Magnetrol Echotel 961/962 Loop Powered Mode d'emploi

Taper
Mode d'emploi
Ultrasonic
Single and
Dual Point
Level Switches
Installation and Operating Manual
ECHOTEL
®
961/962
LOOP POWERED
Model 961
Model 962
2
UNPACKING
U
npack the instrument carefully. Make sure all components
have been removed from the foam protection. Inspect all
components for damage. Report any concealed damage to
the carrier within 24 hours. Check the contents of the car-
ton/crates against the packing slip and report any discrep-
ancies to Magnetrol. Check the nameplate model number to
be sure it agrees with the packing slip and purchase order.
Check and record the serial number for future reference
when ordering parts.
MOUNTING
SPECIAL CONDITIONS FOR ATEX USE
These units are in compliance with:
1.The EMC directive 2014/30/EU. The units have been tested to
EN 61326: 1997 + A1 + A2.
2.Directive 2014/34/EU for equipment or protective system intended for use
in potentially explosive atmospheres. EC-type examination certificate number
FM19ATEX0204X - intrinsically safe and flameproof enclosure.
3. RoHS directive 2011/65/EU (restriction of the use of certain hazardous substances in electrical and elec-
tronic equipment).
N
ameplate:
- part number
- serial n°
1.The enclosure contains aluminum and is considered to present a potential risk of ignition by impact or friction. Care must
be taken during installation and use to prevent impact or friction.
2. To maintain the T6 and/or T4 temperature code care shall be taken to ensure the “Enclosure Temperature” does not
exceed 70 °C.
3. The risk of electrostatic discharge shall be minimized at installation, clean non-conductive surfaces with moist cloth only.
4. Contact the original manufacturer for information in the dimensions of flameproof joints.
5.For installation with ambient temperature of 70 °C, refer to the manufacturers instructions for guidance on proper selection
of conductors.
6. The ultrasonic probe is only for use with the Echotel ultrasonic switch.
High alarm
High high alarm
High alarm
High alarm
Pump control
Auto fill or
empty pump control
Filling line
Pump protection
Pump
Low alarm
Varivent
®
Tri-Clamp
®
DIN 11851Threaded Welded flange
3
WIRING
USER INTERFACE
TIME
DELAY
FAULT
TEST
MODEL 961
Hi 22
Lo 3.6
LOOP
TEST
8 16
+
F
A
U
L
T
Standard shielded
twisted pair cable
(
recommended but not needed
when wired as per NAMUR NE 21
for field strengths up to 10 V/m).
S
tandard trip amplifier
card
S
hield to green grounding screw
External grounding screw,
only for ATEX flameproof
e
nclosure.
Shield not connected
Plugged entry
Testing
fault
signal
Testing
loop
signal
Safe
green
LED
(8 mA)
Alarm
yellow
LED
(16 mA)
Separate
fault red LED
Cable gland
HAZARDOUS AREA
SAFE AREA
Echotel
®
961 electronics Echotel
®
962 electronics
Echotel
®
961 Echotel
®
962
TIME
D
ELAY
FAULT
T
EST
MODEL 962
–+
H
i 22
Lo 3.6
LOOP
T
EST
8 12 16
+
Ground
Important: Connect the unit to the ground for avoiding earth potential drifts.
TIME
DELAY
FAULT
TEST
MODEL 961
Hi 22
Lo 3.6
LOOP
TEST
8 16
+
F
A
U
L
T
TIME
DELAY
FAULT
TEST
MODEL 962
Hi 22
Lo 3.6
LOOP
TEST
8 12 16
+
Testing
fault
signal
Testing
loop
signal
Safe
green
LED
(8 mA)
Lower
gap
yellow
LED
(12 mA)
Upper
gap
red
LED
(16 mA)
Time delay
potentio-
meter
Time delay
potentio -
meter
4
S
ET UP AND FUNCTIONS
Set up
High – Low Level Failsafe selection:
¿
In «Hi» position, the current will shift to 12/16 mA (report alarm) when the transducer is wet.
In «Lo» position, the current will shift to 12/16 mA (report alarm) when the transducer is dry.
