Allen-Bradley Compact 5000 Installation Instructions Manual

Taper
Installation Instructions Manual
Installation Instructions
Original Instructions
Compact 5000 I/O Analog 8-channel Current/Voltage Input
Module
Catalog Number 5069-IF8
The 5069-IF8 analog 8-channel current/voltage input module offers differential, non-isolated input channels that can connect to current or voltage
input devices. The module supports multiple ranges for each input type.Differential inputs have greater resistance to the effects of electromagnetic
noise in a control system.
Compact 5000 I/O™ modules use the Producer/Consumer communication model. The Producer/Consumer communication model is an
intelligent data exchange between module and other system devices in which each module produces data without first being polled.
For more information on how to use Compact 5000 I/O modules, see the publications that are listed in Additional Resources on page 14.
Summary of Changes
The following changes were made to this revision of this publication.
Topic Page
Module Overview 5
Install a System 5
Install the Removable Terminal Block 7
Install the Module 7
Install the End Cap 8
Wire the Removable Terminal Block 9
Disconnect Wires from the Removable Terminal Block 9
Wiring Diagram 10
Use a Cable Tie 12
Power the System 12
Remove the Module 12
Specifications 13
Additional Resources 14
Topic Page(s)
Updated graphics that shows the lower hook that can be used with a cable tie 5, 5, and 10
New module height dimension 5
Additional information about how to install an end cap 8
Additional information in the wiring diagram 10
Description of how to use the cable tie on the module 12
Updates to module specifications 13
2 Rockwell Automation Publication 5069-IN010B-EN-P - November 2017
COMPACT 5000 Analog 8-channel Current/Voltage Input Module
ATTENTION: Read this document and the documents listed in the Additional Resources section about installation, configuration and operation of this equipment before you install, configure, operate or maintain
this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of
practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
⌘᜿˖൘ᆹ㻵ǃ䝽㖞ǃ᫽֌઼㔤ᣔᵜӗ૱ࡽˈ䈧䰵䈫ᵜ᮷ẓԕ৺ Ā ަԆ䍴Ⓚ ā 䜘࠶ࡇࠪⲴᴹޣ䇮༷ᆹ㻵ǃ䝽㖞઼᫽֌Ⲵ⴨ᓄ᮷ẓDŽ䲔Ҷᡰᴹ䘲⭘㿴㤳ǃ⌅ᖻ
઼ḷ߶Ⲵ⴨ޣ㾱≲ѻཆˈ⭘ᡧ䘈ᗵ享⟏ᚹᆹ㻵઼᧕㓯䈤᰾DŽ
ᆹ㻵ǃ䈳ᮤǃᣅ䘀ǃ֯⭘ǃ㓴㻵ǃ᣶ন઼㔤ᣔㅹ਴亩᫽֌ᗵ享⭡㓿䗷䘲ᖃ䇝㓳ⲴуъӪઈ᤹➗䘲⭘Ⲵ᫽֌㿴㤳ᇎᯭDŽ
ྲ᷌ᵚ᤹➗ࡦ䙐୶ᤷᇊⲴᯩᔿ֯⭘䈕䇮༷ˈࡉਟ㜭Պᦏᇣ䇮༷ᨀ׋Ⲵ؍ᣔDŽ
ATENCIÓN: Antes de instalar, configurar, poner en funcionamiento o realizar el mantenimiento de este producto, lea este documento y los documentos listados en la sección Recursos adicionales acerca de la
instalación, configuración y operación de este equipo. Los usuarios deben familiarizarse con las instrucciones de instalación y cableado y con los requisitos de todos los códigos, leyes y estándares vigentes.
El personal debidamente capacitado debe realizar las actividades relacionadas a la instalación, ajustes, puesta en servicio, uso, ensamblaje, desensamblaje y mantenimiento de conformidad con el código de
práctica aplicable.
Si este equipo se usa de una manera no especificada por el fabricante, la protección provista por el equipo puede resultar afectada.
ATENÇÃO: Leia este e os demais documentos sobre instalação, configuração e operação do equipamento que estão na seção Recursos adicionais antes de instalar, configurar, operar ou manter este produto. Os
usuários devem se familiarizar com as instruções de instalação e fiação além das especificações para todos os códigos, leis e normas aplicáveis.
É necessário que as atividades, incluindo instalação, ajustes, colocação em serviço, utilização, montagem, desmontagem e manutenção sejam realizadas por pessoal qualificado e especializado, de acordo com o
código de prática aplicável.
Caso este equipamento seja utilizado de maneira não estabelecida pelo fabricante, a proteção fornecida pelo equipamento pode ficar prejudicada.
ВНИМАНИЕ: Перед тем как устанавливать, настраивать, эксплуатировать или обслуживать данное оборудование, прочитайте этот документ и документы, перечисленные в разделе
«Дополнительные ресурсы». В этих документах изложены сведения об установке, настройке и эксплуатации данного оборудования. Пользователи обязаны ознакомиться с инструкциями по
установке и прокладке соединений, а также с требованиями всех применимых норм, законов и стандартов.
