Samsung AM036TNZDCH/AA Guide d'installation

Catégorie
Climatiseurs split-system
Taper
Guide d'installation

Ce manuel convient également à

Air conditioner
Installation manual
AM0**TNZDCH
Thank you for purchasing this Samsung air conditioner.
Before operating this unit, please read this manual carefully and retain it for future reference.
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 1 2020-02-05 오후 4:15:00
2
English
Contents
Safety Precautions 3
Safety Precautions 3
Installation 5
General Information 5
Product Inspection 6
Accessories 6
Selecting the installation location 6
Indoor unit installation 8
Refrigerant piping 14
Performing leak test & insulation 15
Additional refrigerant 17
Drain pipe installation 18
Water leakage test 19
Drain pipe insulation 19
Wiring Work 20
Wiring Diagram 28
Selecting motor speed 29
Blower CFM tables 30
Setting an indoor unit address and installation option 33
Final Checks and User Tips 43
Appendix 44
Providing information for user 44
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 2 2020-02-05 오후 4:15:00
3
English
Safety Precautions
California Proposition 65 Warning (US)
WARNING :
Cancer and Reproductive Harm - www.P65Warnings.ca.gov.
WARNING
 Always disconnect the air conditioner from the power supply before servicing it or
accessing its internal components.
 
personnel.
 Verify that the air conditioner is not installed in an easily accessible area.
General information
Carefully read the content of this manual before installing the air conditioner and store the manual in a safe place in
order to be able to use it as reference after installation.
For maximum safety, installers should always carefully read the following warnings.
Store the operation and installation manual in a safe location and remember to hand it over to the new owner if the air
conditioner is sold or transferred.
This manual explains how to install an indoor unit with a split system with SAMSUNG units. The use of other types of
units with different control systems may damage the units and invalidate the warranty. The manufacturer shall not be
responsible for damages arising from the use of non compliant units.
The manufacturer shall not be responsible for damage originating from unauthorized changes or the improper
connection of electric and hydraulic lines. Failure to comply with these instructions or to comply with the requirements
set forth in this manual, shall immediately invalidate the warranty.
The air conditioner should be used only for the applications for which it has been designed: the indoor unit is not
suitable to be installed in areas used for laundry.
Do not use the units if damaged. If problems occur, switch the unit off and disconnect it from the power supply.

SAMSUNG’s technical support if the unit produces smoke, if the power cable is hot or damaged or if the unit is very
noisy.
Always remember to inspect the unit, electric connections, refrigerant tubes and protections regularly. These

The unit contains moving parts, which should always be kept out of the reach of children.
Do not attempt to repair, move, alter or reinstall the unit. If performed by unauthorized personnel, these operations


All the materials used for the manufacture and packaging of the air conditioner are recyclable.
The packing material and exhaust batteries of the remote control (optional) must be disposed of in accordance with
current laws.
The air conditioner contains a refrigerant that has to be disposed of as special waste. At the end of its life cycle, the air
conditioner must be disposed of in authorized centers or returned to the retailer so that it can be disposed of correctly
and safely.
Installing the unit

Always disassemble the electric lines before the refrigerant tubes.
Upon receipt, inspect the product to verify that it has not been damaged during transport. If the product appears
damaged, DO NOT INSTALL it and immediately report the damage to the carrier or retailer (if the installer or the
authorized technician has collected the material from the retailer.)
Safety Precautions
Safety Precautions
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 3 2020-02-05 오후 4:15:00
4
English
Safety Precautions
Safety Precautions
After completing the installation, always carry out a functional test and provide the instructions on how to operate the
air conditioner to the user.
Do not use the air conditioner in environments with hazardous substances or close to equipment that release free

The air conditioner should be used only for the applications for which it has been designed: the indoor unit is not
suitable to be installed in areas used for laundry.
Our units must be installed in compliance with the spaces indicated in the installation manual to ensure either
accessibility from both sides or ability to perform routine maintenance and repairs. The units’ components must be
accessible and that can be disassembled in conditions of complete safety either for people or things. For this reason,
where it is not observed as indicated into the Installation Manual, the cost necessary to reach and repair the unit (in
safety, as required by current regulations in force) with slings, trucks, scaffolding or any other means of elevation won’t
be considered in-warranty and charged to end user.
Power supply line, fuse or circuit breaker
Always make sure that the power supply is compliant with current safety standards. Always install the air conditioner
in compliance with current local safety standards.
Always verify that a suitable grounding connection is available.


