Tripp Lite MODBUSCARDSV Mode d'emploi

Taper
Mode d'emploi

Ce manuel convient également à

Operation Manual
Programmable MODBUS Card
for SV, SVX, S3MX 100-200K
3-Phase UPS Systems
1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support
Copyright © 2019 Tripp Lite. All rights reserved.
Operation 2
1. Warning Item 2
2. Capability Setting 3
3. Control Item 3
4. Control Result 4
5. Setting Parameter to Default Value 4
6. UPS Working Status 5
7. UPS Battery Information 5
8. Temperature Inquiry 5
9. 3-Phase Load Inquiry 6
10. 3-Phase Bypass Info 6
11. Output Power Factor Inquiry 6
12. Load Level Inquiry 6
13. UPS Working Mode 6
14. UPS Fault Information 7
15. Loss Point 7
16. Setting Parameter Item 8
17. Setting Parameter Succeed or Fail 8
18. Remote Shutdown and Test 8
19. CPU Information 9
20. UPS Model and Rating Information 9
21. Parallel Inquiry 10
22. Date Inquiry 10
(Sys or Rack Info Inquiry Address)
23. Set Date 10
(Sys or Rack Info Inquiry Address)
Appendix 1 11
Appendix 2 11
Appendix 3 12
Español 13 • Français 25 • Русский 37
2
1. Warning Item
Holding Register (Range 0x0000 - 0x0001, Read Function 0x03)
The Read Holding Registers function code is used to read contents of a contiguous block of Holding Registers in a remote
device. Starting register address and number of registers is specified by the request Protocol Data Unit. Addresses start at 0
and registers numbered 1-16 address as 0-15.
The Write Single Register function code is used to write a Single Holding Register in a remote device. The address of the register
to be written is specified by the request Protocol Data Unit. Addresses start at 0 and registers numbered 1 address as 0.
Address
Description Value 0/Value 1Hex Decimal
0x0000 0
Bit15 = EPO is Active 0:FALSE/1:TRUE
Bit14 = Load is over load level and reach countdown delay 0:FALSE/1:TRUE
Bit12 = Load level is over Overload Alarm Level 0:FALSE/1:TRUE
Bit11 = Battery is not connected
(battery voltage is less than 9V)
0:FALSE/1:TRUE
Bit10 = Battery is over 15V 0:FALSE/1:TRUE
Bit8 = Including: EPO is active, Maintain Bypass is active, DC start, but DC start setting
is disabled
Line Status is not OK (Voltage or Frequency is out of range, Phase sequence is not
correct, Neutral Loss)
SYNCHRO signal is abnormal
TRIG0 signal is abnormal
0:FALSE/1:TRUE
Bit7 = Charger is abnormal 0:FALSE/1:TRUE
Bit6 = Checksum value of EEPROM Data saved in MCU
is not correct
0:FALSE/1:TRUE
Bit5 = Fan locked 0:FALSE/1:TRUE
Bit4 = Line Phase sequence is not correct 0:FALSE/1:TRUE
Bit3 = Bypass Phase sequence is not correct 0:FALSE/1:TRUE
Bit2 = Neutral is absent 0:FALSE/1:TRUE
Bit1 = Initial communication between DSP and MCU is abnormal 0:FALSE/1:TRUE
Bit0 = SYNCHRO signal is abnormal 0:FALSE/1:TRUE
0x0001 1
Bit15 = TRIG0 signal is abnormal 0:FALSE/1:TRUE
Bit14 = Power Module number is not consistent with setting 0:FALSE/1:TRUE
Bit13 = No STS in system 0:FALSE/1:TRUE
Bit12 = Maintain Bypass is active 0:FALSE/1:TRUE
Bit11-Bit0 = Reservation N/A
Operation
3
Operation
2. Capability Setting
Holding Register (Range 0x000E - 0x000F, Read Function 0x03, Write Function 0x10)
Addresses start at 0 and are numbered 1-16 address as 0-15.
The Write function writes to ENABLE/DISABLE in a remote device. A specified constant in the data field requests the ENABLE/
DISABLE state.
Address
Description Value 0/Value 1 Register ValueHex Decimal
0x000E 14
Bit15 = Enable/disable audible alarm 0:FALSE/1:TRUE E:8000 / D:7FFF
Bit10 = Enable/disable auto-Restart 0:FALSE/1:TRUE E:4000 / D:BFFF
Bit7 = Enable/disable code start 0:FALSE/1:TRUE E:200 / D:FDFF
Bit6 = Enable/disable bypass forbidding 0:FALSE/1:TRUE E:100 / D:FEFF
Bit3 = Enable/disable bypass when device turn off 0:FALSE/1:TRUE E:40 / D:FFBF
Bit1 = Enable/disable high efficiency mode 0:FALSE/1:TRUE E:10 / D:FFEF
0x000F 15
Bit15-Bit 13 = Reservation N/A E:8 / D:FFF7
Bit12 = Enable/disable converter mode 0:FALSE/1:TRUE E:4 / D:FFFB
Bit11-Bit8 = Reservation N/A E:2 / D:FFFD
Bit7 = Enable/disable period self test Z 0:FALSE/1:TRUE E:1000 / D:EFFF
Bit0-Bit5 = Reservation N/A N/A
3. Control Item
Holding Register (Read Function 0x03, Write Function 0x10)
Addresses start at 0 and are numbered 1-16 address as 0-15.
The Write function writes to ENABLE/DISABLE in a remote device. A specified constant in the data field requests the ENABLE/
DISABLE state.
