Whirlpool MED8630HW Guide d'installation

Taper
Guide d'installation
DRYER INSTALLATION INSTRUCTIONS
INSTRUCTIONS POUR L’INSTALLATION
DE LA SÉCHEUSE
Para una version de estas instrucciones en español, visite www.whirlpool.com
Table of Contents Table des matières
W11183136B
W11183139B-SP
INSTALLATION NOTES
Date of purchase: ________________________________________
Date of installation: _______________________________________
Installer: _________________________________________________
Model number: ___________________________________________
Serial number: ____________________________________________
NOTES CONCERNANT L’INSTALLATION
Date d’achat: ____________________________________________
Date d’installation: ________________________________________
Installateur: ______________________________________________
Numéro de modéle: _______________________________________
Numéro de série: _________________________________________
DRYER SAFETY ....................................................................... 2
INSTALLATION REQUIREMENTS ........................................... 4
Tools and Parts ..................................................................................4
LOCATION REQUIREMENTS .................................................. 5
ELECTRICAL REQUIREMENTS – U.S.A. ONLY ..................... 7
ELECTRIC DRYER POWER HOOKUP – CANADA ONLY ...... 8
GAS DRYER POWER HOOKUP .............................................. 8
INSTALL LEVELING LEGS ..................................................... 10
MAKE ELECTRICAL CONNECTION – U.S.A. ONLY ............ 11
Power Supply Cord Connection ...................................................11
4-Wire Power Supply Cord Connection ......................................12
MAKE GAS CONNECTION .................................................... 17
VENTING ................................................................................. 18
Venting Requirements ....................................................................18
Plan Vent System ............................................................................ 19
Install Vent System .......................................................................... 20
CONNECT INLET HOSE ....................................................... 21
CONNECT VENT .................................................................... 22
LEVEL DRYER ........................................................................ 23
COMPLETE INSTALLATION CHECKLIST............................. 23
DOOR REVERSAL (OPTIONAL) ............................................ 24
SÉCURITÉ DE LA SÉCHEUSE .............................................. 30
EXIGENCES D’INSTALLATION ............................................. 32
Outillage et pièces ........................................................................32
EXIGENCES D’EMPLACEMENT ........................................... 33
SÉCHEUSE ÉLECTRIQUE RACCORDEMENT
À L’ALIMENTATION ÉLECTRIQUE –
CANADA SEULEMENT .......................................................... 36
RACCORDEMENT D’UNE SÉCHEUSE À GAZ .................... 37
INSTALLATION DES PIEDS DE NIVELLEMENT .................. 38
RACCORDEMENT AU GAZ ................................................... 39
ÉVACUATION ......................................................................... 40
Exigences concernant l’évacuation ................................. 40
Planification du système d’évacuation ............................ 41
Installation du système d’évacuation .............................. 42
RACCORDEMENT DU TUYAU D’ALIMENTATION
(MODÈLE À VAPEUR UNIQUEMENT) .................................. 43
RACCORDEMENT DU CONDUIT D’ÉVACUATION ............. 44
RÉGLAGE DE L’APLOMB DE LA SÉCHEUSE ..................... 45
ACHEVER L’INSTALLATION LISTE DE VÉRIFICATION ....... 45
INVERSION DE LA PORTE (FACULTATIF) ............................ 46
2
DRYER SAFETY
3
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury, death or property
damage.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this
or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
Installation and service must be performed by a qualified installer, service agency, or
the gas supplier.
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Clear the room, building, or area of all occupants.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's
instructions.
If you cannot reach your gas supplier, call the fire department.
IMPORTANT: The gas installation must conform with local codes, or in the absence of local codes, with the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane Installation Code, CSA B149.1.
The dryer must be electrically grounded in accordance with local codes, or in the absence of local codes, with the National
Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, Part 1, CSA C22.1.
In the State of Massachusetts, the following installation instructions apply:
Installations and repairs must be performed by a qualified or licensed contractor, plumber, or gas fitter qualified or licensed by
the State of Massachusetts.
Acceptable Shut-off Devices: Gas Cocks and Ball Valves installed for use shall be listed.
A flexible gas connector, when used, must not exceed 4 feet (121.9 cm).
4
INSTALLATION REQUIREMENTS
Tools and Parts
Gather the required tools and parts before starting installation.