Always verify that the cut-off and protection switches are suitably dimensioned.
Verify that the air conditioner is connected to the power supply in accordance with the instructions provided in the
wiring diagram included in the manual.
Always verify that electric connections (cable entry, section of leads, protections…) are compliant with the electric

the standards applicable to the installation of air conditioners.
CAUTION
 Make sure that you earth/ground the power cables.
Do not connect the earth wire to the gas pipe, water pipe, lighting rod or telephone wire. If earthing

 Install the circuit breaker.

 Make sure that the condensed water dripping from the drain hose runs out properly and safely.
 Install the power cable and communication cable of the indoor and outdoor unit at least 1m (3.28')
away from the electric appliance.
 Install the indoor unit away from lighting apparatus using the ballast.
If you use the wireless remote control, reception error may occur due to the ballast of the lighting
apparatus.
 Do not install the air conditioner in following places.

water may leak. The capacity of the heat exchanger may reduce or the air conditioner may be out of
order.
The place where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outlet.
The copper pipe or connection pipe may corrode and refrigerant may leak.
The place where there is a machine that generates electromagnetic waves.The air conditioner may
not operate normally due to control system.


AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 4 2020-02-05 오후 4:15:00
5
English
Installation
The following list includes important facts and information regarding the electric air handler and its inclusions.
1. Air handler is rated at 240 volts AC at 60 Hertz
2. Air handler size varies by model
3. Two-wire, wired controller operation (only Samsung “N” series wired controllers are compatible).
4. Two-wire system communication
5. Samsung wired controller required
6. Air handlers are equipped with blower for A/C or heat pump operation.
7. 
8. 
9. This air handler must not be operated without the door installed.
10. This air handler will not operate without an outdoor unit connected, completing the system.
NOTE
This air handler and its components listed on the A/C and heat pump equipment sticker were listed in
combination as a system by ETL for the United States and Canada.

These models may be used with or without electric heat.
Only use electric heat that is designed for this unit and provided by Samsung.


horizontal position.
General Information
Installation
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 5 2020-02-05 오후 4:15:00
6
English
Installation
As soon as the air handler is received, it should be inspected for possible damage during transit. If damage is evident, the
extent of the damage should be noted on the carrier’s freight bill. A separate request for inspection by the carrier’s agent
should be made in writing. Before installing the air handler you should check the cabinet for screws or bolts which may
have loosened in transit. There are no shipping or spacer brackets which need to be removed before startup. See local
Distributor for more information. Samsung assumes no liability for freight damage. Also check to be sure all accessories
such as heater kits, and coils are available. Installation of these accessories should be accomplished before the air handler
is set in place or the connecting of the wiring, electric heat, ducts or piping.
Product Inspection
Accessories
The following accessories are supplied with the indoor unit.
Installation manual Warranty card
Selecting the installation location
Decide the installation location, with the consideration of the following conditions, under user’s approval.
 
 

