Allen-Bradley Micro800 Installation Instructions Manual

Taper
Installation Instructions Manual
Installation Instructions
Micro800 4-channel and 8-channel Analog
Voltage/Current Input and Output Modules
Catalog Numbers 2085-IF4, 2085-IF8, 2085-OF4
http://www.rockwellautomation.com/literature/
FR
Cette publication est disponible en français
sous forme électronique (fichier PDF). Pour la
télécharger, rendez-vous sur la page Internet
indiquée ci-dessus.
PT
Esta publicação está disponível em portugués
como PDF. Vá ao endereço web que aparece
acima para encontrar e fazer download da
publicação.
IT
Questa pubblicazione è disponibile in Italiano
in formato PDF. Per scaricarla collegarsi al sito
Web indicato sopra.
ZH
DE
Diese Publikation ist als PDF auf Deutsch
verfügbar. Gehen Sie auf die oben genannte
Web-Adresse, um nach der Publikation zu
suchen und sie herunterzuladen.
ZC
ES
Esta publicación está disponible en español
como PDF. Diríjase a la dirección web indicada
arriba para buscar y descarga esta publicación.
KR
Table of Contents
Topic Page
Important User Information 2
Additional Resources 5
Overview 5
Module Description 6
Mount the Module 6
Wire the Modules 9
Specifications 9
2 Micro800 4-channel and 8-channel Analog Voltage/Current Input and Output Modules
Publication 2085-IN006C-EN-P - November 2016
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines
for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1
available from your local Rockwell
Automation sales office or online at http://www.rockwellautomation.com/literature/
) describes some important differences
between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the
wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that
each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc.,
is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous
environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death,
property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the
consequences.
SHOCK HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that
dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that
surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
Micro800 4-channel and 8-channel Analog Voltage/Current Input and Output Modules 3
Publication 2085-IN006C-EN-P - November 2016
Environment and Enclosure
Preventing Electrostatic Discharge
ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up
to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial
equipment according to IEC/CISPR 11. Without appropriate precautions, there may be
difficulties with electromagnetic compatibility in residential and other environments due to
conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure
that is suitably designed for those specific environmental conditions that will be present and
appropriately designed to prevent personal injury resulting from accessibility to live parts. The
enclosure must have suitable flame-retardant properties to prevent or minimize the spread of
flame, complying with a flame spread rating of 5VA or be approved for the application if
nonmetallic. The interior of the enclosure must be accessible only by the use of a tool.
Subsequent sections of this publication may contain additional information regarding specific
enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
, for
additional installation requirements.
NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of
protection provided by enclosures.
ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal
damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.
4 Micro800 4-channel and 8-channel Analog Voltage/Current Input and Output Modules
Publication 2085-IN006C-EN-P - November 2016
North American Hazardous Location Approval
The following modules are North American Hazardous Location approved:
2085-IF4, 2085-IF8, 2085-OF4
The following information applies when operating
this equipment in hazardous locations:
Informations sur l’utilisation de cet équipement en
environnements dangereux:
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for
use in Class I Division 2 Groups A, B, C, D, Hazardous
Locations and nonhazardous locations only. Each product is
supplied with markings on the rating nameplate indicating
the hazardous location temperature code. When combining
products within a system, the most adverse temperature
code (lowest "T" number) may be used to help determine the
overall temperature code of the system. Combinations of
equipment in your system are subject to investigation by the
local Authority Having Jurisdiction at the time of
installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu'à une utilisation en environnements de Classe
I Division 2 Groupes A, B, C, D dangereux et non dangereux.
Chaque produit est livré avec des marquages sur sa plaque
d'identification qui indiquent le code de température pour les
environnements dangereux. Lorsque plusieurs produits sont
combinés dans un système, le code de température le plus
défavorable (code de température le plus faible) peut être
utilisé pour déterminer le code de température global du
système. Les combinaisons d'équipements dans le système
sont sujettes à inspection par les autorités locales qualifiées
au moment de l'installation.
WARNING: EXPLOSION HAZARD
Do not disconnect equipment unless
power has been removed or the area is
known to be nonhazardous.
Do not disconnect connections to this
equipment unless power has been
removed or the area is known to be
nonhazardous. Secure any external
connections that mate to this
equipment by using screws, sliding
latches, threaded connectors, or other
means provided with this product.
Substitution of components may impair
suitability for Class I, Division 2.
If this product contains batteries, they
must only be changed in an area known
to be nonhazardous.
WARNING: RISQUE D’EXPLOSION
Couper le courant ou s'assurer que
l'environnement est classé non dangereux
avant de débrancher l'équipement.
