Compur Statox 501 IR Manuel utilisateur

Taper
Manuel utilisateur

Ce manuel convient également à

Statox 501 IR Statox 501 IR Sensor Head
Manuel
Manual
Contenu
Contents
1. Instructions de sécurité 1. Safety instructions
2. Construction et fonctions 2. Construction and function
3. Montage et connections 3. Mounting and connections
3.1 Montage murale 3.1 Wall mounting
3.2 Branchement du transmetteur 3.2 Connecting the transmitter
3.3 Raccordement au module de contrôle Statox 501 3.3 Connection to the Statox 501 control modul
3.4 Raccordement à tout autre contrôleur ou PCS 3.4 Connection to any other controller or a PCS
4. Démarrage et Menu 4. Start-up and password menu
4.1 Réglage du zéro et du span avec un gaz étalon 4.1 Zero and span adjustment with gas
4.2 Réglage de l’amplificateur 4.2 Amplifier adjustment
4.3 Test des sorties 4-20 mA 4.3 Testing the analog output
4.4 Choix du signal de sortie en cas de mode service 4.4 Selection of the output signal in the service mode
4.5 Programmation du gaz mesuré 4.5 Programming the measuring gas
5. Remplacement du capteur 5. Sensor replacement
6. Maintenance
6. Maintenance
7. Accessoires et pièces détachées
7. Accessories and spare parts
8. Etats et messages d’erreur
8. Status and error messages
8.1 Messages d’état de fonctionnement 8.1 Status messages
8.2 Messages d’erreur 8.2 Error messages
9. Caractéristiques techniques
9. Technical data
10. Déclaration de conformité CE
10. CE-Declaration of conformity
*************** ***************
1. Instructions de sécurité 1. Safety instructions
Le Statox 501 IR est un transmetteur de sécurité
intrinsèque de groupe II catégorie 2. Il mesure la
concentration des gaz combustibles at des vapeurs
d’hydrocarbures. Il possède un grand niveau de sécurité
et peut être installé en zone 1 et 2
Merci de suivre les instructions suivantes:
Le transmetteur est un appareil de sécurité
intrinsèque. Toutes les règles concernant l’installation
d’équipement anti-déflagrant (ex DIN EN 60079-14,
sections 6, 9 et 10 ) devront être respectées.
Le transmetteur doit exclusivement fonctionner avec
une tension de 18-29VDC (sécurité en très basse
tension).
Le transmetteur ne doit pas être ouvert tant que son
alimentation n’est pas débranchée.
Seulement les pièces détachées et accessoires de
COMPUR doivent être utilisés..
Toute les vis doivent être sérées avant de brancher le
transmetteur.
Faire fonctionner le transmetteur avec un boîtier
endommagé n’est pas sûre.
Le transmeteur ne doit pas fonctionner dans un
environnement en dehors des spécifications.
Le certificat de conformité ne comporte pas de test de
performance.
Tous les avertissements ci-dessus doivent être
observés. Une installation ou le raccordement
incorrecte annulera la protection anti-déflagrante et
sera ainsi dangereux pour la vie et les biens.
The Statox 501 IR is an explosion proof transmitter rated
for use in group II category 2 areas. It measures the
concentration of combustible gases and the vapors of
hydrocarbons. It has a high degree of safety and can be
installed in zone 1 and 2.
Please observe the following instructions:
The transmitter is an explosion proof device. All
regulations regarding installation of explosion proof
equipment (i. e. DIN EN 60079-14, section 6, 9 and 10)
should be observed.
The transmitter must be exclusively operated with 18 –
29 V DC (safety extra-low voltage).
The transmitter may not be opened unless it is
disconnected from the power supply.
Only original Compur spare parts and accessories must
be used.
All screws must be tightened before operating the
transmitter.
Operating the transmitter with a damaged housing is
unsafe.
The transmitter must not be operated in any
environment outside of the approval rating.
The certificate of conformity does not include a
performance approval.
All of the above warnings must be observed. Incorrect
installation or connection will void the explosion proof
rating and thus be dangerous to life and assets.