In both positions, the current will stay at 8 mA to report a safe condition.
Fault selection:
Select for which signal the unit should report a malfunction ≥ 22 mA or 3,6 mA
T
ime delay setting:
Turning the potentiometer clockwise will increase the time delay from 0,5 s to 10 s. Time delay is typically used where turbu-
lence, boiling or splashing can cause false level alarms.
Echotel 961
Echotel 962
Indication
Failsafe
mode
Level
Output
signal
8 mA
green LED
12 mA
yellow LED
16 mA
red LED
«Hi»
High Level
Failsafe
8 mA (± 1 mA) ON OFF OFF
12 mA (± 1 mA) OFF ON OFF
16 mA (± 1 mA) OFF OFF ON
«Lo»
Low Level
Failsafe
8 mA (± 1 mA) ON OFF OFF
12 mA (± 1 mA) OFF ON OFF
16 mA (± 1 mA) OFF OFF ON
Failsafe
¿
mode
Level
Output
signal
8 mA
green LED
16 mA
yellow LED
Fault
red LED
«Hi»
High Level
Failsafe
8 mA (± 1 mA) ON OFF OFF
16 mA (± 1 mA) OFF ON OFF
«Lo»
Low Level
Failsafe
8 mA (± 1 mA) ON OFF OFF
16 mA (± 1 mA) OFF ON OFF
Fault LED is ON = Fault indication
All LED’s OFF = Fault indication
¿
Use the following settings to replace Echotel 915 series with the new Echotel 961 series:
For High Level Failsafe, use «Lo» setting = low current draw (from 16 mA (safe) to 8 mA (alarm))
For Low Level Failsafe, use «Hi» setting = high current draw (from 8 mA (safe) to 16 mA (alarm))
5
MAINTENANCE
Manual Testing
Loop Test: (8 mA / 12mA / 16mA):
Pressing the “Loop Test” pushbutton, will manually test the loop and connected actuators/indicators. The loop test forces the
output and corresponding LED’s to shift from 8 mA to 12 mA (only 962) to 16 mA back to 8 mA. The time delay setting is not
active during testing.
Fault Test (3.6 mA /22 mA):
Pressing the “Fault Test” pushbutton for min 2 s, will manually test the fault output and connected actuators/indicators. The fault
test simulates a circuit failure and forces the output to either 3.6 mA or 22 mA. The time delay setting is not active during
t
esting.
Troubleshooting
Problem Action/Indication Solution
No loop signal No LED’s are ON
Check wiring / input power
Check for malfunction (962). See below
No change in output between
wet gap / dry gap
Gap may be plugged by
solids / dense foam
Clean the transducer
Gap is out of reach of liquid Check mounting section and relocate
the unit or check blocking valves.
Chattering output Excessive aeration / Turbulence Introduce a time delay
Check input power
Relocate the switch
If installed horizontally, make sure the
961 transducer gap is oriented in a ver-
tical position as shown in the mounting
section. This allows proper drainage
from the gap, and prevents air bubbles
from accumulating in the gap.
Fault LED is ON (961)
All LED’s OFF (962)
A system fault has been detected Check input power
Press «Loop Test» pushbutton
to identify the problem:
* --- * : 1 flash (red LED)
Check wiring between transducer and
electronics or replace transducer.