Couper le courant ou s'assurer que
l'environnement est classé non dangereux
avant de débrancher les connecteurs.
Fixer tous les connecteurs externes reliés
à cet équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou autres
moyens fournis avec ce produit.
La substitution de composants peut
rendre cet équipement inadapté à une
utilisation en environnement de Classe I,
Division 2.
S'assurer que l'environnement est classé
non dangereux avant de changer les piles.
WARNING: When you connect or disconnect the Removable Terminal Block (RTB) with field side
power applied, an electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous before proceeding.
WARNING: When used in a Class I, Division 2, hazardous location, this equipment must be
mounted in a suitable enclosure with proper wiring method that complies with the governing
electrical codes.
WARNING: If you connect or disconnect wiring while the field-side power is on, an electrical arc
can occur. This could cause an explosion in hazardous location installations. Be sure that power is
removed or the area is nonhazardous before proceeding.
WARNING: Do not connect directly to line voltage. Line voltage must be supplied by a suitable,
approved isolating transformer or power supply having short circuit capacity not exceeding
100 VA maximum or equivalent.
WARNING: If you insert or remove the module while backplane power is on, an electrical arc can
occur. This could cause an explosion in hazardous location installations. Be sure that power is
removed before proceeding.
WARNING: Do not unscrew the RTB hold down screws and remove the RTB while power is on.
This could cause an explosion in hazardous location installations. Be sure that power is removed
before proceeding.
Micro800 4-channel and 8-channel Analog Voltage/Current Input and Output Modules 5
Publication 2085-IN006C-EN-P - November 2016
Additional Resources
If you would like a manual, you can:
download a free electronic version from the Internet:
http://www.rockwellautomation.com/literature/
.
purchase a printed manual by contacting your local Allen-Bradley distributor or
Rockwell Automation representative
Overview
The Micro800™ expansion I/O is a modular I/O that complements and extends the capabilities
of Micro850™ controllers. These expansion I/O modules interface with Micro850 controllers
using an I/O expansion port.
I/O Module Overview
Resource Description
Micro830 and Micro850 Programmable
Controller User Manual,
publication 2080-UM002
A detailed description of how to install and use a Micro850
Programmable Controller.
Micro800 Bus Terminator Installation
Instructions, publication 2085-IN002
Information on installing the bus terminator module.
Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1
More information on proper wiring and grounding techniques.
5
45317
6
Front view Left side view
45315
1
2085-IF4
3
4
1
6
Front view
45316
1
2085-OF4
2
5
6 Micro800 4-channel and 8-channel Analog Voltage/Current Input and Output Modules
Publication 2085-IN006C-EN-P - November 2016
Mount the Module
For more information on proper grounding guidelines, see the Industrial Automation Wiring
and Grounding Guidelines, publication 1770-4.1.
Module Description
Description Description
1 Mounting screw hole / mounting foot 4 Module interconnect latch
2 Removable Terminal Block (RTB) 5 DIN rail mounting latch
3 RTB hold down screws 6 I/O status LED
This equipment is sensitive to electrostatic discharge (ESD).
Follow ESD prevention guidelines when handling this equipment.
ATTENTION: To comply with UL restrictions, this equipment must be powered from a source
compliant with the following:
Class 2 or Limited Voltage/Current.
ATTENTION: To comply with the CE Low Voltage Directive (LVD), all connected I/O must be
powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
4531945318
1
1
6
Front view
Right top view
1
2085-IF8
2
5
4
3
3
3
Micro800 4-channel and 8-channel Analog Voltage/Current Input and Output Modules 7
Publication 2085-IN006C-EN-P - November 2016
Module Spacing
Maintain spacing from objects such as enclosure walls, wireways and adjacent equipment. Allow
50.8 mm (2 in.) of space on all sides for adequate ventilation, as shown.
Mounting Dimensions and DIN Rail Mounting
DIN Rail Mounting
The module can be mounted using the following DIN rails: 35 x 7.5 mm x 1 mm
(EN 50 022 - 35 x 7.5).
Before mounting the module on a DIN rail, use a flat-blade screwdriver in the DIN rail latch and
pry it downwards until it is in the unlatched position.
1. Hook the top of the DIN rail mounting area of the module onto the DIN rail, and then
press the bottom until the module snaps onto the DIN rail.
2. Push the DIN rail latch back into the latched position.
Use DIN rail end anchors (Allen-Bradley part number 1492-EAJ35 or 1492-EAHJ35)
for vibration or shock environments.
To remove your module from the DIN rail, pry the DIN rail latch downwards until it is in the
unlatched position.
TIP
For environments with greater vibration and shock concerns, use the panel mounting
method, instead of DIN rail mounting.
ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc plated
yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials
(for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result
in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every
200 mm (7.8 in.) and use end-anchors appropriately.
45306
Mounting dimensions do not include mounting feet or DIN rail latches.
90 mm
(3.54 in.)
150 mm (5.91 in.)
2085-IF4 or 2085-OF4
2085-IF8
Micro850 Controller
Bus terminator
28 mm (1.1 in.)
44.5 mm (1.75 in.)
87 mm (3.42 in.)
8 Micro800 4-channel and 8-channel Analog Voltage/Current Input and Output Modules
Publication 2085-IN006C-EN-P - November 2016
Panel Mounting
The preferred mounting method is to use two M4 (#8) per module. Hole spacing tolerance:
±0.4 mm (0.016 in.). For mounting dimensions, refer to Micro830 and Micro850
Programmable Controller User Manual, publication 2080-UM002
.
Follow these steps to install your module using mounting screws.
1. Place the module next to the controller against the panel where you are mounting it.
Make sure the controller and module are spaced properly.
2. Mark drilling holes through the mounting screw holes and mounting feet then remove
the module.
3. Drill the holes at the markings, then replace the module and mount it.
Leave the protective debris strip in place until you are finished wiring the module and
any other devices.
System Assembly
The Micro800 expansion I/O module is attached to the controller or another I/O module by
means of interconnecting latches and hooks, as well as the bus connector. The Micro850
controller and expansion I/O modules must terminate with a 2085-ECR Bus
Terminator module.
Be sure to lock the module interconnect latches and tighten the RTB hold down screws before
applying power to the module.
For installation of the 2085-ECR module, refer to Micro800 Bus Terminator Module
Installation Instructions, publication 2085-IN002
.
Field Wiring Connections
In solid-state control systems, grounding and wire routing helps limit the effects of noise due to
electromagnetic interference (EMI)
.
ATTENTION: Failure to connect a bus terminator module to the last expansion I/O module will
result in a controller hard fault.
ATTENTION: Do not wire more than 2 conductors on any single terminal.
Micro800 4-channel and 8-channel Analog Voltage/Current Input and Output Modules 9
Publication 2085-IN006C-EN-P - November 2016
Wire the Modules
Included with your 2085-IF4 or 2085-OF4 module is a single 12-pin Removable Terminal
Blocks (RTB). Included with your 2085-IF8 module are two 12-pin RTB. Basic wiring of your
module is shown below.
Basic Wiring to the 2085-IF4, 2085-IF8, 2085-OF4 Modules
Specifications
ATTENTION: To comply with UL restrictions, this equipment must be powered from a source
compliant with the following:
Class 2 or Limited Voltage/Current.
General Specifications
Attribute 2085-IF4 2085-OF4 2085-IF8
Number of I/O 4 8
Dimensions
HxWxD
28 x 90 x 87 mm
(1.1 x 3.54 x 3.42 in.)
44.5 x 90 x 87 mm
(1.75 x 3.54 x 3.42 in.)
Shipping weight, approx. 140 g (4.93 oz) 220 g (7.76 oz)
Bus current draw, max 5V DC, 100 mA
24V DC, 50 mA
5V DC, 160 mA
24V DC, 120 mA
5V DC, 110 mA
24V DC, 50 mA
Wire size
CI-0
VI-0
COM0
CI-1
VI-1
COM1
CI-2
VI-2
COM2
CI-3
VI-3
COM3
Current
transmitter
Shielded cable
Current
transmitter
Shielded cable
Voltage
transmitter
Shielded cable
Voltage
transmitter
Shielded cable
45320
CI-0
VI-0
COM0
CI-1
VI-1
COM1
CI-2
VI-2
COM2
CI-3
VI-3
COM3
Current
transmitter
Shielded cable
Current
transmitter
Shielded cable
Voltage
transmitter
Shielded cable
Voltage
transmitter
Shielded cable
CI-4
VI-4
COM4
CI-5
VI-5
COM5
CI-6
VI-6
COM6
CI-7
VI-7
COM7
Current
transmitter
Shielded cable
Current
transmitter
Shielded cable
Voltage
transmitter
Shielded cable
Voltage
transmitter
Shielded cable
45322
2085-IF4 2085-IF8
CO-0
VO-0
COM0
CO-1
VO-1
COM1
CO-2
VO-2
COM2
CO-3
VO-3
COM3
Current
load
Shielded cable
Current
load
Shielded cable
Voltage
load
Shielded cable
Voltage
load
Shielded cable
2085-OF4
45321
Terminal Block 1 Terminal Block 2
Min Max
Solid 0.34 mm
2
(22 AWG) 2.5 mm
2
(14 AWG) Copper wire rated @
90 °C (194 °F ), or greater,
1.2 mm (3/64 in.)
insulation max
Stranded 0.20 mm
2
(22 AWG) 2.5 mm
2
(14 AWG)
10 Micro800 4-channel and 8-channel Analog Voltage/Current Input and Output Modules
Publication 2085-IN006C-EN-P - November 2016
Wiring category
(1)
2 – on signal ports
Wire type Shielded
Terminal screw torque 0.5…0.6 Nm
(4.4…5.3 lb-in.)