2. Construction et fonctions 2. Construction and Function
R
1 Support
2 Presse etoupe
3 Borne au sol
4 Compartiment électronique
avec plaque signalétique: type,
n° de série, date de fabrication
5 Compartiment du capteur
6 Anneau pour sangle
7 Protection pour éclaboussure
8 Adaptateur de calibartion
9 LED de service
10 Affichage
11 Vis bouchon
10
8
7
6
9
11
4
5
3
2
1
1 Mounting bracket
2 Cable gland
3 Grounding terminal
4 Electronic compartment
with type plate,
serial number / date code
5 Sensor compartment
6 Ring for holding strap
7 Splash guard
8 Calibration adapter
9 Service LED
10 Display
11 Plug screw
Le Statox 501 IR détecte les gaz combustibles (Méthane,
Butane) et les vapeurs (Méthanol, Toluène) dans une
gamme de 0 à 100 % LIE. La tête de détection est un
transmetteur 4-20 mA. Il peut être utilisé avec le module
de contrôle dédié Statox 501 ou avec tout autre système
de contrôle de procédé.
Support
Le support et boîtier terminal sont fabriqués en polyamide
renforcé de fibres conductrices. Il est de sécurité accrue
pour l’utilisation dans des environnements explosifs
(EExe), et est livré avec un presse étoupe (M20) et une
vis bouchon de l’autre côté. Un second presse étoupe
peut remplacer cette vis en option.
Boîtier du tranmetteur
Le boîtier en acier inoxydable du transmetteur se
compose d’une partie supérieure et inférieure anti-
déflagrantes. Il contient l’électronique, le capteur et
l’affichage LED à trois chiffres. L’orifice de la sonde est
protégé contre les dommages de l’eau par un filtre anti-
éclaboussure.
Capteur
Le capteur est un capteur NDIR qui consiste en un source
de lumière et deux photo détecteurs. La longueur d’onde
de mesure est calibré sur la longueur d’onde d’absorption
de la liaison C-H des hydrocarbures (3,4 µm). Plus il y a
de molécules de gaz dans le faisceau de lumière (plus la
concentration du gaz est grande) plus la lumière infra
rouge sera absorbée. Le détecteur de référence travaille
à une longueur d’onde différente à laquelle aucune
absorption n’aura lieu. Cela permet ainsi de compenser
les effets de la poussière, de l’humidité ou des variations
de l’intensité de la source lumineuse.
Adaptateur de calibration
L’adaptateur optionnel de calibration se branche sur la
partie inférieure du détecteur. Il est équipé d’un raccord
pour tube 4-6mm et de deux boutons magnétiques. Ces
boutons poussoirs permettent d’accéder au menu, pour la
calibration et le réglage des différents paramètres.
L’utilisation avec la sortie de gaz optionnelle permet de
travailler avec un débit. Pour prévenir toute fuite, le joint
ne doit pas être endommagé et toujours être fixé
solidement dans sa nervure. L’adaptateur peut être fixé
de manière permanente au détecteur avec deux vis.
The Statox 501 IR detects combustible gases (e.g.
Methane, Butane) as well as vapors (e.g. Toluene,
Methanol) in the range of 0 - 100% LEL. The sensor head
is a 4 - 20 mA transmitter. It can be used in combination
with the dedicated Statox 501 controller or any process
control system.
Mounting bracket
The mounting bracket / terminal box is made of conductive
fiber re-enforced polyamide. It features increased safety for
use in explosive environments (EEx e), and comes with one
cable gland (M 20) and one screw plug on the other side.
An optional second cable gland can replace this.
Transmitter Housing
The stainless steel transmitter housing consists of a top
and bottom part, which are rated as explosion proof. It
contains the electronics, the sensor and the three-digit LED
display. The sensor orifice is protected from water damage
by a disposable splash guard.
Sensor
The sensor is a NDIR sensor consisting of a light source
and two photo detectors. The measuring wavelength is
calibrated to the absorption wavelength of the C-H bond of
hydrocarbons (3,4 µm). The more gas molecules are in the
way of the light beam (i.e. the higher the gas concentration
is) the more infrared light will be absorbed. The reference
detector works at a wavelength in which no absorption
takes place to compensate for dust, humidity and variations
of light source intensity.