Address
Description Value 0/Value 1 Alarm DescriptionHex Decimal
0x001A 26
Bit15 = Silence buzzer beep (audible alarm) 0:FALSE/1:TRUE Y:8000
Bit14 = buzzer beep open (audible alarm) 0:FALSE/1:TRUE Y:4000
Bit13 = Test until battery low 0:FALSE/1:TRUE Y:2000
Bit12 = Remote turn off UPS 0:FALSE/1:TRUE Y:1000
Bit11 = Remote turn on UPS 0:FALSE/1:TRUE Y:800
Bit10 = Cancel shutdown 0:FALSE/1:TRUE Y:400
Bit9 = Cancel test 0:FALSE/1:TRUE Y:200
Bit8 = 10 second test 0:FALSE/1:TRUE Y:100
Bit3-Bit 0 = Reservation N/A N/A
0x001B 27
Bit5-Bit 11 = Reservation N/A N/A
Bit10 = UPS turn to bypass 0:FALSE/1:TRUE Y:0400
0x0422 1058
Bit15 = EPO function open 0:FALSE/1:TRUE Y:8000
Bit14 = EPO function close 0:FALSE/1:TRUE Y:4000
Bit13 = Mode output frequency 50 Hz 0:FALSE/1:TRUE Y:2000
Bit12 = Mode output frequency 60 Hz 0:FALSE/1:TRUE Y:1000
Bit11 = Charger On 0:FALSE/1:TRUE Y:0800
Bit10 = Charger Off 0:FALSE/1:TRUE Y:0400
Bit9 = Enable independent battery 0:FALSE/1:TRUE Y:0200
Bit8 = Disable independent battery 0:FALSE/1:TRUE Y:0100
4
Operation
4. Control Result
Holding Register (Read Function 0x03)
Addresses start at 0 and are numbered 1-16 address as 0-15.
Address
Description Value 0/Value 1Hex Decimal
0x0025 37
Bit15 = Flag:Silence buzzer beep (Audible Alarm) 0:FAIL/1:SUCCESS
Bit14 = Flag:buzzer beep open (Audible Alarm) 0:FAIL/1:SUCCESS
Bit13 = Flag:Test until battery low 0:FAIL/1:SUCCESS
Bit12 = Flag:Remote turn off UPS 0:FAIL/1:SUCCESS
Bit11 = Flag:Remote turn on UPS 0:FAIL/1:SUCCESS
Bit10 = Flag:Cancel shutdown 0:FAIL/1:SUCCESS
Bit9 = Flag:Cancel test 0:FAIL/1:SUCCESS
Bit8 = Flag:10 seconds test 0:FAIL/1:SUCCESS
Bit7 = Reservation N/A
Bit6 = Reservation N/A
Bit5 = Reservation N/A
Bit4 = Reservation N/A
Bit3-Bit0 = Reservation N/A
0x0026 38
Bit10 = UPS turn to bypass 0:FAIL/1:SUCCESS
Bit9-Bit0 = Reservation N/A
0x0423 1059
Bit15 = EPO function in normal open 0:FAIL/1:SUCCESS
Bit14 = EPO function in normal close 0:FAIL/1:SUCCESS
Bit13 = Mode output frequency 50 Hz 0:FAIL/1:SUCCESS
Bit12 = Mode output frequency 60 Hz 0:FAIL/1:SUCCESS
Bit11 = Charger On 0:FAIL/1:SUCCESS
Bit10 = Charger Off 0:FAIL/1:SUCCESS
Bit9 = Enable independent battery 0:FAIL/1:SUCCESS
Bit8 = Disable independent battery 0:FAIL/1:SUCCESS
5. Setting Parameter to Default Value
Holding Register (Read Function 0x03, Write Function 0x10)
The Write function writes to ENABLE/DISABLE in a remote device. A specified constant in the data field requests the ENABLE/
DISABLE state.
Address
Description Value 0/Value 1 TypeHex Decimal
0x0030 48
Bit15 = Setting control parameter to default value Y:8000 Read / Write
Bit14-Bit0 = Reservation N/A N/A
0x003B 59
Bit15 = Flag:Setting control parameter to default value 0:FAIL/1:SUCCESS Read Only
Bit14-Bit0 = Reservation N/A N/A
5
Operation
6. UPS Working Status
Holding Register (Read Function 0x03)
Address
Description UnitHex Decimal
0x031E 798 R-Input voltage 0.1V
0x031F 799 S-Input voltage 0.1V
0x0320 800 T-Input voltage 0.1V
0x0321 801 Input frequency 0.1 Hz
0x0322 802 R-Output voltage 0.1V
0x0323 803 S-Output voltage 0.1V
0x0324 804 T-Output voltage 0.1V
0x0325 805 Output frequency 0.1 Hz
0x0326 806 R-Output current 0.1A
0x0327 807 S-Output current 0.1A
0x0328 808 T-Output current 0.1A
0x0329 809 R-Output load percent 1%
0x032A 810 S-Output load percent 1%
0x032B 811 T-Output load percent 1%
0x032C 812 P Battery voltage 0.1V
0x032D 813 N Battery voltage 0.1V
0x032E 814 Max Temperature of the detecting pointers 0.1C
0x032F 815 See Appendix 1 See Appendix 1
7. UPS Battery Information
Holding Register (Read Function 0x03)
Address
Description UnitHex Decimal
0x00BC 188 P-Battery voltage 0.1V
0x00BD 189 P-Battery piece number
0x00BF 191 P-Battery capacity %
0x00C0 192 P-Battery remain time Minutes
0x00C1 193 N-Battery voltage 0.1V
0x00C2 194 N-Battery piece number
0x00C4 196 N-Battery capacity %
0x00C5 197 N-Battery remain time Minutes
0x0318 792 P-Battery charge current 0.01A
0x0319 793 N-Battery charge current 0.01A
0x0307 775 The battery Total Ah information Inquiry Ah
0x0308 776 EPO status QREPO
8000 : Open
7FFF : Close
8. Temperature Inquiry
Holding Register (Read Function 0x03)
Address
Description UnitHex Decimal
0x00CC 204 Temperature1 0.1°C
0x00CD 205 Temperature2 0.1°C
0x00CE 206 Temperature3 0.1°C
0x00CF 207 Temperature4 0.1°C
6
Operation
9. 3-Phase Load Inquiry
Holding Register (Read Function 0x03)
Address
Description UnitHex Decimal
0x00DD 221 R-Phase of load %
0x00FC 252 S-Phase of load %
0x00FD 253 T-Phase of load %
0x00FE 254 The whole load %
10. 3-Phase Bypass Info
Holding Register (Read Function 0x03)
Address
Description Unit
Hex Decimal
0x011A 282 R-Voltage of bypass 0.1V
0x011B 283 S-Voltage of bypass 0.1V
0x011C 284 T-Voltage of bypass 0.1V
0x011D 285 R-Current of bypass 0.1A
0x011E
286 S-Current of bypass 0.1A
0x011F 287 T-Current of bypass 0.1A
0x0123 291 Bypass frequency 0.1 Hz
11. Output Power Factor Inquiry
