Allen Bradley Allen-Bradley 5069-IB16 Compact 5000 Digital 16-point Sinking Input Modules Manuel utilisateur

Taper
Manuel utilisateur
Installation Instructions
Original Instructions
Compact 5000 Digital 16-point Sinking Input Modules
Catalog Numbers 5069-IB16, 5069-IB16F, 5069-IB16K
The 5069-IB16, 5069-IB16F, and 5069-IB16K digital 16-point sinking input modules detect input transitions on field devices. That is, the modules detect when an input changes state
from OFF to ON or from ON to OFF. The input modules convert input state transition signals to the appropriate logic level used in the controller.
Compact 5000™ I/O modules use the Producer/Consumer communication model. The Producer/Consumer communication model is an intelligent data exchange between module
and other system devices in which each module produces data without first being polled.
The modules are used as local I/O modules in CompactLogix™ 5380, Compact GuardLogix® 5380, and CompactLogix 5480, controller systems. They can also be used as remote I/O
modules with CompactLogix 5380, Compact GuardLogix 5380, CompactLogix 5480 controllers, and some other Logix 5000™ controllers.
For more information on how to use Compact 5000 I/O modules, see the publications that are listed in Additional Resources on page 11.
Summary of Changes
Topic Page
About the Module 5
Install a System 5
Install the Removable Terminal Block 7
Install the Module 7
Install the End Cap 8
Wire the Removable Terminal Block 8
Disconnect Wires from the Removable Terminal Block 8
Wiring Diagram 9
Use a Cable Tie 10
Power the System 10
Remove the Module 10
Specifications 11
Additional Resources 11
Topic Pages
Updated graphics Throughout
2Rockwell Automation Publication 5069-IN004D-EN-P - December 2021
Compact 5000 Digital 16-point Sinking Input Modules Installation Instructions
ATTENTION: Read this document and the documents listed in the Additional Resources section about installation, configuration and operation of this equipment before you install, configure, operate or maintain
this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of
practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
岤䠑㖈㸝鄳ծꂁ縨ծ乼⡲ㄤ絶䫡劥❡ㅷ⵸霼ꢓ靀劥俒咓⟄⿺  Ⱖ➭餴彂  鿈ⴔ⴩ⴀ涸剣Ⱒ霃㢊㸝鄳ծꂁ縨ㄤ乼⡲涸湱䎾俒咓կꤑ✫䨾剣鷓欽錞薴ծ岁䖒ㄤ叻ⲥ涸
湱Ⱒ銳宠⛓㢪欽䨪鵮䗳곢擿䜪㸝鄳ㄤ䱹絁霹僈կ
㸝鄳ծ靈侮ծ䫏鵘ծ⢪欽ծ絆鄳ծ䬒⽸ㄤ絶䫡瘝ぐ고乼⡲䗳곢歋絑鵂鷓䔲雲絅涸⚁⚌➃プ䭽撑鷓欽涸乼⡲錞薴㹊倶կ
㥵卓劢䭽撑ⵖ鸣㉁䭷㹁涸倰䒭⢪欽霪霃㢊ⴭ〳腊⠔䰀㹲霃㢊䲿⣘涸⥂䫡կ
ATENCIÓN: Antes de instalar, configurar, poner en funcionamiento o realizar el mantenimiento de este producto, lea este documento y los documentos listados en la sección Recursos adicionales acerca de la
instalación, configuración y operación de este equipo. Los usuarios deben familiarizarse con las instrucciones de instalación y cableado y con los requisitos de todos los códigos, leyes y estándares vigentes.
El personal debidamente capacitado debe realizar las actividades relacionadas a la instalación, ajustes, puesta en servicio, uso, ensamblaje, desensamblaje y mantenimiento de conformidad con el código de
práctica aplicable. Si este equipo se usa de una manera no especificada por el fabricante, la protección provista por el equipo puede resultar afectada.
ATENÇÃO: Leia este e os demais documentos sobre instalação, configuração e operação do equipamento que estão na seção Recursos adicionais antes de instalar, configurar, operar ou manter este produto. Os
usuários devem se familiarizar com as instruções de instalação e fiação além das especificações para todos os códigos, leis e normas aplicáveis.
É necessário que as atividades, incluindo instalação, ajustes, colocação em serviço, utilização, montagem, desmontagem e manutenção sejam realizadas por pessoal qualificado e especializado, de acordo com o
código de prática aplicável.
Caso este equipamento seja utilizado de maneira não estabelecida pelo fabricante, a proteção fornecida pelo equipamento pode ficar prejudicada.
ВНИМАНИЕ:Перед тем как устанавливать, настраивать, эксплуатировать или обслуживать данное оборудование, прочитайте этот документ идокументы,
перечисленные в разделе «Дополнительные ресурсы». В этих документах изложены сведения об установке, настройке и эксплуатации данного оборудования.