Calibration adapter
The optional calibration adapter can be connected to the
bottom side of the sensor head. It has a gas intake for a 4 x
6 mm tube and two magnetic pins. The pins operate Hall
sensors allowing you to access the password-protected
menu, for calibration and setting parameters.
Used with an optional gas outlet, it can serve as a gas
adapter for flow applications. To avoid leaks, the integrated
O-ring must be undamaged and always be fitted securely in
its groove. The calibration adapter can permanently be
fixed to the transmitter with 2 screws.
3. Montage et connections
3. Mounting and Connections
3.1 Montage murale
3.1 Wall Mounting
Utiliser le plan de forage inclus pour placer les trous du
support. Enlever le support du transmetteur.
Use the enclosed drilling plan to position the mounting
holes. Remove the mounting bracket / terminal box from
the transmitter. Fasten it to the wall with 6 mm screws.
3.2 Branchement du transmetteur 3.2 Connecting the Transmitter
Reliez la sangle aux anneaux situés à l’arrière du
détecteur afin de pouvoir le maintenir au support. Ceci
permettra de relier les fils sans avoir à tenir la partie
inférieure. Tirez le câble par le presse étoupe. Branchez
les fils aux bornes selon le schéma. Si deux câbles
séparés pour l’alimentation et le signal de sortie doivent
être utilisés, remplacez la vis bouchon par un deuxième
presse étoupe (Art. 561051).
Rassemblez le transmetteur et le boîtier inférieur,
maintenir le câble tendu en le tirant de l’extérieur pendant
le montage. Serrez les vis et le presse étoupe.
Connect the holding strap to the rings located on the back
side of the transmitter, allowing it to hang on the mounting
bracket. This will conveniently hold the transmitter in place
while connecting the wires. Pull the cable through the
gland. Connect the wires to the terminals according to the
schematics. If two separate cables for signal and power
supply are to be used, replace the plug screw with a
second cable gland (part. # 561051).
Couple the transmitter to the bottom side of the terminal
box, keeping the cable straight by pulling it outward while
mounting. Fasten screws and cable gland(s).
+
-
+
-
24V DC
4-20mA
Sangle
Holding strap
3
2
1
Note importante:
Utilisez uniquement des câbles protégés d’un diamètre
extérieur de 8 à 13 mm, et d’une section > 0.75mm
2
.
Mettre le bouclier à la terre seulement en salle de
contrôle.
Le joint doit être propre et intact, et doit rester dans sa
fente.
Serrez fortement à la main chacun des 4 boulons à
têtes creuses. Couple recommandé de 1 Nm.
Aucun espace ne doit être visible entre le transmetteur
et la boîte terminale..
Important note
Use only shielded cable with an outer diameter of 8 - 13
mm, sectional area > 0,75 mm
2
. Connect the shield to
ground only in the control room.
The O - ring must be clean and intact. It must stay in its
groove.
Fasten all 4 Allen screws hand tight. Recommended
torque 1 Nm.
No gap must be visible between the transmitter and
terminal box.
3.3 Raccordement au module de contrôle Statox
501
3.3 Connection to the Statox 501 Control Module
Lisez et observez le manuel d’utilisation du module de
contrôle Statox 501 !
Avant de relier le transmetteur, choisissez le programme
46 sur le contrôleur. Reliez le câble du signal (4-20mA)
aux bornes 4 (+) et 11 (-) du module de contrôle (voir
image ci-dessous).
Read and observe the operations manual of the Statox 501
controller!
Before connecting the transmitter, select program 46.
Connect the signal cable (4 - 20 mA) to terminals 4(+) and
11(-) of the control module (see picture).
Terminaux sur module de contrôle Statox 501 / Terminals Controlmodule Statox 501
3.4 Raccordement à tout autre contrôleur ou PCS 3.4 Connection to any other Controller or a PCS
Si vous reliez le Statox 501 IR à tout autre dispositif de
commande ou PCS, merci d’observer les caractéristiques
techniques au chapitre 9.
If you connect the Statox 501 IR to any other control device
or PCS, observe the technical data in chapter 9.