** --- ** : 2 flashes (red LED) Replace electronics
*** --- *** : 3 flashes (red LED) The unit senses excessive noise
interference. Check shield connection or
eliminate interference from a walkie-
talkie, radio or other nearby source
6
R
EPLACEMENT PARTS
Replacing electronics/transducer
Replacement parts
E
chotel electronics can be removed in the field under process conditions. Follow below steps to exchange electronics/trans-
ducer:
Note: Adjust set up of the replacing electronics following the settings of the old electronics (see configuration section)
1. Disconnect power before removing the housing cover
2. Remove power/output wires (a)
3. (Skip step 3 if hygienic housing.) Click out the protection cap of the electronics (b)
4. Remove the 2 bracket screws and slide out electronics (c)
5
. Remove the transducer wires (see Wiring section) (d)
6. Re-assemble following the same procedure in opposite way. Make sure that the tip on the bracket of the electronic block is
seated properly in the corresponding recess in the housing base - (e)
No. Description Part Number
1 Cast aluminium cover
(digit 10 = 0 or 1)
Blind
With window
Cast stainless steel cover
(digit 10 = 2 or 3)
Blind
Deep drawn stainless steel cover
(digit 10 = 4 or 5)
Blind
With window
004-9192-009
036-4410-010
004-9224-014
032-3934-001
036-5702-002
2 “O”-Ring
digit 10 = 0, 1, 2 or 3
digit 10 = 4 or 5
012-2201-237
012-2201-155
3 Electronic module for industrial
housing
(
digit 10 = 0, 1, 2 or 3
)
961
962
Electronic module for hygienic
housing (digit 10 = 4 or 5)
961
962
089-7259-005
089-7258-003
089-7256-003
089-7257-003
4 Transducer consult factory
1
3
3
3
3
2
4
a
d
e
b
c
1X
74
2 3 8 9 105 6
Digit in partn°:
Partn°:
Serial n°:
X = product with a specific customer requirement
See nameplate, always provide complete partn° and
serial when ordering spares.
E X P E D I T E S H I P P L A N ( E S P )
Several parts are available for quick shipment, within max.
1 week after factory receipt of purchase order, through the
Expedite Ship Plan (ESP).
Parts covered by ESP service are conveniently grey coded
in the selection tables.
7
MODEL IDENTIFICATION
A complete measuring system consists of:
1. Echotel
®
electronics
2. Echotel
®
transducer
1
.
C
o
d
e
f
o
r
E
c
h
o
t
e
l
®
e
le
c
t
ro
n
ic
s
9 0 A
5
6 0
complete code for Echotel
®
electronics
0 Integral mount electronics
1 2 3 | BASIC MODEL NUMBER
961 Echotel
®
961 electronics for single setpoint 9M1 transducers
9
62 Echotel
®
9
62 electronics for dual setpoint 9M2 transducers
4 5 6 | INPUT POWER
8 | MOUNTING
0 Blind housing cover
1 Housing cover with glass window (not for cast stainless steel housings)
7 | ACCESSORIES
A
ATEX II 1 G Ex ia IIC T4 Ga, intrinsically safe
-
except deep drawn SST housing
C
ATEX II 1/2 G / IEC Ex db IIC T6 Ga/Gb, flameproof enclosure
-
except deep drawn SST housing
1
Weatherproof
-
except deep drawn SST housing
7
Weatherproof
- deep drawn SST housing
9 | APPROVALS
1 Cast aluminium housing with M20 x 1,5 cable entry (2 entries one plugged)
0 Cast aluminium housing with 3/4" NPT cable entry (2 entries one plugged)
3 Cast stainless steel with M20 x 1,5 cable entry (2 entries – one plugged)
2 Cast stainless steel with 3/4" NPT cable entry (2 entries one plugged)
5
Deep drawn 304 stainless steel with M20 x 1,5 cable entry (2 entries one plugged)
4
Deep drawn 304 stainless steel with 1/2"NPT cable entry (1 entry)
10 | HOUSING / CABLE ENTRY
50 A 12 - 35 V DC 2-wire loop powered electronics with current shift output
X = product with a specific customer requirement
2. Code for Echotel
®
transducer
complete code for Echotel
®
transducer
A 316/316L (1.4401/1.4404) stainless steel
B Hastelloy
®
C (2.4819) only available with 9M1
C Monel
®
(2.4360) only available with 9M1
N 316/316L (1.4401/1.4404) stainless steel & NACE MR0175/MR0103
P CPVC
R Kynar
®
(PVDF) – only available with 9M1