Пользователи обязаны ознакомиться синструкциями по установке ипрокладке соединений, атакже стребованиями всех применимых норм, законов и
стандартов.
Все действия, включая установку, наладку, ввод в эксплуатацию, использование, сборку, разборку и техническое обслуживание, должны выполняться
обученным персоналом всоответствии сприменимыми нормами иправилами.
Если оборудование используется не предусмотренным производителем образом, защита оборудования может быть нарушена.
󴎤󲼑 : 󳦥󷢢󱡸󷫤󶔨󳸔󳃮󵫪󱕜󱁃󲔛󱑹󳦥󳥆󳦥󳼤󱬼󷫤󶔨󷫤󲕁󳕽󰽳󱛬󶙌󷽺󳛲󷭪󲰳󵶙󳄾󷪹󸋺󳛒󳥆󵕢󸔑
󷭪󲰳󳧵󰾾󴎁󲲓󷧊󳭔󷦳󰻞󱔈󷫤󶔨󸞂󶊁󳅜󹌬󶗠󴯿󲳴󷦳
󷫤󶔨󷰄󳚮󸖋󸋅󸻛󲄤󰾫󵈾󶅉󵰨󷩒󰽥󱁃󲔛󱞎󷲀󰽳󳵠󷭪󲰳󲕌󳜶󷧊󱑲󲲟󷪯󶊻󱜍󸗞󱐗󰽳󳵠󱢟󲕌󷝥󲳴󷦳
󳦥󳼤󱬼󷢢󸔢󳉸󲕁󳜰󴎁󰾫󵈾󱸦󱝖󳼤󱬼󳏀󰿙󱁃󷶋󳐧󲷋
ACHTUNG: Lesen Sie dieses Dokument und die im Abschnitt „Weitere Informationen“aufgeführten Dokumente, die Informationen zu Installation, Konfiguration und Bedienung dieses Produkts enthalten, bevor Sie
dieses Produkt installieren, konfigurieren, bedienen oder warten. Anwender müssen sich neben den Bestimmungen aller anwendbaren Vorschriften, Gesetze und Normen zusätzlich mit den Installations- und
Verdrahtungsanweisungen vertraut machen.
Arbeiten im Rahmen der Installation, Anpassung, Inbetriebnahme, Verwendung, Montage, Demontage oder Instandhaltung dürfen nur durch ausreichend geschulte Mitarbeiter und in Übereinstimmung mit den
anwendbaren Ausführungsvorschriften vorgenommen werden.
Wenn das Gerät in einer Weise verwendet wird, die vom Hersteller nicht vorgesehen ist, kann die Schutzfunktion beeinträchtigt sein.
ATTENTION : Lisez ce document et les documents listés dans la section Ressources complémentaires relatifs à l’installation, la configuration et le fonctionnement de cet équipement avant d’installer, configurer,
utiliser ou entretenir ce produit. Les utilisateurs doivent se familiariser avec les instructions d’installation et de câblage en plus des exigences relatives aux codes, lois et normes en vigueur.
Les activités relatives à l’installation, le réglage, la mise en service, l’utilisation, l’assemblage, le démontage et l’entretien doivent être réalisées par des personnes formées selon le code de pratique en vigueur.
Si cet équipement est utilisé d’une façon qui n’a pas été définie par le fabricant, la protection fournie par l’équipement peut être compromise.
󻷋󻰧: 󻇇󽴔󻳫󼥗󽴔󻗳󼌧 , 󻗳󻳤, 󻱠󺢨󽴔󺫟󺝣󽴔󻯯󻺏󽴔󻇃󻛧󼨧󺋿󽴔󻳓󻪟󽴔󻇇󽴔󻀇󻗫󺹋󽴔󼢻󼨷󼨧󻪻󽴔󻗳󼌧, 󻗳󻳤󽴔󻃞󽴔󻱠󺢨󻪟󽴔󺇏󼨫󽴔󼄇󺆯󽴔󻱟󺶛󽴔󻘈󻘧󻰧󽴔󻀇󻗫󺦳󻰓󽴔󻃧󺦫󻞫󽴔󻱌󺆯󽴔󻛨󻺏󼨧󻞼󻞫󻫳 . 󻕻󻭸󻱟󺝣󽴔󺽷󺦯󽴔󺇏󺳷󽴔󺊫󻳤 ,
󻅤󺊫󽴔󻃞󽴔󼤫󻷏󻪟󻗫󽴔󻭣󺈻󼨧󺝣󽴔󻕻󼨼󻪟󽴔󺟏󼩃󽴔󻃧󺦫󻞫󽴔󻗳󼌧󽴔󻃞󽴔󻃿󻗯󽴔󻺏󼌷󻰓󽴔󻛨󻺏󼩃󻩋󽴔󼨸󺞗󺞳 .
