ABB System pro M RHI Manuel utilisateur

Taper
Manuel utilisateur

Ce manuel convient également à

1
RLI
EG 598 5 - GH V021 5985 R0001
RHI
EG 599 3 - GH V021 5993 R0001
Minimum current relay
(RLI) and maximum current
relay (RHI)
Relais Mindeststrom (RLI)
und Relais Höchststrom (RHI)
Relé de corrente mínima
(RLI) e máxima (RHI)
Relais de courant minimum
(RLI) et maximum (RHI)
Реле минимального (RLI)
и максимального (RHI)
тока.
Relé de mínima corriente
(RLI) y relé de máxima
corriente (RHI)
ON
313 - 9952
System
pro M
Relè di minima (RLI) e di
massima (RHI) corrente
2
Descrizione generale
I relè di minima o di massima corrente (RLI - RHI) consentono la
protezione ed il controllo delle apparecchiature ad essi collegate.
Infatti l’utilizzo di tali prodotti evita i seguenti principali
inconvenienti:
a) Anomalie nel funzionamento delle apparecchiature
b) Deterioramento delle caratteristiche/funzioni tecniche delle
apparecchiature
c) Danneggiamento delle apparecchiature
d) Eventuali disservizi (fermi macchine, perdita dati, ecc.)
3
Esempio
Principio di funzionamento relè di MINIMA
CORRENTE (RLI):
Dovendo controllare un carico avente i seguenti dati di targa
I
n
= 7 A (corrente nominale di normale funzionamento)
V
n
= 230 Vc.a. (tensione nominale di normale funzionamento)
I
min.
= 6 A (intervento relè RLI)
1° Collegare come da schema (in quanto I
min.
= 6 A).
N.B.: In generale collegare morsetti:
7-10 se I
min.
è 2 A
7-11 se I
min.
è > 2 A e 5 A
7-12 se I
min.
è > 5 A e 10 A
A
12 5643
78 1112109
Allarme
Tensione
di alimentazione
230 Vc.a.
F
N
Carico
RLI
Rete da controllare I
min
6A
C
4
2° Regolare il trimmer “Current %” su 60% in quanto:
I% =
6 (I
min.
)
x 100 = 60%
10 (I
impostata
)
avendo cablato il morsetto 7-12.
3° Regolare il trimmer “Hysteresis %” (finestra di intervento)
scegliendo 10% si ottiene quindi una finestra di intervento
compresa tra 6 e 6,6 A (6 A + 10% = 6,6 A):
l’intervento del relè sarà 6 A ed il ritorno al normale
funzionamento a 6,6 A.
4° Regolare il trimmer “Delay”
Tale operazione consente di ritardare il tempo di intervento del
relè (1... 30 sec)
(durante il ritardo il LED “Power On” lampeggia, terminato il
ritardo il LED “alarm” si illuminerà permanentemente quindi
interverrà il relè).
In=7A
6,6A
Imin=6A
Normale
funzionamento
In allarme
In allarme in quanto all'interno
della finestra di isteresi
Non in allarme perchè fuori
dalla finestra di isteresi
Finestra
di isteresi scelta
= 10%
5
Esempio
principio di funzionamento relè di MASSIMA
CORRENTE (RHI):
Dovendo controllare un carico avente i seguenti dati di targa
I
n
= 5 A (corrente nominale di normale funzionamento)
V
n
= 230 Vc.a. (tensione nominale di normale funzionamento)
I
max
= 6 A (intervento relè RHI)
1° Collegare come da schema (in quanto I
max
= 6 A).
N.B.: In generale collegare morsetti:
7-10 se I
max
è 2 A
7-11 se I
max
è > 2 A e 5 A
7-12 se I
max
è > 5 A e 10 A
A
12 5643
78 1112109
Allarme
Tensione
di alimentazione
230 Vc.a.
F
N
Carico
RHI
Rete da controllare I
max
6A
C
6
2° Regolare il trimmer “Current %” su 60% in quanto:
I% =
6 (I
max
)
x 100 = 60%
10 (I
impostata
)
avendo cablato il morsetto 7-12.