Все действия, включая установку, наладку, ввод в эксплуатацию, использование, сборку, разборку и техническое обслуживание, должны выполняться обученным персоналом в соответствии с
применимыми нормами и правилами.
Если оборудование используется не предусмотренным производителем образом, защита оборудования может быть нарушена.
ὀព ᮏ〇ရࢆタ⨨ࠊᵓᡂࠊ✌ືࡲࡓࡣಖᏲࡍࡿ๓࡟ࠊᮏ᭩࠾ࡼࡧᮏᶵჾࡢタ⨨ࠊタᐃࠊ᧯స࡟ࡘ࠸࡚ࡢཧ⪃㈨ᩱࡢヱᙜ⟠ᡤ࡟グ㍕ࡉࢀ࡚࠸ࡿᩥ᭩࡟┠ࢆ
㏻ࡋ࡚ࡃࡔࡉ࠸ࠋ࣮ࣘࢨࡣࠊࡍ࡭࡚ࡢヱᙜࡍࡿ᮲౛ࠊἲᚊࠊつ᱁ࡢせ௳࡟ຍ࠼࡚ࠊタ⨨࠾ࡼࡧ㓄⥺ࡢᡭ㡰࡟⩦⇍ࡋ࡚࠸ࡿᚲせࡀ࠶ࡾࡲࡍࠋ
タ⨨ㄪᩚࠊ㐠㌿ࡢ㛤ጞࠊ౑⏝ࠊ⤌❧࡚ࠊゎయࠊಖᏲࢆྵࡴㅖసᴗࡣࠊヱᙜࡍࡿᐇ᪋つ๎࡟ᚑࡗ࡚カ⦎ࢆཷࡅࡓ㐺ษ࡞సᴗဨࡀᐇ⾜ࡍࡿᚲせࡀ࠶ࡾࡲࡍࠋ
ᮏᶵჾࡀ〇㐀࣓࣮࢝࡟ࡼࡾᣦᐃࡉࢀ࡚࠸࡞࠸᪉ἲ࡛౑⏝ࡉࢀ࡚࠸ࡿሙྜࠊᶵჾ࡟ࡼࡾᥦ౪ࡉࢀ࡚࠸ࡿಖㆤࡀᦆ࡞ࢃࢀࡿᜍࢀࡀ࠶ࡾࡲࡍࠋ
ACHTUNG: Lesen Sie dieses Dokument und die im Abschnitt „Weitere Informationen“aufgeführten Dokumente, die Informationen zu Installation, Konfiguration und Bedienung dieses Produkts enthalten, bevor
Sie dieses Produkt installieren, konfigurieren, bedienen oder warten. Anwender müssen sich neben den Bestimmungen aller anwendbaren Vorschriften, Gesetze und Normen zusätzlich mit den Installations- und
Verdrahtungsanweisungen vertraut machen.
Arbeiten im Rahmen der Installation, Anpassung, Inbetriebnahme, Verwendung, Montage, Demontage oder Instandhaltung dürfen nur durch ausreichend geschulte Mitarbeiter und in Übereinstimmung mit den
anwendbaren Ausführungsvorschriften vorgenommen werden.
Wenn das Gerät in einer Weise verwendet wird, die vom Hersteller nicht vorgesehen ist, kann die Schutzfunktion beeinträchtigt sein.
ATTENTION : Lisez ce document et les documents listés dans la section Ressources complémentaires relatifs à l’installation, la configuration et le fonctionnement de cet équipement avant d’installer, configurer,
utiliser ou entretenir ce produit. Les utilisateurs doivent se familiariser avec les instructions d’installation et de câblage en plus des exigences relatives aux codes, lois et normes en vigueur.
Les activités relatives à l’installation, le réglage, la mise en service, l’utilisation, l’assemblage, le démontage et l’entretien doivent être réalisées par des personnes formées selon le code de pratique en vigueur.
Si cet équipement est utilisé d’une façon qui n’a pas été définie par le fabricant, la protection fournie par l’équipement peut être compromise.
