Allen-Bradley Compact 1769-IF4 Installation Instructions Manual

Taper
Installation Instructions Manual

Ce manuel convient également à

Publication 1769-IN048A-EN-P
Installation Instructions
Compact™ 1769-IF4 (Series B or
Later) Analog Input Module
Inside
Module Description ..................................................................................2
Module Installation...................................................................................3
System Assembly......................................................................................4
Mounting Expansion I/O ...........................................................................6
Replacing a Single Module within a System ...........................................8
Module Spare/Replacement Parts ...........................................................8
Field Wiring Connections..........................................................................9
I/O Memory Mapping .............................................................................15
Specifications .........................................................................................17
Hazardous Location Considerations .......................................................20
Environnements dangereux ....................................................................20
For More Information..............................................................................21
2 Compact™ 1769-IF4 (Series B or Later) Analog Input Module
Publication 1769-IN048A-EN-P
Module Description
Item Description
1 bus lever
(with locking function)
2a upper panel mounting tab
2b lower panel mounting tab
3 module status LED
4 module door with terminal
identification label
5a movable bus connector
with female pins
5b stationary bus connector
with male pins
6 nameplate label
7a upper
tongue-and-groove slots
7b lower
tongue-and-groove slots
8a upper DIN rail latch
8b lower DIN rail latch
9 write-on label (user ID tag)
10 removable terminal block
(RTB) with finger-safe cover
10a RTB upper retaining screw
10b RTB lower retaining screw
10a
10b
4
10
2b
3
2a
1
5a
9
5b
6
7a
7b
8b
7b
8a
7a
1
7
6
9
-IF
4
DANGER
Do Not Remove RTB Under Power
Unless Area is Non-Hazardous
Ensure Adjacent
Bus Lever is Unlatched/Latched
Before/After
Removing/Inserting Module
A
N
L
G
C
o
m
V
/I in
3
-
+
2
4
V
d
c
d
c
N
E
U
T
V
/I in
1
-
V
/I in
2
-
A
N
G
L
C
o
m
A
N
G
L
C
o
m
V
/I in
0
-
V
in
0
+
V
in
1
+
V
in
2
+
V
in
3
+
I in
0
+
I in
1
+
I in
2
+
I in
3
+
A
N
L
G
C
o
m
OK
Analog
OK
Analog
Compact™ 1769-IF4 (Series B or Later) Analog Input Module 3
Publication 1769-IN048A-EN-P
Module Installation
Compact I/O is suitable for use in an industrial environment when installed
in accordance with these instructions. Specifically, this equipment is
intended for use in clean, dry environments (Pollution degree 2
(1)
) and to
circuits not exceeding Over Voltage Category II
(2)
(IEC 60664-1).
(3)
Prevent Electrostatic Discharge
(1) Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that
occasionally a temporary conductivity caused by condensation shall be expected.
(2) Over Voltage Category II is the load level section of the electrical distribution system. At this level transient
voltages are controlled and do not exceed the impulse voltage capability of the product’s insulation.
(3) Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC)
designations.
!
ATTENTION
Electrostatic discharge can damage integrated circuits or
semiconductors if you touch bus connector pins or the
terminal block. Follow these guidelines when you handle
the module:
Touch a grounded object to discharge static potential.
Wear an approved wrist-strap grounding device.
Do not touch the bus connector or connector pins.
Do not touch circuit components inside the module.
If available, use a static-safe work station.
When not in use, keep the module in its static-shield
box.
4 Compact™ 1769-IF4 (Series B or Later) Analog Input Module
Publication 1769-IN048A-EN-P
Remove Power
System Assembly
The module can be attached to the controller or an adjacent I/O module
before or after mounting. For mounting instructions, see “Panel Mounting”
on page 6, or “DIN Rail Mounting” on page 7. To work with a system that
is already mounted, see “Replacing a Single Module within a System” on
page 8.
The following procedure shows you how to assemble the Compact I/O
system.
!