Holding Register (Read Function 0x03)
Address
Description UnitHex Decimal
0x030F 783 R-Output power factor 0.001
0x0310 784 S-Output power factor 0.001
0x0311 785 T-Output power factor 0.001
12. Load Level Inquiry
Holding Register (Read Function 0x03)
Address
Description UnitHex Decimal
0x0312 786 R-Watt percent %
0x0313 787 S-Watt percent %
0x0314 788 T-Watt percent %
0x0315 789 R-VA percent %
0x0316 790 S-VA percent %
0x0317 791 T-VA percent %
13. UPS Working Mode
Holding Register (Read Function 0x03)
Address
Description UnitHex Decimal
0x00D0 208 UPS Mode inquiry See Appendix 2
7
Operation
14. UPS Fault Information
Holding Register (Read Function 0x03)
Address
Description Unit Example ResponseHex Decimal
0x02A3 675 Fault kind ASCII 00:no fault default:FF See Appendix 3
0x3030 (Not Fault)
0x4646 (Fault)
0x02E5 - 0x02EC 741 - 748 Fault kind1 ASCII module ID : 01-07 See Appendix 3
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x03B0 - 0x03CB 944 - 971 Fault kind1 ASCII module ID : 08-35 See Appendix 3
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x3031
0x3132
0x0000
0x0000
0x3336
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
15. Loss Point
Holding Register (Read Function 0x03)
Address
Description UnitHex Decimal
0x034A 842 High efficiency mode Voltage high loss point V
0x034B 843 High efficiency mode Voltage low loss point V
0x034C 844 Free run mode frequency high loss point 0.1 Hz
0x034D 845 Free run mode frequency low loss point 0.1 Hz
0x034E 846 Bypass Freq. high loss point 0.1 Hz
0x034F 847 Bypass Freq. low loss point 0.1 Hz
0x0350 848 Bypass Voltage high loss point V
0x0351 849 Bypass Voltage low loss point V
8
Operation
16. Setting Parameter Item
Holding Register (Read Function 0x03, Write Function 0x10)
Address
Description Unit Sample Values TypeHex Decimal
0x02ED 749 Setting the battery shut down delay time Second 10 Read / Write
0x02EE 750 Battery Cut-off minimum voltage per cell 0.01V 166 Read Only
0x02EF 751 Cut off voltage per PCS ( ! ! ! ) BATCO (10.00~11.00) 0.01V 1000 Read / Write
0x02f0 752 Battery low voltage per PCS 0.01V 1100 Read / Write
0x02f1 753 Battery low capacity (%) % 20 Read / Write
0x02f3 755 Self-test inquiry period Day 0 Read / Write
0x0309 777 Bat test stop time S 10 Read / Write
0x030A 778 Bat test stop capacity % 20 Read / Write
0x030B 779 Bat test stop voltage 0.01V/PCS 1100 Read / Write
0x0424 1060 Setting battery Total Ah Ah 9 Read / Write
0x05ED 1457 Setting charging current 02 to 64 10 Read / Write
17. Setting Parameter Succeed or Fail
Holding Register (Read Function 0x03)
Address
Description Value 0/Value 1Hex Decimal
0x0384 900
Bit15 = Self-test inquiry period 0:FALSE/1:TRUE
Bit14 = Battery cut-off minimum voltage per cell 0:FALSE/1:TRUE
Bit13 = Battery low voltage per PCS 0:FALSE/1:TRUE
Bit12 = Battery low capacity (%) 0:FALSE/1:TRUE
Bit10 = Bat test stop voltage 0:FALSE/1:TRUE
Bit9 = Bat test stop capacity 0:FALSE/1:TRUE
Bit 8 = Bat test stop time 0:FALSE/1:TRUE
Bit7 = Setting the battery shut down delay time 0:FALSE/1:TRUE
0x0385 901
Bit13 = Flag: Reservation N/A
Bit12 = Flag: Reservation N/A
Bit11 = Flag: Reservation N/A
Bit10 = Flag: The bypass Freq. low loss point and high loss point 0:FALSE/1:TRUE
Bit9 = Flag: The bypass Voltage high loss point 0:FALSE/1:TRUE
Bit8 = Flag: The bypass Voltage low loss point 0:FALSE/1:TRUE
Bit7-Bit0 = Reservation N/A
0x05ED 1517 Bit15 = Setting charging current 0:FALSE/1:TRUE
18. Remote Shutdown and Test
Holding Register (Read Function 0x03 for 0x03DA, 0x030F and 0x0310,
Write Function 0x10 for range 0x03AB - 0x3AC)
Address
Description Unit Value0/Value1 Example for 0x03AB - 0x3AC RangeHex Decimal
0x03AB 939 Shutdown minutes (ASCII) 0x2E32
0x03AC 940 Test for specified time minutes (ASCII) 0x2E32
0x03DA 986
Bit15 = flag:Shutdown 0:FAIL/1:SUCCESS N/A
Bit14 = flag:Test for specified time 0:FAIL/1:SUCCESS N/A
Bit13 = flag:Shutdown and restore 0:FAIL/1:SUCCESS N/A
Bit12-Bit0 = Reservation N/A N/A
0x030F 780 Get shutdown time Unit: second 117
0x0310 781 Get restore time Unit: second 562
9
Operation
19. CPU Information
Holding Register (Read Function 0x03)
Address
Description Unit Sample Additional CommentsHex Decimal
0x03E1 993 STS DSP Firmware version ASCII
0x3241
0x3530
0x4300
If user receives 2A50C,
it describes FW-2A50C
0x01FC 508 10-inch LCD Firmware version ASCII
0x3241
0x3532
0x4200
If user receives 2A52B,
it describes FW-2A52B
0x049C 1180 LCD MCU Firmware version ASCII
0x3241
0x3531
0x4300
If user receives 2A51C,
it describes FW-2A51C
0x03E4 996
Power Stage DSP Firmware
version
ASCII
0x3241
0x3445
0x4300
If user receives 2A4EC,
it describes FW-2A4EC
0x03E7 999
Power Stage MCU Firmware
version
ASCII
0x3241
0x3446
0x4100
If user receives 2A4FA,
it describes FW-2A4FA
20. UPS Model and Rating Information
Holding Register (Read Function 0x03)
Address
Description UnitHex Decimal