㭒㦮 a ⽎G㩲䛞G㍺䂮 SG㍺㩫 SG㧧☯G⡦⓪G㥶㰖G⽊㑮䞮₆G㩚㠦G⽎Gⶎ㍲⯒G䙂䞾䞮㡂G㍺䂮 SG㍺㩫G⹥G㧧☯㠦Gὖ䞲G㺎ἶG㧦⬢G㎏㎮㦮Gⶎ㍲✺㦚G⹮✲㔲G㧓ἶG㑯㰖䞮㕃
㔲㡺 UG㌂㣿㧦⓪G⳾✶Gὖ⩾G′㩫 SG⻫′G⹥G䚲㭖㠦㍲G㣪ῂ䞮⓪G㌂䟃㠦G╖䟊G⹮✲㔲G㍺䂮G⹥G⺆㍶G㰖䂾㦚G㑯㰖䟊㟒G䞿┞┺ U
㍺䂮 SG㫆㩫 SGṖ☯ SG㌂㣿 SG㫆Ⱃ SG⿚䟊 SG㥶㰖⽊㑮G❇G⳾✶G㧧㠛㦖Gὖ⩾G′㩫㠦G➆⧒G㩗㩞䞲Gᾦ㥷㦚G⹱㦖G㌂㣿㧦⯒G䐋䟊㍲ⰢG㑮䟟䟊㟒G䞿┞┺ U
⽎G㧻゚⯒G㩲㫆㌂ṖGⳛ㔲䞮㰖G㞠㦖G⹿⻫㦒⪲G㌂㣿䞮ⳊG㧻゚㦮G⽊䢎G₆⓻㧊G㏦㌗♶G㑮G㧞㔋┞┺ U
ATTENZIONE Prima di installare, configurare ed utilizzare il prodotto, o effettuare interventi di manutenzione su di esso, leggere il presente documento ed i documenti elencati nella sezione “Altre risorse”,
riguardanti l’installazione, la configurazione ed il funzionamento dell’apparecchiatura. Gli utenti devono leggere e comprendere le istruzioni di installazione e cablaggio, oltre ai requisiti previsti dalle leggi, codici
e standard applicabili.
Le attività come installazione, regolazioni, utilizzo, assemblaggio, disassemblaggio e manutenzione devono essere svolte da personale adeguatamente addestrato, nel rispetto delle procedure previste.
Qualora l’apparecchio venga utilizzato con modalità diverse da quanto previsto dal produttore, la sua funzione di protezione potrebbe venire compromessa.
DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın kurulumu, yapılandırılması ve işletimi ile ilgili İlave Kaynaklar bölümünde yer listelenmiş
dokümanları okuyun. Kullanıcılar yürürlükteki tüm yönetmelikler, yasalar ve standartların gereksinimlerine ek olarak kurulum ve kablolama talimatlarını da öğrenmek zorundadır.
Kurulum, ayarlama, hizmete alma, kullanma, parçaları birleştirme, parçaları sökme ve bakım gibi aktiviteler sadece uygun eğitimleri almış kişiler tarafından yürürlükteki uygulama yönetmeliklerine uygun şekilde
yapılabilir.
Bu ekipman üretici tarafından belirlenmiş amacın dışında kullanılırsa, ekipman tarafından sağlanan koruma bozulabilir.
⌘᜿һ丵˖൘ᆹ㼍ǃ䁝ᇊǃ᫽֌ᡆ㏝䆧ᵜ⭒૱ࡽˈ䃻ݸ䯡䆰↔᮷Ԧԕ৺ࡇᯬ NjަԆ䋷Ⓚnjㄐㇰѝᴹ䰌ᆹ㼍ǃ䁝ᇊ㠷᫽֌↔䁝ۉⲴ᮷ԦDŽ֯⭘㘵ᗵ丸⟏ᚹᆹ㼍઼
䝽㐊ᤷ⽪ˈіㅖਸᡰᴹ⌅㾿ǃ⌅ᖻ઼⁉Ⓠ㾱≲DŽ
वᤜᆹ㼍ǃ䃯ᮤǃӔԈ֯⭘ǃ֯⭘ǃ㍴㼍ǃ᣶ন઼㏝䆧ㅹअ֌䜭ᗵ丸Ӕ⭡ᐢ㏃䙾䚙⮦䁃㐤ⲴӪ଑䙢㹼ˈԕㅖਸ䚙⭘Ⲵሖ֌⌅㾿DŽ
ྲ᷌ሷ䁝ۉ⭘ᯬ䶎㼭䙐୶ᤷᇊⲴ⭘䙄ᱲˈਟ㜭ᴳ䙐ᡀ䁝ۉᡰᨀ׋Ⲵ؍䆧࣏㜭ਇᨽDŽ
POZOR: Než začnete instalovat, konfigurovat či provozovat tento výrobek nebo provádět jeho údržbu, přečtěte si tento dokument a dokumenty uvedené v části Dodatečné zdroje ohledně instalace, konfigurace
a provozu tohoto zařízení. Uživatelé se musejí vedle požadavků všech relevantních vyhlášek, zákonů a norem nutně seznámit také s pokyny pro instalaci a elektrické zapojení.
Činnosti zahrnující instalaci, nastavení, uvedení do provozu, užívání, montáž, demontáž a údržbu musí vykonávat vhodně proškolený personál v souladu s příslušnými prováděcími předpisy.
Pokud se toto zařízení používá způsobem neodpovídajícím specifikaci výrobce, může být narušena ochrana, kterou toto zařízení poskytuje.