ATTENTION
Remove power before removing or inserting this module.
When you remove or insert a module with power
applied, an electrical arc may occur. An electrical arc can
cause personal injury or property damage by:
sending an erroneous signal to your system’s field
devices, causing unintended machine motion
causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on
both the module and its mating connector. Worn contacts
may create electrical resistance.
6
5
4
3
1
1
2
Compact™ 1769-IF4 (Series B or Later) Analog Input Module 5
Publication 1769-IN048A-EN-P
1. Disconnect power.
2. Check that the bus lever of the module to be installed is in the unlocked
(fully right) position.
3. Use the upper and lower tongue-and-groove slots (1) to secure the
modules together (or to a controller).
4. Move the module back along the tongue-and-groove slots until the bus
connectors (2) line up with each other.
5. Push the bus lever back slightly to clear the positioning tab (3). Use your
fingers or a small screwdriver.
6. To allow communication between the controller and module, move the
bus lever fully to the left (4) until it clicks. Ensure it is locked firmly in
place.
7. Attach an end cap terminator (5) to the last module in the system by
using the tongue-and-groove slots as before.
8. Lock the end cap bus terminator (6).
!
ATTENTION
When attaching I/O modules, it is very important that the
bus connectors are securely locked together to ensure
proper electrical connection.
IMPORTANT
A 1769-ECR or 1769-ECL right or left end cap must be
used to terminate the end of the communication bus.
6 Compact™ 1769-IF4 (Series B or Later) Analog Input Module
Publication 1769-IN048A-EN-P
Mounting Expansion I/O
Minimum Spacing
Maintain spacing from
enclosure walls,
wireways, adjacent
equipment, etc. Allow
50 mm (2 in.) of space
on all sides for
adequate ventilation, as
shown:
Panel Mounting
Mount the module to a panel using two screws per module. Use M4 or #8
panhead screws. Mounting screws are required on every module.
Panel Mounting Using the Dimensional Template
!
ATTENTION
During panel or DIN rail mounting of all devices, be sure
that all debris (metal chips, wire strands, etc.) is kept
from falling into the module. Debris that falls into the
module could cause damage on power up.
Top
Bottom
Side Side
Host Controller
Compact I/O
Compact I/O
Compact I/O
Compact I/O
Compact I/O
End Cap
Host Controller
Compact I/O
Compact I/O
Compact I/O
End Cap
132 (5.197)
122.6±0.2
(4.826±0.008)
35
(1.38)
28.5
(1.12)
Refer to host controller documentation for this dimension.
For more than 2 modules: (number of modules-1) X 35mm (1.38 in.)
NOTE: All dimensions are in mm (inches).
Hole spacing tolerance: ±0.4 mm (0.016 in.)
Compact™ 1769-IF4 (Series B or Later) Analog Input Module 7
Publication 1769-IN048A-EN-P
Panel Mounting Procedure Using Modules as a Template
The following procedure allows you to use the assembled modules as a
template for drilling holes in the panel. If you have sophisticated panel
mounting equipment, you can use the dimensional template provided on
page 6. Due to module mounting hole tolerance, it is important to follow
these procedures:
1. On a clean work surface, assemble no more than three modules.
2. Using the assembled modules as a template, carefully mark the center of
all module-mounting holes on the panel.
3. Return the assembled modules to the clean work surface, including any
previously mounted modules.
4. Drill and tap the mounting holes for the recommended M4 or #8 screw.
5. Place the modules back on the panel and check for proper hole
alignment.
6. Attach the modules to the panel using the mounting screws.
7. Repeat steps 1 to 6 for any remaining modules.
DIN Rail Mounting
The module can be mounted using the following DIN rails: 35 x 7.5 mm
(EN 50 022 - 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15).
Before mounting the module on a DIN rail, close the DIN rail latches. Press
the DIN rail mounting area of the module against the DIN rail. The latches
will momentarily open and lock into place.