0x03F2 1010 Battery piece number
0x03F3 1011 Battery standard voltage per unit 0.1V
0x03F4 1012 Input phase
0x03F5 1013 Output phase
0x03F6 1014 Nominal I/P Voltage V
0x03F7 1015 Nominal O/P Voltage V
0x03F8 1016 Output power factor
0x03F9 1017 Output rated VA W
0x03FB 1019 Device model
ASCII= 0x2323 ##
0x2323 ##
0x2323 ##
0x5333 S3
0x4D31 M1
0x3030 00
0x4B58 KX
0x4400 D
0x048A 1162 Battery Voltage 0.1V
0x048B 1163 Rating Output Current A
0x048C 1164 Rating Output Frequency 0.1 Hz
0x048D 1165 Rating Output Voltage 0.1V
0x048E 1166 Parallel number
0x031A 794 Setting redundant number
0x05D9 1497 Serial Number
ASCII= 0x3239 29
0x3134 14
0x4156 AV
0x5450 TP
0x5338 S8
0x3830 80
0x3630 60
0x3030 00
0x3031 01
10
Operation
21. Parallel Inquiry
Address
Description Unit Alarm DescriptionHex Decimal
0x02F4 756 Paraller setting ASCII 01:Enable; 0:Disable 0x3030
0x02F5 757 Independent battery setting ASCII 01:Enable; 0:Disable 0x3030
22. Date Inquiry (Sys or Rack Info Inquiry Address)
(Holding Register, Read Function 0x03)
Address
Description Unit Hex ASCII
Hex Decimal
0x03F3 759 BatMaintenYear ASCII
0x3230 20
0x3139 19
0x03F4 761 BatMaintenMonth ASCII
0x3031 01
0x03F5 762 BatMaintenDay ASCII
0x3031 01
0x03F6 763 BatInstalYear ASCII
0x3230 20
0x3139 19
0x03F7 765 BatInstalMonth ASCII
0x3031 01
0x03F8 766 BatInstalDay ASCII
0x3031 01
0x03F9 767 SysMaintenYear ASCII
0x3230 20
0x3139 19
0x03FB 769 SysMaintenMonth ASCII
0x3031 01
0x048A 770 SysMaintenDay ASCII
0x3031 01
0x048B 771 SysInstalYear ASCII
0x3230 20
0x3139 19
0x048C 773 SysInstalMonth ASCII
0x3031 01
0x048D 774 SysInstalDay ASCII
0x3031 01
23. Set Date (Sys or Rack Info Inquiry Address)
Holding Register (Write Function 0x10 for range 0x03F3 - 0x03F6)
Address
Description Unit Alarm Description Additional CommentsHex Decimal
0x03F3 1061 Set SysInstalDate ASC
0x3230
0x3139
0x3035
0x3033
This function only receives the form of address. Ex:
1061-0x3230
1062-0x3139
1063-0x3035
1064-0x3033
0x03F4 1065 Set SysMaintenDate ASC
0x3230
0x3139
0x3035
0x3033
This function only receives the form of address. Ex:
1065-0x3230
1066-0x3139
1067-0x3035
1068-0x3033
0x03F5 1069 Set BatInstalDate ASC
0x3230
0x3139
0x3035
0x3033
This function only receives the form of address. Ex:
1069-0x3230
1070-0x3139
1071-0x3035
1072-0x3033
0x03F6 1073 Set BatMaintenDate ASC
0x3230
0x3139
0x3035
0x3033
This function only receives the form of address. Ex:
1073-0x3230
1074-0x3139
1075-0x3035
1076-0x3033
11
Appendix 1
815 (Bit15-Bit8)
B8b9
00: Standby; bit15 bit14
01: Line-interactive;
10: On-line
b7: Utility Fail
b6: Battery Low
b5: Bypass/Boost Active
b4: UPS Failed
b3: EPO
b2: Test In-Progress
815 (Bit3-Bit0)
b1: Shutdown Active
b0: Bat Silence
a1: Bat Test Fail
a0: Bat Test OK
Appendix 2
0x00D0H
P:
Power-on mode
S: Standby mode
Y: Bypass mode
L: Line mode
B: Battery mode
T: Battery test mode
F: Fault mode
E: HE/ECO mode
C: Converter mode
D: Shutdown mode
12
Code(FF) Name Definition
01 cBusOver BUS Voltage is over 450V
02 cBusUnder BUS Voltage is under 320V, 200 ms
03 cBusUnbalance +BUS, -BUS difference is over 50V, 200 ms
04 cBusShort Hardware Signal Trigged
06 cBusSoftTimeOut BUS soft-start time is over 120 sec
07 cInvSoftTimeOut Inverter soft-start time is over 120 sec
08 cInvVoltHigh Inverter RMS is over 250V, 200 ms
09 cInvVoltLow Inverter RMS is under 150V, 200 ms
10 cRInvVoltShort R-phase voltage is less 70V and current is over 50A
11 cSInvVoltShort S-phase Voltage is less 70V and Current is over 50A
12 cTInvVoltShort T-phase Voltage is less 70V and Current is over 50A
13 cRSInvVoltShort RS-phase Voltage is less 70V and Current is over 50A
14 cSTInvVoltShort ST-phase Voltage is less 70V and Current is over 50A
15 cTRInvVoltShort TR-phase Voltage is less 70V and Current is over 50A
16 cInvRNegPow 800W, 40 ms; 400W, 100 ms
17 cInvSNegPow 800W, 40 ms; 400W, 100 ms
18 cInvTNegPow 800W, 40 ms; 400W, 100 ms
19 cOverLoadFault Overload occured, but bypass is not good
20 cBatteryFault Battery is connected reversely
22 cOverTemperature The max. temperature sensor is over 80°C
25 cCanFault CAN bus is abnormal and droop source needs to be changed
26 cSynSigFault SYNCHRO Signal Fail
27 cTRIG0Fault TRIG0 Signal
28 cRelayFault Inverter Relay Short
29 cLineSCRFail I/P SCR is Open
31 cSPSFault SPS output is abnormal
32 cParaCableLoosenFault Parallel Cable is loose
33 cDSPMCUStopComm DSP and MCU do not communicate
34 cBypassSCRFault STS Bypass SCR fail
35 cBypassTemperatureFault STS is over-temperature
36 cInvVoltOver Inverter Sample voltage is over 380V, 156 us
Appendix 3
19-07-265 93-39CA_RevA
1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support
13
Manual de Operación
Tarjeta Programable para MODBUS
para Sistemas UPS Trifásicos de
100-200K SV, SVX, S3MX
Para conocer las características del producto y las instrucciones para configurar e instalar
MODBUSCARDSV, consulte la Guía de Instalación de MODBUSCARDSV.