UWAGA: Przed instalacją, konfiguracją, użytkowaniem lub konserwacją tego produktu należy przeczytać niniejszy dokument oraz wszystkie dokumenty wymienione w sekcji Dodatkowe źródła omawiające
instalację, konfigurację i procedury użytkowania tego urządzenia. Użytkownicy mają obowiązek zapoznać się z instrukcjami dotyczącymi instalacji oraz oprzewodowania, jak również z obowiązującymi kodeksami,
prawem i normami.
Działania obejmujące instalację, regulację, przekazanie do użytkowania, użytkowanie, montaż, demontaż oraz konserwację muszą być wykonywane przez odpowiednio przeszkolony personel zgodnie z
obowiązującym kodeksem postępowania.
Jeśli urządzenie jest użytkowane w sposób inny niż określony przez producenta, zabezpieczenie zapewniane przez urządzenie może zostać ograniczone.
OBS! Läs detta dokument samt dokumentet, som står listat i avsnittet Övriga resurser, om installation, konfigurering och drift av denna utrustning innan du installerar, konfigurerar eller börjar använda eller
utföra underhållsarbete på produkten. Användare måste bekanta sig med instruktioner för installation och kabeldragning, förutom krav enligt gällande koder, lagar och standarder.
Åtgärder som installation, justering, service, användning, montering, demontering och underhållsarbete måste utföras av personal med lämplig utbildning enligt lämpligt bruk.
Om denna utrustning används på ett sätt som inte anges av tillverkaren kan det hända att utrustningens skyddsanordningar försätts ur funktion.
LET OP: Lees dit document en de documenten die genoemd worden in de paragraaf Aanvullende informatie over de installatie, configuratie en bediening van deze apparatuur voordat u dit product installeert,
configureert, bediend of onderhoudt. Gebruikers moeten zich vertrouwd maken met de installatie en de bedradingsinstructies, naast de vereisten van alle toepasselijke regels, wetten en normen.
Activiteiten zoals het installeren, afstellen, in gebruik stellen, gebruiken, monteren, demonteren en het uitvoeren van onderhoud mogen uitsluitend worden uitgevoerd door hiervoor opgeleid personeel en in
overeenstemming met de geldende praktijkregels.
Indien de apparatuur wordt gebruikt op een wijze die niet is gespecificeerd door de fabrikant, dan bestaat het gevaar dat de beveiliging van de apparatuur niet goed werkt.
Rockwell Automation Publication 5069-IN010B-EN-P - November 2017 3
COMPACT 5000 Analog 8-channel Current/Voltage Input Module
Waste Electrical and Electronic Equipment (WEEE)
At the end of its life, this equipment should be collected separately from any unsorted municipal waste.
Environment and Enclosure
ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications
(as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such
environments.
This equipment is supplied as open-type equipment for indoor use. It must be mounted within an enclosure that is suitably designed for those specific
environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must
have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the
application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain more
information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
Industrial Automation Wiring and Grounding Guidelines, publication
1770-4.1, for more installation requirements.
NEMA Standard 250 and EN/IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.
North American Hazardous Location Approval
The following information applies when operating this equipment in
hazardous locations.
Informations sur l’utilisation de cet équipement en environnements
dangereux.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2
Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product
is supplied with markings on the rating nameplate indicating the hazardous location
temperature code. When combining products within a system, the most adverse
temperature code (lowest "T" number) may be used to help determine the overall
temperature code of the system. Combinations of equipment in your system are
subject to investigation by the local Authority Having Jurisdiction at the time of
installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en
environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux.
Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent
le code de température pour les environnements dangereux. Lorsque plusieurs produits
sont combinés dans un système, le code de température le plus défavorable (code de
température le plus faible) peut être utilisé pour déterminer le code de température
global du système. Les combinaisons d'équipements dans le système sont sujettes à
inspection par les autorités locales qualifiées au moment de l'installation.
WARNING:
Explosion Hazard –
Do not disconnect equipment unless power has been removed
or the area is known to be nonhazardous.
Do not disconnect connections to this equipment unless power
has been removed or the area is known to be nonhazardous.
Secure any external connections that mate to this equipment by
using screws, sliding latches, threaded connectors, or other
means provided with this product.
Substitution of components may impair suitability for Class I,
Division 2.
If this product contains batteries, they must only be changed in
an area known to be nonhazardous.
AVERTISSEMENT:
Risque d’Explosion –
Couper le courant ou s'assurer que l'environnement est classé non
dangereux avant de débrancher l'équipement.
Couper le courant ou s'assurer que l'environnement est classé non
dangereux avant de débrancher les connecteurs. Fixer tous les
connecteurs externes reliés à cet équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou autres moyens fournis avec ce
produit.
La substitution de composants peut rendre cet équipement
inadapté à une utilisation en environnement de Classe I, Division 2.
S'assurer que l'environnement est classé non dangereux avant de
changer les piles.
European Hazardous Location Approval
The following applies to products marked , II 3 G. Such modules:
Are Equipment Group II, Equipment Category 3, and comply with the Essential Health and Safety Requirements relating to the design and construction of such equipment given in Annex II to Directive
94/9/EC. See the EC Declaration of Conformity at http://www.rockwellautomation.com/products/certification for details.