Tools needed for all installations:
Level
Tape measure
Flat-blade screwdriver
Adjustable wrench that
opens to 1" (25 mm) or
hex-head socket wrench
Tin snips (new vent
installations)
Caulking gun and
compound (new vent
installations)
1/4" (6 mm) and
5/16" (8 mm) nut driver
(recommended)
Utility knife
Wire stripper
(direct wire installations)
Leveling legs (4)
Tools needed for gas installations:
8" (203 mm) or 10"
(254 mm) pipe wrench
8" (203 mm) or 10" (254 mm)
adjustable wrench (for gas
connections)
Pipe-joint compound
resistant to propane gas
“Y” connector
Parts package is located in dryer drum. Check that all parts are
included.
NOTE: Do not use leveling legs supplied with dryer if installing
with a pedestal or a stack kit.
Parts supplied (all models):
Parts needed (steam models):
2' (0.6 m) inlet hose
5' (1.52 m) inlet hose
Parts needed (not supplied with dryer):
Vent clamps
Vent elbows and vent work
Rubber washer
#2 Phillips screwdriver
Pliers
5
Additional parts may be required, depending on your installation.
Check local codes. Check existing electrical supply and venting.
Read “Electrical Requirements” and “Venting Requirements”
before purchasing parts.
If using a power supply cord:
Use a UL Listed power supply cord kit marked for use with
clothes dryers. The kit should contain:
A UL Listed 30 A power supply cord, rated 120/240 V
minimum. The cord should be type SRD or SRDT and be at
least 4 ft. (1.22 m) long. The wires that connect to the dryer
must end in ring terminals or spade terminals with upturned
ends.
A UL Listed strain relief.
Optional Equipment (not supplied with dryer):
Refer to your Use and Care Guide for information about
accessories available for your dryer.
LOCATION REQUIREMENTS
Check code requirements. Some codes limit, or do not permit,
installing dryer in garages, closets, mobile homes, or sleeping
quarters. Contact your local building inspector.
You will need:
A location allowing for proper exhaust installation.
See “Venting Requirements.”
A separate 15 or 20 A circuit for a gas dryer or 30 A circuit for
an electric dryer.
If using power supply cord, a grounded electrical outlet
located within 2 ft. (610 mm) of either side of dryer.
See “Electrical Requirements.”
Floor must support dryer weight of 200 lbs. (90.7 kg). Also
consider weight of companion appliance.
Cold water faucets located within 4 ft. (1.2 m) of the water
ll valves, and water pressure of 20–120 psi (138–827 kPa).
You may use your washer’s water supply by purchasing the
necessary parts noted in “Parts needed.”
Level oor with maximum slope of 1" (25 mm) under entire
dryer. If slope is greater than 1" (25 mm), install Extended
Dryer Feet Kit, Part Number 279810. If not level, clothes may
not tumble properly and automatic sensor cycles may not
operate correctly.
For garage installation, place dryer at least 18" (460 mm)
above oor. If using a pedestal, you will need 18" (460 mm) to
bottom of dryer.
The dryer must not be installed or stored in an area where it
will be exposed to water and/or weather.
IMPORTANT: Do not operate, install, or store dryer where it
will be exposed to water, weather, or at temperatures below
40°F (4°C). Lower temperatures may cause dryer not to shut
off at end of automatic sensor cycles, resulting in longer drying
times.
Side view:
Front view:
DRYER DIMENSIONS
*Approx. measurement
Maytag
®
Models
Whirlpool
®
Models
*Approx. measurement
6
Back view:
*Approx. measurement
Recommended installation clearances (dryer only):
0" (0 mm) rear spacing is allowed for straight back venting only.
For steam models only, inlet hose must not be kinked.
Custom under-counter installation:
NOTE: Most installations require a minimum of 5" (127 mm)
clearance behind dryer for exhaust vent with elbow. See “Venting
Requirements.”
Installation Clearances
For each arrangement, consider allowing more space for ease of
installation and servicing, spacing for companion appliances, and
clearances for walls, doors, and oor moldings. Space must be
large enough to allow door to fully open. Add spacing on all sides
of dryer to reduce noise transfer. If a closet door or louvered door
is installed, top and bottom air openings in door are required.
Check code requirements. Some codes limit, or do not permit,
installation of the dryer in garages, closets, mobile homes, or
sleeping quarters. Contact your local building inspector.
NOTE: No other fuel-burning appliance can be installed in the
same closet as a dryer.
Installation spacing for recessed area or closet
installation
All dimensions show recommended and minimum spacing
allowed.
Additional spacing should be considered for ease of
installation and servicing.
Additional clearances might be required for wall, door, oor
moldings, dryer venting, and gas line.
Additional spacing should be considered on all sides of the
dryer to reduce noise transfer.
For closet installation with a door, minimum ventilation
openings in the top and bottom of the door are required.
Louvered doors with equivalent ventilation openings are
acceptable.
