Mammoth DF6SF Manuel utilisateur

Catégorie
Cheminées
Taper
Manuel utilisateur
SINGLE PACKAGE GAS HEATING / ELECTRIC COOLING UNIT
SINGLE PACKAGE DUAL FUEL - GAS HEAT / ELECTRIC HEAT PUMP UNIT
USER'S MANUAL
NON-CONDENSING MODEL
CONDENSING MODEL
WARNING AVERTISSEMENT
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could
result in serious injury or property damage.
RISQUE D’INCENDIE OU D’EXPLOSION
Si les consignes de sécurité ne sont pas suivies à la
lettre, cela peut entraîner la mort, de graves blessures
ou des dommages matériels.
Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use
any phone in your building.
Leave the building immediately.
Immediately call your gas supplier from a
neighbors phone. Follow the gas suppliers
instructions.
If you cannot reach your gas supplier, call the
fire department.
Installation and service must be performed by
a qualified installer, service agency or the gas
supplier.
– Ne pas entreposer ni utiliser de l’essence ni d’autres
vapeurs ou liquides inflammables dans le voisinage
de cet appareil, ni de tout autre appareil.
QUE FAIRE SI UNE ODEUR DE GAZ EST
DÉTECTÉE
Ne mettre en marche aucun appareil.
Ne toucher aucun interrupteur électrique; ne pas
utiliser de téléphone dans le bâtiment.
Quitter le bâtiment immédiatement.
Appeler immédiatement le fournisseur de gaz
en utilisant le téléphone d’un voisin. Suivre les
instructions du fournisseur de gaz.
Si le fournisseur de gaz n’est pas accessible, appeler
le service d’incendie.
L’installation et l’entretien doivent être effectués
par un installateur ou une entreprise d’entretien
qualifié, ou le fournisseur de gaz.
DO NOT DESTROY THIS MANUAL. READ ALL INSTRUCTIONS IN THIS MANUAL AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
NE PAS DÉTRUIRE. LIRE TOUTES LES INSTRUCTIONS DONNÉE DANS LE MANUEL ET CONSERVER EN UN LIEU SÛR POUR RÉFÉRENCE ULTÉRIEURE.
2
Please read all information in this manual thoroughly and
become familiar with the capabilities and use of your appliance
before attempting to operate or maintain this unit. Pay attention
to all safety warnings and any other special notes highlighted
in the manual. Safety markings are used frequently throughout
this manual to designate a degree or level of seriousness and
should not be ignored.
WARNING indicates a potentially hazardous situation that if
not avoided, could result in personal injury or death. CAUTION
indicates a potentially hazardous situation that if not avoided,
may result in minor or moderate injury or property damage.
Keep this literature where you have easy access to it in the
future. If a problem occurs, check the instructions and follow
recommendations given. If these suggestions don’t eliminate
your problem, call your servicing contractor. Do not attempt to
service this unit yourself!
Under no circumstances should the appliance owner attempt to
install and/or service this equipment. Some local codes require
licensed installation / service personnel for this type of equipment.
Improper service, adjustment, or maintenance may cause
explosion, fire, electrical shock or other hazardous conditions
which may result in personal injury or property damage.
WARNING:
To avoid possible equipment damage, fire, or
personal injury, the following instructions must
be observed regarding unit maintenance and
operational procedures.
• To achieve optimum performance and minimize equipment
failure, it is recommended that periodic maintenance be
performed on this unit. The ability to properly perform
maintenance on this equipment requires certain mechanical
skills and tools. Please consult your dealer for maintenance
information and availability of maintenance contracts.
The area around the gas heating / electric cooling unit and the
vicinity of any other gas appliances must be kept clear and
free of combustible materials, gasoline, and other flammable
vapors and liquids. Do not store or use flammable items such
as paint, varnish, or strippers in the vicinity of the unit.
Do not use the area around the unit as a storage area. This area
must be kept clean and clear of loose or exposed insulation
materials. Examine the unit’s area when it is installed or when
insulation is added, since some insulation materials may be
combustible.
Do not use this furnace if any part has been under water. A
flood-damaged furnace is extremely dangerous. Attempts
to use the furnace can result in fire or explosion. A qualified
service agency should be contacted to inspect the furnace
and to replace all gas controls, control system parts, electrical
parts that have been wet or the furnace if deemed necessary.