S 316/316L (1.4401/1.4404) stainless steel with 0,5 µm Ra (20 Ra) surface finish
1 2 3 | BASIC MODEL NUMBER
9M1 Echotel
®
961 transducer with single setpoint
9M2 Echotel
®
962 transducer with dual setpoints
4 | TRANSDUCER MATERIALS (use only metal transducers for hazardous area)
9 M
X = product with a specific customer requirement
SEE NEXT PAGE
1 75 642 3 8 9 10
1
7
5
64
2 3 8 9 10
8
MODEL IDENTIFICATION
2. Code for Echotel
®
transducer
9 M
complete code for Echotel
®
transducer
8 9 10 | ACTUATION LENGTH specify per cm (0.39") increment
Total insertion length = actuation length + 6 mm (0.25")
9M1 transducers
003 Minimum 3 cm (1.2") for metal transducers with NPT connections only
005 Minimum 5 cm (2") for all other connections
304 Maximum 304 cm (120") for Kynar
®
(PVDF) material
330 Maximum 330 cm (130") for all other materials
9M2 transducers "A" length
specify "B" length separately
(see drawing and note shown in the dimensions section)
013 Minimum 13 cm (5.1") for metal transducers with NPT connections only
015 Mininimum 15 cm (5.9") for all other connections
330 Maximum 330 cm (130")
A
Standard sensor: min -40 °C / max +165 °C (-40 °F / +325 °F)
C
Low temperature sensor: min -80 °C / max +120 °C (-110 °F / +250 °F) only
available with 9M1-A
7 | SENSOR TYPE
X = product with a specific customer requirement
23 1" 150 lbs ASME RF
¡
33 1 1/2" 150 lbs ASME RF
¡
43 2" 150 lbs ASME RF
¡
ASME Flanges for plastic transducers
¿
BA
DN 25 PN 16 EN 1092-1 Type A
CA
DN 40 PN 16 EN 1092-1 Type A
DA
DN 50 PN 16 EN 1092-1 Type A
EN Flanges for plastic transducers
¿
3T 1 1/2" Tri-clamp
®
4T 2" Tri-clamp
®
VV DN 65 Varivent
®
type N
Hygienic
BS DN 25 DIN 11851
CS DN 40 DIN 11851
DS DN 50 DIN 11851
¿ CPVC flanges for CPVC transducers, Kynar
®
cladded SST flanges for Kynar
®
transducers
¡ FF (flat face) flanges for CPVC transducers
5 6 | PROCESS CONNECTION
Threaded (plastic transducers are only available with 3/4" NPT connection)
11 3/4" NPT
21 1" NPT
1
2 3/4" BSP (G 3/4")
22 1" BSP (G 1")
23 1" 150 lbs ASME RF
24 1" 300 lbs ASME RF
25 1" 600 lbs ASME RF
33 1 1/2" 150 lbs ASME RF
34 1 1/2" 300 lbs ASME RF
35 1 1/2" 600 lbs ASME RF
43 2" 150 lbs ASME RF
44 2" 300 lbs ASME RF
45 2" 600 lbs ASME RF
53 3" 150 lbs ASME RF
54 3" 300 lbs ASME RF
55 3" 600 lbs ASME RF
63 4" 150 lbs ASME RF
64 4" 300 lbs ASME RF
65 4" 600 lbs ASME RF
ASME Flanges for metal transducers
BB DN 25
PN 16/25/40
EN 1092-1 Type A
BC DN 25   PN 63/100 EN 1092-1 Type B2
CB DN 40
PN 16/25/40
EN 1092-1 Type A
CC DN 40   PN 63/100 EN 1092-1 Type B2
DA DN 50   PN 16 EN 1092-1 Type A
DB DN 50   PN 25/40 EN 1092-1 Type A
DD DN 50   PN 63 EN 1092-1 Type B2
DE DN 50   PN 100 EN 1092-1 Type B2
EA DN 80   PN 16 EN 1092-1 Type A
EB DN 80   PN 25/40 EN 1092-1 Type A
ED DN 80   PN 63 EN 1092-1 Type B2
EE DN 80   PN 100 EN 1092-1 Type B2
FA DN 100 PN 16 EN 1092-1 Type A
FB DN 100 PN 25/40 EN 1092-1 Type A
FD DN 100 PN 63 EN 1092-1 Type B2
FE DN 100 PN 100 EN 1092-1 Type B2
EN Flanges for metal transducers
SEE PREVIOUS PAGE
1
7
5
6
4
2 3 8 9 10
9
D
IMENSIONS IN mm (inches)
1
02
(4)
6 (0.25)
46 (1.8) Typical
Ø
22,9 (0.90)
A
ctuation length
for NPT connection
Actuation
length
f
or BSP
connection
1
13 (4.43) without window
123 (4.85) with window
102
(4)
6 (0.25)
6
0 (2.35) Typical
Ø 22,9 (0.90)
Actuation length
113 (4.43) without window
1
23 (4.85) with window
961 - Threaded connection
961 - Flanged connection
102
(4)
6 (0.25)
46 (1.8) Typical
Ø 22,9 (0.90)
Actuation length “A”
for NPT connection
Actuation length “B”
f
or NPT connection
Actuation
length “A”
for BSP
connection
Actuation length
B” for BSP
connection
113 (4.43) without window
123 (4.85) with window
1
02
(4)
6 (0.25)
60 (2.35) Typical
Ø 22,9 (0.90)
Actuation length “A”
Actuation length
“B”
113 (4.43) without window
1
23 (4.85) with window
962 - Threaded connection 962 - Flanged connection
Note: - Difference between actuation lengths "A" and "B" must be min. 8 cm.
