Intermatic T30000R SERIES Installation, Operation & Service Manual

Taper
Installation, Operation & Service Manual
T30000R SERIES
POOL/SPA EQUIPMENT CONTROLS
INSTALLATION
OPERATION &
SERVICE MANUAL
C
C
O
O
N
N
T
T
R
R
O
O
L
L
P
P
A
A
N
N
E
E
L
L
W
W
I
I
T
T
H
H
T
T
I
I
M
M
E
E
S
S
W
W
I
I
T
T
C
C
H
H
F
F
O
O
R
R
I
I
N
N
D
D
O
O
O
O
R
R
/
/
O
O
U
U
T
T
D
D
O
O
O
O
R
R
U
U
S
S
E
E
Suitable for Pool Equipment Control and for Direct Connection of Underwater Lights
ELECTRICAL RATINGS: See inside Enclosure Door
Many of toda
y’s energy efficient pools and spas
utilize the advantages of a single electrical panel,
containing all the necessary controls for the safe,
efficient and automatic operation of the pool/spa
equipment. In addition, this Panel can also be
used to control any outdoor equipment, sign or
pump within its rated capacity.
The all-weather enclosure contains none one or
two heavy-duty, industrial grade Time Switches.
Also,
it has provisions to install switches or a
GFCI receptacle on the side as well as the inside.
The Time Switch can also accommodate an
optional heater control (fireman) switch.
The Control is designed to operate any pump,
within its rated capacity. However, if protection
to prevent dry start is required by the pump
manufacturer, it must be provided in addition
to this Control. Contact pump manufactur
er
if not sure and/or for more details.
1
DANGER! TO AVOID RISK OF INJURY:
...do not permit children to operate the Control Unit or use the Pool/Spa unless they are closely supervised at all times.
...test GROUND FAULT protection regularly. If it fails to reset, DO NOT USE THE POOL or SPA!
Contact a qualified service technician.
...always disconnect electricity before servicing this control or the equipment connected to it.
READ, FOLLOW AND SAVE THIS INSTRUCTION MANUAL
GENERAL INFORMATION
Because of our commitment to continuing research and improvements, Intermatic Incorporated reserves the right to make changes, without notice, in the specifications and material
contained herein and shall not be responsible for any damages, direct or consequential, caused by reliance on the material presented.
I
I
N
N
T
T
E
E
R
R
M
M
A
A
T
T
I
I
C
C
I
I
N
N
C
C
O
O
R
R
P
P
O
O
R
R
A
A
T
T
E
E
D
D
,
,
SPRING GROVE, IL 60081-9698
http://www.intermatic.com
158TP10425
4
WARRANTY
If within one (1) year from the date of installation, this product fails due to a defect in material or workmanship, Intermatic Incorporated
will repair or replace it free of charge.
The warranty does not cover labor for removal or reinstallation and does not apply to: (a) damage caused by accident, abuse, mishan-
dling, or dropping; (b) a unit which has been subject to unauthorized repair; (c) units not used in accordance with directions; (d) damages
exceeding the cost of the product. Some states do not allow a limitation of damages so the foregoing warranty may not apply to you. This
warranty gives you specific legal rights and you may also have other rights which vary from state to state.
This warranty service is available, if the defective product or its defective component is returned with proof of purchase and date of
installation, either (a) to the dealer from whom the unit was pur
chased or (b) by shipping prepaid to the Intermatic Incorporated/After Sales
Service, 7777 Winn Rd., Spring Grove, IL 60081-9698/815-675-7000 http://www.intermatic.com
WIRING DIAGRAM
Typical 120 Volt Installation Typical 240 Volt Installation
Filter and Cleaner Timer Inter-Connections
NOTES:
1. Grounding connections are not shown but must be provided. Refer to the National Electrical Code for details.
2. Diagrams above are only two of the many variations this Panel can accommodate.
http://waterheatertimer.org/Intermatic-control-centers-and-manuals.html#30000R
INSTALLATION
OPERATION
TROUBLESHOOTING
1. Remove the four #10 hex head screws from the
back of the enclosure and attach mounting brackets
to enclosure.
2. Select the proper location for the Control and hang
enclosure on a flat vertical surface or other support,
using hardware suitable for the purpose.
3. Prepare the necessary conduit runs, terminate them
at both ends and pull in the conductors as specif
ied
by the installation layout.