 
 Place where condensation can be drained easily.
 Place that allows refrigerant pipe connection within allowable distance.
 Place where indoor unit will not be exposed to direct sunlight.
 Place that can keep the distance of at least 3.28 ft (1 m) between power/communication cable and any electronic
devices (depending on the circumstances, problem may occur even if you secure 3.28 ft (1 m) of distance).
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 6 2020-02-05 오후 4:15:00
7
English
Installation
Dimensions
Unit : inch
5
BOTTOM
TOP
LEFT SIDE RIGHT SIDEFRONT
DIMENSIONAL DATA MULTI-POSITION AIR HANDLER
MODEL A B C D E F G H J K L M N P R
AM0 12/18/24 TNZDCH 17.50 43.00 21.00 15.50 12.50 13.50 11.00 6.75 16.75 14.00 11.00 8.5 2.00 4.00 2.00
AM0 30/36 TNZDCH 21.00 48.00 21.00 19.00 12.50 15.375 13.00 6.75 20.00 17.00 12.75 10.30 2.30 4.35 2.50
AM0 48/54/60/72 TNZDCH 24.50 58.75 21.75 19.50 16.25 19.75 17.25 6.75 26.00 23.00 16.75 14.35 2.30 4.35 2.00
NOTE
ALL DIMENSION ARE IN INCHES AND ARE APPROXIMATE. ALL DIMENSIONS ARE ROUNDED
No. Name Description
1 Liquid pipe connection
**012/018**: ø 1/4”
**024/030/036/048/054/060/072**: ø 3/8”
2 Gas pipe connection
**012/018**: ø 1/2”
**024/030/036/048**: ø 5/8”
**054/060/072**: ø 3/4”
3 3/4" NPT
4 -
5 -
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 7 2020-02-05 오후 4:15:01
8
English
Installation
Location
Access for servicing is an important factor in the location of any air handler. Provide a minimum of 30 inches in front of the

door or by locating the appliance so that a wall or partition is not less than 30 inches from the front access panel. Location

decided, consider the following in choosing a suitable location.
1. Select a location with adequate structural support, space for service access, and clearance for return and supply duct
connections.
2. 
bedrooms, study, etc.
3. Caution should be taken to locate the unit so that supply and return air ducts are about the same length causing even air
distribution of supply and return air to and from the living spaces.
4. Locate appliance where electrical supply wiring can be easily routed to main electrical panel and where electrical wiring will
not be damaged.
5. Locate appliance where control wiring can be easily routed to the controller and where the wiring will not be damaged.
6. Locate appliance where refrigerant lines can be easily routed from the evaporator coil to the system.
7. Locate the appliance where condensate lines can be easily routed to an available drain. Be sure to route condensate drain

8. The coil is installed in a draw-thru application and will create a negative pressure situation in the condensate drain system.
To prevent condensate from being drawn into the blower it is recommended to trap the primary (Main) and secondary

it must be capped. This unit has a connection terminal for drain system monitoring. Refer to Wiring Work section for

9. The draw-thru design will cause exterior surface of cabinet to sweat when unit is installed in a non-conditioned space
such as an attic or garage. Installer must provide protection such as full size auxiliary drain pan on all units installed in a
non-conditioned space to prevent damage from condensation runoff. Some states, cities and counties require additional
insulation to be installed on the exterior casing of the air handler to prevent sweating. Refer to the state, city, county or local
code for insulation requirement to be sure the installation is in compliance. It is recommended that air handlers installed in
non-conditioned spaces be insulated on the exterior of the entire cabinet, including the front access panel with one (1) inch

10. 
drain piping, as described for the intake duct installation and in Drain pipe installation”.
H
H
Clearance - Access for service
30" minimum
Right side of unit
Vertical installation Horizontal installation
Refrigerant pipe work must be done before installing the indoor unit.
Indoor unit installation
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 8 2020-02-05 오후 4:15:01
9
English
Installation
This appliance is approved for zero (0) inches clearance to combustible material on any part of the air handler exterior
casing and the inlet or outlet ducts providing NO electric heater is being used. There is a one (1) inch clearance on the
supply plenum and supply air duct when an electric heater is installed in the appliance. Refer to Table below for clearance
to combustibles information.
Top (inches) Back (inches) Sides (inches)
Front of unit
Duct (inches)
Alcove (inches) Closet (inches)
0 0 0 30 6 1 *
* when electric heat kit accessory is installed
Return air requirements
0" 0"
Return Air Requirements
In order for the air handler to work properly, a closet or alcove must have a certain total free area opening for the return air.
For A/C and HP Air Handlers 1/3 HP Blower Motor
Minimum 200 in² free area opening
 