The type of protection is "Ex nA IIC T4 Gc" according to EN 60079-15.
The 5069-IF8 module complies to standards: EN 60079-0:2012+A11:2013, EN 60079-15:2010, reference certificate number DEMKO 15 ATEX 1484X.
Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short periods. Such locations
correspond to Zone 2 classification according to ATEX directive 1999/92/EC.
4 Rockwell Automation Publication 5069-IN010B-EN-P - November 2017
COMPACT 5000 Analog 8-channel Current/Voltage Input Module
IEC Hazardous Location Approval
The following applies to products with IECEx certification: Such modules:
Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short periods. Such locations
correspond to Zone 2 classification to IEC 60079-0.
The type of protection is "Ex nA IIC T4 Gc" according to IEC 60079-15.
The 5069-IF8 module complies to standards IEC 60079-0:6th Edition, IEC-60079-15:4th Edition, reference IECEx certificate number IECEx UL 15.0055X.
Special Conditions for Safe Use
WARNING:
This equipment is not resistant to sunlight or other sources of UV radiation.
This equipment shall be mounted in an ATEX/IECEx Zone 2 certified enclosure with a minimum ingress protection rating of at least IP54 (as defined in
EN/IEC 60529) and used in an environment of not more than Pollution Degree 2 (as defined in EN/IEC 60664-1) when applied in Zone 2 environments. The
enclosure must be accessible only by the use of a tool.
This equipment shall be used within its specified ratings defined by Rockwell Automation.
Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140% of the rated voltage when applied in
Zone 2 environments.
The instructions in the user manual shall be observed.
This equipment must be used only with ATEX/IECEx certified Rockwell Automation backplanes.
Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this
product.
Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
Earthing is accomplished through mounting of modules on rail.
Devices shall be used in an environment of not more than Pollution Degree 2.
Prevent Electrostatic Discharge
ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when
you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.
Electrical Safety Considerations
ATTENTION:
Do not wire more than 1 conductor on any single RTB terminal.
In case of malfunction or damage, no attempts at repair should be made. The module should be returned to the manufacturer for repair. Do not dismantle
the module.
This equipment is certified for use only within the surrounding air temperature range of 0…60 °C (32…140 °F) The equipment must not be used outside of
this range.
Use only a soft dry anti-static cloth to wipe down equipment. Do not use any cleaning agents.
IMPORTANT Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for the purposes of example. Since there are
many variables and requirements associated with any particular installation, Rockwell Automation does not assume responsibility or liability for actual use
based upon the examples shown in this publication.
Rockwell Automation Publication 5069-IN010B-EN-P - November 2017 5
COMPACT 5000 Analog 8-channel Current/Voltage Input Module
Module Overview Install a System
Based on your application design, you must install a
CompactLogix 5380 controller or Compact 5000 I/O EtherNet/IP
adapter before you can install the module.
For more information on how to install these components, see
Additional Resources on page 14.
Required Components
To install the module, you need these components.
ANALOG INPUT
5069-IF8
Module Status Indicator
I/O Status Indicator
Top Interlocking Piece
Bottom Interlocking Piece
DIN Rail Latch
RTB Handle
RTB
MOD Power Bus
and SA Power Bus
Connectors
(isolated from each
other internally)
RTB Lower Tab
Lower hook for use
with cable tie.
Component Description
Removable
terminal blocks
One of the following RTB types.
5069-RTB18-SPRING RTB
5069-RTB18-SCREW RTB
IMPORTANT: You must order RTBs separately. RTBs do not ship with
Compact 5000 I/O modules. We recommend that you order only the RTB
type that your system requires.
End cap
An end cap ships with the CompactLogix 5380 controllers and the
Compact 5000 I/O EtherNet/IP adapters.
Tools
The following tools are needed:
Screwdriver
Wire stripper
Wires
For more information on available wire sizes and wire insulation stripping
length, see
Specifications on page 13.
6 Rockwell Automation Publication 5069-IN010B-EN-P - November 2017
COMPACT 5000 Analog 8-channel Current/Voltage Input Module
Dimensions Ground Considerations
You must ground DIN rails according to the Industrial Automation
Wiring and Grounding Guidelines, publication
1770-4.1.
You can use the EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail
with Compact 5000 I/O modules.
System Power Considerations
A CompactLogix 5380 controller or Compact 5000 I/O EtherNet/IP
adapter provides power to the module.
The following power types are available:
Module (MOD) power - System-side power that is required to
operate the Compact 5000 I/O modules. MOD power is
provided through the MOD power RTB and passed across the
MOD power bus.
Sensor/Actuator (SA) power - Field-side power that is used to
power field-side devices. SA power is provided through the SA
power RTB and passed across the SA power bus.
The first component in the system, that is, the controller or the
adapter, establishes an SA power bus.