1111 W. 35th Street, Chicago, IL 60609 EE. UU. • tripplite.com/support
Copyright © 2019 Tripp Lite. Todos los derechos reservados.
Operación 14
1. Elemento de Advertencia 14
2. Configuración de Capacidad 15
3. Elemento de Control 15
4. Resultado de Control 16
5. Configuración de Parámetro a Valor 16
Predeterminado
6. Estado de Trabajo del UPS 17
7. Información de la Batería del UPS 17
8. Consulta de Temperatura 17
9. Consulta de Carga Trifásica 18
10. Información de Derivación Trifásica 18
11. Consulta de Factor de Potencia de Salida 18
12. Consulta de Nivel de Carga 18
13. Modo de Trabajo del UPS 18
14. Información de Falla del UPS 19
15. Punto de Pérdida 19
16. Elemento de Parámetro de Configuración 20
17. Configuración Exitosa o Fallida de Parámetro 20
18. Prueba y Apagado Remoto 20
19. Información del CPU 21
20. Modelos de UPS e Información de Capacidad 21
21. Consulta de Paralelo 22
22. Consulta de Fecha 22
(Dirección de Consulta de Información
de Sistema o Rack)
23. Configurar Fecha 22
(Dirección de Consulta de Información
de Sistema o Rack)
Apéndice 1 23
Apéndice 2 23
Apéndice 3 24
English 1 • Français 25 • Русский 37
14
1. Elemento de Advertencia
Registro de Tenencia (Rango 0x0000 - 0x0001, Función de Lectura 0x03)
El código de la función Read Holding Registers (Leer Registros de Tenencia) se utiliza para leer el contenido de un bloque
contiguo de Registros de Tenencia en un dispositivo remoto. La dirección de registro inicial y el número de registros se
especifican mediante la solicitud de Unidad de Datos de Protocolo. Las direcciones comienzan en 0 y la dirección 1-16 de
registros numerados como 0-15.
El código de la función Write Single Register (Escribir Registro Único) se utiliza para escribir un Registro de Tenencia único en un
dispositivo remoto. La dirección del registro a escribir se especifica mediante la solicitud de Unidad de Datos de Protocolo. Las
direcciones comienzan en 0 y la dirección 1 de registros numerados como 0.
Dirección
Descripción Valor 0/Valor 1
Hexa Decimal
0x0000 0
Bit15 = EPO está Activo. 0:FALSO / 1:VERDADERO
Bit14 = La carga está en nivel de sobrecarga y alcanza el retraso del conteo regresivo 0:FALSO / 1:VERDADERO
Bit12 = El nivel de carga supera el Nivel de Alarma de Sobrecarga 0:FALSO / 1:VERDADERO
Bit11 = La batería no está conectada
(el voltaje de la batería es inferior a 9V)
0:FALSO / 1:VERDADERO
Bit10 = La batería tiene más de 15V 0:FALSO / 1:VERDADERO
Bit8 = Incluye: EPO está activo, Derivación de Mantenimiento está activa, inicio de
CD, pero la configuración de inicio de CD está desactivada
El Estado de Línea no es correcto (El Voltaje o Frecuencia está fuera de rango, la
secuencia de fase no es correcta, pérdida del neutro)
La señal de SYNCHRO es anormal
La señal de TRIG0 es anormal
0:FALSO / 1:VERDADERO
Bit7 = El cargador es anormal 0:FALSO / 1:VERDADERO
Bit6 = El valor de checksum de los datos de la EEPROM en MCU
es incorrecto
0:FALSO / 1:VERDADERO
Bit5 = Ventilador bloqueado 0:FALSO / 1:VERDADERO
Bit4 = La secuencia de fase de la línea es incorrecta 0:FALSO / 1:VERDADERO
Bit3 = La secuencia de fase de la derivación es incorrecta 0:FALSO / 1:VERDADERO
Bit2 = Falta el neutro 0:FALSO / 1:VERDADERO
Bit1 = La comunicación inicial entre DSP y MCU es anormal 0:FALSO / 1:VERDADERO
Bit0 = La señal de SYNCHRO es anormal 0:FALSO / 1:VERDADERO
0x0001 1
Bit15 = La señal de TRIG0 es anormal 0:FALSO / 1:VERDADERO
Bit14 = El número del Módulo de Potencia no coincide con la configuración 0:FALSO / 1:VERDADERO
Bit13 = No hay STS en el sistema 0:FALSO / 1:VERDADERO
Bit12 = La Derivación para Mantenimiento está activa 0:FALSO / 1:VERDADERO
Bit11-Bit0 = Reservación N/A
Operación
15
Operación
2. Configuración de Capacidad
Registro de Tenencia (Rango 0x000E - 0x000F, Función de Lectura 0x03, Función de Escritura 0x10)
Las direcciones comienzan en 0 y las direcciones 1-16 se numeran como 0-15.