4. Démarrage et Menu 4. Start-up and Password Menu
Après avoir été relié à l’alimentation 24 V, le Statox 501
IR affiche la version du logiciel et le code du gaz (liste
4.5). Après le préchauffage, il entre dans le mode de
détection et affiche la concentration du gaz en % LIE.
Pour accéder au menu utilisateur, reliez l’adaptateur de
calibration au détecteur. Il y a deux boutons qui peuvent
être utilisés sur l’adaptateur. Le bouton Enter vous
permet de vous diriger vers le prochain point du menu ou
de sélectionner le code menu. Le bouton Reset R vous
ramène toujours au mode de mesure.
Appuyer sur le bouton Enter pour accéder au menu. Le
premier chiffre commencera à alterner. Choisissez le
code désiré en pressant le bouton enter dès que le
premier chiffre est correcte. Le second chiffre
commencera à alterner de la même manière. Choisissez
le second chiffre en poussant le bouton enter quand le
code sera correcte. Un diagramme illustré du menu est
disponible dans ce document..
After being connected to the 24 V power supply, the Statox
501 IR will display the software index and then the gas
code (see list 4.5). After warm up it will go into the detection
mode and start displaying the gas concentration.
To access the user menu, connect the calibration adapter
to the sensor head. There are 2 keys that can be used on
the calibration adapter. Pressing the Enter button will
bring you to the next menu point or selects a menu code. R
(Reset) always brings you back into the measuring mode.
Push the Enter button to access the password menu. The
first digit will start alternating. Select the desired code by
pushing the Enter button when the correct first digit
appears. The second digit will start alternating in the same
way. Select the secondary code by pushing the Enter
button when the correct digit arrives. An illustrated menu
diagram is available in this document.
4.1 Réglage du zéro et du span avec un gaz étalon 4.1 Zero and Span Adjustment
Sélectionner le menu 11.
Le transmetteur est pré calibré en usine. Avant d’effectuer
une calibration, laissez stabiliser le transmetteur au moins
une heure. Après avoir lancer le programme de
calibration, le zéro sera ajusté. Pendant ce processus
“000” clignotera sur l’affichage.
Le mise à zéro doit absolument être effectuée dans une
atmosphère propre. Si vous êtes incertain de
l’environnement, utilisez de l’air synthétique. Pour
retourner au mode de mesure et éviter la calibration,
appuyez sur le bouton Reset. En appuyant sur le bouton
enter
vous commencez la calibration. Le gaz étalon à
utiliser doit se situer entre 30 et 70% de la LIE. Branchez
le gaz étalon au raccord de l’adaptateur et commencez la
procédure de calibration en apuyant sur le bouton enter
Pendant la calibration “Go” s’affiche à l’écran. Après un
certain temps “Go” commence à clignoter, cela indique
que le gaz étalon a été détecté. Quand la calibration est
réussie, l’affichage indique Con. Jusqu’à cette affichage
aucune nouvelle donnée n’est enregistrée. En appuyant
sur le bouton Reset, vous retournerez dans le mode de
mesure et le transmetteur utilisera les anciennes données
de calibration.
La dernière étape pour la calibration est d’entrer la
concentration du gaz étalon. La dernière valeur utilisée
s’affiche à l’écran. Si aucun changement est nécessaire,
appuyez sur le bouton enter. Dès que le transmetteur est
Select code 11.
The transmitter is pre-calibrated. Before starting a
calibration allow at least 1 hour to stabilize. After initiating
the calibration program, the zero will be adjusted. During
this process the display will flash “000”.
Zeroing must be done in a clean atmosphere. If you are
unsure about the environment, use synthetic air. To return
to the measuring mode and avoid the calibration procedure,
press the reset button. Pushing Enter button starts a gas
calibration. Span gas with a concentration from 30 to 70%
LEL should be used. Connect the gas to the intake of the
calibration adapter and start the procedure by pushing the
Enter button.
During a calibration “Go” will appear on the display. After a
while “Go” will start flashing, indicating that the calibration
gas has been detected. When the calibration has been
successfully finished, the display will show Con. Up to this
point no new data has been stored. Pushing the Reset
button will return to the measuring mode and the transmitter
will use the previous calibration data.