󻗳󼌧 , 󻴿󻳤 , 󺃏󺢨 , 󻕻󻭸 , 󻴿󺺌 , 󻉓󼩃 , 󻯯󻺏󻇃󻛧󽴔󺧀󽴔󺽷󺦯󽴔󻱠󻪔󻰏󽴔󺇏󺳷󽴔󺊫󻳤󻪟󽴔󺧿󺱋󽴔󻳐󻳗󼨫󽴔󺈟󻯰󻰓󽴔󻃪󻰏󽴔󻕻󻭸󻱟󺹋󽴔󼚄󼩃󻗫󺺛󽴔󻛧󼩘󼩃󻩋󽴔󼨸󺞗󺞳 .
󻇇󽴔󻱴󻌓󺹋󽴔󻳫󻴿󻕻󺃏󽴔󺽔󻞫󼨧󻺏󽴔󻨙󻰏󽴔󻃸󻅤󻰋󺴫󽴔󻕻󻭸󼨧󺽃󽴔󻱴󻌓󻰧󽴔󻇃󼬇󽴔󺋿󺝴󻱃󽴔󻙟󻖐󺣯󽴔󻛧󽴔󻱗󻞄󺞗󺞳 .
ATTENZIONE Prima di installare, configurare ed utilizzare il prodotto, o effettuare interventi di manutenzione su di esso, leggere il presente documento ed i documenti elencati nella sezione “Altre risorse”,
riguardanti l’installazione, la configurazione ed il funzionamento dell’apparecchiatura. Gli utenti devono leggere e comprendere le istruzioni di installazione e cablaggio, oltre ai requisiti previsti dalle leggi, codici e
standard applicabili.
Le attività come installazione, regolazioni, utilizzo, assemblaggio, disassemblaggio e manutenzione devono essere svolte da personale adeguatamente addestrato, nel rispetto delle procedure previste.
Qualora l’apparecchio venga utilizzato con modalità diverse da quanto previsto dal produttore, la sua funzione di protezione potrebbe venire compromessa.
DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın kurulumu, yapılandırılması ve işletimi ile ilgili İlave Kaynaklar bölümünde yer listelenmiş
dokümanları okuyun. Kullanıcılar yürürlükteki tüm yönetmelikler, yasalar ve standartların gereksinimlerine ek olarak kurulum ve kablolama talimatlarını da öğrenmek zorundadır.
Kurulum, ayarlama, hizmete alma, kullanma, parçaları birleştirme, parçaları sökme ve bakım gibi aktiviteler sadece uygun eğitimleri almış kişiler tarafından yürürlükteki uygulama yönetmeliklerine uygun şekilde
yapılabilir.
Bu ekipman üretici tarafından belirlenmiş amacın dışında kullanılırsa, ekipman tarafından sağlanan koruma bozulabilir.
岤䠑✲갪㖈㸞酤鏤㹁乽⡲䧴笞隌劥欴ㅷ⵹锞⯓ꠗ隡姽俒⟝⟃⿻⴪倴 չⰦ➮须彂պ畎眏⚥剤ꡠ㸞酤鏤㹁莅乽⡲姽鏤⪔涸俒⟝⢪欽罏䗳갭擿䜫㸞酤ㄤꂂ箁䭸
爚⚛痘ざ䨾剤岁鋊岁䖒ㄤ垦彋銴宠
⺫䭍㸞酤锅侮❜➰⢪欽⢪欽穉酤䬓⽹ㄤ笞隌瘞⹛⡲鿪䗳갭❜歋䊺竤麕黠殹鎯箻涸➃㆞鹎遤⟃痘ざ黠欽涸㻜⡲岁鋊
㥶卓㼟鏤⪔欽倴ꬌ醢鸤㉂䭸㹁涸欽鸁儘〳腋剚鸤䧭鏤⪔䨾䲿⣘涸⥃隌⸆腋「䴦
POZOR: Než začnete instalovat, konfigurovat či provozovat tento výrobek nebo provádět jeho údržbu, přečtěte si tento dokument a dokumenty uvedené v části Dodatečné zdroje ohledně instalace, konfigurace
a provozu tohoto zařízení. Uživatelé se musejí vedle požadavků všech relevantních vyhlášek, zákonů anorem nutně seznámit také s pokyny pro instalaci a elektrické zapojení.
Činnosti zahrnující instalaci, nastavení, uvedení do provozu, užívání, montáž, demontáž a údržbu musí vykonávat vhodně proškolený personál v souladu s příslušnými prováděcími předpisy.
Pokud se toto zařízení používá způsobem neodpovídajícím specifikaci výrobce, může být narušena ochrana, kterou toto zařízení poskytuje.