Companion appliance spacing should also be considered.
Mobile home – Additional installation requirements:
This dryer is suitable for mobile home installations.
The installation must conform to the Manufactured Home
Construction and Safety Standard, Title 24 CFR, Part 3280
(formerly the Federal Standard for Mobile home construction and
Safety, Title 24, HUD Part 280) or Standard CAN/CSA-Z240 MH.
Mobile home installations require:
Metal exhaust system hardware, available for purchase
from your dealer. For further information, see “Assistance or
Service” in your Use and Care Guide.
Special provisions must be made in mobile homes to
introduce outside air into dryer. Openings (such as a nearby
window) should be at least twice as large as dryer exhaust
opening.
For mobile home installation of gas dryers:
Mobile Home Installation Hold-down Kit Part Number 346764
is available to order. For further information, see “Assistance
or Service” in your Use and Care Guide.
Water inlet
(Steam Models Only)
Vent
Gas
7
ELECTRICAL REQUIREMENTS –
U.S.A. ONLY
It is your responsibility:
To contact a qualied electrical installer.
To be sure that the electrical connection is adequate and in
conformance with the National Electrical Code, ANSI/NFPA 70
– latest edition and all local codes and ordinances.
The National Electrical Code requires a 4-wire power supply
connection for homes built after 1996, dryer circuits involved
in remodeling after 1996, and all mobile home installations.
A copy of the above code standards can be obtained from:
National Fire Protection Association, One Batterymarch Park,
Quincy, MA 02269.
To supply the required 3 or 4 wire, single-phase, 120/240 V,
60 Hz, AC-only electrical supply (or 3 or 4 wire, 120/208 V
electrical supply, if specied on the serial/rating plate) on a
separate 30 A circuit, fused on both sides of the line. Connect
to an individual branch circuit. Do not have a fuse in the
neutral or grounding circuit.
Do not use an extension cord.
If codes permit and a separate ground wire is used, it is
recommended that a qualied electrician determine that the
ground path is adequate.
Electrical Connection
To properly install your dryer, you must determine the type of
electrical connection you will be using and follow the instructions
provided for it here.
This dryer is manufactured ready to install with a 3-wire
electrical supply connection. The neutral ground conductor is
permanently connected to the neutral conductor (white wire)
within the dryer. If the dryer is installed with a 4-wire electrical
supply connection, the neutral ground conductor must be
removed from the external ground connector (green screw),
and secured under the neutral terminal (center or white wire)
of the terminal block. When the neutral ground conductor is
secured under the neutral terminal (center or white wire) of the
terminal block, the dryer cabinet is isolated from the neutral
conductor. The green ground wire of the 4-wire power cord
must be secured to the dryer cabinet with the green ground
screw.
If local codes do not permit the connection of a neutral ground
wire to the neutral wire, see “Optional External Ground for
3-Wire Connection” in the “Power Supply Cord Connection”
section.
A 4-wire power supply connection must be used when the
appliance is installed in a location where grounding through
the neutral conductor is prohibited. Grounding through the
neutral is prohibited for (1) new branch-circuit installations
after 1996, (2) mobile homes, (3) recreational vehicles, and (4)
areas where local codes prohibit grounding through the neutral
conductors.
If using a power supply cord:
Use a UL Listed power supply cord kit marked for use with
clothes dryers. The kit should contain:
A UL Listed 30 A power supply cord, rated 120/240 V
minimum. The cord should be type SRD or SRDT and be at
least 4 ft. (1.22 m) long. The wires that connect to the dryer
must end in ring terminals or spade terminals with upturned
ends.
A UL Listed strain relief.
Then choose a 3-wire power supply cord with
ring or spade terminals and UL listed strain
relief. The 3-wire power supply cord, at least
4 ft. (1.22 m) long, must have three 10-gauge
copper wires and match a 3-wire receptacle of
NEMA Type 10-30R.
4-wire receptacle
(14-30R)
3-wire receptacle
(10-30R)
If connecting by direct wire:
Power supply cable must match power supply (4-wire or 3-wire)
and be:
Flexible armored cable or nonmetallic sheathed copper cable
(with ground wire), covered with exible metallic conduit. All
current-carrying wires must be insulated.
10-gauge solid copper wire (do not use aluminum) at least
5 ft. (1.52 m) long.
If your outlet looks like this:
Then choose a 4-wire power supply cord with
ring or spade terminals and UL Listed strain
relief. The 4-wire power supply cord, at least
4 ft. (1.22 m) long, must have four 10-gauge
copper wires and match a 4-wire receptacle of
NEMA Type 14-30R. The ground wire (ground
conductor) may be either green or bare. The
neutral conductor must be identified by a white
cover.