For A/C and HP Air Handlers 1/2 HP Blower Motors
 Minimum 250 in² free area opening
 
For A/C and HP Air Handlers with Electric Heat use 3/4 HP Blower Motor
 Minimum 390 in² free area opening
 
For A/C and HP Air Handlers use 1.0 HP Blower Motor)
 Minimum 430 in² free area opening
 Use Return Grille with a minimum 430 in² free area opening


minimum clearance between the appliance and the wall or door must be provided on the side where the return is located


AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 9 2020-02-05 오후 4:15:01
10
English
Indoor unit installation
Installation
Return air requirements
Closet Wall
Typical Closet Installations
Provisions shall be made to permit the air in the rooms and the living spaces to return to the air handler. Failure to comply


premature heating element failure (if electric heat kits are installed).
Upow Accessory Filter Box Kit



NOTE

ADJUSTMENT KNOB
FOR 1" OR 2" FILTER
ADJUSTMENT KNOB
FOR 1" OR 2" FILTER
Accessory Air Filter Box for 1” or 2” Air Filters. Filter Size Adjustment knob is on both sides.
FILTER BASE ASSEMBLY KIT MODEL NUMBERS - FIELD INSTALLED, PURCHASED SEPARATELY
VFB-1 – 16” X 20” X 2” Small Cabinet (9/12/18/24K )
VFB-2 – 20” X 20” X 2” Medium Cabinet (30/36K)
VFB-3 – 20” X 24” X 2” Large Cabinet (48/54/60/72K)
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 10 2020-02-05 오후 4:15:01
11
English
Installation
Arrangement:

Horizontal left means when the unit is laid on its side and you are facing the unit, the supply air opening is to the left and

Airflow Airflow
Horizontal left arrangement
Upow application


platform framed in. The platform must have an opening centered in the closet that measures at least 12 inches in height


shown in the table below.
 
800 CFM = 20 x 20 x 1
1000 CFM = 20 x 25 x 1
1200 CFM = 20 x 30 x 1
1400 CFM = 25 x 30 x 1
1600 CFM = 25 x 30 x 1
1800 CFM = 30 x 30 x 1
2000 CFM = 30 x 40 x 1 or two 30 x 20 x 1
2400 CFM = 30 x 40 x 1 or two 30 x 20 x 1
800 CFM = 16 x 16 x 1
1000 CFM = 18 x 20 x 1
1200 CFM = 20 x 20 x 1
1400 CFM = 20 x 20 x 1
1600 CFM = 20 x 25 x 1
1800 CFM = 20 x 30 x 1 or two 20 x 15 x 1
2000 CFM = 20 x 30 x 1 or two 20 x 15 x 1
2400 CFM = 25 x 30 x 1 or two 14 x 30 x 1


between the unit and the base.
Connect the supply air outlet to a plenum to the top of the unit and secure it with screws. Use a Non-tape sealant such as
mastic or an aerosol sealant to seal duct leakage. If installed in a basement, run supply and return duct work in accordance
with local codes. Use a Non-tape sealant such as mastic or an aerosol sealant to seal duct leakage.
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 11 2020-02-05 오후 4:15:02
12
English
Indoor unit installation
Installation
Horizontal application
Horizontal applications will normally be used in an attic
or crawl space. This type of installation requires supply air
plenum or duct to be connected to the supply collar and a
return air plenum or duct be attached to the unit inlet collar.
The supply ducts will be connected to the supply air plenum
and routed through the attic to a register in each room. Use
a Non-tape sealant such as mastic or an aerosol sealant to
prevent leaks in the ducts and the plenum.
The opposite end of the return air duct is attached to a return


tape sealant such as mastic or an aerosol sealant to prevent
leaks in the ducts and the plenum.
Refrigerant pipe
conections
Horizontal left
(right to left) drain
connections
Horizontal right
(left to right)
drain pan
opening
Horizontal right application (left to right)

1. Remove the unit access panels
2. Remove the cooling coil after disassembling bracket coil and plate.
3. Move the condensate drain pan to the right side of the unit chassis.
4. Move the Evap In temperature sensor to holder of the right side.
5. Reinstall the cooling coil.
6. Connect the condensate drains and refrigerant lines. DRY NITROGEN MUST BE FLOWED THROUGH REFRIGERANT LINES
DURING SOLDERING OPERATION.
7. Reinstall unit access panels.