3° Regolare il trimmer “Hysteresis %” (finestra di intervento)
scegliendo 10% si ottiene quindi una finestra di intervento
compresa tra 5,4 e 6 A (6 A - 10% = 5,4 A):
l’intervento del relè sarà 6 A ed il ritorno al normale
funzionamento a 5,4 A.
4° Regolare il trimmer “Delay”
Tale operazione consente di ritardare il tempo di intervento del
relè (1... 30 sec)
(durante il ritardo il LED “Power On” lampeggia, terminato il
ritardo il LED “alarm” si illuminerà permanentemente quindi
interverrà il relè).
I
max
=6A
5,4A
I
n
=5A
Normale
funzionamento
In allarme
In allarme in quanto all'interno
della finestra di isteresi
Non in allarme perchè fuori
dalla finestra di isteresi
Finestra
di isteresi scelta
= 10%
7
Caratteristiche tecniche:
Tensione nominale U
n
(V) c.a. 230
Portata del contatto in scambio (A) 16
Frequenza nominale (Hz) 50/60
Soglie di intervento (A) 2, 5, 10
Taratura regolabile di I
n
(%) 30... 100
Valore di isteresi regolabile (%) 1... 45
Tempo di ritardo intervento (s) 1... 30
LED “POWER ON” acceso Funzionamento normale
LED “POWER ON” lampeggiante Pre allarme
LED “ALARM” acceso Intervento Relé
Potenza dissipata (W) 2
Moduli (n°)3
8
Dimensioni d’ingombro
5852,5
85
45
12 5643
78 1112109
3 Moduli
9
General description
Minimum current relays and maximum current relays are used to
protect and control equipments to which they are connected,
preventing the following problems:
a) Malfunctioning
b) Deterioration of technical characteristics and functions
c) Damages
d) Faults (stoppages, data loss, etc.)
10
Example
How an MINIMUM CURRENT RELAY (RLI) works:
Supposing it is used to control a load with the following ratings:
I
n
= 7 A (rated regular operating current)
V
n
= 230 V ac (rated regular operating voltage)
I
min.
= 6 A (current at which RLI relay is requested to trip)
1° Connect as shown in diagram (for I
min.
= 6 A).
N.B.: Normally, connect terminals:
7-10 if I
min.
is 2 A
7-11 if I
min.
is > 2 A and 5 A
7-12 if I
min.
is > 5 A and 10 A
A
12 5643
78 1112109
Allarme
Tensione
di alimentazione
230 Vc.a.
F
N
Carico
RLI
Rete da controllare I
min
6A
C
Power supply
voltage
230 V ac
Output relay
(alarm)
Line current to be controlled
I
min.
6A
Load
11
2° Set “Current %” trimmer to 60% since:
I% =
6 (I
min.
)
x 100 = 60%
10 (I
limit
)
having wired terminals 7 - 12.
3° Set “Hysteresis %” trimmer (tripping window) to 10% to
obtain a tripping window of 6 to 6.6 A (6 A + 10% = 6.6 A):
the relay will trip at 6 A and regular operation will start again
at 6.6 A.
4° Set the “Delay” trimmer
This makes it possible to delay the relay tripping time (1.... 30
sec). (During the delay the “Power on” LED will flash; at the
end of the delay the “Alarm” LED will turn on and the relay will
trip).
In
=7A
6,6A
I
min
=6A
Normale
funzionamento
In allarme
In allarme in quanto all'interno
della finestra di isteresi
Non in allarme perchè fuori
dalla finestra di isteresi
Finestra
di isteresi scelta
= 10%
Selected
hysteresis
window = 10%
Regular
operation
Alarm
condition
No alarm because
outside of hysteresis
window
Still in alarm because within
the hysteresis window
12
Example
How a MAXIMUM CURRENT RELAY (RHI) works:
Supposing it is to control a load with the following ratings:
I
n
= 5 A (rated regular operating current)
V
n
= 230 V ac (rated regular operating voltage)
I
max
= 6 A (current at which RHI relay trips)
1° Connect as shown in diagram (for I
max
= 6 A).
