Lumination LVR Series LED Volumetric Retrofit Kit Guide d'installation

Taper
Guide d'installation
LED.com
© 2023 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 1 of 7
(Rev 06/28/23)
IND405-Lumination-LVR-Series-LED-Volumetric-Retrofit-Kit-Installation-Guide_R01
Installation Guide
IND405
Lumination® LED Luminaire
LED Volumetric Retrot Kit
(LVR Series)
BEFORE YOU BEGIN
Read these instructions completely and carefully.
WARNING/AVERTISSEMENT
RISK OF FIRE OR ELECTRIC SHOCK
Luminaire wiring and electrical parts may be damaged
when drilling for installation of LED retrot kit. Check for
enclosed wiring and components.
LED Retrot Kit installation requires knowledge of
luminaires electrical systems. If not qualied, do not
attempt installation. Contact a qualied electrician.
Install this kit only in luminaires that have the construction
features and dimensions shown in the photographs and/
or drawings and where the input rating of the retrot kit
does not exceed the input rating of the luminaire.
To prevent wiring damage or abrasion, do not expose
wiring to edges of sheet metal or other sharp objects.
Do not make or alter any open holes in an enclosure of
wiring or electrical components during kit installation.
Suitable for damp locations.
RISQUE D’INCENDIE OU D’ELECTROCUTION
Le câblage du luminaire ainsi que ses composantes électriques peuvent être
endommagés lors du perçage requis pour l’installation de l’ensemble de mise à
niveau à DEL. Vériez le câblage et les composants.
L’installation de l’ensemble de mise à niveau à DEL requiert des connaissances en
système électrique d’éclairage. Si vous n’avez pas les qualications adéquates, ne
procédez pas à l’installation et contactez un électricien qualié.
N’installez cet ensemble de mise à niveau à DEL que sur des luminaires ayant
une construction et des dimensions indiquées sur les photos et dessins et ce,
seulement dans la mesure où les spécications d’entrées de l’ensemble de mise à
niveau à DEL n’excède pas les spécications d’entrée du Luminaires dans lequel il
sera installé.
An de prévenir tout dommage ou abrasion aux ls électriques, évitez que ceux-ci
ne viennent en contact avec les bordures métalliques ou d’autres ojets pointus.
Ne laissez aucune ouverture dans le boitier ou le compartiment où se trouvent les
composants électriques.
Convenient aux emplacements humides.
Save These Instructions
These instructions do not purport to cover all details or variations in components nor to provide for every possible contingency to be
met in connection with installation, operation or maintenance. Should further information be desired or should particular problem arise
which are not covered suciently for the purchaser’s purpose, the matter should be referred to General Electric Company. GE Lighting
does not claim liability for any installation not performed according to this guide or not by a qualied electrician.
Retrot kit may fall down if not installed properly, follow installation
instructions.
This device is not intended for use with Emergency Exits.
For Your Safety
Read and observe all CAUTIONS and WARNINGS shown throughout these instructions. Use this product only in the manner intended
by the manufacturer. If there are any questions or concerns, contact the manufacturer.
CAUTION ATTENTION
L’ensemble de mise à niveau à DEL peut tomber s’il n’est pas installé
correctement. Suivre les instructions d’installation.
Cet appareil n’est pas conçu pour utilisation avec sortie de secours.
LED.com
© 2023 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 2 of 7
(Rev 06/28/23)
IND405-Lumination-LVR-Series-LED-Volumetric-Retrofit-Kit-Installation-Guide_R01
Lumination® (LVR - Series) Installation Guide
Prior to installation, disconnect all incoming power to
xture. Remove existing hardware (lens/lens frame,
parabolic louver, reectors/ballast covers, brackets, lamps/
lamp holders). Leave supply and grounding leads.
NOTE: Follow all federal and local regulations when
disposing of lamps and removed components.
12
Carefully unpack unit from its packaging. Properly inspect
for defects before installing. Wear
work gloves to prevent dirt and oil from being transferred
to the luminaire.
Install LVR Mounting Bracket to each end of the xture by
sliding LVR Mounting Brackets between the xture and
T-grid, ensuring the mounting bracket is centered in the
xture. Secure the LVR Mounting Brackets to the xture
using 4 of the provided #8x1/2” self-drilling screws.
3 4
Install the LVR Fixture T-hinges into the LVR Mounting
Bracket cutouts.
Installation
Components Supplied
The components have been properly packed to avoid damage during transit. Inspect the components to conrm there is no physical
damage. Do not install damaged components.
LVR Fixture (1)
LVR Mounting Bracket (2)
#8x1/2” Self-Drilling Screw (5)
Green Ground Screw - Optional (1)
LED.com
© 2023 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 3 of 7
(Rev 06/28/23)
IND405-Lumination-LVR-Series-LED-Volumetric-Retrofit-Kit-Installation-Guide_R01