8
ELECTRIC DRYER POWER HOOKUP –
CANADA ONLY
ELECTRICAL REQUIREMENTS
It is your responsibility:
To contact a qualied electrical installer.
To be sure that the electrical connection is adequate and in
conformance with Canadian Electrical Code, C22.1 – latest
edition and all local codes. A copy of above codes standard
may be obtained from: Canadian Standards Association,
178 Rexdale Blvd., Toronto, ON M9W 1R3 CANADA.
To supply the required 4-wire, single-phase, 120/240 V, 60 Hz,
AC-only electrical supply on a separate 30 A circuit, fused on
both sides of the line. A time-delay fuse or circuit breaker is
recommended. Connect to an individual branch circuit.
This dryer is equipped with a UL Listed and/
or CSA International Certied Power Cord
intended to be plugged into a standard
14-30R wall receptacle. The cord is
5 ft. (1.52 m) long. Be sure wall receptacle
is within reach of dryer’s nal location.
If using a replacement power supply cord, it
is recommended that you use Power Supply
Cord Replacement Part Number 8529008.
For further information, please reference service numbers located
in the “Assistance or Service” section of your Use and Care
Guide.
GAS DRYER POWER HOOKUP
ELECTRICAL REQUIREMENTS
120 V, 60 Hz, AC-only, 15 or 20 A fused electrical supply is
required. A time-delay fuse or circuit breaker is recommended.
It is also recommended that a separate circuit serving only this
dryer be provided.
4-wire receptacle
(14-30R)
GROUNDING INSTRUCTIONS
SAVE THESE INSTRUCTIONS
For a grounded, cord-connected dryer:
This dryer must be grounded. In the event of malfunction or
breakdown, grounding will reduce the risk of electric shock
by providing a path of least resistance for electric current.
This dryer is equipped with a cord having an equipment-
grounding conductor and a grounding plug. The plug must
be plugged into an appropriate outlet that is properly
installed and grounded in accordance with all local codes
and ordinances.
WARNING: Improper connection of the equipment-
grounding conductor can result in a risk of electric shock.
epresentative
or personnel if you are in doubt as to whether the dryer is
properly grounded. Do not modify the plug provided with
oper outlet
GROUNDING INSTRUCTIONS
SAVE THESE INSTRUCTIONS
For a grounded, cord-connected dryer:
This dryer must be grounded. In the event of malfunction or
breakdown, grounding will reduce the risk of electric shock
by providing a path of least resistance for electric current.
This dryer is equipped with a cord having an equipment-
grounding conductor and a grounding plug. The plug must
be plugged into an appropriate outlet that is properly
installed and grounded in accordance with all local codes
and ordinances.
WARNING: Improper connection of the equipment-
grounding conductor can result in a risk of electric shock.
epresentative
or personnel if you are in doubt as to whether the dryer is
properly grounded. Do not modify the plug provided with
oper outlet
9
A. 3/8" flexible gas connector
B. 3/8" pipe to flare adapter fitting
C. 1/8" NPT minimum plugged tapping
D. 1/2" NPT gas supply line
E. Gas shut-off valve
GAS SUPPLY REQUIREMENTS
GAS TYPE
Natural Gas:
This dryer is equipped for use with natural gas. It is certied by
UL for use with propane gas with appropriate conversion.
Your dryer must have the correct burner for the type of gas in
your home. Burner information is located on the rating plate in
the door well of your dryer. If this information does not agree
with the type of gas available, contact your dealer or call the
phone numbers referenced in the “Assistance or Service”
section of your Use and Care Guide.
Propane Gas Conversion:
IMPORTANT: Conversion must be made by a qualied
technician.
No attempt shall be made to convert the appliance from the gas
specied on the model/serial rating plate for use with a different
gas without consulting your gas company.
GAS SUPPLY LINE
Option 1 (Recommended Method)
Flexible stainless steel gas connector:
If local codes permit, use a new exible stainless steel gas
connector (Design Certied by the American Gas Association
or CSA International) to connect your dryer to the rigid gas
supply line. Use an elbow and a 3/8" are x 3/8" NPT adapter
tting between the stainless steel gas connector and the dryer
gas pipe, as needed, to prevent kinking.
Option 2 (Alternate Method)
Approved aluminum or copper tubing:
Must include 1/8" NPT minimum plugged tapping accessible
for test gauge connection, immediately upstream of the gas
connection to the dryer. See illustration below.
1/2" IPS pipe is recommended.
