Simplicity 030657-00 Manuel utilisateur

Catégorie
Groupes électrogènes
Taper
Manuel utilisateur

Ce manuel convient également à

Not for
Reproduction
BRIGGS & STRATTON POWER PRODUCTS GROUP, LLC
MILWAUKEE, WISCONSIN, U.S.A.
Manual No. 80012141 Revision -
Portable Generator
Operator’s Manual
This generator is certified in accordance with CSA (Canadian Standards Association) standard C22.2 No. 100-04
(motors and generators) and rated in accordance with PGMA (Portable Generator Manufacturers’ Association)
standard PGMA G200 (Standard for Testing and Validating Performance of Portable Generators).
Not for
Reproduction
2 BRIGGSandSTRATTON.COM
Thank you for purchasing this quality-built Briggs & Stratton® generator. We are pleased that you’ve placed your
confidence in the Briggs & Stratton brand. When operated and maintained according to the instructions in this
manual, your Briggs & Stratton generator will provide many years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with generator
products and how to avoid them. This generator is designed and intended only for supplying electrical power
for operating compatible electrical lighting, appliances, tools and motor loads, and is not intended for any other
purpose. It is important that you read and understand these instructions thoroughly before attempting to start or
operate this equipment. Save these original instructions for future reference.
This generator requires final assembly before use. Refer to the Assembly section of this manual for
instructions on final assembly procedures. Follow the instructions completely.
Where to Find Us
You never have to look far to find Briggs & Stratton support and service for your generator. Consult your Yellow
Pages. There are over 30,000 Briggs & Stratton authorized service dealers worldwide who provide quality service.
You can also contact Briggs & Stratton Customer Service by phone at (800) 743-4115, or on the Internet at
BRIGGSandSTRATTON.COM.
Generator Engine
Model Number ______________________ Model Number ________________________
Revision
____________________ Type Number _________________________
Serial Number
_________________ Code Number _________________________
Date Purchased ____________________
Table of Contents
Safe Operation Checklist ............... 3
Operator Safety....................... 4
Assembly............................ 9
Features and Controls ................ 14
Operation........................... 17
Maintenance ........................ 21
Troubleshooting ..................... 26
Warranty ........................... 28
Product Specifications ................ 32
Common Service Parts ............... 32
Copyright © 2014. Briggs & Stratton Power Products Group, LLC
Milwaukee, WI, USA. All rights reserved.
BRIGGS & STRATTON POWER PRODUCTS is a registered
trademark of Briggs & Stratton Corporation
Milwaukee, WI, USA
Not for
Reproduction
3
Safe Operation Checklist
Safe operation of the portable generator requires the completion of the following tasks:
Carbon Monoxide (CO) Alarm
Carbon monoxide (CO) alarm(s) in working order.
Smoke Alarm
Smoke alarm(s) in working order.
Generator Location
Generator placed in a Carbon Monoxide (CO) safe zone. See Generator Location to reduce the Risk of
Carbon Monoxide Poisoning.
Generator placed in a fire safe zone. See Generator Location to reduce the Risk of Fire.
Generator located on flat and level surface.
Oil and Fuel
Engine has proper oil level. See Verify Engine Oil Level.
Fuel tank filled at or below baffle. See Add Fuel.
Inspect fuel lines, tank, cap and fittings each time before using generator. DO NOT use if fuel leak or damage
is found.
Electrical
When connecting to a buildings electrical system install listed transfer equipment. See Connecting to a
Building’s Electrical System.
Electrical cords are rated for intended loads. See Cord Sets and Receptacles.
Electrical cords do not run through doorways, windows, holes in ceilings, walls or floors.
Inspect electrical cords thoroughly before each use. DO NOT use if damaged.
All labeled electrical cord safeties are understood and being followed.
Operation
Start engine. See Starting the Engine.
Not for
Reproduction
4 BRIGGSandSTRATTON.COM
Operator Safety
Safety Labels
The generator safety labels shown below and on the next page are placed on your portable generator to draw
attention to potential safety hazards.
202997
Not for
Reproduction
5
Not for
Reproduction
6 BRIGGSandSTRATTON.COM
Equipment Description
Read this manual carefully and become
familiar with your generator. Know its
applications, its limitations and any hazards
involved.
The generator is an engine-driven, revolving field,
alternating current (AC) generator equipped with a
voltage regulator. The voltage regulator is designed to
automatically maintain a constant output voltage level.
It was designed to supply electrical power for operating
compatible electrical lighting, appliances, tools and
motor loads. The generator’s revolving field is driven at
about 3600 rpm by a single cylinder engine.
NOTICE
Exceeding generators wattage/amperage
capacity could damage generator and/or electrical
devices connected to it.
DO NOT exceed the generator’s wattage/amperage
capacity. See Don’t Overload Generator in the Operation
section.