La función de Escritura escribe para ACTIVAR/DESACTIVAR en un dispositivo remoto. Una constante especificada en el campo
de datos solicita el estado de ACTIVADO/DESACTIVADO.
Dirección
Descripción Valor 0/Valor 1 Valor de Registro
Hexa Decimal
0x000E 14
Bit15 = Activar/desactivar alarma audible 0:FALSO / 1:VERDADERO E:8000 / D:7FFF
Bit10 = Activar/desactivar Reinicio automático 0:FALSO / 1:VERDADERO E:4000 / D:BFFF
Bit7 = Activar/desactivar inicio de código 0:FALSO / 1:VERDADERO E:200 / D:FDFF
Bit6 = Activar/Desactivar prohibición de derivación 0:FALSO / 1:VERDADERO E:100 / D:FEFF
Bit3 = Activar/Desactivar derivación cuando se apaga el
dispositivo
0:FALSO / 1:VERDADERO E:40 / D:FFBF
Bit1 = Activar/desactivar modo de alta eficiencia 0:FALSO / 1:VERDADERO E:10 / D:FFEF
0x000F 15
Bit15-Bit 13 = Reservación N/A E:8 / D:FFF7
Bit12 = Activar/Desactivar modo de convertidor 0:FALSO / 1:VERDADERO E:4 / D:FFFB
Bit11-Bit8 = Reservación N/A E:2 / D:FFFD
Bit7 = Activar/desactivar autodiagnóstico de período Z 0:FALSO / 1:VERDADERO E:1000 / D:EFFF
Bit0-Bit5 = Reservación N/A N/A
3. Elemento de Control
Registro de Tenencia (Función de Lectura 0x03, Función de Escritura 0x10)
Las direcciones comienzan en 0 y las direcciones 1-16 se numeran como 0-15.
La función de Escritura escribe para ACTIVAR/DESACTIVAR en un dispositivo remoto. Una constante especificada en el campo
de datos solicita el estado de ACTIVADO/DESACTIVADO.
Dirección
Descripción Valor 0/Valor 1 Descripción de la Alarma
Hexa Decimal
0x001A 26
Bit15 = Silenciar sonido de zumbador (alarma audible) 0:FALSO / 1:VERDADERO Y:8000
Bit14 = sonido de zumbador abierto (alarma audible) 0:FALSO / 1:VERDADERO Y:4000
Bit13 = Prueba hasta batería baja 0:FALSO / 1:VERDADERO Y:2000
Bit12 = Apagar UPS en forma remota 0:FALSO / 1:VERDADERO Y:1000
Bit12 = Encender UPS en forma remota 0:FALSO / 1:VERDADERO Y:800
Bit10 = Cancelar apagado 0:FALSO / 1:VERDADERO Y:400
Bit9 = Cancelar prueba 0:FALSO / 1:VERDADERO Y:200
Bit8 = Prueba por 10 segundos 0:FALSO / 1:VERDADERO Y:100
Bit3-Bit 0 = Reservación N/A N/A
0x001B 27
Bit5-Bit 11 = Reservación N/A N/A
Bit10 = Cambiar UPS a derivación 0:FALSO / 1:VERDADERO Y:0400
0x0422 1058
Bit15 = Función EPO abierta 0:FALSO / 1:VERDADERO Y:8000
Bit14 = Función EPO cerrada 0:FALSO / 1:VERDADERO Y:4000
Bit13 = Modo frecuencia de salida 50 Hz 0:FALSO / 1:VERDADERO Y:2000
Bit12 = Modo frecuencia de salida 60 Hz 0:FALSO / 1:VERDADERO Y:1000
Bit11 = Cargador Encendido 0:FALSO / 1:VERDADERO Y:0800
Bit10 = Cargador Apagado 0:FALSO / 1:VERDADERO Y:0400
Bit9 = Activar batería independiente 0:FALSO / 1:VERDADERO Y:0200
Bit8 = Desactivar batería independiente 0:FALSO / 1:VERDADERO Y:0100
16
Operación
4. Resultado de Control
Registro de Tenencia (Función de Lectura 0x03)
Las direcciones comienzan en 0 y las direcciones 1-16 se numeran como 0-15.
Dirección
Descripción Valor 0/Valor 1
Hexa Decimal
0x0025 37
Bit15 = Bandera:Silenciar sonido de zumbador (Alarma Audible) 0:FALLA / 1:ÉXITO
Bit14 = Bandera:sonido de zumbador abierto (Alarma Audible) 0:FALLA / 1:ÉXITO
Bit13 = Bandera:Prueba hasta batería baja 0:FALLA / 1:ÉXITO
Bit12 = Bandera:Apagar UPS en forma remota 0:FALLA / 1:ÉXITO
Bit11 = Bandera: Encender UPS en forma remota 0:FALLA / 1:ÉXITO
Bit10 = Bandera:Cancelar apagado 0:FALLA / 1:ÉXITO
Bit9 = Bandera:Cancelar prueba 0:FALLA / 1:ÉXITO
Bit8 = Bandera:Prueba por 10 segundos 0:FALLA / 1:ÉXITO
Bit7 = Reservación N/A
Bit6 = Reservación N/A
Bit5 = Reservación N/A
Bit4 = Reservación N/A
Bit3-Bit0 = Reservación N/A
0x0026 38
Bit10 = Cambiar UPS a derivación 0:FALLA / 1:ÉXITO
Bit9-Bit0 = Reservación N/A
0x0423 1059
Bit15 = Función EPO en normalmente abierta 0:FALLA / 1:ÉXITO
Bit14 = Función EPO en normalmente cerrada 0:FALLA / 1:ÉXITO
Bit13 = Modo frecuencia de salida 50 Hz 0:FALLA / 1:ÉXITO
Bit12 = Modo frecuencia de salida 60 Hz 0:FALLA / 1:ÉXITO
Bit11 = Cargador Encendido 0:FALLA / 1:ÉXITO
Bit10 = Cargador Apagado 0:FALLA / 1:ÉXITO
Bit9 = Activar batería independiente 0:FALLA / 1:ÉXITO
Bit8 = Desactivar batería independiente 0:FALLA / 1:ÉXITO
5. Configuración de Parámetro a Valor Predeterminado
Registro de Tenencia (Función de Lectura 0x03, Función de Escritura 0x10)
La función de Escritura escribe para ACTIVAR/DESACTIVAR en un dispositivo remoto. Una constante especificada en el campo
de datos solicita el estado de ACTIVADO/DESACTIVADO.