• Ne pas utiliser cet appareil de chauffage s’il a été en partie
immergé dans l’eau. Un appareil de chauffage endommagé
par une inondation est extrêmement dangereux. S’il est
utilisé, un incendie ou une explosion peut se produire. Il faut
avoir recours à une entreprise d’entretien qualifiée pour faire
inspecter l’appareil de chauffage et remplacer toutes les
commandes de gaz, les pièces du système de contrôle, les
pièces électriques qui sont entrées en contact avec l’eau ou
l’appareil de chauffage lui-même, si cela est jugé nécessaire.
Familiarize yourself with the controls that shut off the gas and
electrical power to the unit. If the unit is to be shut down for an
extended period of time, turn off both the gas and electrical
power. For your safety always turn off both the gas and
electrical power before performing service or maintenance
on the furnace. If the gas supply to the unit must be shut off,
refer to the gas valve label (Figure 3, page 6).
Combustion Air Supply
The gas heating/electric cooling unit needs an adequate supply
of combustion and ventilation air for proper and safe operation.
Do not block or obstruct air openings on the unit or air openings
supplying the area where it is installed.
If the unit is operated with inadequate combustion air supply,
the flame roll-out control switch located above the burners will
open, turning off the gas supply to the burners. The flame roll-
out control is a manual reset device. Do not attempt to reset
this device yourself! Call your servicing contractor.
WARNING:
Combustion air must not be drawn from a corrosive
atmosphere.
To maximize heat exchanger life, the combustion air must be
free of chemicals which form corrosive acidic compounds in the
combustion gases.
IMPORTANT NOTE:
Do not store any chemicals with flammable or caustic
vapors near the vent termination. Some examples of these
chemicals are:
CARBON TETRACHLORIDE • GASOLINE/KEROSENE
CEMENTS, GLUES, PAINT
REMOVERS, VARNISHES, ETC. HALOGEN TYPE REFRIGERANTS
CLEANING SOLVENTS HYDROCHLORIC ACID
CHLORINE BASED SWIMMING
POOL CHEMICALS
MASONRY ACID WASHING
MATERIALS
CHLORINATED WAXES &
CLEANERS
PERMANENT WAVE SOLUTIONS
DE-ICING SALTS OR CHEMICALS WATER SOFTENING CHEMICALS
Ductwork
WARNING:
Failure to prevent products of combustion from
being circulated into the occupied space can create
potentially hazardous conditions including carbon
monoxide poisoning that could result in personal
injury or death.
The duct connections must be physically sound and sealed to
the unit’s casing to prevent products of combustion from entering
the occupied space.
The return air and circulating air ductwork must not be connected
to any other heat producing device such as a fireplace insert,
stove, etc. Doing so may result in fire, explosion, personal injury,
carbon monoxide poisoning, or property damage.
IMPORTANT SAFETY INFORMATION
3
ABOUT THE GAS HEATING / ELECTRIC
COOLING UNIT
This gas heating unit with electric cooling has been designed
and built to provide many years of safe and dependable comfort,
providing it is properly installed and maintained. With regular
maintenance, this unit will operate satisfactorily year after year.
Abuse, improper use, and/or improper maintenance can shorten
the life of the appliance and create unsafe hazards. A regular
service and maintenance schedule should be established to
ensure efficient and safe operation of the unit. See System
Maintenance on page 5.
OPERATING INSTRUCTIONS
Thermostat styles vary. Some models may not include the AUTO
mode and others will have the AUTO in place of the HEAT
and COOL. Others may include all three. Please refer to the
thermostat’s User manual for detailed programming instructions.
The thermostat should be mounted about 5 feet above the floor
on an inside wall and not on an outside wall or other location
where its operation may be adversely affected by radiant heat
from fireplaces, sunlight, or lighting fixtures, and convective heat
from warm air registers or electrical appliances.
Cooling Operation (1 or 2 Stage Operation)
1. Set the thermostat system mode to COOL and the thermostat
fan mode to AUTO. See Figure 1.
2. Set the thermostat temperature selector to the desired
temperature level. The outdoor fan, compressor, and
indoor blower will all cycle on and off to maintain the indoor
temperature at the desired cooling level.
For 2-Stage Models Only: If Stage 1 cool does not satisfy the
thermostat demand, stage 2 cool will energize. The outdoor
compressor and indoor blower will ramp to high speed.
NOTE: If the temperature level is re-adjusted, or the system
mode is reset, the fan and compressor in the outdoor unit
may not start immediately. There may be a protective timer
circuit in the thermostat which holds the compressor and
the outdoor fan off for approximately 5 minutes following a
previous operation or the interruption of the main electrical
power.