3/8" approved aluminum or copper tubing is acceptable for
lengths under 20 ft. (6.1 m) if local codes and gas supplier
permit.
If you are using natural gas, do not use copper tubing.
Lengths over 20 ft. (6.1 m) should use larger tubing and a
different size adapter tting.
If your dryer has been converted to use propane gas, 3/8"
propane compatible copper tubing can be used. If the total
length of the supply line is more than 20 ft. (6.1 m), use larger
pipe.
NOTE: Pipe-joint compounds that resist the action of propane
gas must be used. Do not use TEFLON
®†
tape.
Must include shut-off valve.
In the U.S.A.:
An individual manual shut-off valve must be installed
within six (6) ft. (1.8 m) of the dryer in accordance with
the National Fuel Gas Code, ANSI Z223.1. The location
should be easy to reach for opening and closing.
In Canada:
An individual manual shut-off valve must be installed in
accordance with the B149.1, Natural Gas and Propane
Installation Code. It is recommended that an individual
manual shut-off valve be installed within six (6) ft. (1.8 m)
of the dryer. The location should be easy to reach for
opening and closing.
®
TEFLON is a registered trademark of Chemours.
WARNING
Explosion Hazard
Use a new CSA International approved gas supply line.
Install a shut-off valve.
Securely tighten all gas connections.
If connected to propane, have a qualified person make
sure gas pressure does not exceed 13" (33 cm) water
column.
Examples of a qualified person include:
licensed heating personnel,
authorized gas company personnel, and
authorized service personnel.
Failure to do so can result in death, explosion, or fire.
10
INSTALL LEVELING LEGS
GAS SUPPLY CONNECTION REQUIREMENTS
Use an elbow and a 3/8" are x 3/8" NPT adapter tting
between the exible gas connector and the dryer gas pipe,
as needed to avoid kinking.
Use only pipe-joint compound. Do not use TEFLON
®
tape.
This dryer must be connected to the gas supply line with a
listed exible gas connector that complies with the standard
for connectors for gas appliances, ANSI Z21.24 or CSA 6.10.
BURNER INPUT REQUIREMENTS
Elevations above 2,000 ft. (610 m):
When installed above 2,000 ft. (610 m) a 4% reduction of the
burner Btu rating shown on the model/serial number plate is
required for each 1,000 ft. (305 m) increase in elevation.
Gas supply pressure testing
The dryer must be disconnected from the gas supply piping
system during pressure testing at pressures greater than
1/2 psi.
DRYER GAS PIPE
The gas pipe that comes out through the rear of your dryer has
a 3/8" male pipe thread.
* NOTE: If the dryer is mounted on a pedestal, the gas
pipe height must be an additional 10" (254 mm) or
15.5" (394 mm) from the oor, depending on the pedestal
model. For a garage installation, the gas pipe height must
be an additional 18" (460 mm) from the oor.
1. Prepare dryer for leveling legs
To avoid damaging oor, use a large at piece of cardboard from
dryer carton; place under entire back edge of dryer. Firmly grasp
dryer body (not console panel) and gently lay dryer down on
cardboard.
Examine leveling legs and locate the diamond marking. Screw
legs into leg holes by hand – use a wrench to nish turning legs
until diamond marking is no longer visible.
Place a carton corner post from dryer packaging under each of
the two dryer back corners. Stand the dryer up. Slide the dryer
on the corner posts until it is close to its nal location. Leave
enough room to connect the exhaust vent.
3/8" NPT dryer gas pipe
2. Screw in leveling legs
Diamond
marking
11
MAKE ELECTRICAL CONNECTION –
U.S.A. ONLY
ELECTRICAL CONNECTION
1. Choose electrical connection type
Power supply cord 4-wire receptacle
(NEMA Type 14-30R).
Go to “Power Supply Cord Connection.”
3-wire direct connection:
Go to “Direct Wire Connection.”
4-wire direct connection:
Go to “Direct Wire Connection.”
Power supply cord 3-wire receptacle
(NEMA Type 10-30R).
Go to “Power Supply Cord Connection.”
NOTE: If local codes do not permit connection of a
cabinet-ground conductor to neutral wire, go to “Optional
External Ground for 3-Wire Connection.” This connection
may be used with either a power supply cord or a direct
wire connection.
Before you start: disconnect power.
Remove hold-down screw and terminal block cover.
2. Remove terminal block cover
Power Supply Cord Connection
Power supply cord strain relief
1. Attach power supply cord strain relief
Remove the screws from a 3/4" (19 mm) UL Listed strain relief.
Put the tabs of the two clamp sections (C) into the hole below the
terminal block opening (B) so that one tab is pointing up (A) and the
other is pointing down (D), and hold in place. Tighten strain relief
screws just enough to hold the two clamp sections (C) together.