The final step for calibration is entering the span gas
concentration. The last concentration used will appear on
the display. If no change is needed, push the Enter button.
Once the instrument has returned to the normal detection
mode, it verifies the calibration by displaying the actual gas
concentration.
retourné en mode de détection normal, il vérifie la
calibration en affichant la concentration actuelle du gaz
mesuré.
4.2 Réglage de l’amplificateur 4.2 Amplifier Adjustment
Sélectionner le menu 44.
Ce dispositif est utilisé pour obtenir la plus grande
précision après le remplacement du capteur, en ajustant
automatiquement le gain de l’amplificateur. Après cela, un
ajustement du zéro et une calibration avec un gaz étalon
sont nécessaire. Si vous n’êtes pas sûre que l’air ambiant
est propre, utilisez de l’air synthetique. Ceci sera indiqué
par CAL clignotant sur l’afficheur (voir 4.1).
Select code 44.
This feature is used to obtain the highest accuracy after
sensor replacement, by automatically adjusting the
amplifier gain. After this zero adjustment and a gas
calibration is mandatory. If you are not sure that ambient air
is clean, use synthetic air. This will be indicated by CAL
flashing on the display (see 4.1).
4.3 Test des sorties 4-20 mA 4.3 Testing the analog output
Sélectionner le menu 12.
Cette fonction permet à l’utilisateur de vérifier la sortie 4 -
20 mA. Vous pouvez simuler un signal de 4, 12 ou 20mA
en appuyant sur le bouton Enter. Vous pouvez retourner
au mode de mesure à tout moment en pressant le bouton
Reset.
Attention: Neutralisez les dispositifs périphériques
d’alarme afin d’éviter de fausses alarmes!
Select code 12.
This function allows the user to test the 4 - 20 mA output.
You can simulate a 4, 12, or 20 mA signal by pressing the
Enter button. Return to the measuring mode at any time by
pushing the Reset button.
Caution: Disable peripheral alarm devices to avoid false
alarms!
4.4 Choix du signal de sortie en cas de mode
service
4.4 Selection of the output signal in the service
mode
Sélectionner le menu 13.
Choisir la valeur du courantde sortie que vous désirez en
mode de service. Par défaut c’est la valeur de 2 mA.
Select code 13.
Select the current value to which the analog output shall be
set when in the service mode. Default setting is 2 mA.
4.5 Programmation du gaz mesuré 4.5 Programming the measuring gas
Pour programmer le gaz, entrer dans le menu 45.
Dans ce menu vous pouvez modifier la configuration
sortie d’usine. Chaque fois que vous changez le type de
gaz, une calibration vous sera demandée. Ceci est
visualisé par le signe CAL clignotant à l’écran. Assurez
vous, avant d’entrer dans ce menu, d’avoir tous les
accessoires nécessaires pour réaliser une calibration.
Liste des gaz:
1 Méthane
2 Propane
3 n-Butane
4 n-Pentane
5 c-Pentane
6 n-Hexane
7 Methanol
8 Propene
9 2-Propanol
To program the gas, enter menu 45.
In this menu you can alter the ex works setting. Whenever
you change the gas a new calibration is mandatory. This is
visualised by CAL flashing on the display. Make sure to
enter this menu only if you have everything on hand you
need for a gas calibration.
Gas list:
1 Methane
2 Propane
3 n-Butane
4 n-Pentane
5 c-Pentane
6 n-Hexane
7 Methanol
8 Propene
9 2-Propanol
5. Remplacement du capteur 5. Sensor Replacement
Débranchez l’alimentation du transmetteur. Placer la
sangle autour du support et l’attacher aux anneaux sur les
cotés afin de maintenir en place le compartiment du
capteur. Enlevez les 6 vis de la partie inférieure et
débranchez la sonde. Branchez le nouveau capteur et
rattachez le boîtier inférieur avec les anneaux sur l’arrière
Serrez les vis seulement à la force des mains. Le couple
recommandé est 3 - 3,5 Nm. Aucun espace ne doit être
visible entre les deux pièces. Chacune des 6 vis doit être
utilisée!