Heating Operation (1 or 2 Stage Operation)
1. Set the thermostat system mode to Heat and the thermostat
fan mode to AUTO. See Figure 1.
2. Set the thermostat temperature selector to the desired
temperature level. The indoor blower and gas heat module
will cycle on and off to maintain the indoor temperature at
the desired heating level.
For 2-Stage Models Only: If Stage 1 heat does not satisfy the
thermostat demand, stage 2 heat will energize. The inducer
motor and indoor blower will ramp to high speed.
Figure 1. Digital Thermostat
FAN
MODE
TEMPERATURE
SELECTOR
SYSTEM
MODE
WARNING:
Should the gas supply fail to shut off or if overheating
occurs, shut off the gas valve to the furnace before
shutting off the electrical supply.
AVERTISSEMENT:
En cas de température excessive, ou s’il est
impossible de couper l’alimentation en gaz,
fermer le robinet manuel d’alimentation en gaz
du générateur d’air chaud avant de couper
l’alimentation électrique..
System Shutdown
Set the thermostat system mode to OFF (see Figure 1) and
the thermostat fan mode to AUTO. NOTE: The system will not
operate, regardless of the thermostat temperature selector’s
setting.
Continuous Indoor Blower Operation
The continuous indoor blower operation is typically used to
circulate the indoor air to equalize a temperature imbalance
due to a solar load, cooking, or fireplace operation.
Set the thermostat fan mode to ON (see Figure 1). The indoor
blower will start immediately and will run continually until the fan
switch is reset to AUTO. NOTE: On some thermostat models
the setting may be called CONT.
The continuous indoor blower operation can be obtained with
the thermostat system switch set in any position, including OFF.
GAS HEATING / ELECTRIC COOLING UNITS
4
ABOUT THE HEAT PUMP
(Dual Fuel Models Only)
Your heat pump is a unique, all weather comfort-control appliance
that will heat and cool your building year round and provide
energy saving comfort. It’s an unknown fact that heat is always
in the air, even when the outside temperature is below freezing.
The heat pump uses this basic law of physics to provide energy
saving heat during the winter months.
In colder temperatures, the heat pump performs like an air
conditioner run in reverse. Available heat energy outside the
building is absorbed by the refrigerant and exhausted inside.
This efficient process means you only pay for “moving” the heat
from the outdoors to the indoor area. You do not pay to generate
the heat, as is the case with more traditional furnace designs.
During summer, the heat pump reverses the flow of the heat-
absorbing refrigerant to become an energy-efficient, central air
conditioner. Excess heat energy inside the home is absorbed
by the refrigerant and exhausted outside the building.
OPERATING INSTRUCTIONS
A thermostat with fossil fuel back-up heat capability is required
to operate the Dual Fuel iHybrid™ heat pump system. The
thermostat should be mounted about 5 feet above the floor on
an inside wall and not on an outside wall or other location where
its operation may be adversely affected by radiant heat from
fireplaces, sunlight, or lighting fixtures, and convective heat from
warm air registers or electrical appliances.
Thermostat styles vary. Some models will not include the AUTO
mode and others will have the AUTO in place of the HEAT
and COOL. Others may include all three. Please refer to the
thermostat’s User Manual for detailed programming instructions.
NOTE: If the temperature level is re-adjusted, or the system
mode is reset, the fan and compressor in the outdoor unit
may not start immediately. A protective timer circuit holds the
compressor and the outdoor fan off for approximately 5 minutes
following a previous operation or the interruption of the main
electrical power.
Cooling Operation (1 or 2 Stage Operation)
1. Set the thermostat system mode to COOL and the thermostat
fan mode to AUTO. See Figure 1.
2. Set the thermostat temperature selector to the desired
temperature level. The outdoor fan, compressor, and
indoor blower will all cycle on and off to maintain the indoor
temperature at the desired cooling level.
NOTE: If Stage 1 cool does not satisfy the thermostat demand,
stage 2 cool will energize. The outdoor compressor and indoor
blower will ramp to high speed.
Heating Operation - Heat Pump Mode
1. Set the thermostat’s system mode to HEAT or AUTO and
change the fan mode to AUTO. See Figure 1 (pg 3).
2. Set the temperature selector to the desired temperature level.
The compressor, outdoor fan, and blower motor will cycle
on and off to maintain the indoor temperature at the desired
heating level.