Power Supply Cord:
12
1. Prepare to connect neutral ground
wire and neutral wire
Remove center terminal block screw (B). Remove neutral ground
wire (E) from green external ground conductor screw (A).
2. Connect neutral ground wire
and neutral wire
Connect neutral ground wire (E) and neutral wire (white or center)
(C) of power supply cord under center terminal block screw (B).
Tighten screw.
3. Connect ground wire
Connect ground wire (F) (green or bare) of power supply cord
under green external ground conductor screw (A). Tighten screw.
4-Wire Power Supply Cord Connection
4-wire receptacle
(NEMA type 14-30R)
4 prong plug
Spade terminals
with upturned ends
Ring terminals
IMPORTANT: A 4-wire connection is required for mobile homes
and where local codes do not permit the use of 3-wire connections.
2. Attach power supply cord
to strain relief
Put power supply cord through the strain relief. Be sure that the
wire insulation on the power supply cord is inside the strain relief.
The strain relief should have a tight fit with the dryer cabinet and
be in a horizontal position. Do not further tighten strain relief
screws at this point.
Power supply cord 4-wire receptacle
(NEMA Type 14-30R):
Go to “4-Wire Power Supply Cord
Connection” on this page.
If your outlet looks like this:
Power supply cord 3-wire receptacle
(NEMA Type 10-30R):
Go to “3-Wire Power Supply Cord
Connection” on page 13.
13
1. Remove center screw
Remove center terminal block screw (B).
3. Connect remaining wires
2. Connect neutral wire
Connect remaining wires under outer terminal block screws.
Tighten screws. Finally, reinsert tab of terminal block cover into
slot of dryer rear panel. Secure cover with hold-down screw. Now
go to “Venting Requirements.”
Connect neutral wire (white or center) (C) of power supply cord
under center terminal block screw (B). Tighten screw.
3-wire receptacle
(NEMA type 10-30R)
3 prong plug
Spade terminals
with upturned ends
Ring terminals
4. Connect remaining wires
Connect remaining wires under outer terminal block screws.
Tighten screws. Finally, reinsert tab of terminal block cover into
slot of dryer rear panel. Secure cover with hold-down screw. Now
go to “Venting Requirements.”
3-Wire Power Supply Cord Connection
Use where local codes permit connecting cabinet-ground
conductor to neutral wire.
14
Direct Wire Connection
2. Attach direct wire cable to strain relief
Put direct wire cable through the strain relief. The strain relief
should have a tight fit with the dryer cabinet and be in a horizontal
position. Tighten strain relief screw against the direct wire cable.
3-wire direct connection:
Go to “3-Wire Direct Wire Connection”
on page 15.
4-wire direct connection:
Go to “4-Wire Direct Wire Connection”
on this page.
If your wiring looks like this:
4-Wire Direct Wire Connection
IMPORTANT: A 4-wire connection is required for mobile homes
and where local codes do not permit 3-wire connections.
1. Prepare your 4-wire cable
for direct connection
Direct wire cable must have 5 ft. (1.52 m) of extra length so dryer
may be moved if needed.
Strip 5" (127 mm) of outer covering from end of cable, leaving
bare ground wire at 5" (127 mm). Cut 1
1
/2" (38 mm) from remaining
three wires. Strip insulation back 1" (25 mm). Shape ends of wires
into hooks.
For direct wire installations:
1. Attach direct wire strain relief
Unscrew the removable conduit connector (A) and any screws
from a 3/4" (19 mm) UL Listed strain relief. Put the threaded
section of the strain relief (C) through the hole below the terminal
block opening (B). Reaching inside the terminal block opening,
screw the removable conduit connector (A) onto the strain relief
threads and tighten securely.
Direct wire strain relief
15
2. Prepare to connect neutral ground
wire and neutral wire
Remove center terminal block screw (B). Remove neutral ground
wire (E) from green external ground conductor screw (A).
2. Remove center screw
Remove center terminal block screw (B).
4. Connect ground wire
Connect ground wire (green or bare) (F) of direct wire cable under
green external ground conductor screw (A). Tighten screw.
5. Connect remaining wires
Place hooked ends of remaining direct wire cable wires under
outer terminal block screws (hooks facing right). Squeeze
hooked ends together and tighten screws. Finally, reinsert tab of
terminal block cover into slot of dryer rear panel. Secure
cover
with hold-down screw. Now go to “Venting Requirements.”
1. Prepare your 3-wire cable
for direct connection
Direct wire cable must have 5 ft. (1.52 m) of extra length so dryer
may be moved if needed.