4. Refer to Figure 1 below;
note that this enclosure
contains one or two Time
Switch(es). To wire the
panel, follow the wiring diagram located inside the
enclosure door
. Make sure that connections to time
switc
h terminals are tight (25 lb
.-in. minimum) and
insulation clears the pressure plate - see illustration.
5. If required by the heater manufacturer, install
fireman switch kit 156T4042A (not furnished)
on
Time Switch Plate and make the fireman switch
connections. Use at least #18 AWG wiring with
insulation rated 300 Volt or higher. Place heater
ON/OFF switch on heater to
ON (see Figure 2).
Some heaters may require a special connecting
har
ness,
contact hea
ter manufacturer
for details.
6. F
or dir
ect wir
ing of underw
ater lights, refer to
1999 NEC 680-21(b), 2002 NEC 680-24(b) or
CEC 680-060,
062 and 066 f
or fur
ther details.
7. T
o install ad
ditional wir
ing de
vices inside the
enclosure, first remove rectangular knock-out(s) in
dead front. Next, remove hex head screws in back
of enclosure and install stand-offs* in place of
screws. Attach wiring device to stand-offs.
Stand-offs are not furnished. Order 21T156A for
a set of four (4) stand-offs and mounting hardware.
8. If external bonding is required, install a bonding
lug at bottom of enclosure and bond installation
according to code requirements.
9. Testing of the installation is optional and recom-
mended only if pump is securely in place and will
not be damaged by this test:
a. Turn the manual lever of the Time Switch to OFF.
b. Turn ON power at breaker panel.
c. Move the manual lever of Time Switch to the
right (ON). Pump should star
t and run on full speed
.
In case of unsa
tisf
actory results, turn OFF power,
check your wiring, refer to Troubleshooting on Page 3.
10.Install fr
ont panel o
ver wiring compar
tment.
The contr
ol is now ready for programming,
see OPERATION section on Page 3.
TO SET FILTER PUMP TIME SWITCH, follow
instructions on the right. The length of the daily filtration/
heating cycle depends on many variables such as size, shape,
geographic location of the pool, water chemistry, type of
pool equipment, usage and season of year. If not sure,
contact your local pool service professional for advice.
THE FIREMAN SWITCH (Heater Protection Mechanism),
if required, is factory set and shuts OFF the heater 20
minutes before the Time Switch turns OFF the filter pump.
The Fireman Switch requires no setting or service.
SYMPTOM
1. Time Switch will not keep
time but dial is turning.
2. Time Switch Dial stops
at ON or OFF tripper.
3. Dial stops after switc
h
turns OFF.
4. Load is ON at all times -
dial is turning.
5. Dead clock motor. (Clock
motor gears do not rotate).
CAUSE(S)
1a.Frequent power outages
1b.Wrong voltage/cycle
1c.Loose clock motor connections
2a.Loose tripper
2b.Bent dial
2c.Defective motor
3a.LINE leads are connected
to LOAD terminals
4a.Welded contacts
4b.Two ON trippers and
no OFF tripper on dial
4c.Defective mechanism
5a.Defective clock motor
(open coil due to lightning or surge)
5b.Loose clock motor connections
5c.Wrong voltage
CORRECTIVE ACTION
Reset dial
Change clock motor
Check connections
Check/change tripper
Check/change mechanism
Change clock motor
Rever
se LINE and LOAD
connections
Change mechanism
Change tripper
Change mechanism
Change clock motor
Check connections
Change clock motor
2 3
IMPORTANT SAFETY INSTRUCTIONS
W
hen installing and operating this Product and other associated equipment, basic safety precautions should always be followed,
including the following:
1. Read and follow all instructions.
2. This Control must be installed by a qualified electrician, according to National and Local Electrical Codes.
3. Install this control not less than 5 feet (3 meters in Canada) from inside edge of pool. USE COPPER CONDUCTORS ONLY.
4. Do not exceed the maximum ratings of individual components, wiring devices, and current carrying capacity of conductors.
5. For Control grounding, bonding, installing and the wiring of underwater lights, refer to Article 680 of the National Electrical
Code or Article 68 of the Canadian Electrical Code.
6
. The Control should not operate any equipment which would cause bodily injury or property damage should it be activated unexpectedly.
READ, FOLLOW AND SAVE THIS INSTRUCTION MANUAL
TIME SWITCH OPERATING
INSTRUCTIONS
1. TO SET "ON" AND
"
OFF" TIMES:
H
old
T
RIPPERS against edge of
CLOCK-DIAL, pointing
to time (AM or PM) when
ON and OFF operations
are desired. Tighten tripper
screws firmly.