Evap. In Temperature Sensor
Move drain pan to right side of coil
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 12 2020-02-05 오후 4:15:02
13
English
Installation
Closet installation

and control wiring.
1. Remove the top shipping cover and corner posts.
2. Remove the bottom shipping cover.
3. Remove the blower and control box access panel (door).
4. Remove the coil compartment access panel (door).
5. Place the unit into position by sliding the unit over the duct opening until the opening in the unit lines up with the duct

6. 

7. 

8. Connect the electrical supply wires and the control wires in the control box.
9. Connect the refrigerant lines to the coil. DRY NITROGEN MUST BE FLOWED THROUGH REFRIGERANT LINES DURING
SOLDERING OPERATION.
10. Re-install the coil compartment access panel (door) and secure with the screws that were removed in step 3.
11. Re-install the blower and control box access panel (door) and secure with the screws that were removed in step 2.
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 13 2020-02-05 오후 4:15:02
14
English
Installation
NOTE


service port on the suction pipe. Ensure that the service port cap is installed before pressurizing the system.
Air Handlers with DX type evaporator coils require liquid and suction piping sized in accordance with condensing unit
manufacturer’s instructions. The evaporator coils have sweat copper connections. Refrigerant lines should be soldered
with silver solder or high temperature brazing alloy.
DRY NITROGEN MUST BE FLOWED THROUGH REFRIGERANT LINES DURING SOLDERING OPERATION.
REFER TO OUTDOOR UNIT INSTALLATION MANUALS FOR PRESSURE CHECKING AND VACUUM DRYING
PROCEDURES.
There are two refrigerant pipes of differing diameters:
 A smaller one for the liquid refrigerant
 A larger one for the gas refrigerant
 The inside of copper pipe must be clean & have no dust.
Prepare the connecting pipe referring to the list below.
 Refrigerant pipe diameters (inches)
12 18 24 30 36 48 54 60 72
Liquid pipe 1/4 1/4 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Gas pipe 1/2 1/2 5/8 5/8 5/8 5/8 3/4 3/4 3/4
Cutting the pipes
1. Make sure that you prepared the required tools. (pipe cutter, reamer, aring tool and pipe holder)
2. If you want to shorten the pipe, cut it using a pipe cutter ensuring that the cut edge remains at 90° with the side of the pipe.
There are some examples of correctly and incorrectly cut edges below.
Oblique
Rough
Burr
90
Refrigerant piping
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 14 2020-02-05 오후 4:15:03
15
English
Installation
Leak test
LEAK TEST WITH NITROGEN (before opening valves)
In order to detect basic refrigerant leaks, before recreating the vacuum and recirculating the R-410A, it’s responsible of
installer to pressurize the whole system with nitrogen (using a pressure regulator) at a pressure above 595 PSI (4.1MPa).
LEAK TEST WITH R-410A (after opening valves)
Before opening valves, discharge all the nitrogen in the system and create vacuum. After opening valves check leaks using
a leak detector for refrigerant R-410A.
CA
UTION
Discharge all the nitrogen to create a vacuum and charge the system
Leak
check
Insulation
Once you have checked that there are no leaks in the system, you can insulate the piping and hose.
1. To avoid condensation problems, place T13.0mm (0.51”) or thicker
Acrylonitrile Butadien Rubber separately around each refrigerant pipe.
 You can contact the gas side and liquid side pipes but the pipes should not
be pressed together tightly.
 When contacting the gas side and liquid side pipe, use 1 grade thicker
insulator.
NOTE
Always make the seam of pipes face upwards.
2. Wind insulating tape around the pipes and drain hose avoiding to compress the
insulation too much.
3. Finish wrapping insulating tape around the rest of the pipes leading to the
outdoor unit.
4. The pipes and electrical cables connecting the indoor unit with the outdoor unit

