1769-5.15
Installation Instructions
1769 Compact I/O Communication Bus
Expansion Cables
(Cat. No. 1769-CRR1, 1769-CRR3, 1769-CLL1, 1769-CLL3,
1769-CRL1, 1769-CRL3)
Inside ...
For More Information .............................. 2
Hazardous Location Considerations ........ 3
Environnements dangereux ..................... 3
Overview ................................................ 4
Cable Types and Lengths ........................ 4
System Configurations ............................ 5
Installation .............................................. 6
Allen-Bradley
2 1769 Compact I/O Communication Bus Expansion Cables
1769-5.15
For More Information
For Refer to this Document Pub. No.
Information on installing and operating
your Compact 1769-IA16 module.
Compact 1769-IA16 120V ac Input
Module Installation Instructions
1769-5.1
Information on installing and operating
your Compact 1769-OW8 module.
Compact 1769-OW8 AC/DC Relay
Output Module Installation
Instructions
1769-5.2
Information on installing and operating
your Compact 1769-IQ16 module.
Compact 1769-IQ16 24V dc Sink/
Source Input Module Installation
Instructions
1769-5.3
Information on installing and operating
your Compact 1769-OB16 module.
Compact 1769-OB16 Solid State
24V dc Source Output Module
Installation Instructions
1769-5.4
Information on installing and operating
your Compact 1769-OA8 module.
Compact 1769-OA8 100 to 240V ac
Solid State Output Module
Installation Instructions
1769-5.5
Information on installing and operating
your Compact 1769-OV16 module.
Compact 1769-OV16 Solid State
24V dc Sink Output Module
Installation Instructions
1769-5.6
Information on installing and operating
your Compact 1769-IQ6XOW4 module.
Compact 1769-IQ6XOW4 24V dc
Sink/Source Input AC/DC Relay
Output Module Installation
Instructions
1769-5.7
Information on installing and operating
your Compact 1769-IM12 module.
Compact 1769-IM12 240V ac Input
Module Installation Instructions
1769-5.8
Information on installing and operating
Compact I/O Power Supplies.
Compact 1769 Expansion I/O Power
Supplies
1769-5.14
Information on installing Compact I/O
End Cap/Terminators.
Compact I/O End Caps/Terminators
Installation Instructions
1769-5.16
Detailed information on installing,
configuring, and troubleshooting your
Compact Analog I/O modules.
Compact I/O Analog Modules User
Manual
1769-6.0
A detailed description of how to install
and use your Compact I/O with
MicroLogix 1500 programmable
controller.
MicroLogix 1500 Programmable
Controllers User Manual
1764-6.1
More information on proper wiring and
grounding techniques.
Industrial Automation Wiring and
Grounding Guidelines
1770-4.1
1769 Compact I/O Communication Bus Expansion Cables 3
1769-5.15
If you would like a manual, you can:
download a free electronic version from the internet:
www.ab.com/micrologix
or
www.theautomationbookstore.com
purchase a printed manual by:
contacting your local distributor or Rockwell Automation representative
visiting
www.theautomationbookstore.com
and placing your order
calling
1.800.963.9548
(USA/Canada) or
001.330.725.1574
(Outside USA/Canada)
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or
non-hazardous locations only. The following ATTENTION statement applies to
use in hazardous locations.
Environnements dangereux
Cet équipement est conçu pour être utilisé dans des environnements de Classe 1,
Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante
s’applique à une utilisation dans des environnements dangereux.
!
ATTENTION:
EXPLOSION HAZARD
Substitution of components may impair suitability for Class I,
Division 2.
Do not replace components or disconnect equipment unless
power has been switched off.
Do not connect or disconnect components unless power has
been switched off.
This product must be installed in an enclosure.
!
ATTENTION:
DANGER D’EXPLOSION
La substitution de composants peut rendre cet équipement
impropre à une utilisation en environnement de Classe 1,
Division 2.
Ne pas remplacer de composants ou déconnecter l'équipement
sans s'être assuré que l'alimentation est coupée.
Ne pas connecter ou déconnecter des composants sans s'être
assuré que l'alimentation est coupée.
Ce produit doit être installé dans une armoire.
Allen-Bradley
4 1769 Compact I/O Communication Bus Expansion Cables
1769-5.15
Overview
The 1769-CLLx, -CRRx, and -CRLx cables extend the 1769 bus communication
lines. A maximum of two cables can be used in a 1769 system, allowing for three
groups or banks of I/O modules. Each bank requires its own power supply.
See System Configurations on page 5.
Cable Types and Lengths
Note:
Some controllers do not support three I/O banks. Refer to your
controller’s manual for details.
Some controllers provide power to the I/O bank. Refer to your
controller’s manual for details.
Catalog Number Cable Type
Length
(1)
(1)
Approximate cable length is measured from end-to-end of the cable only.
1769-CLL1 Left bank-to-left bank expansion 305 mm (1 ft.)
1769-CLL3 Left bank-to-left bank expansion 1 m (3.28 ft.)
1769-CRR1 Right bank-to-right bank expansion 305 mm (1 ft.)