UWAGA: Przed instalacją, konfiguracją, użytkowaniem lub konserwacją tego produktu należy przeczytać niniejszy dokument oraz wszystkie dokumenty wymienione w sekcji Dodatkowe źródła omawiające
instalację, konfigurację i procedury użytkowania tego urządzenia. Użytkownicy mają obowiązek zapoznać się z instrukcjami dotyczącymi instalacji oraz oprzewodowania, jak również z obowiązującymi kodeksami,
prawem i normami.
Działania obejmujące instalację, regulację, przekazanie do użytkowania, użytkowanie, montaż, demontaż oraz konserwację muszą być wykonywane przez odpowiednio przeszkolony personel zgodnie z
obowiązującym kodeksem postępowania.
Jeśli urządzenie jest użytkowane w sposób inny niż określony przez producenta, zabezpieczenie zapewniane przez urządzenie może zostać ograniczone.
OBS! Läs detta dokument samt dokumentet, som står listat i avsnittet Övriga resurser, om installation, konfigurering och drift av denna utrustning innan du installerar, konfigurerar eller börjar använda eller utföra
underhållsarbete på produkten. Användare måste bekanta sig med instruktioner för installation och kabeldragning, förutom krav enligt gällande koder, lagar och standarder.
Åtgärder som installation, justering, service, användning, montering, demontering och underhållsarbete måste utföras av personal med lämplig utbildning enligt lämpligt bruk.
Om denna utrustning används på ett sätt som inte anges av tillverkaren kan det hända att utrustningens skyddsanordningar försätts ur funktion.
LET OP: Lees dit document en de documenten die genoemd worden in de paragraaf Aanvullende informatie over de installatie, configuratie en bediening van deze apparatuur voordat u dit product installeert,
configureert, bediend of onderhoudt. Gebruikers moeten zich vertrouwd maken met de installatie en de bedradingsinstructies, naast de vereisten van alle toepasselijke regels, wetten en normen.
Activiteiten zoals het installeren, afstellen, in gebruik stellen, gebruiken, monteren, demonteren en het uitvoeren van onderhoud mogen uitsluitend worden uitgevoerd door hiervoor opgeleid personeel en in
overeenstemming met de geldende praktijkregels.
Indien de apparatuur wordt gebruikt op een wijze die niet is gespecificeerd door de fabrikant, dan bestaat het gevaar dat de beveiliging van de apparatuur niet goed werkt.
Rockwell Automation Publication 5069-IN004D-EN-P - December 2021 3
Compact 5000 Digital 16-point Sinking Input Modules Installation Instructions
ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications
(as defined in EN/IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such
environments.
This equipment is supplied as open-type equipment for indoor use. It must be mounted within an enclosure that is suitably designed for those specific
environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure
must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for
the application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain
more information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for more installation requirements.
NEMA Standard 250 and EN/IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.
North American Hazardous Location Approval
The following information applies when operating this equipment in hazardous
locations. Informations sur l’utilisation de cet équipement en environnements dangereux.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups
A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is
supplied with markings on the rating nameplate indicating the hazardous location
temperature code. When combining products within a system, the most adverse
temperature code (lowest "T" number) may be used to help determine the overall
temperature code of the system. Combinations of equipment in your system are subject
to investigation by the local Authority Having Jurisdiction at the time of installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en
environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux.
Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent
le code de température pour les environnements dangereux. Lorsque plusieurs produits
sont combinés dans un système, le code de température le plus défavorable (code de
température le plus faible) peut être utilisé pour déterminer le code de température
global du système. Les combinaisons d'équipements dans le système sont sujettes à
inspection par les autorités locales qualifiées au moment de l'installation.
WARNING:
Explosion Hazard –
Do not disconnect equipment unless power has been removed or
the area is known to be nonhazardous.
Do not disconnect connections to this equipment unless power has
been removed or the area is known to be nonhazardous. Secure any
external connections that mate to this equipment by using screws,
sliding latches, threaded connectors, or other means provided with
this product.
Substitution of components may impair suitability for Class I,
Division 2.
If this product contains batteries, they must only be changed in an
area known to be nonhazardous.
AVERTISSEMENT:
Risque d’Explosion –
Couper le courant ou s'assurer que l'environnement est classé non
dangereux avant de débrancher l'équipement.
Couper le courant ou s'assurer que l'environnement est classé non
dangereux avant de débrancher les connecteurs. Fixer tous les
connecteurs externes reliés à cet équipement à l'aide de vis,
loquets coulissants, connecteurs filetés ou autres moyens fournis
avec ce produit.
La substitution de composants peut rendre cet équipement
inadapté à une utilisation en environnement de Classe I, Division 2.
S'assurer que l'environnement est classé non dangereux avant de
changer les piles.
European Hazardous Location Approval
The following applies to products marked , II 3 G. Such modules:
Are Equipment Group II, Equipment Category 3, and comply with the Essential Health and Safety Requirements relating to the design and construction of such equipment
given in Annex II to Directive 2014/34/EU See the EC Declaration of Conformity at rok.auto/certifications for details.