Leak check
NBR [T13.0mm (0.51”) or thicker]
Insulation
Indoor unit
Be sure to
overlap the
insulation
Gas pipe
Insulation
Liquid pipe
Insulation pipe
CAUTION
All refrigerant connection must be accessible, in order to permit
either unit maintenance or removing it completely.
CA
UTION

body without a gap.
Performing leak test & insulation
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 15 2020-02-05 오후 4:15:03
16
English
Performing leak test & insulation
Installation
5. Select the insulation of the refrigerant pipe.
 Insulate the gas side and liquid side pipe referring to the thickness according to the pipe size.
 Indoor temperature of 86 °F(30 °C) and humidity of 85% is the standard condition. If install in a high humidity
condition,use one grade thicker insulator by referring to the table below. If installing in an unfavorable conditions,
use a thicker wall insulation.
 Insulators heat-resistance temperature should be more than 248 °F (120 °C).
Pipe
Outer diameter
Insulation Type (Cooling/Heating)
Remarks
General [30°C (86°F),
85% or below]
High humidity [30°C
(86°F), more than 85%]
EPDM, NBR
mm inch mm inch mm inch
Liquid pipe
6.35~9.52 1/4~3/8 9 3/8 9 3/8
Internal
temperature
is higher
than 248 °F
(120 °C)
12.7~50.8 1/2~2 13 1/2 13 1/2
Gas pipe
6.35 1/4 13 1/2 19 3/4
9.52~25.4 3/8~1 19 3/4 25 1
28.58~44.45 1 1/8~1 3/4 19 3/4 32 1 1/4
50.8 2 25 1 38 1 1/2
 When installing insulation in places and conditions below, use the same insulation that is used for high humidity
conditions.
<Geological condition>
High humidity places such as shoreline, hot spring, near lake or river, and ridge (when the part of the building is
covered by earth and sand.)
<Operation purpose condition>
Restaurant ceiling, sauna, swimming pool etc.
<Building construction condition>
The ceiling frequently exposed to moisture and cooling is not covered.
e.g. The pipe installed at a corridor of a dormitory and studio or near an exit that opens and closes frequently.
The place where the pipe is installed is highly humid due to the lack of ventilation system.
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 16 2020-02-05 오후 4:15:03
17
English
Installation
 System refrigerant volume is based on linear feet of liquid line pipe and indoor equipment model/quantity.
 Refer to the outdoor unit installation manuals for information regarding refrigerant volume for system components.
 See table below for additional refrigerant volumes for each air handler.
Model Additional refrigerant per indoor unit (oz.)
AM012TNZDCH/AA 11.6
AM018TNZDCH/AA 17.6
AM024TNZDCH/AA 17.6
AM030TNZDCH/AA 29.3
AM036TNZDCH/AA 31
AM048TNZDCH/AA 41.6
AM054TNZDCH/AA 44.8
AM060TNZDCH/AA 59.6
AM072TNZDCH/AA 59.6
Additional refrigerant
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 17 2020-02-05 오후 4:15:03
18
English
Installation
The air handlerA” coil drain pan has two ¾” NPT female primary and two secondary connections (left or right hand). The