Strip 3
1
/2" (89 mm) of outer covering from end of cable. Strip
insulation back 1" (25 mm). If using 3-wire cable with ground
wire, cut bare wire even with outer covering. Shape wire ends
into hooks.
3. Connect neutral ground wire
and neutral wire
Connect neutral ground wire (E) and place
hooked end (hook facing right) of neutral wire
(white or center wire) (C) of direct wire cable
under center screw of terminal block (B). Squeeze
hooked ends together and tighten screw.
3-Wire Direct Wire Connection
Use where local codes permit connecting cabinet-ground
conductor to neutral wire.
16
Optional External Ground for 3-Wire
Connection (Power Supply Cord Shown)
IMPORTANT: You must verify with a qualified electrician that this
grounding method is acceptable before connecting.
1. Prepare to connect neutral ground
wire and neutral wire
Install the correct strain relief for your electrical connection
method, as shown on page 12 or 14.
Remove center terminal block screw (B). Remove neutral ground
wire (E) from green external ground conductor screw (A).
Connect a separate copper ground wire (G) under the green
external ground conductor screw (A) to an adequate ground.
Finally, reinsert tab of terminal block cover into slot of dryer rear
panel. Secure cover with hold-down screw. Now go to “Venting
Requirements.”
4. Connect external ground wire
Connect neutral ground wire (E) and neutral wire (white or center
wire) (C) of power supply cord or cable under center terminal
block screw (B). Tighten screw.
2. Connect neutral ground wire
and neutral wire
Place ends of remaining wires under outer terminal block screws.
Tighten screws.
3. Connect remaining wires
Place hooked ends of remaining direct wire cable wires under
outer terminal block screws (hooks facing right). Squeeze
hooked ends together and tighten screws. Finally, reinsert tab of
terminal block cover into slot of dryer rear panel. Secure cover
with hold-down screw. Now go to “Venting Requirements.”
4. Connect remaining wires
3. Connect neutral wire
Place hooked end of neutral wire (white or
center) (C) of direct wire cable under center
terminal block screw (B), hook facing right.
Squeeze hooked end together. Tighten screw.
17
1. Connect gas supply to dryer
Remove red cap from gas pipe. Using a wrench to tighten,
connect gas supply to dryer. Use pipe-joint compound
on threads of all non-flared male fittings. If flexible metal
tubing is used, be sure there are no kinks.
NOTE: For propane gas connections, you must use
pipe-joint compound resistant to action of propane gas.
Do not use TEFLON
®
tape.
2. Plan pipe fitting connection (Option 1)
A combination of pipe fittings must be used to connect dryer to
existing gas line. A recommended connection is shown. Your
connection may be different, according to supply line type, size,
and location.
3. Open shut-off valve
Open shut-off valve in supply line; valve is open when handle is
parallel to gas pipe. Then, test all connections by brushing on
an approved noncorrosive leak-detection solution. Bubbles will
show a leak. Correct any leak found.
MAKE GAS CONNECTION
(Gas models only)
A. Flared male fitting
B. Non-flared male fitting
A. 3/8" flexible gas connector
B. 3/8" dryer gas pipe
C. 3/8" to 3/8" pipe elbow
D. 3/8" pipe-to-flare adapter
fitting
A. Closed valve
B. Open valve
WARNING
Explosion Hazard
Use a new CSA International approved gas supply line.
Install a shut-off valve.
Securely tighten all gas connections.
If connected to propane, have a qualified person make
sure gas pressure does not exceed 13" (33 cm) water
column.
Examples of a qualified person include:
licensed heating personnel,
authorized gas company personnel, and
authorized service personnel.
Failure to do so can result in death, explosion, or fire.
18
Louvered Hood
Angled Hood
Box Hood
Recommended Styles:
Acceptable Style:
Venting Requirements
VENTING
WARNING: To reduce the risk of fire, this dryer MUST BE
EXHAUSTED OUTDOORS.
IMPORTANT: Observe all governing codes and ordinances.
Dryer exhaust must not be connected into any gas vent,
chimney, wall, ceiling, attic, crawlspace, or a concealed space
of a building. Only rigid or flexible metal vent shall be used for
exhausting.
4" (102 mm) heavy metal exhaust vent
Exhaust hoods:
An exhaust hood should cap the vent to keep rodents and
insects from entering the home.
Must be at least 12" (305 mm) from ground or any object
that may obstruct exhaust (such as owers, rocks, bushes,
or snow).
Do not use an exhaust hood with a magnetic latch.
Only a 4" (102 mm) heavy metal exhaust vent and clamps may
be used.
