîner des dommages corporels et / ou matériels. Ne pas tenter d’entreprendre l’installation avant d’être
familiarisé avec les procédures suivantes. Toute installation doit être conforme au code électrique local et / ou national et être
effectuée par un électricien qualifié.
Veiller à ce que le circuit soit mis hors tension avant de commencer l’installation ou la maintenance.
Vérifier si le luminaire est mis à la terre. S’il n’est pas mis à la terre il pourrait causer des risques de choc électrique
susceptibles d’entraîner des blessures graves ou la mort.