NOTES:
If Stage 1 heat does not satisfy the thermostat demand, stage
2 heat will energize. The outdoor compressor and indoor
blower will ramp to high speed.
On some thermostats, if the heating load on the conditioned
space is not met in a normal period of time or the difference
between the thermostat set point and room temperature is
large, the heat pump will automatically shut off and the gas
heat will operate until the thermostat demand for heat is met.
Emergency Heat - Gas Heat mode
Heat pump thermostats include a system mode called EM HT or
AUX HT, etc. This is a back-up heating mode that should only
be used if a problem is suspected. With the mode set to EM HT,
etc., the compressor and outdoor fan will be locked off and the
gas furnace will be used as a source of heat. Sustained use of
gas heat in place of the heat pump will result in an increase in
this utility cost. Refer to the thermostat manual for more info.
Defrost Operation
During cold weather heating operation, the outdoor unit will
develop a coating of snow and ice on the heat transfer coil.
This is normal and the unit will defrost itself. This unit features
Demand Defrost that monitors ambient and coil temperatures
to regulate the defrost function accordingly.
At the beginning of the defrost cycle, both the outdoor condenser
fan and compressor will turn off. After approximately 30 seconds,
the compressor will turn on and begin to heat the outdoor coil
causing the ice and snow to melt.
During the defrost period, the gas funace will energize and
produce warm air to offset the heat pump operation while in its
reverse cycle. Initially the air out of the supply registers may
be slightly cooler since the heat pump has reversed its cycle
and is now in the cooling mode to aide in the defrosting of the
outdoor coil. The air will rise in temperature as the gas furnace
continues to operate and the blower speed increases.
NOTE: While the ice and snow is melting, some steam may
rise from the outdoor unit as the warm coil causes the melting
frost to evaporate. When defrost is completed, the outdoor
fan motor will start, and the compressor will turn off again. In
approximately 30 seconds the compressor will start up again
and continue normal operation. The gas heat will shut down at
the end of the defrost cycle.
Automatic Heat Pump Operation (Cooling &
Heating)
1. Set the thermostat system mode to AUTO and the thermostat
fan mode to AUTO. See Figure 1 (page 3).
2. Set the thermostat’s temperature selector to the desired
heating and cooling temperature level(s). The outdoor unit and
the indoor blower will then cycle on and off in either the heating
or cooling mode of operation as required to automatically
maintain the indoor temperature within the desired limits.
Continuous Indoor Blower Operation
The continuous indoor blower operation is typically used to
circulate the indoor air to equalize a temperature imbalance
due to a solar load, cooking, or fireplace operation.
Set the thermostat fan mode to ON (see Figure 1). The indoor
blower will start immediately and will run continually until the fan
switch is reset to AUTO. NOTE: On some thermostat models
the setting may be called CONT.
Continuous indoor blower
operation can be obtained with the thermostat system switch
set in any position, including OFF.
System Shutdown
Set the thermostat system mode to OFF and the thermostat fan
mode to AUTO. See Figure 1. NOTE: The system will not operate,
regardless of the thermostat temperature selector’s setting.
DUAL FUEL UNITS - GAS HEAT / ELECTRIC HEAT PUMP
5
SYSTEM MAINTENANCE
CAUTION:
Verify all electrical power to the unit is disconnected
and the gas is shut off before performing the
following recommended maintenance.
Proper maintenance is most important to achieve the best
performance from the appliance and should be performed by
a qualified service technician at least once a year. Follow the
maintenance schedule and the instructions below for years of
safe, trouble free operation.
Annually inspect the physical support of the unit to ensure
that it is physically sound without sagging, cracks, gaps, etc.,
around the base so as to provide a seal between the support
and the base.
Annually inspect the return-air connection to ensure that it is
physically sound and is still sealed to the casing of the unit.
Also inspect the unit, ductwork, and vent system for signs of
physical deterioration.
Do not operate the unit without all doors and covers in place.
Avoid operating the unit when windows and doors are open.
Refer to the Maintenance Schedule below (Table 1) for
recommended maintenance information.
CAUTION:
DO NOT make contact with any of the internal
electrical components while cleaning the unit.
Regular Cleaning
Remove any leaves and grass clippings from the outdoor
coil. Check for and remove any obstructions such as twigs,
sticks, etc. Be careful not to damage the aluminum fins
Air Filters
WARNING:
Never operate the unit without a filter in the return
air system. Dust and lint in the return air can build
up on the internal components, resulting in loss
of efficiency, equipment damage, and possible
fire risk.