NOTE
If mounting more modules, mount only the last one of
this group and put the others aside. This reduces
remounting time during drilling and tapping of the next
group.
8 Compact™ 1769-IF4 (Series B or Later) Analog Input Module
Publication 1769-IN048A-EN-P
Replacing a Single Module within a System
The module can be replaced while the system is mounted to a panel (or
DIN rail). Follow these steps in order:
1. Remove power. See important note on page 4.
2. On the module to be removed, remove the upper and lower mounting
screws from the module (or open the DIN latches using a flat-blade or
phillips-style screwdriver).
3. Move the bus lever to the right to disconnect (unlock) the bus.
4. On the right-side adjacent module, move its bus lever to the right
(unlock) to disconnect it from the module to be removed.
5. Gently slide the disconnected module forward. If you feel excessive
resistance, check that the module has been disconnected from the bus
and that both mounting screws have been removed (or DIN latches
opened).
6. Before installing the replacement module, be sure that the bus lever on
the module to be installed, and on the right-side adjacent module are in
the unlocked (fully right) position.
7. Slide the replacement module into the open slot.
8. Connect the modules together by locking (fully left) the bus levers on
the replacement module and the right-side adjacent module.
9. Replace the mounting screws (or snap the module onto the DIN rail).
Module Spare/Replacement Parts
Terminal block, catalog number 1769-RTBN18 (1 per kit)
Door Labels, catalog number 1769-RL2 Series B (2 per kit)
Door, catalog number 1769-RD (2 per kit)
NOTE
It may be necessary to rock the module slightly from front
to back to remove it, or, in a panel-mounted system, to
loosen the screws of adjacent modules.
Compact™ 1769-IF4 (Series B or Later) Analog Input Module 9
Publication 1769-IN048A-EN-P
Field Wiring Connections
Grounding the Module
This product is intended to be mounted to a well-grounded mounting
surface such as a metal panel. Additional grounding connections from the
module’s mounting tabs or DIN rail (if used), are not required unless the
mounting surface cannot be grounded. Refer to Industrial Automation
Wiring and Grounding Guidelines, Allen-Bradley publication 1770-4.1, for
additional information.
System Wiring Guidelines
Consider the following when wiring your system:
All module commons (ANLG COM) are connected in the analog module.
The analog common (ANLG COM) is not connected to earth ground
inside the module.
Do not use the analog module’s NC terminals as connection points.
Channels are not isolated from each other.
Use Belden™ 8761, or equivalent, shielded wire.
Under normal conditions, the drain wire and shield junction must be
connected to earth ground via a panel or DIN rail mounting screw at the
analog I/O module end. Keep the shield connection to ground as short
as possible.
(1)
To ensure optimum accuracy, limit overall cable impedance by keeping
your cable as short as possible. Locate the I/O system as close to your
sensors or actuators as your application will permit.
If multiple power supplies are used with analog inputs, the power
supply commons must be connected.
(1) In environments where high-frequency noise may be present, it may be necessary to directly ground cable
shields to earth at the module end and via a 0.1µF capacitor at the sensor end.
10 Compact™ 1769-IF4 (Series B or Later) Analog Input Module
Publication 1769-IN048A-EN-P
The 1769-IF4 module does not provide loop power for analog inputs.
Use a power supply that matches the input transmitter specifications.
Differential analog inputs are more immune to noise than single-ended
analog inputs.
Voltages on Vin+, V/Iin-, and Iin+ of the 1769-IF4 module must be
within ±10V dc of analog common.
External Power Switch
The 1769-IF4 (Series B or later) has an external 24V dc power switch which
gives you the option of using an external power supply. The switch is
located in on the lower left portion of the module’s circuit board, as shown
below. With this switch in the up position (default), 24V dc power is drawn
from the 1769 system power supply via the 1769 I/O bus. In the down
position, 24V dc power is drawn from the external power supply.
Wire the external power supply to the module via the module’s terminal
block. The external power supply must be rated Class 2, with a 24V dc
range of 20.4 to 26.4V dc and 60 mA minimum.
