NQ/NQM Panelboards and QONQ Load
Centers
Class 1640
Instruction Bulletin
80043-712-06, Rev. 07
02/2023
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and furnished
for informational use only. No part of this guide may be reproduced or transmitted in
any form or by any means (electronic, mechanical, photocopying, recording, or
otherwise), for any purpose, without the prior written permission of Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as is"
basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
Class 1640
Table of Contents
Safety Information ............................................................................................5
Please Note.....................................................................................................5
Introduction........................................................................................................6
Safety Precautions ...........................................................................................6
Installation .........................................................................................................7
Interior Mounting for Square D Brand Enclosures ...............................................7
Surface Mounting (Enclosure Mounted on Wall)............................................7
Flush Mounting (Enclosure Recessed in Wall) ..............................................8
Neutral Bonding Strap/Cable Installation............................................................9
100 or 250 A Maximum NQ Panelboards....................................................10
400 or 600 A Maximum NQ Panelboards and QONQ Load Centers.............. 11
QO and QOB Circuit Breaker Installation and Removal .....................................13
QO and QOB Circuit Breaker Installation....................................................13
QO and QOB Circuit Breaker Removal.......................................................14
Circuit Breaker Reset Instructions....................................................................15
Deadfront Preparation ....................................................................................16
Appendix 1: Specifications............................................................................18
Typical Wiring ................................................................................................18
Integral Main or Sub-Feed: DJ, FI, KI, H, J, LA, LC, LH, QB, QD, QG, QJ,
QO(B)VH.................................................................................................19
Panelboard Ratings........................................................................................23
CE Marking....................................................................................................32
QO2150VH, QO2175VH and QO2200VH Restrictions ...................................... 33
Appendix 2: Accessory Kits ..........................................................................35
Equipment Ground Bar Kits.............................................................................35
Oversized Neutral Lug Kits for 100–600 A Panelboards ....................................35
Sub-Feed Lug Kits for 100–400 A Panelboards ................................................36
Main Lug Kits.................................................................................................36
Line Side Barrier and Neutral Bonding Strap Kits ..............................................37
80043-712-06 3
Safety Information Class 1640
Safety Information
Read these instructions carefully and look at the equipment to become familiar with
the device before trying to install, operate, service, or maintain it. The following special
messages may appear throughout this user guide or on the equipment to warn of
hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of either symbol to a “Danger” or “Warning” safety
label indicates that an electrical hazard exists which will result
in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to personal
injury hazards. Obey all safety messages that follow this
symbol to avoid possible injury or death.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result
in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
NOTE: Provides additional information to clarify or simplify a procedure.
Please Note
Electrical equipment should be installed, operated, serviced, and maintained only by
qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training to
recognize and avoid the hazards involved.
Electrical equipment should be transported, stored, installed, and operated only in the
environment for which it is designed.
80043-712-06 5
Class 1640 Introduction
Introduction
This bulletin contains instructions for installing Square D™ brand NQ circuit breaker
panelboards and QONQ load centers. These panelboards and load centers are
Underwriters Laboratories (cULus) listed and accept QO™ and QOB branch circuit
breakers.
NOTE: For technical support on the installation of this panelboard, contact the
Schneider Electric Customer Information Center at 1-888-778-2733.
NOTE: See the labels on the equipment for rating and safety information.
Additional equipment labels are provided with this document.
Safety Precautions
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe electrical
work practices. See NFPA 70E, NOM-029-STPS or CSA Z462 or local
equivalent.
This equipment must only be installed and serviced by qualified electrical
personnel.
Turn off all power supplying this equipment before working on or inside
equipment.
Locking the manual operation or locking the motor cover does not disconnect
the secondary motor circuit.
Always use a properly rated voltage sensing device to confirm power is off.
Read and understand this entire instruction bulletin and the included NEMA PB
1.1 standards publication before installing, operating, or maintaining this
equipment.
Local codes vary, but are adopted and enforced to promote safe electrical
installations. A permit may be needed to do electrical work, and some codes
may require an inspection of the electrical work.
Replace all devices, doors, and covers before turning on power to this
equipment.
Do not allow petroleum based paints, solvents, or sprays to contact the
nonmetallic parts of this product.
Failure to follow these instructions will result in death or serious injury.
WARNING: This product can expose you to chemicals including Nickel compounds, which are
known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the
State of California to cause birth defects or other reproductive harm. For more information go to
www.P65Warnings.ca.gov.