This unit is not supplied with air filter(s) and has no means for
accommodating internal air filter(s). The installer is responsible
for installing a filtration system into the return air duct of this
system. The filter(s) of this system should be checked at monthly.
It is very important to replace or clean the filter(s) installed in
the return air duct of this system. A clogged filter could cause
airflow related problems and reduce the overall efficiency of your
unit. Depending upon which type of filter was installed with your
unit, clean (permanent) or replace (disposable) filter(s) of your
system at the beginning of every heating season, the beginning
of every cooling season, and when an accumulation of dust and
dirt are visible on the filter.
IMPORTANT NOTE:
Replace disposable filter(s) installed in your system only with
the same size dimensional filters that are being replaced. Clean
permanent filter(s) as described by the manufacturer.
Troubleshooting
Before you call a Technician, check the following:
Check the thermostat setting. Make sure the system mode
and temperature settings are correct.
Check the electrical panel for tripped circuit breakers.
Check the filters for dust accumulation.
Check the unit and make sure it is clean and not covered with
grass or leaves.
If the items above don’t resolve your problems, then call your
nearest service technician.
MAINTENANCE ITEM
FREQUENCY OF MAINTENANCE
BEGINNING OF
HEATING
SEASON
END OF
HEATING
SEASON
MONTHLY
VERIFY AREA AROUND THE UNIT IS FREE OF COMBUSTIBLE MATERIALS
X X
VERIFY COMBUSTION AND VENTILATION AIR IS NOT RESTRICTED
X X X
VERIFY NO SIGNS OF PHYSICAL DETERIORATION OF THE FURNACE
X X X
VERIFY HEAT EXCHANGER CONDENSATE DRAINAGE AREA IS ABOVE GRADE
LEVEL (CONDENSING STYLE FURNACES)
X X
INSPECT UNIT SUPPORT
X X
INSPECT RETURN AIR CONNECTIONS
X X
CLEAN OR REPLACE FILTER(S)
X
Table 1. Maintenance Schedule
MAINTENANCE & TROUBLESHOOTING
6
Figure 2. Gas Valve Label
A. This appliance does not have a pilot. It is equipped with
an ignition device which automatically lights the burner.
Do not try to light the burner by hand.
B. BEFORE OPERATING smell all around the appliance
area for gas. Be sure to smell next to the oor because
some gas is heavier than air and will settle on the oor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone
in your building.
Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the re
department.
C. Use only your hand to push in or turn the gas control
knob. Never use tools. If the knob will not push in or move
by hand, do not try to repair it, call a qualifi ed service
technician. Force or attempted repair may result in a re
or explosion.
D. Do not use this appliance if any part has been under
water. Immediately call a qualied service technician
to inspect the appliance and to replace any part of the
control system and any gas control which has been
under water.
1. ATTENTION! Lire d’abord la liste des mesures de
sécurité ci-dessus.
2. Mettre le thermostat à la position minimale.
3. Couper le courant électrique qui mène à l’appareil.
4. Cet appareil ménager étant doté d’un système
d’allumage automatique, ne pas essayer d’allumer le
brûleur manuellement.
5. Retirer le panneau/volet d’accès de commande
(panneau supérieur s’il s’agit d’un modèle à deux
panneaux).
6. Réglez l’interrupteur de commande du gaz à la position
“OFF”. (voir Figure 1).
7. Attendre cinq (5) minutes pour s’assurer de la
dissipation du gaz.
En cas d’odeur, ARRÊTER LE PROCÉDÉ. Suivre les
instructions ci-dessus (Section B). En l’absence de
toute odeur de gaz, avancer à l’étape suivante.
8. Réglez l’interrupteur de commande du gaz à la position
“ON”. (voir Figure 1).
9. Remettre le panneau/volet d’accès de commande en
place (panneau supérieur s’il s’agit d’un modèle à deux
panneaux).
10. Rebrancher l’appareil sur le réseau électrique.
11. Ajuster le thermostat à la position désirée.
12. Si l’appareil ne fonctionne pas, suivre les “Directives
d’arrêtcidessous et appeler le technicien de service.
A. Cet appareil ménager n’a pas de veilleuse. II est doté
d’un système d’allumage automatique. Ne pas essayer
d’allumer le brûleur manuellement.