!
ATTENTION
Be careful when stripping wires. Wire fragments that fall
into a module could cause damage at power up. Once
wiring is complete, ensure the module is free of all metal
fragments.
External Power Switch
Bus Power (default)
External Power
Compact™ 1769-IF4 (Series B or Later) Analog Input Module 11
Publication 1769-IN048A-EN-P
Wiring Differential Inputs
(1) The external power supply must be rated Class 2, with a 24V dc range of 20.4 to 26.4V dc and 60 mA
minimum.
(2) Series B and later modules provide this option.
+
V in 0 +
V/I in 0 -
I in 0+
ANLG Com
V in 1 +
V/I in 1 -
I in 1+
ANLG Com
V in 2 +
V/I in 2 -
I in 2+
ANLG Com
V in 3 +
V/I in 3 -
I in 3+
ANLG Com
dc NEUT
+24V dc
+
-
earth ground the
shield locally at
the module
analog source
Belden 8761 cable (or equivalent)
External 24V dc
Power Supply
(1)
(optional)
(2)
12 Compact™ 1769-IF4 (Series B or Later) Analog Input Module
Publication 1769-IN048A-EN-P
Wiring Single-Ended Sensor/Transmitter Types
(1) The external power supply must be rated Class 2, with a 24V dc range of 20.4 to 26.4V dc and 60 mA
minimum.
(2) Series B and later modules provide this option.
+
V in 0 +
V/I in 0 -
I in 0 +
ANLG Com
V in 1 +
V/I in 1 -
I in 1 +
ANLG Com
V in 2 +
V/I in 2 -
I in 2 +
ANLG Com
V in 3 +
V/I in 3 -
I in 3 +
ANLG Com
+24V dc
dc NEUT
+
+
+
-
+
-
Current
Transmitter
Sensor/
Transmitte r
Supply
Voltage
Transmitter
Voltage
Transmitter
Signal
Signal
Signal
Ground
Ground
1769-IF4 Terminal Block
External 24V dc
Power Supply
(1)
(optional)
(2)
Compact™ 1769-IF4 (Series B or Later) Analog Input Module 13
Publication 1769-IN048A-EN-P
Wiring Mixed Transmitter Types
(1) The external power supply must be rated Class 2, with a 24V dc range of 20.4 to 26.4V dc and 60 mA
minimum.
(2) Series B and later modules provide this option.
Labeling the Terminals
A removable, write-on label is provided with the module. Remove the label
from the door, mark the identification of each terminal with permanent ink,
and slide the label back into the door. Your markings (ID tag) will be
visible when the module door is closed.
+
V in 0 +
V/I in 0 -
I in 0 +
ANLG Com
V in 1 +
V/I in 1 -
I in 1 +
ANLG Com
V in 2 +
V/I in 2 -
I in 2 +
ANLG Com
V in 3 +
V/I in 3 -
I in 3 +
ANLG Com
+24V dc
dc NEUT
+
+
+
+
+
+
+
Single-ended
Voltage
Transmitter
Differential
Voltage
Transmitte r
Differential
Current
Transmitte r
2-Wire
Current
Transmitter
Signal
Signal
Signal
Signal
Supply
Supply
1769-IF4 Terminal Block
Sensor/
Transmitter
Supply
External 24V dc
Power Supply
(1)
(optional)
(2)
14 Compact™ 1769-IF4 (Series B or Later) Analog Input Module
Publication 1769-IN048A-EN-P
Removing the Finger-Safe Terminal Block
To remove the terminal block, loosen the upper and lower retaining
screws. The terminal block will back away from the module as you remove
the screws. When replacing the terminal block, torque the retaining screws
to 0.46 Nm (4.1 in-lbs).
Wiring the Finger-Safe Terminal Block
When wiring the terminal block, keep the finger-safe cover in place.