N.B.: Normally, connect terminals:
7-10 if I
max
is 2 A
7-11 if I
max
is > 2 A and 5 A
7-12 if I
max
is > 5 A and 10 A
A
12 5643
78 1112109
Allarme
Tensione
di alimentazione
230 Vc.a.
F
N
Carico
RHI
Rete da controllare I
max
6A
C
Power supply
voltage
230 V ac
Load
Output relay
(alarm)
Line current to be controlled
I
max.
6A
13
2° Set “Current %” trimmer to 60% since:
I% =
6 (I
max
)
x 100 = 60%
10 (I
limit
)
having wired terminals 7 - 12.
3° Set “Hysteresis %” trimmer (tripping window) to 10% to
obtain a tripping window of 5.4 to 6 V (6 A -10% = 5.4 A):
the relay will trip at 6 A and regular operation will start again
at 5.4 A.
4° Set the “Delay” trimmer
This makes it possible to delay the relay tripping time (1.... 30
sec). (During the delay the “Power on” LED will flash; at the
end of the delay the “Alarm” LED will turn on and the relay will
trip).
I
max
=6A
5,4A
I
n
=5A
Normale
funzionamento
In allarme
In allarme in quanto all'interno
della finestra di isteresi
Non in allarme perchè fuori
dalla finestra di isteresi
Finestra
di isteresi scelta
= 10%
Selected
hysteresis
window = 10%
Regular
operation
Alarm
condition
No alarm because
outside of hysteresis
window
Still in alarm because within
the hysteresis window
14
Technical characteristics:
Rated voltage U
n
(V) 230 ac
Change-over contact (A) 16
Rated frequency (Hz) 50/60
Trip thresholds (A) 2, 5, 10
Adjustable I
n
calibration (%) 30... 100
Adjustable hysteresis value (%) 1... 45
Trip time delay (s) 1... 30
“POWER ON” LED ON Regular operation
“POWER ON” LED flashing Pre-alarm
“ALARM” LED ON Alarm (Relay tripped)
Power consumption (W) 2
Width (Modules) (n°)3
15
Overall dimensions
5852,5
85
45
12 5643
78 1112109
3 Moduli
3 Modules
16
Allgemeine Beschreibung
Die Relais für den Mindeststrom oder den Höchststrom (RLI - RHI)
gestatten den Schutz und die Kontrolle der daran
angeschlossenen Geräte.
Die Verwendung dieser Schutzvorrichtungen gestattet die
Vermeidung der folgenden Hauptstörungen:
a) Anomalien beim Betrieb der Geräte
b) Verschlechterung der Betriebsweise/der technischen
Funktionen der Geräte
c) Beschädigung der Geräte
d) Eventuelle Betriebsausfälle ( Maschinenstillstand,
Datenverluste usw.)
17
Beispiel
Funktionsweise des Relais für den
MINDESTSTROM (RLI):
Wenn eine Last mit den folgenden Daten kontrolliert werden muss:
I
n
= 7 A (Nennstrom bei Normalbetrieb)
V
n
= 230 Vac (Nennspannung bei Normalbetrieb)
I
min.
= 6 A (Eingriff Relais RLI)
1° Gemäß Schaltplan anschließen (da I
min
= 6A).
Anm.: Im Allgemein Klemmen anschließen:
7-10 wenn I
min.
è 2 A
7-11 wenn I
min.
è > 2 A und 5 A
7-12 wenn I
min.
è > 5 A und 10 A
A
12 5643
78 1112109
Allarme
Tensione
di alimentazione
230 Vc.a.
F
N
Carico
RLI
Rete da controllare I
min
6A
C
Netz von Klemmleiste
I
min.