Dirección
Descripción Valor 0/Valor 1 TipoHexa Decimal
0x0030 48
Bit15 = Configuración de parámetro de control a valor predeterminado Y:8000 Lectura / Escritura
Bit14-Bit0 = Reservación N/A N/A
0x003B 59
Bit15 = Bandera:Configuración de parámetro de control a valor
predeterminado
0:FALLA / 1:ÉXITO Solo Lectura
Bit14-Bit0 = Reservación N/A N/A
17
Operación
6. Estado de Trabajo del UPS
Registro de Tenencia (Función de Lectura 0x03)
Dirección
Descripción Unidad
Hexa Decimal
0x031E 798 Voltaje de entrada R 0.1V
0x031F 799 Voltaje de entrada S 0.1V
0x0320 800 Voltaje de entrada T 0.1V
0x0321 801 Frecuencia de Entrada 0.1 Hz
0x0322 802 Voltaje de salida R 0.1V
0x0323 803 Voltaje de salida-S 0.1V
0x0324 804 Voltaje de salida T 0.1V
0x0325 805 Frecuencia de salida 0.1 Hz
0x0326 806 Corriente de salida R 0.1A
0x0327 807 Corriente de salida S 0.1A
0x0328 808 Corriente de salida T 0.1A
0x0329 809 Porcentaje de carga de salida R 1%
0x032A 810 Porcentaje de carga de salida S 1%
0x032B 811 Porcentaje de carga de salida T 1%
0x032C 812 Voltaje de la Batería P 0.1V
0x032D 813 Voltaje de la Batería N 0.1V
0x032E 814 Temperatura máxima de los punteros de detección 0.1C
0x032F 815 Ver Apéndice 1 Ver Apéndice 1
7. Información de la Batería del UPS
Registro de Tenencia (Función de Lectura 0x03)
Dirección
Descripción Unidad
Hexa Decimal
0x00BC 188 Voltaje de la Batería P 0.1V
0x00BD 189 Número de pieza de la batería P
0x00BF 191 Capacidad de la batería P %
0x00C0 192 Tiempo restante de la batería P Minutos
0x00C1 193 Voltaje de la Batería N 0.1V
0x00C2 194 Número de pieza de la batería N
0x00C4 196 Capacidad de la batería N %
0x00C5 197 Tiempo restante en batería N Minutos
0x0318 792 Corriente de carga de batería P 0.01A
0x0319 793 Corriente de carga de batería N 0.01A
0x0307 775 La consulta de información de Ah Totales de la batería Ah
0x0308 776 QREPO de estado del EPO
8000 : Abierto
7FFF : Cerrado
8. Consulta de Temperatura
Registro de Tenencia (Función de Lectura 0x03)
Dirección
Descripción UnidadHexa Decimal
0x00CC 204 Temperature1 0.1°C
0x00CD 205 Temperature2 0.1°C
0x00CE 206 Temperature3 0.1°C
0x00CF 207 Temperature4 0.1°C
18
Operación
9. Consulta de Carga Trifásica
Registro de Tenencia (Función de Lectura 0x03)
Dirección
Descripción Unidad
Hexa Decimal
0x00DD 221 Fase R de carga %
0x00FC 252 Fase S de carga %
0x00FD 253 Fase T de carga %
0x00FE 254 Carga total %
10. Información de Derivación Trifásica
Registro de Tenencia (Función de Lectura 0x03)
Dirección
Descripción Unidad
Hexa Decimal
0x011A 282 Voltaje R de derivación 0.1V
0x011B 283 Voltaje S de derivación 0.1V
0x011C 284 Voltaje T de derivación 0.1V
0x011D 285 Corriente R de derivación 0.1A
0x011E 286 Corriente S de derivación 0.1A
0x011F 287 Corriente T de derivación 0.1A
0x0123 291 Frecuencia de derivación 0.1 Hz
11. Consulta de Factor de Potencia de Salida
Registro de Tenencia (Función de Lectura 0x03)
Dirección
Descripción Unidad
Hexa Decimal
0x030F 783 Factor de potencia de salida R 0.001
0x0310 784 Factor de potencia de salida S 0.001
0x0311 785 Factor de potencia de salida T 0.001
12. Consulta de Nivel de Carga
Registro de Tenencia (Función de Lectura 0x03)
Dirección
Descripción UnidadHexa Decimal
0x0312 786 Porciento de potencia de R en watts %
0x0313 787 Porciento de potencia de S en watts %
0x0314 788 Porciento de potencia de T en watts %
0x0315 789 Porciento de potencia de R en VA %
0x0316 790 Porciento de potencia de S en VA %
0x0317 791 Porciento de potencia de T en VA %
13. Modo de Trabajo del UPS
Registro de Tenencia (Función de Lectura 0x03)
Dirección
Descripción UnidadHexa Decimal
0x00D0 208 Consulta de modo de UPS Ver Apéndice 2
19
Operación
14. Información de Falla del UPS
Registro de Tenencia (Función de Lectura 0x03)
Dirección
Descripción Unidad Respuesta de Ejemplo
Hexa Decimal
0x02A3 675
Tipo de falla ASCII 00:sin falla
predeterminada:FF
Ver Apéndice 3
0x3030 (Sin Falla)
0x4646 (Falla)
0x02E5 - 0x02EC 741 - 748 ID de módulo de tipo de falla1 ASCII 01-07 Ver Apéndice 3
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x03B0 - 0x03CB 944 - 971 ID de módulo de tipo de falla1 ASCII 08-35 Ver Apéndice 3