1. Loosen the terminal screws to be wired.
2. Route the wire under the terminal pressure plate. You can use the bare
wire or a spade lug. The terminals will accept a 6.35 mm (0.25 in.) spade
lug.
3. Tighten the terminal screw making sure the pressure plate secures the
wire. Recommended torque when tightening terminal screws is 0.68 Nm
(6 in-lbs).
NOTE
The terminal screws are non-captive. Therefore, it is
possible to use a ring lug [maximum 1/4 inch o.d. with a
0.139 inch minimum i.d. (M3.5)] with the module.
NOTE
If you need to remove the finger-safe cover, insert a screw
driver into one of the square wiring holes and gently pry
the cover off. If you wire the terminal block with the
finger-safe cover removed, you will not be able to put it
back on the terminal block because the wires will be in the
way.
wiring the
finger-safe
terminal block
upper retaining screw
lower retaining screw
Compact™ 1769-IF4 (Series B or Later) Analog Input Module 15
Publication 1769-IN048A-EN-P
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires with the following restrictions:
I/O Memory Mapping
Input Data File
For each input module, slot x, words 0-3 in the input data file contain the
analog values of the inputs.
The bits are defined as follows:
SGN = Sign bit in two’s complement format
Sx = General status bit for channels 0 through 3. This bit is set (1) when
an error (over- or under-range) exists for that channel.
Ux = Under-range flag bits for channels 0 through 3. These bits can be
used in the control program for error detection.
Ox = Over-range flag bits for channels 0 through 3. These bits can be
used in the control program for error detection.
Wire Type Wire Size Terminal Screw
Torque
Retaining Screw
Torque
Solid Cu-90°C (194°F) #14 to #22 AWG 0.68 Nm (6 in-lbs) 0.46 Nm (4.1 in-lbs)
Stranded Cu-90°C (194°F) #16 to #22 AWG 0.68 Nm (6 in-lbs) 0.46 Nm (4.1 in-lbs)
Word
Bit Position
15 14131211109876543210
0 SGN Analog Input Data Channel 0
1 SGN Analog Input Data Channel 1
2 SGN Analog Input Data Channel 2
3 SGN Analog Input Data Channel 3
4 Not Used S3 S2 S1 S0
5 U0 O0U101U2O2U3O3 Set to 0
16 Compact™ 1769-IF4 (Series B or Later) Analog Input Module
Publication 1769-IN048A-EN-P
Configuration Data File
The manipulation of the bits from this file is normally done with
programming software (e.g. RSLogix 500, RSNetworx for DeviceNet, etc.)
during initial configuration of the system. In that case, graphical screens are
provided by the programmer to simplify configuration. However, some
systems, like the 1769-ADN DeviceNet Adapter, also allow the bits to be
altered as part of the control program, using communication rungs. In that
case, it is necessary to understand the bit arrangement. Refer to the
Compact™ Analog I/O User Manual, publication number
1769-UM002A-EN-P for additional details.
Words 0 to 3 of the configuration file allow you to change the parameters
of each channel independently. For example, word 0 corresponds to
channel 0.
Define To Select Make these bit settings
1514 13 12111098 4-7 3210
Input Filter
Selection/
-3 dB
Frequency
60 Hz/15.7 Hz
Not Used
0000
50 Hz/13.1 Hz
0001
Not Used
0010
250 Hz/65.5 Hz
0011
500 Hz/131Hz
0100
Spare
(1)
(1) An attempt to write any non-valid (spare) bit configuration into any selection field results in a module
configuration error.
Input Type/
Range
-10 to +10V dc
0000
0 to 5V dc
0001
0 to 10V dc
0010
4 to 20 mA
0011
1 to 5V dc
0100
0 to 20 mA
0101
Spare
(1)
Input Data
Format
Raw/Proportional
Data
000
Engineering Units
001
Scaled-for-PID
010
Percent Range
011
Spare
(1)
Enable
Channel
Enabled
1
Disabled
0
Compact™ 1769-IF4 (Series B or Later) Analog Input Module 17
Publication 1769-IN048A-EN-P
Specifications
General Specifications
Specification Value
Dimensions 118 mm (height) x 87 mm (depth) x 35 mm (width)
height including mounting tabs is 138 mm
4.65 in. (height) x 3.43 in (depth) x 1.38 in (width)
height including mounting tabs is 5.43 in.