The type of protection is "Ex ec IIC T4 Gc" according to EN 60079-7.
The 5069-IB16, 5069-IB16F, and 5069-IB16K modules comply to standards: EN 60079-0:2018, EN 60079-7:2015+A1:2018, reference certificate number DEMKO 15 ATEX 1484X.
Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for
short periods. Such locations correspond to Zone 2 classification according to ATEX directive 2014/34/EU.
IEC Hazardous Location Approval
The following applies to products with IECEx certification: Such modules:
Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for
short periods. Such locations correspond to Zone 2 classification to IEC 60079-0.
The type of protection is "Ex ec IIC T4 Gc" according to IEC 60079-7.
The 55069-IB16, 5069-IB16F, and 5069-IB16K modules comply to standards IEC 60079-0:7th edition, IEC-60079-7:5.1 Edition, reference IECEx certificate number IECEx UL
15.0055X.
May have catalog numbers followed by a “K” to indicate a conformal coating option.
ATTENTION:
Do not wire more than 1 conductor on any single RTB terminal.
In case of malfunction or damage, no attempts at repair should be made. The module should be returned to the manufacturer for repair. Do not dismantle
the module.
This equipment is certified for use only within the surrounding air temperature range of 0…60 °C (32…140 °F) The equipment must not be used outside of
this range.
Use only a soft dry anti-static cloth to wipe down equipment. Do not use any cleaning agents.
4Rockwell Automation Publication 5069-IN004D-EN-P - December 2021
Compact 5000 Digital 16-point Sinking Input Modules Installation Instructions
WARNING:
This equipment is not resistant to sunlight or other sources of UV radiation.
This equipment shall be mounted in an ATEX/IECEx Zone 2 certified enclosure with a minimum ingress protection rating of at least IP54 (as defined in
EN/IEC 60079-0) and used in an environment of not more than Pollution Degree 2 (as defined in EN/IEC 60664-1) when applied in Zone 2 environments. The
enclosure must be accessible only by the use of a tool.
This equipment shall be used within its specified ratings defined by Rockwell Automation.
Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140% of the rated voltage when applied in
Zone 2 environments.
The instructions in the user manual shall be observed.
This equipment must be used only with ATEX/IECEx certified Rockwell Automation backplanes.
Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this
product.
Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
Earthing is accomplished through mounting of modules on rail.
Devices shall be used in an environment of not more than Pollution Degree 2.
ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines
when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.
IMPORTANT Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for the purposes of example. Since
there are many variables and requirements associated with any particular installation, Rockwell Automation does not assume responsibility or
liability for actual use based upon the examples shown in this publication.
Rockwell Automation Publication 5069-IN004D-EN-P - December 2021 5
Compact 5000 Digital 16-point Sinking Input Modules Installation Instructions
About the Module Install a System
Based on your application design, you must install a CompactLogix 5380 controller,
CompactLogix 5480 controller, Compact GuardLogix 5380 controller, or a
Compact 5000 I/O EtherNet/IP™ adapter before you can install the module.
For more information on how to install these components, see Additional Resources on
page 11.
Required Components
To install the module, you need the following components.
Module Status indicator
I/O Status Indicator
Top Interlocking Piece
Bottom Interlocking Piece
DIN Rail Latch
RTB Handle
RTB
MOD Power Bus
and SA Power Bus
Connectors
(isolated from
each other
internally)
RTB Lower Tab
Lower hook for
use with cable tie.
Component Description
Removable terminal
blocks
One of the following RTB types.
5069-RTB18-SPRING RTB
5069-RTB18-SCREW RTB
IMPORTANT: You must order RTBs separately. RTBs do not ship with
Compact 5000 I/O modules. We recommend that you order only the
RTB type that your system requires.
End cap An end cap ships with the CompactLogix 5380 controllers,
CompactLogix 5480 controller, and Compact GuardLogix 5380
controllers and the Compact 5000 I/O EtherNet/IP adapters.
Tools
The following tools are needed:
•Screwdriver
Wire stripper
•Wires
For more information on available wire sizes and wire insulation-
stripping length, see Specifications on page 11.
6Rockwell Automation Publication 5069-IN004D-EN-P - December 2021
Compact 5000 Digital 16-point Sinking Input Modules Installation Instructions
Dimensions Ground Considerations
You must ground DIN rails according to the Industrial Automation Wiring and Grounding
Guidelines, publication 1770-4.1.
Use the EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail with Compact 5000 I/O
modules.
System Power Considerations
A CompactLogix 5380 controller, Compact GuardLogix 5380, CompactLogix 5480
controller, or Compact 5000 I/O EtherNet/IP adapter provides power to the module.
The following power types are available:
Module (MOD) power - System-side power that is required to operate the
Compact 5000 I/O modules. MOD power is provided through the MOD power
RTB and passed across the MOD power bus. A system has only one MOD power
bus.