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x3031
0x3132
0x0000
0x0000
0x3336
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
15. Punto de Pérdida
Registro de Tenencia (Función de Lectura 0x03)
Dirección
Descripción UnidadHexa Decimal
0x034A 842 Punto de pérdida de Voltaje Alto en modo de alta eficiencia V
0x034B 843 Punto de pérdida de Voltaje Bajo en modo de alta eficiencia V
0x034C 844 Punto de pérdida de alta frecuencia en modo de funcionamiento libre 0.1 Hz
0x034D 845 Punto de pérdida de baja frecuencia en modo de funcionamiento libre 0.1 Hz
0x034E 846 Punto de pérdida de alta frecuencia en derivación 0.1 Hz
0x034F 847 Punto de pérdida de baja frecuencia en derivación 0.1 Hz
0x0350 848 Punto de pérdida de alto voltaje en derivación V
0x0351 849 Punto de pérdida de bajo voltaje en derivación V
20
Operación
16. Elemento de Parámetro de Configuración
Registro de Tenencia (Función de Lectura 0x03, Función de Escritura 0x10)
Dirección
Descripción Unidad
Valores de
Muestra Tipo
Hexa Decimal
0x02ED 749 Configuración de tiempo de retardo de apagado de la batería Segunda 10 Lectura / Escritura
0x02EE 750 Voltaje mínimo de corte de batería por celda 0.01V 166 Solo Lectura
0x02EF 751 Voltaje de corte por PCS ( ! ! ! ) BATCO (10.00~11.00) 0.01V 1000 Lectura / Escritura
0x02f0 752 Bajo voltaje de batería por PCS 0.01V 1100 Lectura / Escritura
0x02f1 753 Capacidad baja de la batería (%) % 20 Lectura / Escritura
0x02f3 755 Período de consulta de autodiagnóstico Día 0 Lectura / Escritura
0x0309 777 Tiempo de paro de prueba de la batería S 10 Lectura / Escritura
0x030A 778 Capacidad de paro de prueba de la batería % 20 Lectura / Escritura
0x030B 779 Voltaje de paro de prueba de la batería 0.01V/PCS 1100 Lectura / Escritura
0x0424 1060 Configuración de Ah Totales de la batería Ah 9 Lectura / Escritura
0x05ED 1457 Configuración de corriente de carga 02 a 64 10 Lectura / Escritura
17. Configuración Exitosa o Fallida de Parámetro
Registro de Tenencia (Función de Lectura 0x03)
Dirección
Descripción Valor 0/Valor 1
Hexa Decimal
0x0384 900
Bit15 = Período de consulta de autodiagnóstico 0:FALSO / 1:VERDADERO
Bit14 = Voltaje mínimo de corte de batería por celda 0:FALSO / 1:VERDADERO
Bit13 = Bajo voltaje de batería por PCS 0:FALSO / 1:VERDADERO
Bit12 = Capacidad baja de la batería (%) 0:FALSO / 1:VERDADERO
Bit10 = Voltaje de paro de prueba de la batería 0:FALSO / 1:VERDADERO
Bit9 = Capacidad de paro de prueba de la batería 0:FALSO / 1:VERDADERO
Bit 8 = Tiempo de paro de prueba de la batería 0:FALSO / 1:VERDADERO
Bit7 = Configuración de tiempo de retardo de apagado de la batería 0:FALSO / 1:VERDADERO
0x0385 901
Bit13 = Bandera: Reservación N/A
Bit12 = Bandera: Reservación N/A
Bit11 = Bandera: Reservación N/A
Bit10 = Bandera: El punto de pérdida alta y punto de pérdida baja de frecuencia de derivación
0:FALSO / 1:VERDADERO
Bit9 = Bandera: Punto de pérdida de alto voltaje en derivación 0:FALSO / 1:VERDADERO
Bit8 = Bandera: El punto de pérdida de bajo voltaje en derivación 0:FALSO / 1:VERDADERO
Bit7-Bit0 = Reservación N/A
0x05ED 1517 Bit15 = Configuración de corriente de carga 0:FALSO / 1:VERDADERO
18. Prueba y Apagado Remoto
Registro de Tenencia (Función de Lectura 0x03 para 0x03DA, 0x030F y 0x0310,
Función de Escritura 0x10 para rango 0x03AB - 0x3AC)
Dirección
Descripción
Valor0/Valor1 de
Unidad
Ejemplo para Rango 0x03AB -
0x3ACHexa Decimal
0x03AB 939 Apagado minutos (ASCII) 0x2E32
0x03AC 940 Prueba para tiempo especificado minutos (ASCII) 0x2E32
0x03DA 986
Bit15 = Bandera:Apagado 0:FALLA / 1:ÉXITO N/A
Bit14 = bandera: Prueba para tiempo especificado
0:FALLA / 1:ÉXITO N/A
Bit13 = Bandera: Apagar y restablecer 0:FALLA / 1:ÉXITO N/A
Bit12-Bit0 = Reservación N/A N/A
0x030F 780 Obtener tiempo de apagado Unidad: segundo 117
0x0310 781 Obtener tiempo de restablecimiento Unidad: segundo 562
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

Tripp Lite MODBUSCARDSV Mode d'emploi

Taper
Mode d'emploi
Ce manuel convient également à

dans d''autres langues