Approximate Shipping Weight
(with carton)
300g (0.65 lbs.)
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Operating Temperature 0°C to +60°C (32°F to +140°F)
Operating Humidity 5% to 95% non-condensing
Operating Altitude 2000 meters (6561 feet)
Vibration Operating: 10 to 500 Hz, 5G, 0.030 in. peak-to-peak
Relay Operation: 2G
Shock Operating: 30G, 11 ms panel mounted
(20G, 11 ms DIN rail mounted)
Relay Operation: 7.5G panel mounted
(5G DIN rail mounted)
Non-Operating: 40G panel mounted
(30G DIN rail mounted)
Agency Certification C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives
Hazardous Environment Class Class I, Division 2, Hazardous Location, Groups A, B, C, D
(UL 1604, C-UL under CSA C22.2 No. 213)
Radiated and Conducted Emissions EN50081-2 Class A
Electrical /EMC: The module has passed testing at the following levels:
ESD Immunity (IEC1000-4-2) 4 kV contact, 8 kV air, 4 kV indirect
Radiated Immunity (IEC1000-4-3) 10 V/m , 80 to 1000 MHz, 80% amplitude modulation,
+900 MHz keyed carrier
Fast Transient Burst (IEC1000-4-4) 2 kV, 5kHz
Surge Immunity (IEC1000-4-5) 1 kV galvanic gun
Conducted Immunity (IEC1000-4-6)
10 V, 0.15 to 80MHz
(1)
(1) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is
30 MHz to 1000 MHz.
18 Compact™ 1769-IF4 (Series B or Later) Analog Input Module
Publication 1769-IN048A-EN-P
Input Specifications
Specification 1769-IF4 (Series B or later)
Analog Normal Operating
Ranges
(1)
(1) The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The
module will continue to convert the analog input up to the maximum full scale range. The flag automatically
resets when within the normal operating range.
Voltage: ± 10V dc, 0 to 10V dc, 0 to 5V dc, 1 to 5V dc
Current: 0 to 20 mA, 4 to 20 mA
Full Scale Analog Ranges
(1)
Voltage: ± 10.5V dc, -0.5 to 10.5V dc, -0.5 to 5.25V dc, 0.5 to 5.25V dc
Current: 0 to 21 mA, 3.2 to 21 mA
Number of Inputs 4 differential or single-ended
Bus Current Draw (max.) 120 mA at 5V dc
60 mA at 24V dc
(6)
(6) If the optional 24V dc Class 2 power supply is used, the 24V dc current draw from the bus is 0 mA.
Heat Dissipation 2.52 Total Watts (The Watts per point, plus the minimum Watts,
with all points energized.)
Converter Type Delta Sigma
Response Speed per Channel Input filter and configuration dependent. See your users manual.
Resolution (max.)
(2)
(2) Resolution is dependent upon your filter selection. The maximum resolution is achieved with either the 50 or
60 Hz filter selected. For resolution with other filter selections, refer to the user manual, publication
1769-UM002A-EN-P.
14 bits (unipolar)
14 bits plus sign (bipolar)
Rated Working Voltage
(3)
(3) Rated working voltage is the maximum continuous voltage that can be applied at the input terminal,
including the input signal and the value that floats above ground potential (for example, 10V dc input signal
and 20V dc potential above ground).
30V ac/30V dc
Common Mode Voltage
Range
(4)
(4) For proper operation, both the plus and minus input terminals must be within ±10V dc of analog common.
±10V dc maximum per channel
Common Mode Rejection greater than 60 dB at 50 and 60 Hz with the 50 or 60 Hz filter
selected, respectively.