6 80043-712-06
Installation Class 1640
Installation
This section provides instructions for the following NQ panelboard and QONQ load
center procedures:
Interior Mounting for Square D Brand Enclosures, page 7.
Neutral Bonding Strap/Cable Installation, page 9.
QO and QOB Circuit Breaker Installation and Removal, page 13.
Circuit Breaker Reset Instructions, page 15.
Deadfront Preparation, page 16.
Interior Mounting for Square D Brand Enclosures
A separate standards publication, titled “General Instructions for Proper Installation,
Operation, and Maintenance of Panelboards Rated 600 Volts or Less” (NEMA PB1.1),
has been provided with this equipment. Familiarize yourself with the content of this
document before proceeding with any of the following procedures.
If you did not receive a copy of this document, or if you have any questions regarding
this equipment, contact your local distributor or Schneider Electric representative.
NOTICE
HAZARD OF EQUIPMENT DAMAGE DUE TO LOOSE CONNECTIONS
Ensure all connections are properly tightened.
Refer to the torque information label provided on the panelboard before
tightening the connections.
Failure to follow these instructions can result in equipment damage.
To properly mount and install the NQ panelboard or QONQ load center interior, please
refer to the NEMA PB 1.1 standards publication, and follow the instructions below for
either Surface Mounting (Enclosure Mounted on Wall), page 7 or Flush Mounting
(Enclosure Recessed in Wall), page 8.
Surface Mounting (Enclosure Mounted on Wall)
1. Mount the enclosure as instructed in the NEMA PB 1.1 standards publication.
2. Remove the deadfront from the deadfront brackets.
3. Install the interior as described below:
a. Set the interior on the enclosure studs. An elevating screw is not required
(See Interior Mounting for Square D Brand Enclosures, page 7).
b. Tighten the Keps nuts against the interior side rails until the rails are against
the back of the enclosure.
4. Based on the application and adopted installation code, Neutral Bonding Strap
and Line Side Barrier may be required. See the Neutral Bonding Strap/Cable
Installation, page 9 and Appendix 2: Accessory Kits, page 35.
5. Apply equipment labels (located in the bag assembly) as directed by the
instructions on the back of the equipment label sheet. Please consult local codes
and standards.
80043-712-06 7
Class 1640 Installation
6. Remount the deadfront after wiring.
Flush Mounting (Enclosure Recessed in Wall)
1. Mount the enclosure as instructed in the NEMA PB 1.1 standards publication.
2. Remove the deadfront from the deadfront brackets.
3. Install the interior as described below:
a. Thread the (4) 10-32 x 0.875 in. self-tapping, elevating screws provided with
the flush trim into the side rails.
b. Set the interior on the enclosure studs (see Interior Mounting of Square D
Brand Enclosures, page 9). Place the keps nuts onto the enclosure studs,
but do not tighten.
c. Adjust the screws so that the lip of the deadfront is approximately 0.25
inches (6.35 mm) from the wall line.
d. Tighten the keps nuts against the side rails.
4. Based on the application and adopted installation code, Neutral Bonding Strap
and Line Side Barrier may be required. Please consult local codes and standards.
See the Neutral Bonding Strap/Cable Installation, page 9 and Appendix 2:
Accessory Kits, page 35.
5. Apply equipment labels (located in the bag assembly) as directed by the
instructions on the back of the equipment label sheet.
6. Remount the deadfront after wiring.
8 80043-712-06
Installation Class 1640
Figure 1 - Interior Mounting of Square D Brand Enclosures
Deadfront Bracket
Enclosure Stud
Keps Nut
Enclosure
Deadfront
Wall
Elevating Screw
Side Rail
0.25 in.
(6.35 mm)
Neutral Bonding Strap/Cable Installation
Based on the application and the adopted installation code, a line side barrier and
neutral bonding strap may be required.
To properly bond the neutral to the panelboard, follow the instructions for either 100 or
250 A Maximum NQ Panelboards, or 400 or 600 A Maximum NQ Panelboards and
QONQ Load Centers, page 11.
80043-712-06 9
Class 1640 Installation
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe electrical
work practices. See NFPA 70E, NOM-029-STPS or CSA Z462 or local
equivalent.
Turn off all power supplying this equipment before working on or inside
equipment.
Locking the manual operation or locking the motor cover does not disconnect
the secondary motor circuit.
The neutral bonding strap/cable should be used only when the panelboard is
installed as service entrance equipment.
Do not mix the mounting screws with the deadfront screws.
Failure to follow these instructions will result in death or serious injury.