(2)
Power dissipation, total 1.7 W 3.7 W 1.75 W
Enclosure type rating None (open-style)
Status indicators 1 green health indicator
4 red error indicator
1 green health indicator 1 green health indicator
8 red error indicators
Isolation voltage 50V (continuous), Reinforced Insulation Type, channel to system.
Type tested @ 720V DC for 60 s
North American temp code T4
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1.
(2)
RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.
Input Specifications – 2085-IF4 and 2085-IF8
Attribute 2085-IF4 2085-IF8
Number of inputs 4 8
Resolution
Voltage
Current
14 bits (13 bits plus sign bit)
1.28 mV/cnt unipolar; 1.28 mV/cnt bipolar
1.28 A/cnt
Data format Left justified, 16 bit 2 s complement
Conversion type SAR
Update rate <2 ms per enabled channel without 50 Hz/60 Hz rejection, <8 ms for all channel
8 ms with 50 Hz/60 Hz rejection
Step response time
up to 63%
4…60 ms without 50Hz/60 Hz rejection – depends on number of enabled channel and
filter setting
600 ms with 50 Hz/60 Hz rejection
Input current terminal,
user configurable
4…20 mA (default)
0…20 mA
Input voltage terminal,
user configurable
10V
0…10V
Input impedence Voltage terminal >1 M
Current terminal <100
Absolute accuracy 0.10% Full Scale @ 25 C
Accuracy drift with temp Voltage terminal – 0.00428 % Full Scale/C
Current terminal – 0.00407 % Full Scale/C
Calibration required Factory calibrated. No customer calibration supported.
Overload, max. 30V continuous or 32 mA continuous, one channel at a time.
Channel diagnostics Over and under range or open circuit condition by bit reporting
General Specifications
Attribute 2085-IF4 2085-OF4 2085-IF8
Micro800 4-channel and 8-channel Analog Voltage/Current Input and Output Modules 11
Publication 2085-IN006C-EN-P - November 2016
Output Specifications – 2085-OF4
Attribute 2085-OF4
Number of outputs 4
Resolution
Voltage
Current
12 bits unipolar; 11 bits plus sign bipolar
2.56 mV/cnt unipolar; 5.13 mV/cnt bipolar
5.13 A/cnt
Data format Left justified, 16 bit 2s complement
Step response time up to 63% 2 ms
Conversion rate, max 2 ms per channel
Output current terminal,
user configurable
0 mA output until module is configured
4…20 mA (default)
0…20 mA
Output voltage terminal,
user configurable
10V
0…10V
Current load on voltage output,
max
3 mA
Absolute accuracy
Voltage terminal
Current terminal
0.133 % Full Scale @ 25 C or better
0.425 % Full Scale @ 25 C or better
Accuracy drift with temp Voltage terminal – 0.0045 % Full Scale/C
Current terminal – 0.0069 % Full Scale/C
Resistive load on mA output 15…500 @ 24V DC
Environmental Specifications
Attribute Value
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…65 °C (-4…149 °F)
Temperature, surrounding air, max 65 °C (149 °F)
Temperature, non-operating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing
Vibration IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g
Shock, non-operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g – for DIN rail mount
35 g – for panel mount
Emissions CISPR 11
Group 1, Class A
Publication 2085-IN006C-EN-P - November 2016 PN-396504
Supersedes Publication 2085-IN006B-EN-P - December 2012 Copyright © 2016 Rockwell Automation, Inc. All rights reserved. Printed in Singapore.
Allen-Bradley, Rockwell Automation, Micro800 and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Automation maintains current product environmental information on its website at
http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page
ESD immunity IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4:
±2 kV @ 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
Conducted RF immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications
Certification (when
product is marked)
(1)
Value
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada.
See UL File E322657.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and
Canada. See UL File E334470
CE European Union 2014/30/EU EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
RCM Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
KC Korean Registration of Broadcasting and Communications Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 3
EAC Russian Customs Union TR CU 020/2011 EMC Technical Regulation
(1)
See the Product Certification link athttp://www.rockwellautomation.com/products/certification/ for Declaration of Conformity, Certificates, and
other certification details.
Environmental Specifications
Attribute Value