Normal Mode Rejection
Ratio
-50 dB at 50 and 60 Hz with the 50 or 60 Hz filter selected,
respectively.
Input Impedance Voltage Terminal: 220K Ω (typical)
Current Terminal: 250
Overall Accuracy
(5)
(5) Includes offset, gain, non-linearity and repeatability error terms.
Voltage Terminal: ±0.2% full scale at 25°C
Current Terminal: ±0.35% full scale at 25°C
Compact™ 1769-IF4 (Series B or Later) Analog Input Module 19
Publication 1769-IN048A-EN-P
Specification 1769-IF4 (Series B or later)
Accuracy Drift with
Temperature
Voltage Terminal: ±0.003% per °C
Current Terminal: ±0.0045% per °C
Optional 24V dc Class 2 Power
Supply Voltage Range
20.4 V to 26.4 V dc
(3)
(3) Failure to use a Class 2 power supply without regulation within these limits could result in improper module
operation.
Calibration The module performs autocalibration on channel enable and on a
configuration change between channels.
Non-linearity (in percent full
scale)
±0.03%
Repeatability
(1)
(1) Repeatability is the ability of the input module to register the same reading in successive measurements for
the same input signal.
±0.03%
Module Error over Full
Temperature Range
(0 to +60°C [+32°F to +140°F])
Voltage: ±0.3%
Current: ±0.5%
Input Channel Configuration via configuration software screen or the user program (by writing a
unique bit pattern into the modules configuration file). Refer to
your controller’s user manual to determine if user program
configuration is supported.
Module OK LED On: module has power, has passed internal diagnostics, and is
communicating over the bus.
Off: Any of the above is not true.
Channel Diagnostics Over- or under-range by bit reporting
Maximum Overload at Input
Terminals
(2)
(2) Damage may occur to the input circuit if this value is exceeded.
Voltage Terminal: ±30V dc continuous, 0.1 mA
Current Terminal: ±32 mA continuous, ±7.6 V dc
System Power Supply Distance
Rating
8 (The module may not be more than 8 modules away from the
system power supply.)
Recommended Cable Belden™ 8761 (shielded)
Input Group to Bus Isolation 500V ac or 710V dc for 1 minute (qualification test)
30V ac/30V dc working voltage (IEC Class 2 reinforced insulation)
Vendor I.D. Code 1
Product Type Code 10
Product Code 35
20 Compact™ 1769-IF4 (Series B or Later) Analog Input Module
Publication 1769-IN048A-EN-P
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D
or non-hazardous locations only. The following ATTENTION statement
applies to use in hazardous locations.
Environnements dangereux
Cet équipement est conçu pour être utilisé dans des environnements de
Classe 1, Division 2, Groupes A, B, C, D ou non dangereux. La mise en
garde suivante s’applique à une utilisation dans des environnements
dangereux.
!
WARNING
EXPLOSION HAZARD
Substitution of components may impair suitability for
Class I, Division 2.
Do not replace components or disconnect equipment
unless power has been switched off or the area is
known to be non-hazardous.
Do not connect or disconnect components unless
power has been switched off or the area is known to
be non-hazardous.
This product must be installed in an enclosure.
All wiring must comply with N.E.C. article 501-4(b).
!
MISE EN GARDE
DANGER D’EXPLOSION
La substitution de composants peut rendre cet
équipement impropre à une utilisation en
environnement de Classe 1, Division 2.
Ne pas remplacer de composants ou déconnecter
l'équipement sans s'être assuré que l'alimentation est
coupée et que l'environnement est classé non
dangereux.
Ne pas connecter ou déconnecter des composants sans
s'être assuré que l'alimentation est coupée ou que
l'environnement est classé non dangereux.
Ce produit doit être installé dans une armoire.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

Allen-Bradley Compact 1769-IF4 Installation Instructions Manual

Taper
Installation Instructions Manual
Ce manuel convient également à

dans d''autres langues