Sensor/Actuator (SA) power - Field-side power that is used to power field-
side devices that are connected to some Compact 5000 I/O digital modules.
SA power is provided through the SA power RTB and passed across the SA
power bus.
The first component in the system, that is, the controller or the adapter,
establishes an SA power bus. A system can have multiple SA power buses.
You use 5069-FPD field potential distributors to establish a new SA power bus.
SA power buses are isolated from each other. If a system includes Compact
5000 I/O modules that use AC SA power and modules that use DC SA power,
you must install them on separate SA power buses.
To keep the modules on separate SA power buses, complete the following
steps.
a. Install the modules that use one type of SA power, for example DC, to the
right of the adapter or controller, that is, the first SA power bus.
b. Install the 5069-FPD field potential distributor to establish a second SA
power bus.
c. Install the modules that use the other type of SA power, for example AC, on
the second SA power bus.
109.09 mm (4.29 in.)
25.56 mm (1.01 in.)
144.57 mm
(5.69 in.)
105.42 mm (4.15 in.)
22 mm (0.87 in.)
ATTENTION: This product is grounded through the DIN rail to
chassis ground. Use zinc-plated chromate-passivated steel
DIN rail to assure proper grounding. The use of other DIN rail
materials (for example, aluminum or plastic) that can corrode,
oxidize, or are poor conductors, can result in improper or
intermittent grounding. Secure DIN rail to mounting surface
approximately every 200 mm (7.8 in.) and use end-anchors
appropriately. Be sure to ground the DIN rail properly. Refer to
Industrial Automation Wiring and Grounding Guidelines,
Rockwell Automation® publication 1770-4.1 for more
information.
IMPORTANT We recommend that you use separate external power
supplies for MOD power and SA power respectively.
This practice helps to prevent unintended
consequences that can result if you use one supply.
If you use separate external power supplies, the loss
of power from one external power supply does not
affect the availability of power from the other supply.
For example, if separate external power supplies are
used and SA power is lost, MOD power remains
available for the Compact 5000 I/O modules.
Rockwell Automation Publication 5069-IN004D-EN-P - December 2021 7
Compact 5000 Digital 16-point Sinking Input Modules Installation Instructions
Install the Removable Terminal Block
1. Hook the bottom of the RTB on the module.
2. Push the RTB against the module until the RTB clicks into place.
3. Push the RTB handle against the RTB until you hear another click.
Install the Module
Install the I/O module next to the right-most device in the system.
1. Confirm that MOD power and all sources of SA power are off.
If you remove the module with power applied, the system MOD power bus and
SA power bus are affected. For example, you can interrupt MOD power to the
other modules in the system. Unintended consequences can occur as a result.
2. If an end cap is installed on the right-most module that is installed in the
system, remove it and keep for later use.
3. Confirm that the DIN rail latch is closed.
4. If the DIN rail latches are open, gently push the rear latch back until the front
latch pops up and clicks.
5. Align the interlocking pieces of the module with the device on the left.
The top interlocking pieces engage first.
6. Push the module toward the DIN rail until a click indicates that the module is
locked in place.
7. Verify that the module is installed in one of the following ways:
If the module is installed next to a controller or adapter, the front of the
module is set back slightly from the front of the controller or adapter.
If the module is installed next to another I/O module, the fronts of both
modules are flush with each other.
WARNING: If you connect or disconnect the removable terminal
block (RTB) with power applied, an electric arc can occur. This
could cause an explosion in hazardous location installations.
The removable terminal block (RTB) does not support "removal
and insertion under power" (RIUP) capability. Do not connect or
disconnect the removable terminal block (RTB) while power is
applied. Be sure that power is removed before proceeding.
WARNING: If you insert or remove the module while backplane
power is on, an electric arc can occur. This could cause an
explosion in hazardous location installations.
The module does not support "removal and insertion under
power" (RIUP) capability. Do not connect or disconnect the
module while power is applied. Be sure that power is removed
before proceeding.
ATTENTION: Do not discard the end cap. Use this end
cap to cover the exposed interconnections on the last
module on the DIN rail. Failure to do so could result in
equipment damage or injury from electric shock.
Open PositionClosed Position
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Top
Interlocking
Pieces
Bottom
Interlocking
Piece
8Rockwell Automation Publication 5069-IN004D-EN-P - December 2021
Compact 5000 Digital 16-point Sinking Input Modules Installation Instructions
Install the End Cap
You must install an end cap on the last module in your system.
1. Align the end cap with the interlocking pieces on the module.
2. Push the end cap toward the DIN rail until it locks in place.
Wire the Removable Terminal Block
1. Confirm that MOD power and all sources of SA power are turned off.
2. Strip insulation from the wires that you connect to the RTB.
3. Connect the wire to the terminal.
Disconnect Wires from the Removable
Terminal Block
Disconnect wires from the RTB.