minimum trap and each run in such a manner as to provide enough slope for adequate drainage to a visible area. Do not
Prime drain with water before operating the unit by pouring water
into the condensate pan. Cap unused connections.
2" minimum
2" minimum
Anti-syphon air vent
Refrigerant pipe
conections
Horizontal left
(right to left)
drain
connections
Horizontal right
(left to right)
drain pan
opening
2" minimum
Typical Condensate Traps
CA
UTION
 Make sure to keep the drain hose from getting tangled or loosened (on the connection part).
 Insulate all condensate pipes connected to the indoor unit to prevent condensation formation.
Condensate formation on condensate pipes can lead to property damage and unsafe environment
conditions.
When passing the drain hose through the hole drilled in the wall, make sure to avoid following cases.
CA
UTION
 Since the draining is of natural drain type, install the drain hose in downward direction.
 If you do not tie the drain hose with a cable tie, leakage may occur
 Drain pipe may get clogged if there is any foreign substances within the drain pan, so you must remove
any foreign substances after completing the installation.
Drain pipe installation
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 18 2020-02-05 오후 4:15:03
19
English
Installation
1. Pour water into the condensate pan.
2. Make sure that draining is done properly by checking end of the drain pipe.
3. If water leakage occurs, make sure the indoor unit is level. Also verify the drain pipe is installed with a downward slope away
from the indoor unit.
CA
UTION
 After connecting the drain pipe to the indoor unit, you must perform leakage test. If the drain test has
not done properly, water may get into the indoor and cause property damage.
 Empty the condensation water in the drain pan before any repair/maintenance service.
Water leakage test
Drain pipe insulation
Fix securely without any gap.
Indoor unit
CA
UTION
 You must insulate drain pipes.
 Make sure to prevent any gap between the insulation on drain pipe elbows.
 Make sure that insulation is overlapped.
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 19 2020-02-05 오후 4:15:04
20
English
Installation
WARNING
 For personal safety be sure to turn the electrical power “OFF” at the main entrance (Home
Circuit Breaker Box) and at the unit control box circuit breakers before attempting any service or
maintenance operations. Homeowners should never attempt to perform any maintenance which
requires opening the air handler control box door.
 This air handler is not equipped with a shield that covers the line voltage electrical supply wires and
the circuit breaker connections. Take precautions to prevent accidental electrical shock. Be sure to
turn the electrical power “OFF” at the main entrance (Home Circuit Breaker Box) and at the control box
circuit breakers before removing the front panel.
Power supply wiring
 The unit internal wiring is complete except for the power supply and control wires.
 The use of cable connectors on incoming power supply wires to relieve any strain on wiring is recommended.
 Follow the steps below to connect the power supply wires.
 Supply voltage is 208/240V, 1ø, 60 Hz.
 If you are installing optional heat kits, refer to the heat kit installation instructions for line voltage connection
instructions
Single circuit line wiring connections
CA
UTION
If an accessory heat kit is installed, power must enter the unit on the top or the top-left side of the unit as
shown below (A).
1. Before wiring work, you must turn off all power source.
2. Indoor unit power should be supplied through the breaker
(ELCB or MCCB+ELB ) separate from the outdoor power.
ELCB : Earth Leakage Circuit Breaker
MCCB : Molded Case Circuit Breaker
ELB : Earth Leakage Breaker
3. Only copper power cables should be used.
4. Remove the blower and control box access panel (door).
5. Install the cable connectors on the 7/8” diameter holes on the right
side of the control box.
6. Insert the wires through the holes in the casing and through the
cable connectors.
7. Connect the black supply wire to the L1[1(L)] high voltage connection
terminal with compressed ring terminals.
8. Connect the white supply wire to the L2[2(N)] high voltage
connection terminal with compressed ring terminals.
9. Connect the green wire to the ground lug near the supply wire
connections with a compressed ring terminal and tighten the ground
screw. Make sure to leave extra slack in the ground wire to allow
service to the unit without disconnecting the ground wire.
A
C
A
A
B
Left side Right side
A - Power conduit connection opening
(must use when installing accessory electric heat kit).
B - Power conduit connection opening
(do not use when installing accessory electric heat kit).
C - Communication wire conduit connection opening

the air handler or the tables in this manual for more information.
IMPORTANT - Refer to the NEC National Electrical Code (NFPA 70) or the Canadian Electrical Code, Part I (CSA C22.1) and
local codes for wiring material requirements.
Wiring Work
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 20 2020-02-05 오후 4:15:04
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92

Samsung AM036TNZDCH/AA Guide d'installation

Catégorie
Climatiseurs split-system
Taper
Guide d'installation
Ce manuel convient également à

dans d''autres langues