NOTE: Refer to Line Side Barrier and Neutral Bonding Strap Kits, page 38 for
information.
NOTE: The terms “neutral bonding strap” and “neutral bonding cable”, describe
the components which meet the requirements for a “neutral bonding conductor”.
These are equivalent terms.
100 or 250 A Maximum NQ Panelboards
To install a neutral bonding strap on NQ panelboards with mains rated up to 225 A
(with main lugs or main circuit breaker), or up to 250 A with a factory assembled main
circuit breaker, refer to Bonding Strap Installation—100 or 250 A Maximum NQ
Panelboards, page 11, and follow the instructions below.
1. Align the bonding strap on the side rail, as pictured.
NOTE: For some applications, it may be necessary to remove the lug (not
pictured) before installing the bonding strap.
2. Insert the two mounting screws, as pictured. Tighten the 10-32 screw to 10–12
lb.-in. (1.1–1.4 N•m) and the 1/4-20 to 25–30 lb.-in. (2.8–3.4 N•m).
NOTE: Lug mounting screws are provided in the bonding strap bag assembly.
a. If the lug was removed in step 1 above, reinstall it on top of the bonding
strap.
b. Use 1/4-20 x 9/16 in. screw in mounting for 100/225 A interiors with no
options. Refer to note C and D for other options.
c. Use the 1/4-20 screw x 11/16 in. lug mounting screw on applications with
feed-through lug, sub-feed lug, sub-feed circuit breaker, or 200% neutral
applications.
d. Use the 1/4-20 x 7/8 in. lug mounting screw on applications with 200%
neutrals and with feed-through lugs, sub-feed lugs, or sub-feed circuit
breakers.
10 80043-712-06
Installation Class 1640
Figure 2 - Bonding Strap Installation—100 or 250 A Maximum NQ Panelboards
NOTE: For bonding strap lug options, refer to C and D for the correct length of the 1/4-20 screw.
Mounting Screws
Bonding Strap
1/4-20 x 9/16 in.
10/32 x 7/16 in.
Neutral Bus
Side Rail
400 or 600 A Maximum NQ Panelboards and QONQ Load Centers
To install a neutral bonding cable on a 400 or 600 A maximum NQ panelboard and
QONQ load center, refer to Bonding Cable Installation — 400 or 600 A Maximum NQ
Panelboards and QONQ Load Centers, page 12, and follow the instructions below.
1. Align the lug on the side rail mounting hole, as pictured.
2. Tighten the lug mounting screw against the side rail to 10–12 lb.-in. (1.1–1.4
N•m).
3. Align the bonding cable, as pictured, and insert it into the lug and neutral
mounting holes.
4. Tighten both the lug wire binding screw and the neutral wire binding screw to 45–
50 lb.-in. (5.1–5.6 N•m).
80043-712-06 11
Class 1640 Installation
Figure 3 - Bonding Cable Installation — 400 or 600 A Maximum NQ Panelboards and QONQ Load Centers
Neutral
Lug Mounting
Screw
Bonding Cable
Bonding Cable Mounting Hole
Side Rail
Lug
Side Rail
Mounting Hole
Neutral Wire
Binding Screw
Lug
Wire
Binding
Screw
Bonding Cable Mounting Hole
12 80043-712-06
Installation Class 1640
QO and QOB Circuit Breaker Installation and Removal
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe electrical
work practices. See NFPA 70E, NOM-029-STPS or CSA Z462 or local
equivalent.
This equipment must only be installed and serviced by qualified electrical
personnel.
Turn off all power supplying this equipment before working on or inside
equipment.
Locking the manual operation or locking the motor cover does not disconnect
the secondary motor circuit.
Always use a properly rated voltage sensing device to confirm power is off.
All unused spaces must be filled with filler plates.
Replace all devices, doors, and covers before turning on power to this
equipment.
Failure to follow these instructions will result in death or serious injury.
WARNING
HAZARD OF PERSONAL INJURY OR EQUIPMENT DAMAGE
This equipment is designed and tested by Schneider Electricto performance
levels which meet Underwriter’s Laboratories®(UL®) standards and Mexican
Official Standards (NOM) listing.
Use only Square Dbrand circuit breakers and accessories.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
QO and QOB Circuit Breaker Installation
Refer to QO and QOB Circuit Breaker Installation and Removal, page 15, for the
following instructions:
1. Turn OFF all power to the panelboard.
2. Turn the circuit breaker OFF.
3. Remove the deadfront.
4. Snap the wire terminal end of the circuit breaker onto the mounting rail.
5. Engage the branch connector.
For QO Circuit Breakers: Push inward until the plug-on jaws fully engage the
branch connector.