6A
Last
Spannung Speisung
230 Vac
Alarm
18
2° Den Trimmer “Current %” auf 60% einstellen, da:
I% =
6 (I
min.
)
x 100 = 60%
10 (I
insert equation
)
wenn Klemme 7 - 11 verkabelt ist.
3° Den Trimmer “Hysteresis %” (Eingriffsfenster)
bei der Wahl von 10% erhält man ein Eingriffsfenster zwischen
6 und 6,6A (6A + 10% = 6,6A):
Der Eingriff des Relais erfolgt bei 6A und die Rückkehr zum
normalen Betrieb erfolgt bei 6,6A.
4° Den Trimmer “Delay” einstellen.
Dies gestattet die Verzögerung der Eingriffszeit des Relais
(1 - 30 Sekunden).
(Während der Verzögerung blinkt die Led “Power On”, nach
Ende der Verzögerung leuchtet die Led “Alarm”
ununterbrochen auf und das relais greift ein).
In=7A
6,6A
Imin=6A
Normale
funzionamento
In allarme
In allarme in quanto all'interno
della finestra di isteresi
Non in allarme perchè fuori
dalla finestra di isteresi
Finestra
di isteresi scelta
= 10%
Fenster gewählte
Hysterese 10%
In Alarm
Normaler
Betrieb
Nicht in Alarm, da außerhalb
des Hysteresefensters
In Alarm, da innerhalb
des Hysteresefensters
19
Beispiel
Funktionsweise des Relais für den
HÖCHSTSPANNUNG (RHI):
Wenn eine Last mit den folgenden Daten kontrolliert werden muss:
I
n
= 5 A (Nennstrom bei Normalbetrieb)
V
n
= 230 Vac (Nennspannung bei Normalbetrieb)
I
max
= 6 A (Eingriff Relais RHI)
1° Gemäß Schaltplan anschließen (da I
max
= 6 A).
Anm.: Im Allgemein Klemmen anschließen:
7-10 wenn I
max
è 2 A
7-11 wenn I
max
è > 2 A und 5 A
7-12 wenn I
max
è > 5 A und 10 A
A
12 5643
78 1112109
Allarme
Tensione
di alimentazione
230 Vc.a.
F
N
Carico
RHI
Rete da controllare I
max
6A
C
Netz von Klemmleiste
I
max.
6A
Last
Spannung Speisung
230 Vac
Alarm
20
2° Den Trimmer “Current %” auf 60% einstellen, da:
I% =
6 (I
max
)
x 100 = 60%
10 (I
insert equation
)
wenn Klemme 7 - 12 verkabelt ist.
3° Den Trimmer “Hysteresis %” (Eingriffsfenster)
bei der Wahl von 10% erhält man ein Eingriffsfenster zwischen
5,4 A und 6 A (6A - 10% = 5,4 A)
Der Eingriff des Relais erfolgt bei 6 A und die Rückkehr zum
normalen Betrieb erfolgt bei 5,4 A.
4° Den Trimmer “Delay” einstellen.
Dies gestattet die Verzögerung der Eingriffszeit des
Relais (1 - 30 Sekunden).
(Während der Verzögerung blinkt die Led “Power On”, nach
Ende der Verzögerung leuchtet die Led “Alarm”
ununterbrochen auf und das Relais greift ein).
I
max
=6A
5,4A
I
n
=5A
Normale
funzionamento
In allarme
In allarme in quanto all'interno
della finestra di isteresi
Non in allarme perchè fuori
dalla finestra di isteresi
Finestra
di isteresi scelta
= 10%
Fenster gewählte
Hysterese 10%
In Alarm
Normaler
Betrieb
Nicht in Alarm, da außerhalb
des Hysteresefensters
In Alarm, da innerhalb
des Hysteresefensters
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50

ABB System pro M RHI Manuel utilisateur

Taper
Manuel utilisateur
Ce manuel convient également à