Every effort has been made to ensure that the
information in this manual is both accurate and current.
However, the manufacturer reserves the right to
change, alter or otherwise improve the generator and
this documentation at any time without prior notice.
The Emission Control System for this generator is
warranted for standards set by the Environmental
Protection Agency and the California Air Resources
Board.
This spark ignition system complies with the Canadian
standard ICES-002.
Important Safety Information
The manufacturer cannot possibly anticipate every
possible circumstance that might involve a hazard.
The warnings in this manual, and the tags and decals
affixed to the unit are, therefore, not all-inclusive.
If you use a procedure, work method or operating
technique that the manufacturer does not specifically
recommend, you must satisfy yourself that it is safe
for you and others. You must also make sure that the
procedure, work method or operating technique that
you choose does not render the generator unsafe.
Safety Symbols and Meanings
The safety alert symbol indicates a potential
personal injury hazard. A signal word (DANGER,
WARNING, or CAUTION) is used with the alert symbol
to designate a degree or level of hazard seriousness.
A safety symbol may be used to represent the type of
hazard. The signal word NOTICE is used to address
practices not related to personal injury.
DANGER indicates a hazard which, if not avoided,
will result in death or serious injury.
WARNING indicates a hazard which, if not
avoided, could result in death or serious injury.
CAUTION indicates a hazard which, if not
avoided, could result in minor or moderate injury.
NOTICE address practices not related to personal
injury.
Fire
Explosion
Toxic Fumes
Hot Surface
Moving Parts
Electrical Shock
Kickback
Flying Objects
Operator’s Manual
Not for
Reproduction
7
WARNING The engine exhaust from this
product contains chemicals known to the State of
California to cause cancer, birth defects, or other
reproductive harm.
WARNING Certain components in this product
and related accessories contain chemicals known to
the State of California to cause cancer, birth defects
or other reproductive harm. Wash hands after
handling.
WARNING
This generator does not meet U. S. Coast Guard
Regulation 33CFR-183 and should not be used on
marine applications.
Failure to use the appropriate U. S. Coast Guard
approved generator could result in death or serious injury.
WARNING Fuel and its vapors are extremely
flammable and explosive which
could cause burns, fire or explosion
resulting in death or serious injury.
WHEN ADDING OR DRAINING FUEL
Turn generator engine OFF and let it cool at least 2
minutes before removing fuel cap. Loosen cap slowly to
relieve pressure in tank.
Fill or drain fuel tank outdoors.
DO NOT overfill tank. Allow space for fuel expansion.
If fuel spills, wait until it evaporates before starting engine.
Keep fuel away from sparks, open flames, pilot lights,
heat, and other ignition sources.
Check fuel lines, tank, cap and fittings frequently for
cracks or leaks. Replace if necessary.
DO NOT light a cigarette or smoke.
WHEN STARTING EQUIPMENT
Ensure spark plug, muffler, fuel cap, and air cleaner are
in place.
DO NOT crank engine with spark plug removed.
WHEN OPERATING EQUIPMENT
DO NOT operate this product inside any building,
carport, porch, mobile equipment, marine applications, or
enclosure.
DO NOT tip engine or equipment at angle which causes
fuel to spill.
DO NOT stop engine by moving choke control to
CHOKE (
) position.
WHEN TRANSPORTING, MOVING OR REPAIRING
EQUIPMENT
Transport/move/repair with fuel tank EMPTY or with fuel
shutoff valve OFF (0).
DO NOT tip engine or equipment at angle which causes
fuel to spill.
Disconnect spark plug wire.
WHEN STORING FUEL OR EQUIPMENT WITH FUEL IN
TANK
Store away from furnaces, stoves, water heaters, clothes
dryers, or other appliances that have pilot light or other
ignition source because they could ignite fuel vapors.
WARNING Starter cord kickback (rapid
retraction) will pull hand and arm toward
engine faster than you can let go which
could cause broken bones, fractures,
bruises, or sprains resulting in serious injury.
When starting engine, pull cord slowly until resistance is
felt and then pull rapidly to avoid kickback.
NEVER start or stop engine with electrical devices
plugged in and turned on.
WARNING POISONOUS GAS HAZARD.
Engine exhaust contains carbon monoxide,
a poisonous gas that could kill you in
minutes. You CANNOT smell it, see it, or
taste it. Even if you do not smell exhaust fumes, you
could still be exposed to carbon monoxide gas.
Operate this product ONLY outside far away from
windows, doors and vents to reduce the risk of carbon
monoxide gas from accumulating and potentially being
drawn towards occupied spaces.
Install battery-operated carbon monoxide alarms or
plug-in carbon monoxide alarms with battery back-up
according to the manufacturer’s instructions. Smoke
alarms cannot detect carbon monoxide gas.