A la suite du remplacement du capteur, un ajustement du
gain (4.2) et une calibration avec un gaz étalon (4.1)
doivent être effectués!
Disconnect the transmitter from the power supply. Hold it in
place by fastening the holding strap to the rings on the
transmitters backside and hanging it around the mounting
bracket. Remove the 6 screws from the bottom part and
disconnect it. Plug the new sensor in and reattach the
bottom housing, with rings on the backside.
Fasten the screws only hand tight. The recommended
torque is 3 - 3,5 Nm. No gap must be visible between the
two parts. All 6 screws must be used.
Following the sensor replacement, a gain adjustment (4.2)
and gas calibration (4.1) must be performed.
CAL
R
R
4
5
PAr
don
1
9
Menucodes
Étape suivante
next step
retour au mode mesure
back to measuring mode
60 s timeout
R
R
R
CAL
R
Menu
Password menu
Mode de mesure
Measuring mode
Code du gaz
gas code
Version du
software
R
R
R
R
R
R
R
R
R
R
do
n
do
n
00
0
2
4
5
0
Co
n
1o
t
4.
4
4
2
0
1
2
1
3
1
2
1
.
1
.
1
1.
1
1
1S
t
4
PA
S
0
Ab
6
CAL
6A
S
6
o
00
0
-1
-
Diagramme du menu / Menu diagramm
6. Maintenance
6. Maintenance
Inspection visuel du boîtier pour être sûre qu’il est
intacte et que le filtre est propre
Ajustement du zéro : seulement si besoin
Calibration avec gaz étalon: l’intervale dépends des
régles locales
Ajustement du gain: seulement si besoin et après
chaque remplacement du capteur.
Visual inspection of the housing to make sure it is intact
and the splash guard is clean.
Zero adjustment: Only if needed.
Gas calibration: Interval according to local regulations.
Gain adjustment: Only if needed and after sensor
replacement.
7. Accessoires et pièces détachées
7. Accessories and Spare Parts
561053 Capteur IR
561051 Presse étoupe
561055 Filtre à éclaboussure
561057 Set de joint
562031 Adaptateur de calibration
561059 Adaptateur de 6mm pour sortie du gaz
561053 IR-Sensor
561051 Cable gland
561055 Splash guard
561057 O-Ring-Set
562031 Calibration adapter
561059 6mm-Adapter gas outlet
8. Etats et messages d’erreur
8. Status and Error Messages
8.1 Messages d’état de fonctionnement 8.1 Status Messages
La LED jaune clignote tant que le transmetteur est en
mode service.
La sortie analogique est fixée à 2 ou 4 mA.
The yellow LED will flash while the transmitter is in the
service mode.
The analog output is set to 2 resp. 4 mA.
Code d’erreur
Description
Remarque Error code Description Remark
Ajustement du gain
en cours
Optimisation du gain
Gain adjustment in
process
Optimizing gain
Caliration
Pendant la calibration
et le zéro
Gas calibration
startet
During gas
calibration and
zeroing
Entrer la
concentration du
gaz étalon
Dernière
concentration affiché
Enter span gas
concentration
Concentration
used last time on
display
Sélection du gaz
Gas selection
Effectué
Done
Ouvrir la bouteille
de gaz
Départ de la
calibration
Turn gas on
Start gas
calibration
Clignote losque le
gaz est détecté
When flashing span
gas is detected
Sortie analogique
en mode service
2 mA ou 4 mA
Current output in the
service mode
2 mA or 4 mA
Test de la sortie
analogique
4, 12, 20 mA
Current output test 4, 12, 20 mA
Acces au menu
Access menu
Ajustement du zéro
Pendant la calibration
ou après un
ajustement du gain
Zero adjustment
During gas
calibration or after
gain adjustment
Clignote lorsque la
pleine échelle est
dépassé
Flashing when the
measuring range is
exceeded
10
0
10
0
PA
r
PA
r
00
0
PA
S
IS
t
Io
t
6
o
6A
S
do
n
Co
n
CAL
Ab
6
00
0
PA
S
IS
t
Io
t
6
o
6A
S
do
n
Co
n
CAL
Ab
6
8.2 Codes d’erreur 8.2 Error Codes
Pour retourner au mode de mesure à partir d’un code
d’erreur, presser le bouton Reset.