A system can have more than one SA power bus. You use
5069-FPD field potential distributors to establish a new SA
power bus. SA power buses are isolated from each other.
If a system includes Compact 5000 I/O modules that use AC
SA power and modules that use DC SA power, you must
install them on separate SA power buses.
ANALOG INPUT
5069-IF8
109.09 mm (4.29 in.)
25.56 mm (1.01 in.)
144.57 mm
(5.69 in.)
105.42 mm (4.15 in.)
22 mm (0.87 in.)
ATTENTION: This product is grounded through the DIN rail to
chassis ground. Use zinc-plated chromate-passivated steel DIN
rail to assure proper grounding. The use of other DIN rail
materials (for example, aluminum or plastic) that can corrode,
oxidize, or are poor conductors, can result in improper or
intermittent grounding. Secure DIN rail to mounting surface
approximately every 200 mm (7.8 in.) and use end-anchors
appropriately. Be sure to ground the DIN rail properly. Refer to
Industrial Automation Wiring and Grounding Guidelines,
Rockwell Automation® publication
1770-4.1 for more
information.
Rockwell Automation Publication 5069-IN010B-EN-P - November 2017 7
COMPACT 5000 Analog 8-channel Current/Voltage Input Module
To keep the modules on separate SA power buses, complete the
following steps.
a. Install the modules that use one type of SA power, for
example AC, to the right of the adapter or controller, that
is, the first SA power bus.
b. Install the 5069-FPD field potential distributor to establish
a second SA power bus.
c. Install the modules that use the other type of SA power, for
example DC, on the second SA power bus.
Install the Removable Terminal Block
1. Hook the bottom of the RTB on the module.
2. Push the RTB against the module until the RTB clicks
into place.
3. Push the RTB handle against the RTB until you hear
another click.
Install the Module
Install the I/O module next to the right-most device in the system. To
install the module, complete these steps.
1. Confirm that MOD power and all sources of SA power are off.
If you remove the module with power applied, the system
MOD power bus and SA power bus are affected. For example,
you can interrupt MOD power to the other modules in the
system. Unintended consequences can occur as a result.
2. If an end cap is installed on the right-most module that is
installed in the system, remove it and keep for later use.
3. Confirm that the DIN rail latch is closed.
4. If the DIN rail latches are open, gently push the rear latch back
until the front latch pops up and clicks.
ATTENTION: To reduce susceptibility to noise, power
analog modules and digital modules from separate
power supplies.
IMPORTANT We recommend that you use separate external power supplies
for MOD power and SA power respectively. This practice helps
to prevent unintended consequences that can result if you use
one supply.
If you use separate external power supplies, the loss of power
from one external power supply does not affect the
availability of power from the other supply. For example, if
separate external power supplies are used and SA power is
lost, MOD power remains available for the Compact 5000 I/O
modules.
WARNING: If you connect or disconnect the removable terminal
block (RTB) with power applied, an electric arc can occur. This
could cause an explosion in hazardous location installations.
The removable terminal block (RTB) does not support "Removal
and Insertion Under Power" (RIUP) capability. Do not connect or
disconnect the removable terminal block (RTB) while power is
applied. Be sure that power is removed before proceeding.
WARNING: If you insert or remove the module while backplane
power is on, an electric arc can occur. This could cause an explosion
in hazardous location installations.
The module does not support "Removal and Insertion Under
Power" (RIUP) capability. Do not connect or disconnect the
module while power is applied. Be sure that power is removed
before proceeding.
ATTENTION: Do not discard the end cap. Use this end
cap to cover the exposed interconnections on the last
module on the DIN rail. Failure to do so could result in
equipment damage or injury from electric shock.
Open PositionClosed Position
8 Rockwell Automation Publication 5069-IN010B-EN-P - November 2017
COMPACT 5000 Analog 8-channel Current/Voltage Input Module
5. Align the interlocking pieces of the module with the device on
the left.
The top interlocking pieces engage first.
6. Push the module toward the DIN rail until a click indicates
that the module is locked in place.
7. Verify that the module is installed in one of the following ways:
If the module is installed next to a controller or adapter, the
front of the module is set back slightly from the front of the
controller or adapter.
If the module is installed next to another I/O module, the
fronts of both modules are flush with each other.
Install the End Cap
You must install an end cap on the last module in your system.
1. Align the end cap with the interlocking pieces on the module.
2. Push the end cap toward the DIN rail until it locks in place.
ADAPTER
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Top
Interlocking
Pieces
Bottom
Interlocking
Piece
IMPORTANT You install the end cap after the last module is installed on
the DIN rail. This design helps to prevent the end cap from
going beyond the locked position.
If you push the end cap beyond the locked position or insert it
from the backwards direction, you can damage the MOD
power bus and SA power bus connector.
ADAPTER
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
ADAPTER
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Interlocking
Pieces
End Cap
End Cap
Rockwell Automation Publication 5069-IN010B-EN-P - November 2017 9
COMPACT 5000 Analog 8-channel Current/Voltage Input Module
Wire the Removable Terminal Block
1. Confirm that MOD power and all sources of SA power are
turned off.