2. TO SET TIME-OF-DAY:
P
ull CLOCK-DIAL outward. Turn in either direction
and align the exact time-of-day on the CLOCK-
DIAL (the time now, when switch is being put into
operation) to the pointer.
TO OPERATE SWITCH MANUALLY: Move
MANUAL LEVER below CLOCK-DIAL left or
right as indicated by arrows. This will not affect
the next operation.
FOR MORE THAN ONE DAILY ON-OFF
OPERATION:
Place additional tripper pairs on
CLOCK-DIAL (order 156T1978A).
IN CASE OF POWER FAILURE: Reset CLOCK-
DIAL to proper time of day. See step 2 above.
Figure 2
Figure 1
www.intermatic.com
Pool & Spa Controls
T30000R5
T30004R
T32404R
T30000R Series
100 Amp Pool/Spa Control Panels
The T30000R Series Control Panels reduce installation costs and provide all of
ÌiÊiiVÌÀV>ÊÀiµÕÀiiÌÃÊvÀÊ>ÞÊ«Ê>`ÉÀÊë>ÊÃÌ>>Ì°Ê/iÞÊvviÀÊ>Ê>
in-one electrical control center which can be custom wired for a wide variety of
ÀiµÕÀiiÌÃ>i>ÌiÊÌiÊii`ÊvÀÊ>``Ì>ÊÕVÌÊLÝiÃÊ>ÃÛViÊ
panels. The enclosure accepts any combination of P1353ME or P4243ME or T100M or
RC2000M or PF1000M Series mechanisms.
Applications:
UÊÌiÀÊ*Õ«ÃÊÊ UÊÃÌiÀÊ*Õ«ÃÊ UÊi>Ì-ÞÃÌiÃÊ UÊ}ÌÃ
UÊi>-ÞÃÌiÃÊ UÊ-iVÕÀÌÞÊ-ÞÃÌiÃÊ UÊÕÌ>ÃÊÊ UÊ-«ÀiÀÊÃÌiÃ
UÊ>`ÃV>«ÀÊÊ}Ì}
Specifications:
Enclosure: 0.048 in. steel with electrostatically applied beige finish
16
1
2
in. (41.9 cm) H x 10
7
8
in. (27.6 cm) W x 4
1
4
in. (10.8 cm) D
Knockouts: Two
1
2
in., three combination
1
2
3
4
in., and two combination
3
4
1 in.
knockouts on the bottom. Four
1
2
in., three combination
1
2
3
4
in. on the back. One
combination
3
4
1 in. on the left side. One 1
3
4
x 2
3
4
in. knockout on the right side for
mounting switches and GFCI
Panel Rating: 100 Amp, 120, 240 VAC or 120, 208 VAC single phase, 60 Hz.
Time Switch Rating: 30 Amp Resistive/Inductive, Tungsten or 1000 VA Pilot Duty
each pole, 120, 208, 240 VAC; 2 HP (24 FLA), 120 VAC; 5 HP (28 FLA), 240 VAC
Shipping Weight: See table
Agency Approval: CSA/C-US
Description/ Clock Supply Shipping
Model # Mechanism Switch Volts AC, 60 Hz Weight
T30000R5 Enclosure Only None NA/NA 15.5 lbs (7.0 kg)
T30004R One T104M None/DPST NA/240 16.4 lbs (7.4 kg)
T30401R T104M & T101M DPST/SPST 240/120 17.3 lbs (7.8 kg)
T30404R Two T104M DPST/DPST 240/240 17.3 lbs (7.8 kg)
T30604R T106M & T104M SPDT/DPST 240/240 17.3 lbs (7.8 kg)
T32404R* T104M201 & T104M DPST/DPST 240/240 17.3 lbs (7.8 kg)
* The heater protection switch (fireman switch) is closed when the time switch
contacts are open to allow remote operation of the heater. A flow or pressure
switch must always be part of the heater control circuit.
For additional trippers ( 1 ON 1 OFF per pack), order No. 156T1978A.
For additional OFF trippers (25 OFF per pack), order No. PA115.
For stand-offs for décor knockouts (4 stand-offs per pack), order No. 21T156A.
Note: See page 130 for a detailed list of replacement mechanisms.
Mechanical Controls
134
  • Page 1 1
  • Page 2 2
  • Page 3 3

Intermatic T30000R SERIES Installation, Operation & Service Manual

Taper
Installation, Operation & Service Manual

dans d''autres langues