Henny Penny CEC-106 Guide d'installation

Taper
Guide d'installation

Ce manuel convient également à

Model CEC-103, 104, 106, 108
2-1. INTRODUCTION This section provides the installation and unpacking instructions for
Henny Penny cold express case.
Installation of this unit should be performed only by a
qualified service technician.
Do not puncture the unit with any objects such as
drills or screws, or component damage or electrical
shock could result.
2-2. UNPACKING The Henny Penny cold express case has been tested, inspected,
and expertly packed to insure arrival at its destination in the best
possible condition. The grids are packed separately inside the
unit. The cabinet rests on a wooden skid and is then packed inside
a heavy cardboard carton with sufficient padding to withstand
normal shipping treatment.
To avoid damage to the components, do not lay the unit
on its side. If the unit has been on its side, the unit must
be in an upright position for at least 4 hours before power
is applied to the unit.
Check all components, for signs of being loose or dam-
aged, and make sure the system has refrigerant.
When moving the cold express case be careful not to
damage the refrigerent circuit.
Any shipping damage should be noted in the presence
of the delivery agent and signed prior to his or her
departure.
To remove the Henny Penny cold case from the carton:
1. Carefully cut banding straps.
2. Lift the carton off the unit.
3. Lift the unit off the skid.
303 2-1
SECTION 2. INSTALLATION
Model CEC-103, 104, 106, 108
2-2. UNPACKING
Take care when moving the unit to prevent personal
injury or damage to the refrigeration system. The units
weigh between 550 lbs. (250 kg) and 1200 lbs.
(544 kg).
4. Peel off any protective covering from exterior of the cabinet.
5. Install the shelves into unit.
6. Your cold express case is now ready for operation.
2-3. ELECTRICAL The cold express case is available as a 120 VAC, or 240VAC,
60 Hz., single phase unit, both for domestic and international use.
(See table below) The data plate, located on the left side of the
unit, specifies the correct electrical supply. The cold express
cases are shipped with cord and plug, and requires a grounded
receptacle with a separate electrical line protected by a fuse or
circuit breaker of the proper rating.
This unit must be adequately and safely grounded.
Refer to local electrical codes for correct grounding
procedures. If unit is not adequately grounded, electri-
cal shock could result.
To avoid electrical shock, this appliance must be
equipped with an external circuit breaker which will
disconnect all ungrounded (unearthed) conductors.
Refer to the table below for electrical ratings:
Model No. Volts Amps Phase Max. Fuse Size
CEC-103 120 18.3 1 20
CEC-104 240 12.6 1 20
CEC-106 240 10.9 1 30
CEC-108 240 16.1 1 30
(Continued)
2-2 503
Model CEC-103, 104, 106, 108
303 2-3
2-5. REFRIGERANT Design Pressure
INFORMATION High Low
CEC-103 R22 2 lbs (.9 kg) 175psig 30 psig
(12.1 bar) (2.1 bar)
CEC-104 R22 5 lbs (2.3 kg) 175psig 30 psig
(12.1 bar) (2.1 bar)
CEC-106 R22 6 lbs (2.7 kg) 175psig 30 psig
(12.1 bar) (2.1 bar)
CEC-108 R22 6 lbs (2.7 kg) 175psig 30 psig
(12.1 bar) (2.1 bar)
2-6. COMPRESSOR SIZE CEC-103 CEC-104
1/2 Horsepower 3/4 Horsepower
CEC-106 CEC-108
1-1/4 Horsepower 1-3/4 Horsepower
Refrigerant Type Amount of Refrig.
2-7. DRAIN CONNECTION Cold express cases do not require a plumbed drain.
2-4. LOCATION Place the cold express cases in an area where product can be
loaded and unloaded without interruption. For proper operation,
level the unit by adjusting the bolts under the case.
For maximum efficiency, units should be operated in an air-condi-
tioned environment, with maximum air temperature of 75° F
(24° C), and 55% relative humidity.
Wait at least 4 hours before plugging the unit into an
electrical supply. The gases and oils in the refrigeration
system need to settle before operating the compressor, or
damage to the compressor could result.
Model CEC-103, 104, 106, 108
2-8. FOOT PRINT DRAWING
CEC MODELS
DRAIN/ELECTRICAL BOX
2-4 1101
36
34
Ø1-5/8
Drain
(Egoutten dans la
pan sous le comptoir)
Refrigeration
Electrical
20
14-3/8
48-1/2
34
32
2
20
Ø1-5/8
Drain
(Egoutten dans la
pan sous le comptoir)
Refrigeration
Electrical
2
72-1/4
34
32
2
2
Ø1-5/8
Drain
(Egoutten dans la
pan sous le comptoir)
Refrigeration
2
Electrical
20
14-3/8
96
20
14-3/8
Drain
(Egoutten dans la
pan sous le comptoir)
Refrigeration
Electrical
Ø1-5/8
3-3/8
3-3/8
3-3/8
3-3/8
2
32
34
2
CEC-103 CEC-104
CEC-106 CEC-108
2
14-3/8
2-9. FLOURESCENT LIGHTING No. of Lights and Size
Model Canopy Shelves
CEC-103 1 - 24 in. (61.0 cm) 4 - 24 in. (61.0 cm)
CEC-104 1 - 36 in. (91.4 cm) 4 - 36 in. (91.4 cm)
CEC-106 1 - 24 in. (61.0 cm) 8 - 24 in. (61.0 cm)
1 - 36 in. (91.4 cm)
CEC-108 1 - 36 in. (91.4 cm) 8 - 36 in. (91.4 cm)
1 - 48 in. (122 cm)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Henny Penny CEC-106 Guide d'installation

Taper
Guide d'installation
Ce manuel convient également à

dans d''autres langues