2. Strip insulation from the wires that you connect to the RTB.
3. Connect the wire to the terminal.
Disconnect Wires from the Removable Terminal Block
Disconnect wires from the RTB.
WARNING: If you connect or disconnect wiring while power is
applied, an electric arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is removed or
the area is nonhazardous before proceeding.
RTB Type Action
Screw Strip12 mm (0.47 in.) of insulation from the wires.
Spring Strip 10 mm (0.39 in.) of insulation from the wires.
RTB Type Action
Screw
1. Insert the wire into the terminal.
2. Turn the screwdriver to close the terminal on the wire. Torque the
screw to 0.4 N•m (3.5 lb•in).
Spring
Push the wire into the terminal.
If the wire is too thin, crimp a wire ferrule on the wire and insert it.
5069-RTB18-SPRING RTB5069-RTB18-SCREW RTB
WARNING: If you connect or disconnect wiring while power is
applied, an electric arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is removed or
the area is nonhazardous before proceeding.
RTB Type Action
Screw
1. Turn the screwdriver counter-clockwise to open the terminal.
2. Remove the wire.
Spring
1. Insert and hold a screwdriver in the right-side terminal.
2. Remove the wire.
3. Pull out the screwdriver.
5069-RTB18-SCREW RTB
5069-RTB18-SPRING RTB
10 Rockwell Automation Publication 5069-IN010B-EN-P - November 2017
COMPACT 5000 Analog 8-channel Current/Voltage Input Module
Wiring Diagram
The following is an example wiring diagram for the 5069-IF8 analog input module in current mode.
ANALOG INPUT
5069-IF8
Input 0 +
Input 0 -
Input 1 +
Input 1 -
Input 2 +
Input 2 -
Input 3 +
Input 3 -
Input 4 +
Input 4 -
Input 5 +
Input 5 -
Input 6 +
Input 6 -
Input 7 +
Input 7 -
Shield
Shield
2-wire
Transmitter
24V DC
+
+
Shield
Ground
A
A
i
IMPORTANT: Place additional loop devices, for
example, strip chart recorders, at either A
location in the current loop.
Channel Connections
The diagram shows a device that is connected to
channel 0. You are not restricted to using only
this channel.
You can connect devices to any channel or
combination of channels as needed.
Rockwell Automation Publication 5069-IN010B-EN-P - November 2017 11
COMPACT 5000 Analog 8-channel Current/Voltage Input Module
The following is an example wiring diagram for the 5069-IF8 analog input module in voltage mode.
ANALOG INPUT
5069-IF8
Input 0 +
Input 0 -
Input 1 +
Input 1 -
Input 2 +
Input 2 -
Input 3 +
Input 3 -
Input 4 +
Input 4 -
Input 5 +
Input 5 -
Input 6 +
Input 6 -
Input 7 +
Input 7 -
Shield
Shield
User Analog
Input Device
24V DC
+
+
Shield
Ground
Channel Connections
The diagram shows a device that is connected to
channel 0. You are not restricted to using only
this channel.
You can connect devices to any channel or
combination of channels as needed.
12 Rockwell Automation Publication 5069-IN010B-EN-P - November 2017
COMPACT 5000 Analog 8-channel Current/Voltage Input Module
Use a Cable Tie
After you connect the required wires to the RTB, you can use a cable
tie to bundle the wires. There is a lower hook at the bottom of the
module that you use to secure the tied bundle to the module.
1. Make sure that you have a cable tie long enough to contain the
wires that are connected to the module.
The maximum width of the cable tie is 4.5 mm (0.18 in).
2. Gather the wires at the bottom of the module.
3. Thread the cable tie through the lower hook at the bottom of
the RTB..
4. Wrap the cable tie around the wires and secure it.
Power the System
After you install all Compact 5000 I/O modules, you can turn on
MOD power and, if used, SA power to the system.
For more information on MOD power and SA power, see
System
Power Considerations on page 6.
Remove the Module
1. Confirm that MOD power and all sources of SA power are
turned off.
2. If necessary, remove the end cap from the right side of the
module.
3. If desired, disconnect wires from the RTB as described on
page 9.
4. Press the DIN rail latch down until it clicks and let go of the
latch.
5. Pull the module off the DIN rail.
6. To replace the module, follow the steps that are described
beginning at
Install the Module on page 7.
ATTENTION: Do not remove or replace the module while power is
applied. Interruption of the backplane can result in unintentional
operation or machine motion.
IMPORTANT Before you remove power from the MOD power RTB
and, if used, SA power RTB, consider the effect on
your system.
When you remove MOD power and SA power from a
controller or adapter, you shut down power to all
Compact 5000 I/O modules in the system. That is, all
system-side and field-side power is removed.