Si une erreur est s’est produite, la LED jaune
s’allumera .
La sortie analogique sera de 0 mA dans le cas d’une
erreur fatale, autrement la sortie sera au choix à 2 ou
4 mA pour toute autre erreur.
To go from an error code back to the measuring mode,
press the Reset button.
If an error has occurred, the yellow LED will go on.
The analog output will be set to 0 mA in case of a fatal
error, otherwise the output will be 2 or 4 mA for all other
errors.
Code d’ereur Problème Raison potentielle Solution
Défaut du capteur
- Manque le capteur
- Capteur défectueux
Erreur fatale!
Remplacer le capteur.
Surcharge de
l’amplificateur
- Signal du capteur trop haut
- Erreur de hardware
Erreur fatale!
Ajuster le gain et calibrer. Si le
détecteur ne fonctionne pas
contacter l’usine
Timeout pendant la
caliration
- Pas de Gaz Etalon
- Concentration du Gaz Et trop faible
- Le capteur a perdu en sensibilité
L’appareil conserve sa calibration
précédente. Ouvrir le gaz, utiliser le
gaz approprié. Remplacer le capteur
apteur Zéro négatif - Dérive du zéro
Erreur fatale!
Ajuster le zéro.
Erruer d’EEPROM - Problème de hardware
Erreur fatale!
Contacter l’usine
Le zéro ne peut être
effectué
- Présence de gaz pendant
l’ajustement du zéro
L’appareil conserve sa calibration
précédente. Refaire le zéro en
utilisant de l’ai synthétique
Clignote: Demande de
calibration
- La calbration n’a pas été validée
après l’ajustement de l’amplification
(4.2) ou changement du gaz à
mesurer (4.5)
Erreur fatale!
Faire une calibration (4.1).
Clignote en alternance
avec la valeur mesurée
- La calibration n’a pas été validée
après le timeout
Faire une calibration (4.1).
Error code Problem Potential reason Trouble shooting
Sensor defective
- Sensor missing
- Sensor defective
Fatal Error!
Replace sensor.
Amplifier overload
- Sensor signal too high
- Hardware error
Fatal Error!
Adjust gain and calibrate. If it still
does not function, contact the
factory.
Timeout during calibration
- No span gas
- Span gas concentration too low
- Sensor has lost sensitivity
Continuous operation with origin
calibration data. Turn gas on, use
proper gas. Replace sensor.
Negative zero - Zero drift
Fatal Error!
Adjust zero.
EEProm Error - Hardware problem
Fatal Error!
Contact factory.
Zero could not be attained
- Gas present during zero
adjustment
Continuous operation with origin
calibration data. Repeat zero, use
synthetic air.
Flashing: Calibration
reqest
- no successful calibration after
amplifier adjustment (4.2) or
altering the measuring gas (4.5)
Fatal Error!
Calibrate (see 4.1).
flashing in change with
actual measuring value
- no successful calibration after
timeout
Calibrate (see 4.1).
CAL
CAL
CAL
CAL
E
r
6
E
r
5
E
r
4
E
r
3
E
r
2
E
r
1
E
r
6
E
r
5
E
r
4
E
r
3
E
r
2
E
r
1
9. Caratéristiques techniques
9. Technical Data
Nom du produit Transmetteur Statox 501 IR Product name Statox 501 IR Transmitter
Type 5370 063
Fabricant COMPUR Monitors, Munich
Echelle de mesure 0 - 100% UEG
Principe de mesure NDIR à 2 voies
Limite de détection 3% LIE Méthane
Affichage LED, trois digites
Temps de réponse CH
4
t
50
< 10s, t
90
< 25s
Précision (pleine échelle) < ± 2% LIE
Temps de chauffe 20 s
Spécifications atteintes après 30 min
Température d’utilisation -20°C à +44°C
Température de stockage -20°C à +60°C
Humidité 0 - 99% HR.