B. AVANT L’USAGE. Attention à une possible odeur de
gaz surtout au niveau du plancher où les gaz les plus
lourds ont la tendance de se concentrer.
EN CAS D’ODEUR DE GAZ.
Ne mettre en marche aucun appareil électrique.
Ne toucher à aucun commutateur électrique, ne pas
employer le téléphone.
Quitter le bâtiment immédiatement et avertir la
compagnie du gaz en utili sant le téléphone d’un voisin.
A défaut de la compagnie du gaz, avertir le service des
pompiers.
C. Enfoncer ou faire tourner le robinet à gaz à la main
seulement. Ne jamais utiliser d’outils. S’il n’est pas
possible de faire tourner ou d’enfoncer le robinet à la
main, ne pas essayer de le réparer. Faire appel à un
spécialiste. Forcer ou tenter de réparer le robinet pourrait
être à l’origine d’une explosion ou d’un incendie.
D. II est déconseillé d’utiliser cet appareil en contact
prolongé avec l’eau. Faire inspecter ou remplacer
toute commande par un technicien qualifi é si un des
systèmes de contrôle du gaz s’est trouvé sous l’eau.
1. STOP! Read the safety information above on this label.
2. Set the thermostat to the lowest setting.
3. Turn off all electrical power to the appliance.
4. The appliance’s ignition device automatically lights the
burner. Do not try to light burner by hand.
5. Remove the control access door/panel (upper door if
two-door model).
6. Move the gas control switch to the “OFF” position. (See Figure 1)
7. Wait fi ve (5) minutes to clear out any gas. Then smell for gas,
including near the fl oor. If you smell gas, STOP! Follow “B” in above
information. If you don’t smell gas, go to the next step.
8. Move the gas control
switch to the “ON”
position. (See Figure 1)
9. Replace the control
access door/panel
(upper door if two
door model).
10. Turn on all electrical
power to the appliance.
11. Turn the thermostat to a
desired setting.
12. If the appliance will not
operate, follow the
instructions “To Turn Off Gas To Appliance” and call your
service technician or gas supplier.
10186330 (Replaces 7106740)
(10/17)
1. Mettre le thermostat à la position minimale.
2. Débrancher l’appareil en prévision de la réparation.
3. Retirer le panneau/volet d’accès de commande
(panneau supérieur s’il s’agit d’un modèle à deux
panneaux).
4. Réglez l’interrupteur de commande du gaz à la position
“OFF”. Ne forcez pas. (voir Figure 1).
5. Remettre le panneau/volet d’accès de commande en
place (panneau supérieur s’il s’agit d’un modèle à deux
panneaux).
POUR VOTRE SÉCURITÉ.
À LIRE AVANT L’EMPLOI
FOR YOUR SAFETY READ
BEFORE OPERATING
1. Set the thermostat to the lowest setting.
2. Turn off all electrical power to the appliance if service is
to be performed.
3. Remove the control access door/panel (upper door if
two-door model).
4. Move the gas control switch to the “OFF” position. Do
not use force. (See Figure 1)
5. Replace the control access door/panel (upper door if
two-door model).
ATTENTION!
L’inobservation de ces instructions
peut entraîner un incendie ou une explosion pouvant
causer des dam mages à votre propriété à votre
personne, ou la mort.
WARNING:
If you do not follow these instructions
exactly, a re or explosion may result causing property
damage, personal injury, or loss of life.
TO TURN OFF
GAS TO APPLIANCE
DIRECTIVES D’ARRÊT
MODE D’EMPLOI
OPERATING INSTRUCTIONS
SWITCH
(L’INTERRUPTEUR )
7
WARRANTY INFORMATION
A warranty certificate with full details is included with the equipment. Carefully review these responsibilities with your dealer or
service company. The manufacturer will not be responsible for any costs found necessary to correct problems due to improper
setup, improper installation, adjustments, improper operating procedure on the part of the user. Some specific examples of service
calls which are not included in the limited warranty are:
Correcting wiring problems in the electrical circuit supplying the equipment.
Resetting circuit breakers or other switches.
Adjusting or calibrating of thermostat.
Specifications & illustrations subject to change without notice or incurring obligations (09/18).
O’Fallon, MO, © Nortek Global HVAC LLC 2018. All Rights Reserved.
10239660
(Replaces 7096230)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Mammoth DF6SF Manuel utilisateur

Catégorie
Cheminées
Taper
Manuel utilisateur

dans d''autres langues