We strongly recommend that you take the
appropriate actions to help prevent unintended
consequences that can result from a system power
shutdown before you remove MOD power and
SA power.
ADAPTER
AENTR
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
ADAPTER
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Rockwell Automation Publication 5069-IN010B-EN-P - November 2017 13
COMPACT 5000 Analog 8-channel Current/Voltage Input Module
Specifications
This table lists a subset of the module specifications. For a list of all specifications, see the Compact 5000 I/O Modules and EtherNet/IP Adapters
Technical Data, publication
5069-TD001.
5069-IF8 Analog 8-channel Current/Voltage Input Module Specifications
Attribute Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max 60 °C (140 °F)
Enclosure type rating None (open-style)
Voltage and current ratings
Analog input ratings 0…20 mA, +/–10V DC (per channel)
MOD Power 75 mA @ 18…32V DC
MOD Power (Passthrough)
(1)
(1) Maximum level of MOD Power current that the module can pass through to the next module in the system. The specific level of current passed through varies based on system configuration.
9.55 A @ 18…32V DC
SA Power 100 mA @ 18…32V DC
SA Power (Passthrough)
(2)
(2) Maximum level of SA Power current that the module can pass through to the next module in the system. The specific level of current passed through varies based on system configuration.
9.95 A @ 18…32V DC
Do not exceed 10 A MOD or SA Power (Passthrough) current draw
Isolation voltage
300V (continuous), Basic Insulation Type
50V Functional Isolation between SA power and input ports
No isolation between individual input ports
Wire size
5069-RTB18-SCREW and 5069-RTB14CJC-SCREW connections
0.5…1.5 mm
2
(22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater,
3.5 mm (0.14 in.) max diameter including insulation, single wire connection only.
5069-RTB18-SPRING and 5069-RTB14CJC-SPRING connections
0.5…1.5 mm
2
(22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater,
2.9 mm (0.11 in.) max diameter including insulation, single wire connection only.
Insulation stripping length
5069-RTB18-SCREW and 5069-RTB14CJC-SCREW connections 12 mm (0.47 in.)
5069-RTB18-SPRING and 5069-RTB14CJC-SPRING connections 10 mm (0.39 in.)
RTB torque specifications (5069-RTB18-SCREW RTB and 5069-RTB14CJC-SCREW RTB only) 0.4 N·m (3.5 lb·in)
North American Temp Code T4
ATEX Temp Code T4
IECEx Temp Code T4
14 Rockwell Automation Publication 5069-IN010B-EN-P - November 2017
COMPACT 5000 Analog 8-channel Current/Voltage Input Module
Additional Resources
You can view or download publications at http://www.rockwellautomation.com/global/literature-library/overview.page. To order paper copies of
technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
Resource Description
Compact 5000 I/O Modules and EtherNet/IP Adapters Technical Data, publication
5069-TD001
Provides specifications for Compact 5000 I/O modules and EtherNet/IP adapters.
Compact 5000 I/O Analog Modules User Manual, publication 5000-UM005 Describes how to use the Compact 5000 I/O analog modules.
EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual,
publication ENET-UM004
Describes how to use Compact 5000 I/O EtherNet/IP adapters.
CompactLogix 5380 Controllers User Manual, publication 5069-UM001 Describes how to use CompactLogix 5380 controllers.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, http://www.rockwellautomation.com/global/certification/
overview.page
Provides declarations of conformity, certificates, and other certification details.
Rockwell Automation Publication 5069-IN010B-EN-P - November 2017 15
COMPACT 5000 Analog 8-channel Current/Voltage Input Module
Notes:
Allen-Bradley, Compact 5000, CompactLogix, Rockwell Automation, Rockwell Software, and Studio 5000 Logix Designer are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation maintains current product environmental information on its website at
http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.
Publication 5069-IN010B-EN-P - November 2017 PN-469204
Supersedes Publication 5069-IN010A-EN-P -October 2015 Copyright © 2017 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Rockwell Automation Support
Use the following resources to access support information.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the
How Are We Doing? form at
http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.
Technical Support Center
Knowledgebase Articles, How-to Videos, FAQs, Chat, User
Forums, and Product Notification Updates.
https://rockwellautomation.custhelp.com/
Local Technical Support Phone Numbers Locate the phone number for your country.
http://www.rockwellautomation.com/global/support/get-support-now.page
Direct Dial Codes
Find the Direct Dial Code for your product. Use the code to
route your call directly to a technical support engineer.
http://www.rockwellautomation.com/global/support/direct-dial.page
Literature Library
Installation Instructions, Manuals, Brochures, and
Technical Data.
http://www.rockwellautomation.com/global/literature-library/overview.page
Product Compatibility and Download
Center (PCDC)
Get help determining how products interact, check
features and capabilities, and find associated firmware.
http://www.rockwellautomation.com/global/support/pcdc.page
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Allen-Bradley Compact 5000 Installation Instructions Manual

Taper
Installation Instructions Manual

dans d''autres langues