- Max. length for dimension "B" is 322 cm.
10
D
IMENSIONS IN mm (inches)
Cable entry
6
0
(2.36)
125
(4.92)
4
52
(2.05)
58
(2.28)
109
(4.28)
43° View
PRESSURE / TEMPERATURE RATINGS
0-40 40 80 120 165
40
80
120
160
316/316L (1.4401/1.4404)
¡
Hastelloy
®
C (2.4819)
Monel
®
(2.4360)
Range with 3/4" NPT
Range with 150# flange
Range with PN16 flange
138 bar
¿
103 bar
82,8 bar
Process temperature (°C)
Process temperature (°C)
Process pressure (bar)
Process pressure (bar)
30
25
20
15
10
5
-40 0 40 80 120
0
Kynar
®
Transducer Ratings
Process temperature (°C)
Process pressure (bar)
30
25
20
15
10
5
-40 0 40 80 120
0
CPVC Transducer Ratings
Metal Transducer Ratings
¿
Only applicable to NPT-connections with actuation length = 3 cm
and BSP/ASME/EN-connections with actuation length = 5 cm
¡
For low temperature sensor: from -80 °C up to +120 °C
29 (1.14)
Ø 22,9 (0.90)
A
ctuation Length
T
ri-Clamp
®
3
5 (1.38)
Ø 22,9 (0.90)
Actuation Length
D
IN 11851
4
6 (1.81)
Ø 22,9 (0.90)
6 (0.25)
6 (0.25)
6 (0.25)
Actuation Length
Varivent
®
11
SPECIFICATIONS
Description Specification
Input Voltage 2 wire loop powered, 12 - 35 V DC
Power Consumption < 1 Watt
Output
9
61: 8 mA (safe), 16 mA (alarm) ± 1 mA
962: 8 mA (safe), 12 mA (lower gap alarm), 16 mA (upper gap alarm) ± 1 mA
961/962: ≤ 3,6 or ≥ 22 mA error signal
Time delay 0,5 to 10 s adjustable (in addition to transducer response time)
Indication
LED’s for process alarm status, malfunction (error of transducer, electronics or elec-
trical noise interference)
Selftest
Automatic Continuously verifies electronics, transducer and noise interference
M
anual
V
ia pushbutton for checking alarm output(s) and error output/function.