IMPORTANT You install the end cap after the last module is installed on
the DIN rail. This design helps to prevent the end cap from
going beyond the locked position.
If you push the end cap beyond the locked position or
insert it from the backwards direction, you can damage the
MOD power bus and SA power bus connector.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Interlocking
Pieces
End Cap
End Cap
WARNING: If you connect or disconnect wiring while power is
applied, an electric arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is removed or
the area is nonhazardous before proceeding.
RTB Type Action
Screw Strip12 mm (0.47 in.) of insulation from the wires.
Spring Strip 10 mm (0.39 in.) of insulation from the wires.
RTB Type Action
Screw 1. Insert the wire into the terminal.
2. Turn the screwdriver to close the terminal on the wire. Torque the screw to
0.4 N•m (3.5 lb•in).
Spring Push the wire into the terminal.
If the wire is too thin, crimp a wire ferrule on the wire and insert it.
WARNING: If you connect or disconnect wiring while power is
applied, an electric arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is removed or
the area is nonhazardous before proceeding.
RTB Type Action
Screw 1. Turn the screwdriver counter-clockwise to open the terminal.
2. Remove the wire.
Spring 1. Insert and hold a screwdriver in the right-side terminal.
2. Remove the wire.
3. Pull out the screwdriver.
5069-RTB18-SPRING RTB5069-RTB18-SCREW RTB
Rockwell Automation Publication 5069-IN004D-EN-P - December 2021 9
Compact 5000 Digital 16-point Sinking Input Modules Installation Instructions
Wiring Diagram
The following example wiring diagram applies to the 5069-IB16, 5069-IB16F, and 5069-IB16K digital input modules.
Input Channel 0 (I00)
Input Channel 1 (I01)
Input Channel 2 (I02)
Input Channel 3 (I03)
Input Channel 4 (I04)
Input Channel 5 (I05)
Input Channel 6 (I06)
Input Channel 7 (I07)
Input Channel 8 (I08)
Input Channel 9 (I09)
Input Channel 10 (I10)
Input Channel 11 (I11)
Input Channel 12 (I12)
Input Channel 13 (I13)
Input Channel 14 (I14)
Input Channel 15 (I15)
No Connect
No Connect
DC (+)
2-wire
Sensor
3-wire
Sensor
DC (–)
Channel Connections
The diagram shows devices that are connected to channels 0,
3, and 6. You are not restricted to use only those channels.
You can connect devices to any channel or combination of
channels as needed.
SA Power
Connections to an external power supply that provides SA
power via the SA Power RTB on one of the following:
CompactLogix 5380 controller
5069-AENTR or 5069-AEN2TR EtherNet/IP Adapter
5069-FPD field potential distributor
IMPORTANT: Remember the following:
The 5069-IB16 and 5069-IB16F module inputs use a shared
common. The inputs have a return through internal module
circuitry to the SA (–) terminal on the SA Power RTB. For
more information, see page 6.
If you install modules in a Compact 5000 I/O system that
use AC SA power and DC SA power, you must install them
on separate SA power buses.
You use the 5069-FPD field potential distributor to establish a
new SA power bus in a Compact 5000 I/O system. SA power
buses are isolated from each other. To keep the modules on
separate SA power buses, complete the following steps.
1. Install the modules that use one type of SA power, for
example AC, to the right of the adapter or controller, that is,
the first SA power bus.
2. Install the 5069-FPD field potential distributor to establish a
second SA power bus.
3. Install the modules that use the other type of SA power, for
example DC, on the second SA power bus.
10 Rockwell Automation Publication 5069-IN004D-EN-P - December 2021
Compact 5000 Digital 16-point Sinking Input Modules Installation Instructions
Use a Cable Tie
After you connect the required wires to the RTB, you can use a cable tie to bundle the
wires. There is a lower hook at the bottom of the module that you use to secure the tied
bundle to the module.
1. Make sure that you have a cable tie long enough to contain the wires that are
connected to the module. The maximum width of the cable tie is 4.5 mm
(0.18 in).
2. Gather the wires at the bottom of the module.
3. Thread the cable tie through the lower hook at the bottom of the RTB.
4. Wrap the cable tie around the wires and secure it.
Power the System
After you install all Compact 5000 I/O modules, you can turn on MOD power and, if
used, SA power to the system.
For more information on MOD power and SA power, see System Power Considerations
on page 6.
Remove the Module
1. Confirm that MOD power and all sources of SA power are turned off.
2. If necessary, remove the end cap from the module.
3. If desired, disconnect wires from the RTB as described on page 8.
4. Press the DIN rail latch down until it clicks and let go.
5. Pull the module off the DIN rail.
6. To replace the module, follow the steps that are described beginning at Install
the Module on page 7.
ATTENTION: Do not remove or replace the module while
power is applied. Interruption of the backplane can result in
unintentional operation or machine motion.