Do not use plastic or metal foil vent.
Rigid metal vent:
Recommended for best drying performance and to avoid
crushing and kinking.
Flexible metal vent: (Acceptable only if accessible to clean)
Must be fully extended and supported in nal dryer location.
Remove excess to avoid sagging and kinking that may result
in reduced airow and poor performance.
Do not install in enclosed walls, ceilings, or oors.
The total length should not exceed 7¾ ft. (2.4 m).
The length of exible metal vent used must be included in
the overall vent system design as shown in the “Vent System
Charts.”
NOTE: If using an existing vent system, clean lint from entire
length of the system and make sure exhaust hood is not plugged
with lint. Replace plastic or metal foil vents with rigid metal
or exible metal vents. Review “Vent System Charts” and, if
necessary, modify existing vent system to achieve best drying
performance.
Elbows:
45° elbows provide better airow than 90° elbows.
Clamps:
Use clamps to seal all joints.
Exhaust vent must not be connected or secured with screws
or other fastening devices that extend into interior of duct and
catch lint. Do not use duct tape.
Better
Good
WARNING
Fire Hazard
Use a heavy metal vent.
Do not use a plastic vent.
Do not use a metal foil vent.
Failure to follow these instructions can result in death
or fire.
19
Plan Vent System
Recommended exhaust installation:
A. Dryer
B. Elbow
C. Wall
D. Exhaust hood
E. Clamps
F. Rigid metal or flexible
metal vent
G. Vent length necessary
to connect elbows
H. Exhaust outlet
Optional exhaust installations:
This dryer can be converted to exhaust out the right side,
left side (all models except long vent), or through the bottom.
If you prefer, you may contact your local dealer to have the
dryer converted.
A. Standard rear offset exhaust installation
B. Left- or right-side exhaust installation
C. Bottom exhaust installation
Special provisions for mobile homes:
Exhaust vent must be securely fastened to a noncombustible
portion of mobile home and must not terminate beneath the
mobile home. Terminate exhaust vent outside.
Determine vent path:
Select route that will provide straightest and most direct path
outdoors.
Plan installation to use fewest number of elbows and turns.
When using elbows or making turns, allow as much room as
possible.
Bend vent gradually to avoid kinking.
Use as few 90° turns as possible.
Determine vent length and elbows needed for best
drying performance:
Use the following “Vent System Charts” to determine type of
vent material and hood combinations acceptable to use.
NOTE: Do not use vent runs longer than those specied in
“Vent System Charts.”
Exhaust systems longer than those specied will:
Shorten life of dryer.
Reduce performance, resulting in longer drying times and
increased energy usage.
The “Vent System Charts” provide venting requirements that will
help achieve best drying performance.
Standard Vent System Chart
Number of 90°
elbows
Type of vent Angled hoods
0
Rigid metal 64 ft. (20 m)
1
Rigid metal 54 ft. (16.5 m)
2
Rigid metal 44 ft. (13.4 m)
3
Rigid metal 35 ft. (10.7 m)
4
Rigid metal 27 ft. (8.2 m)
WARNING
Fire Hazard
Cover unused exhaust holes with a manufacturer’s
exhaust cover kit.
Contact your local dealer.
Failure to follow these instructions can result in death,
fire, electrical shock, or serious injury.
G
20
Long Vent System Chart
Number of 90°
elbows
Type of vent Angled hoods
0
Rigid metal 160 ft. (48.8 m)
1
Rigid metal 150 ft. (45.7 m)
2
Rigid metal 140 ft. (42.7 m)
3
Rigid metal 130 ft. (39.6 m)
4
Rigid metal 120 ft. (36.6 m)
Install Vent System
1. Install exhaust hood
2. Connect vent to exhaust hood
Install exhaust hood and use caulking compound to seal exterior
wall opening around exhaust hood.
Vent must fit over the exhaust hood. Secure vent to exhaust
hood with 4" (102 mm) clamp. Run vent to dryer location using
straightest path possible. Avoid 90° turns. Use clamps to seal all
joints. Do not use duct tape, screws, or other fastening devices
that extend into interior of vent to secure vent, because they can
catch lint.
To determine if your model has a long vent system, refer to
the type code located on the serial number plate in the inner
door well. Example: An electric model would be DJAV – ELE –
XXXXXXX-XXX. A gas model would be DJAV – NAT – XXXXXXX-
XXX.
NOTE: For long vent systems, use of box/louvered hoods will
improve venting regardless of length.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52

Whirlpool MED8630HW Guide d'installation

Taper
Guide d'installation

dans d''autres langues