Lumination® (LVR - Series) Installation Guide
Secure LVR xture to existing uorescent xture using
provided safety tether. Ensure safety tether loop is secured
around T-shaped tab in LVR Mounting Bracket.
5
Safety tether
6
Ground wire
Install grounding wire using provided green ground screw
(if existing hole is available) OR #8x1/2” self-drilling screw.
Connect the LED driver to AC line using the provided
ballast disconnect. See “Electrical Connections” section for
wiring details.
7
AC line
8
Secure swing door by locking latches found on the end of
the assembled LVR Door.
Diffuser panel
Screw is engagedScrew is disengaged
Squeeze
The diuser panel is engaged over 4 screws on both ends of the LVR luminaire. It may become loose during shipping or if the luminaire
is signicantly twisted during installation. It is important to ensure the diuser is completely engaged to avoid it falling out after
installation is complete. Grasp diuser and gently squeeze together to re-engage over screws.
9
LED.com
© 2023 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 4 of 7
(Rev 06/28/23)
IND405-Lumination-LVR-Series-LED-Volumetric-Retrofit-Kit-Installation-Guide_R01
Lumination® (LVR - Series) Installation Guide
GE DRIVER
VIOLET (1-10V +)
PINK (1-10V –)
BLUE (LED –)
RED (LED +) TO LEDs
BLACK (LINE)
WHITE (NEUTRAL)
LVT POSITIVE LEAD
WHITE (NEUTRAL)
LVR CONTROLS AC LINE LEAD
LVT24 POSITIVE LEAD
RED (LOAD)
BLACK (LINE)
VIOLET (1-10V +)
PINK (1-10V –)
LG CONTROLLER
Electrical Connections
Using the provided quick-connect, connect the black (line) of
the AC line to the black 120-277V or 347V wire and the white
(neutral) wires of the AC line to the white or red wires.
Optional: If using a 0-10V dimming controller, connect
matching-colored wires together.
Emergency Bypass Option: Using the provided quick-connect,
connect the black and red wires from the xture to the normal,
non-emergency AC wires to detect whether or not the xture
is in emergency mode.
NOTES:
Other wires not shown for clarity.
Self-Test Input must be from same branch circuit as normal
neutral and normal hot.
Remote test input is performed when input is CLOSED.
LVR2XXXXXXXXXXTQRMWHTE Wiring Diagram
120-277V
WHITE COMMON NEUTRAL
BLACK UNSWITCHED LINE
GROUND
PINK DIMMING 0-10V
VIOLET DIMMING (+)
LVR Fixture
347V
LVR Fixture
RED COMMON NEUTRAL 347V
BLACK UNSWITCHED LINE 347V
GROUND
PINK DIMMING 0-10V
VIOLET DIMMING (+)
EMERGENCY BYPASS OPTION
RED NORMAL NEUTRAL
NORMAL HOT
SELF-TEST INPUT (optional)
REMOTE-TEST INPUT (optional)
REMOTE-TEST INPUT (optional)
BLACK
WHITE/BLACK
WHITE/BLUE
WHITE/RED
Exterior Wires
LVR Fixture
LED.com
© 2023 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 5 of 7
(Rev 06/28/23)
IND405-Lumination-LVR-Series-LED-Volumetric-Retrofit-Kit-Installation-Guide_R01
Lumination® (LVR - Series) Installation Guide
LVR2XXXXXXXXXXTQRMWHTEEL Wiring Diagram
LINE FILTER
BODINE BSL310 EMBB
YELLOW
YELLOW/BLACK
BLUE
RED
RED
VIOLET
BROWN
BLACK
RED/WHITE
WHITE
WHITE/BLACK
TO LEDs
GE DRIVER
BLACK (LINE)
WHITE (NEUTRAL)
VIOLET (1-10 +)
PINK (1-10 –)
BLUE (LED –)
RED (LED +)
LG CONTROLLER
WHITE (NEUTRAL)
RED (LOAD)
BLACK (LINE)
VIOLET (1-10 +)
PINK (1-10 –)
LED.com
© 2023 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 6 of 7
(Rev 06/28/23)
IND405-Lumination-LVR-Series-LED-Volumetric-Retrofit-Kit-Installation-Guide_R01
6
Lumination® (LVR- Series) Installation Guide
LVR CONTROLS
DIMMING LEAD
LVR CONTROLS
DIMMING LEAD
TO LEDs
LVR CONTROLS
AC LINE LEAD
LVT POSITIVE LEAD
LVR CONTROLS
RELAY LEAD
AC SENSE POWER
LVR CONTROLS
AC LINE LEAD
LVT24 POSITIVE LEAD
AC NORMAL/
EMERGENCY POWER
ESRB
WHITE (Self-Test Input)
BLUE (Emergency hot switched to load)
YELLOW (Emergency Neutral)
BROWN (Emergency Hot)
RED (Emergency Neutral)
BLACK (Emergency Hot)
LG CONTROLLER
WHITE (NEUTRAL)
VIOLET (1-10 +)
VIOLET (1-10 +)
WHITE/BLUE (Remote Test Input)
WHITE/RED (Remote Test Input)
RED (LOAD)
BLACK (LINE)
VIOLET (1-10 +)
GE DRIVER
PINK (1-10 –)
BLACK (LINE)
WHITE (NEUTRAL)
VIOLET (1-10 +)
PINK (1-10 –)
BLUE (LED –)
RED (LED +)
LVR2XXXXXXXXXXTQRMWHTEB2 Wiring Diagram
LED.com
© 2023 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 7 of 7
(Rev 06/28/23)
IND405-Lumination-LVR-Series-LED-Volumetric-Retrofit-Kit-Installation-Guide_R01
Lumination® (LVR - Series) Installation Guide
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that may cause undesired operation. CAN ICES-005 (A) / NMB-005 (A).
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference
to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to
correct the interference at his own expense.
Note: CONTACT FACTORY for details and limitations when seeking to incorporate this product with an emergency system other than Battery Backup.
Daintree Node
Reset Button &
LED Indicator
Daintree label to be used for
Daintree Node Identication Label and Reset (optional)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7

Lumination LVR Series LED Volumetric Retrofit Kit Guide d'installation

Taper
Guide d'installation