1769-CRR3 Right bank-to-right bank expansion 1 m (3.28 ft.)
1769-CRL1 Right bank-to-left bank expansion 305 mm (1 ft.)
1769-CRL3 Right bank-to-left bank expansion 1 m (3.28 ft.)
18 mm
(0.71 in.)
15 mm
(0.59 in.)
15 mm
(0.59 in.)
118 mm
(4.65 in.)
118 mm
(4.65 in.)
118 mm
(4.65 in.)
32 mm
(1.26 in.)
18 mm
(0.71 in.)
32 mm
(1.26 in.)
1769-CLLx
1769-CRRx 1769-CRLx
1769 Compact I/O Communication Bus Expansion Cables 5
1769-5.15
System Configurations
The following illustration show examples of two valid system setups.
Note:
When configuring your system using a MicroLogix 1500
controller, only one expansion cable, one expansion power supply,
and a maximum of eight I/O modules may be used allowing for
two banks of I/O modules (maximum).
1769-CRRx
1769-CRRx
1769-CLLx
1769 I/O
1769 I/O
1769 I/O
1769 I/O
1769 I/O
1769-CLLx
1769 I/O
1769 I/O
1769 I/O
1769 End Cap
1769 I/O
1769 Power Supply
Bus Master with
Power Supply
Bank 1
Bank 3
1769 Power Supply
Bank 2
I/O Slot Number
12
34 5
6789
I/O Slot Number
I/O Slot Number
Right-to-Right
Left-to-Left
1769 End Cap
1769 I/O
1769 I/O
1769-CRLx
1769-CRLx
1769-CRLx
1769-CRLx
1769 I/O
1769 I/O
1769 I/O
1769 I/O
1769 Power Supply
1769 Power Supply
Bus Master with
Power Supply
Bank 3Bank 2Bank 1
12 3 4 5 6I/O Slot Number
Right-to-Left
Allen-Bradley
6 1769 Compact I/O Communication Bus Expansion Cables
1769-5.15
Installation
Prevent Electrostatic Discharge
Remove Power
Attaching Cables
!
ATTENTION:
Electrostatic discharge can damage integrated
circuits or semiconductors if you touch bus connector pins or the
terminal block. Follow these guidelines when handling 1769
Compact I/O components:
Touch a grounded object to discharge static potential.
Wear an approved wrist-strap grounding device.
Do not touch the bus connector or connector pins.
Do not touch circuit components inside the module.
If available, use a static-safe workstation.
When not in use, keep cables in static shield packaging.
!
ATTENTION:
Remove power before making or breaking cable
connections. When you remove or insert a cable connector with
power applied, an electrical arc may occur. An electrical arc can
cause personal injury or property damage by:
sending an erroneous signal to your system’s field devices,
causing unintended machine motion
causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create
electrical resistance.
Note:
A maximum of two expansion cables may be used in a 1769 system.
Each I/O bank requires its own power supply. The 1769 cables
extend the 1769 communication bus, but do not extend bus power.
1769 Compact I/O Communication Bus Expansion Cables 7
1769-5.15
1.
Disconnect power
2.
Check bus lever position.
Left cover: Make sure the bus lever (4) on the left-most I/O module is in the
unlocked (fully right) position.
Right cover: Make sure the bus lever (4) on the right cover is in the unlocked
(fully right) position.
3.
Use the upper and lower tongue-and-groove slots (1) to secure the cable cover
to the module.
4.
Move the cable cover back along the tongue-and-groove slots until the bus
connectors (2) line up with each other.
5.
If necessary, push the bus lever back slightly to clear the bus locking tab (3).
Use your fingers or a small screwdriver.
6.
To allow communication between the module and the cable connector, move
the bus lever firmly to the left (4) until it clicks. Ensure that it is locked firmly
in place.
!
ATTENTION:
When attaching cables, it is very important that the
bus connectors are securely locked together to ensure proper
electrical connection.
4
4
1
1
1
1
2
3
1
1
3
Left Cover
Right Cover
Allen-Bradley
´H'*d!¶Bd¨
Publication 1769-5.15 - August 1999 PN 40071-068-01(B)
© (1999) Rockwell International Corporation. Printed in the U.S.A.
Specifications
Approximate Shipping
Weight (with carton)
3-foot cables: 350 g (0.77lbs.)
1-foot cables: 300 g (0.66 lbs.)
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Operating Temperature 0°C to +60°C (32°F to +140°F)
Operating Humidity 5% to 95% non-condensing
Operating Altitude 2000 meters (6561 feet)
Vibration Operating: 10 to 500 Hz, 5G, 0.015 in. peak-to-peak
Relay Operation: 2G
Shock Operating: 30G panel mounted (20G DIN rail mounted)
Relay Operation: 7.5G panel mounted (5G DIN rail mounted)
Non-Operating: 40G panel mounted (30G DIN rail mounted)
Agency Certification C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives
Hazardous Environment
Class
Class I, Division 2, Hazardous Location, Groups A, B, C, D
(UL 1604, C-UL under CSA C22.2 No. 213)