Pression 800 - 1100 hPa,
Déviation < ± 0,1% / hPa
Explosionsschutz EEx de IIC T5
Class instrument II 2 G
Certification BVS 04 ATEX E 006 X
Tension
24VDC (18-29VDC)
Puissance 1 Watt
Courant max. 80 mA à 24 V
Sorties 4-20 mA,Rmax 220 Ohm
Demande de service LED jaune clignote,
Sortie 2 ou 4mA
Erreu du système LED jaune allumée,
Sortie 2 ou 4mA,
erreur fatale 0 mA
Protection EN 60529 IP 67
Dimensions (LxlxP) 150x120x120mm
Instruction d’installation Capteur vers le bas et
position droite à ± 90°
Poids 3,1 kg
Matériaux PA et acier 1.4305
EMV EN 50270
Performance approuvée EN 61779-1 et -4
Type 5370 063
Manufacturer COMPUR Monitors, Munich
Measuring Range 0 - 100% LEL
Measuring principle 2-channel NDIR
Detectable limit 3% LEL Methane
Display LED, three digit
Response time, i.e. CH
4
t
50
< 10s, t
90
< 25s
Accuracy (full scale) < ± 2% LEL at RT
Warm up time 20 s
Specifications reached after 30 min
Temperature -20°C to +44°C (-4 to +112°F)
Storage Temperature -20°C to +60°C (-4 to +140°F)
Humidity 0 - 99% r.F.
Pressure range 800 - 1100 hPa,
Deviation < ± 0,1% / hPa
Approval EEx de IIC T5
Instrument class II 2 G
Certificate BVS 04 ATEX E 006 X
Voltage 24VDC (18-29VDC)
Power 1 Watt
Current max. 80 mA at 24 V
Output 4-20 mA, max. load 220 Ohm
Service request yellow LED flashing,
output 2 or 4mA
System failure yellow LED on,
output 2 or 4mA,
fatal error 0 mA
Protection class EN 60529 IP 67
Dimensions (HxWxD) ca. 150x120x120mm
(5,9x4,7x4,7in)
Installation instructions upright position ± 90° ,
sensor downwards
Weight ca. 3,1 kg (6,8 pound)
Material PA and Steel 1.4305
EMV according to EN 50270
Performance approval EN 61779-1 and -4
Les caractéristiques techniques de ce produit peuvent faire l’objet de
modifications sans préavis. Compur Monitors n’a pas de contrôle sur
l’utilisation de ses produits. Pour cette raison, il est de la responsabilité
de l’utilisateur de se renseigner sur nos produits afin de déterminer s’ils
sont adaptés à l’utilisation, à l’application et aux conditions envisagés.
Toutes les informations fournies ne font pas l’objet d’une garantie.
Compur Monitors se dégage de toute responsabilité pour toute utilisation
non conforme ou incorrecte, négligence, ou autre de ses produits et de
ses informations. Tout élément ou recommandation non contenus dans
ce document ne sont pas autorisés et ne peuvent en aucun cas
impliquer la responsabilité de Compur Monitors. Aucun élément décrit
dans ce manuel ne peut être assimilé à une recommandation
d’utilisation de produits qui sont sous la protection d’un brevet. Les
appareils sont fabriqués par Compur Monitors GmbH & Co. KG, Munich.
Les conditions générales de vente et de service de Compur Monitors
GmbH & Co. KG sont applicables.
Specifications are subject to change without notice, and are provided only for
comparison of products. The conditions, under which our products are used,
are beyond our control. Therefore, the user must fully test our products and/or
information to determine suitability for any intended use, application, condition
or situation. All information is given without warranty or guarantee. Compur
Monitors disclaims any liability, negligence or otherwise, incurred in
connection with the use of the products and information. Any statement or
recommendation not contained herein is unauthorized and shall not bind
Compur Monitors. Nothing herein shall be construed as a recommendation to
use any product in conflict with patents covering any material or device or its
use. No licence is implied or in fact granted under the claims of any patent.
Instruments are manufactured by Compur Monitors GmbH & Co. KG, Munich.
The General Conditions of Supply and Service of Compur Monitors GmbH &
Co. KG are applicable.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11

Compur Statox 501 IR Manuel utilisateur

Taper
Manuel utilisateur
Ce manuel convient également à

dans d''autres langues