Housing material IP66, cast aluminium, cast stainless steel or deep drawn 304 stainless steel (IP 67)
Approvals
¿
ATEX II 1 G Ex ia IIC T4 Ga, intrinsically safe
ATEX II 1/2 G Ex db IIC T6 Ga/Gb, flameproof enclosure
IEC Ex d IIC T6 Ga/Gb + Ex ia IIC T4 Ga
Overfill prevention TÜV - WHG § 63 / VLAREM II 5.17.7
Other approvals are available, consult factory for more details
SIL (Safety Integrity Level)
Functional safety to SIL 2 in accordance to IEC 61508 – SFF > 90 %
Full FMEDA report and declaration sheets available at request
Electrical data Ui = 28,4 V, li = 94 mA, Pi = 0,67 W
Equivalent data Ci = 10,4 nF, Li = 3 µH
Shock/Vibration ANSI/ISA-S71.03 Class SA1 (shock), ANSI/ISA-S71.03 Class VC2 (vibration)
Net weight
Aluminium / Deep drawn 304 SST: 1 kg (2.2 lbs) – electronics only
Cast SST: 2,5 kg (5.5 lbs) – electronics only
Description Specification
Response time 0,5 s typical
Repeatability ± 2 mm (0.078")
Ambient Temperature -40 °C to +70 °C (-40 °F to +160 °F)
Humidity 0-99 %, non-condensing
Electromagnetic Compatibility Meets CE requirements (EN 61326: 1997 + A1 + A2) and NAMUR NE 21
Electronics specifications
Performance
Transducer specifications
¿
Only available with cast aluminium or cast stainless steel housings
Description Plastic transducers Metal transducers
Material
CPVC
Kynar
®
(PVDF)
316/316L SST (1.4401/1.4404)
Hastelloy
®
C (2.4819)
Monel
®
(2.4360)
Mounting Threaded (NPT/BSP) – Flanged (ASME - EN) – Hygienic
Actuation length
From 5 cm up to 304 cm
(2" up to 120") PVDF
From 5 cm up to 330 cm
(2" up to 130") CPVC
From 3 cm up to 330 cm (1.2" up to 130")
Process temp. (consult temp/
press. graphs)
-40 °C to +120 °C (-40 °F to +250 °F) – PVDF
-40 °C to +80 °C (-40 °F to +180 °F) – CPVC
-40 °C to +165 °C (-40 °F to +325 °F) – standard
-80 °C to +120 °C (-110 °F to +250 °F) – low
temperature version in 316/316L SST
Max pressure (consult temp/
press. graphs)
13,8 bar @ +40 °C (200 psi @ +100 °F)
for NPT threaded units
82,8 bar (1200 psi) for Monel transducers
Consult temp/press. graphs for other
materials
Flanged models are downrated to the design pressure of the selected flange
IMPORTANT
SERVICE POLICY
Owners of Magnetrol products may request the return of a control; or, any part of a control for complete rebuilding or
replacement. They will be rebuilt or replaced promptly. Magnetrol International will repair or replace the control, at no cost to
t
he purchaser, (or owner) other than transportation cost if:
a. Returned within the warranty period; and,
b. The factory inspection finds the cause of the malfunction to be defective material or workmanship.
If the trouble is the result of conditions beyond our control; or, is NOT covered by the warranty, there will be charges for labour
and the parts required to rebuild or replace the equipment.
In some cases, it may be expedient to ship replacement parts; or, in extreme cases a complete new control, to replace the
original equipment before it is returned. If this is desired, notify the factory of both the model and serial numbers of the
control to be replaced. In such cases, credit for the materials returned, will be determined on the basis of the applicability of
our warranty.
No claims for misapplication, labour, direct or consequential damage will be allowed.
RETURNED MATERIAL PROCEDURE
So that we may efficiently process any materials that are returned, it is essential that a “Return Material Authorisation” (RMA)
form will be obtained from the factory. It is mandatory that this form will be attached to each material returned. This form is
available through Magnetrol’s local representative or by contacting the factory. Please supply the following information:
1. Purchaser Name
2. Description of Material
3. Serial Number and Ref Number
4. Desired Action
5. Reason for Return
6. Process details
Any unit that was used in a process must be properly cleaned in accordance with the proper health and safety standards
applicable by the owner, before it is returned to the factory.
A material Safety Data Sheet (MSDS) must be attached at the outside of the transport crate or box.
All shipments returned to the factory must be by prepaid transportation. Magnetrol will not accept collect shipments.
All replacements will be shipped Ex Works.
BULLETIN N°: BE 51-646.12
EFFECTIVE: AUGUST 2020
SUPERSEDES: August 2017
UNDER RESERVE OF MODIFICATIONS