For QOB Circuit Breakers: Push inward until the circuit breaker connector is
centered on the branch connector mounting hole. Engage the screw into the
branch connector hole and tighten it to the torque values shown on the interior
wiring and torque diagram.
6. Install the load wire.
7. Reinstall the deadfront.
8. Install a filler plate in all branch circuit breaker spaces not used.
80043-712-06 13
Class 1640 Installation
QO and QOB Circuit Breaker Removal
Refer to QO and QOB Circuit Breaker Installation and Removal, page 15, for the
following instructions:
1. Turn OFF all power to the panelboard.
2. Remove the deadfront.
3. Remove the load wire.
4. Disengage the branch connector.
For QO Circuit Breakers:
Pull outward until the plug-on jaws fully disengage the branch connector.
For QOB Circuit Breakers:
Loosen the screw in the circuit breaker connector and pull the circuit breaker off
of the branch connector.
5. Snap the wire terminal end of the circuit breaker off of the mounting rail.
6. Reinstall the deadfront.
7. Install a filler plate in all branch circuit breaker spaces not used.
14 80043-712-06
Installation Class 1640
Figure 4 - QO and QOB Circuit Breaker Installation and Removal
QO
QOB
Plug-On Jaw
Branch Connector
Branch Connector
Bolt-On
Connector
Screw
Rail
Wire
Terminal
Wire
Terminal
Rail
Circuit Breaker Reset Instructions
If the circuit breaker is tripped, the handle will be at the mid-position between ON and
OFF. To reset the circuit breaker, push the handle to the OFF position, then to the ON
position.
80043-712-06 15
Class 1640 Installation
Figure 5 - Circuit Breaker Handle Positions
ONOFFTripped
Handle
Visi-Trip™ Indicator
NOTE: When the circuit breaker has tripped, the handle assumes a center
position and the red Visi-Trip indicator appears in a window in the circuit breaker
case. The red Visi-Trip indicator is only visible when the circuit breaker has
tripped.
Deadfront Preparation
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe electrical
work practices. See NFPA 70E, NOM-029-STPS or CSA Z462 or local
equivalent.
Before energizing the panelboard, all unused spaces must be filled with filler
plates.
Replace all devices, doors, and covers before turning on power to this
equipment.
Failure to follow these instructions will result in death or serious injury.
16 80043-712-06
Installation Class 1640
Figure 6 - Deadfront Diagram
Filler plates
Deadfront
NOTE: The back of the deadfront lists the catalog number for the corresponding
compatible filler plates.
80043-712-06 17
Class 1640 Appendix 1: Specifications
Appendix 1: Specifications
Typical Wiring
Table 1 - Panelboard Typical Wiring1
Voltage AC 1-Phase Panelboards 1-Phase Panelboards
Phase Wires Phase Wires
208Y/120 — — 3 4
120/240 1 3 — —
24021 2 3 4
24031 3 — —
240/1204— — 3 4 Delta
18 80043-712-06
1. Additional information is provided on the panelboard. See the main circuit breaker rating, if used.
2. For this system, the neutral is not used and only circuit breakers rated 240 Vac minimum should be used. Do not use circuit breakers rated
120 V or 120/240 Vac.
3. For a grounded “B” phase system, only circuit breakers rated 240 Vac minimum should be used. Do not use circuit breakers rated 120 V or
120/240 Vac.
4. When wiring for a delta system, phases “A” and “C” must be 120 V to neutral, phase “B” 208 V to neutral. Connect only circuit breakers rated
240 Vac minimum. Do not use circuit breakers rated 120 V or 120/240 V to “B” phase.
Appendix 1: Specifications Class 1640
Integral Main or Sub-Feed: DJ, FI, KI, H, J, LA, LC, LH, QB, QD, QG,
QJ, QO(B)VH
Figure 7 - NQ/NQM 100–225 A Main Lugs or 100–250 A Main Circuit Breaker Diagram
80043-712-06 19
Class 1640 Appendix 1: Specifications
Figure 8 - NQ Panelboard or QONQ Load Center 400–600 A Main Lugs or Main Circuit Breaker with or
without Feed-Through Lugs Diagram
Load
Feed-Through Lugs
(when installed)
Integral Main
Circuit Breaker
(when installed)
Enclosure Bonding
(when required) Neutral
Ground
(when required)
20 80043-712-06
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109