IMPORTANT Before you remove MOD power and, if used, SA
power, consider the effect on your system.
When you remove MOD power from the controller
or adapter, you shut down power to all modules in
the system. That is, all system-side is removed.
When you remove SA power from the controller,
adapter or a field potential distributor, all field-
side power that is provided by that component is
removed.
We strongly recommend that you take the
appropriate actions to help prevent unintended
consequences that can result from a system
power shutdown before removing MOD power or
SA power.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Rockwell Automation Publication 5069-IN004D-EN-P - December 2021 11
Compact 5000 Digital 16-point Sinking Input Modules Installation Instructions
Specifications
For a list of all specifications, see the Compact 5000 I/O Modules and EtherNet/IP Adapters Technical Data, publication 5069-TD001.
Additional Resources
You can view or download publications at rok.auto/literature. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation
sales representative.
Attribute 5069-IB16, 5069-IB16F, 5069-IB16K
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max 60 °C (140 °F)
Enclosure type rating None (open-style)
Voltage and current ratings
Input ratings 4…7.4 mA per channel @ 10…32V DC
MOD Power 75 mA @ 18…32V DC
MOD Power Passthrough(1) 9.55 A @ 1832V DC
SA Power 200 mA @ 10…32V DC
SA Power Passthrough(2) 9.95 A @ 1032V DC
Do not exceed 10 A MOD or SA Power (Passthrough) current draw.
Isolation voltage 250V (continuous), Basic Insulation Type
No isolation between SA power and input ports
No isolation between individual input ports
Wire size
5069-RTB18-SCREW connections 0.5…1.5 mm2 (22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 3.5 mm
(0.14 in.) max diameter including insulation, single wire connection only.
5069-RTB18-SPRING connections 0.5…1.5 mm2 (22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 2.9 mm
(0.11 in.) max diameter including insulation, single wire connection only.
Insulation stripping length
5069-RTB18-SCREW connections 12 mm (0.47 in.)
5069-RTB18-SPRING connections 10 mm (0.39 in.)
RTB torque specifications (5069-RTB18-SCREW RTB only) 0.4 N·m (3.5 lb·in)
DIN rail Compatible zinc-plated, yellow-chromate steel DIN rail. You can use the following DIN rail sizes:
EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.)
EN50022 - 35 x 15 mm (1.38 x 0.59 in.)
North American Temp Code T4
ATEX Temp Code T4
IECEx Temp Code T4
(1) Maximum level of MOD Power current that the module can pass through to the next module in the system. The specific level of current passed through varies based on system configuration.
(2) Maximum level of SA Power current that the module can pass through to the next module in the system. The specific level of current passed through varies based on system configuration.
Resource Description
Compact 5000 I/O Modules and EtherNet/IP Adapters Technical Data, publication
5069-TD001 Provides specifications for Compact 5000 I/O modules and EtherNet/IP adapters.
Compact 5000 I/O Digital Modules User Manual, publication 5069-UM004 Describes how to use the Compact 5000 I/O standard and safety digital modules.
Compact 5000 EtherNet/IP Adapters User Manual, publication 5069-UM007 Describes how to use Compact 5000 EtherNet/IP adapters.
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual,
publication 5069-UM001 Describes how to use CompactLogix 5380 and Compact GuardLogix 5380 controllers.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation® industrial system.
Product Certifications website, rok.auto/certifications Provides declarations of conformity, certificates, and other certification details.
Rockwell Automation Support
Use these resources to access support information.
Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback.
Technical Support Center Find help with how-to videos, FAQs, chat, user forums, and product notification updates. rok.auto/support
Knowledgebase Access Knowledgebase articles. rok.auto/knowledgebase
Local Technical Support Phone Numbers Locate the telephone number for your country. rok.auto/phonesupport
Literature Library Find installation instructions, manuals, brochures, and technical data publications. rok.auto/literature
Product Compatibility and Download Center (PCDC) Download firmware, associated files (such as AOP, EDS, and DTM), and access product release notes. rok.auto/pcdc
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur
PN-648439
Allen-Bradley, Compact 5000, CompactLogix, GuardLogix, Rockwell Automation, Rockwell Software, RSLinx, and Studio 5000 Logix Designer are trademarks of Rockwell Automation, Inc.
EtherNet/IP is a trademark of ODVA, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 5069-IN004D-EN-P - December 2021 | Supersedes Publication 5069-IN004C-EN-P - October 2018
Copyright © 2021 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback.
For technical support, visit rok.auto/support.
Waste Electrical and Electronic Equipment (WEEE)
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
At the end of life, this equipment should be collected separately from any unsorted municipal waste.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Allen Bradley Allen-Bradley 5069-IB16 Compact 5000 Digital 16-point Sinking Input Modules Manuel utilisateur

Taper
Manuel utilisateur