DO NOT run this product inside homes, garages,
basements, crawlspaces, sheds, or other partially-
enclosed spaces even if using fans or opening doors
and windows for ventilation. Carbon monoxide can
quickly build up in these spaces and can linger for hours,
even after this product has shut off.
ALWAYS place this product downwind and point the
engine exhaust away from occupied spaces.
If you start to feel sick, dizzy, or weak while using this
product, get to fresh air RIGHT AWAY. See a doctor. You
may have carbon monoxide poisoning.
Not for
Reproduction
8 BRIGGSandSTRATTON.COM
NOTICE
Exceeding generators wattage/amperage
capacity could damage generator and/or electrical
devices connected to it.
DO NOT exceed the generator’s wattage/amperage
capacity. See Don’t Overload Generator in the Operation
section.
Start generator and let engine stabilize before connecting
electrical loads.
Connect electrical loads in OFF position, then turn ON for
operation.
Turn electrical loads OFF and disconnect from generator
before stopping generator.
NOTICE
Improper treatment of generator could
damage it and shorten its life.
Use generator only for intended uses.
If you have questions about intended use, ask dealer or
contact local service center.
Operate generator only on level surfaces.
DO NOT expose generator to excessive moisture, dust,
dirt, or corrosive vapors.
DO NOT insert any objects through cooling slots.
If connected devices overheat, turn them off and
disconnect them from generator.
Shut off generator if:
-electrical output is lost;
-equipment sparks, smokes, or emits flames;
-unit vibrates excessively.
WARNING Starter and other rotating parts
could entangle hands, hair, clothing, or
accessories resulting in serious injury.
NEVER operate generator without protective housing or
covers.
DO NOT wear loose clothing, jewelry or anything that
could be caught in the starter or other rotating parts.
Tie up long hair and remove jewelry.
CAUTION Excessively high operating speeds
could result in minor injury.
Excessively low operating speeds impose a heavy
load.
DO NOT tamper with governor spring, links or other parts
to increase engine speed. Generator supplies correct
rated frequency and voltage when running at governed
speed.
DO NOT modify generator in any way.
WARNING
Generator voltage could cause
electrical shock or burn resulting in death or
serious injury.
Use listed transfer equipment, suitable for the intended
use, to prevent backfeed by isolating generator from
electric utility workers.
When using generator for backup power, notify utility
company.
Use a ground fault circuit interrupter (GFCI) in any damp
or highly conductive area, such as metal decking or steel
work.
DO NOT touch bare wires or receptacles.
DO NOT use generator with electrical cords which are
worn, frayed, bare or otherwise damaged.
DO NOT operate generator in the rain or wet weather.
DO NOT handle generator or electrical cords while
standing in water, while barefoot, or while hands or feet
are wet.
DO NOT allow unqualified persons or children to operate
or service generator.
WARNING Exhaust heat/gases could ignite
combustibles, structures or damage
fuel tank causing a fire, resulting in
death or serious injury.
Contact with muffler area could cause burns
resulting in serious injury.
DO NOT touch hot parts and AVOID hot exhaust gases.
Allow equipment to cool before touching.
Keep at least 5 ft. (1.5 m) of clearance on all sides of
generator including overhead.
It is a violation of California Public Resource Code,
Section 4442, to use or operate the engine on any forest-
covered, brush-covered, or grass-covered land unless
the exhaust system is equipped with a spark arrester, as
defined in Section 4442, maintained in effective working
order. Other states or federal jurisdictions may have
similar laws.
Contact the original equipment manufacturer, retailer,
or dealer to obtain a spark arrester designed for the
exhaust system installed on this engine.
Replacement parts must be the same and installed in the
same position as the original parts.
WARNING Unintentional sparking could cause
fire or electric shock resulting in
death or serious injury.
WHEN ADJUSTING OR MAKING REPAIRS TO YOUR
GENERATOR
Disconnect the spark plug wire from the spark plug and
place the wire where it cannot contact spark plug.
WHEN TESTING FOR ENGINE SPARK
Use approved spark plug tester.
DO NOT check for spark with spark plug removed.
Not for
Reproduction
9
Assembly
Your generator requires some assembly and is ready
for use after it has been properly serviced with the
recommended fuel and oil level is verified.
If you have any problems with the assembly of
your generator, please call the generator helpline
at (800) 743-4115. If calling for assistance, please
have the model, revision, and serial number from the
identification label available.
Unpack Generator
1. Set the carton on a rigid, flat surface.
2. Remove everything from carton except generator.
3. Open carton completely by cutting each corner
from top to bottom.
4. Leave generator on carton to install wheel kit.
The generator is supplied with:
Operator’s manual
Wheel kit
Install Wheel Kit
NOTICE Wheel kit is not intended for over-the-road
use.
Install the wheel kit as follows:
1. Tip generator so that engine end is up.
2. Slide a washer (A) over axle stud (B).
3. Slide a wheel (C) over axle stud (B).
NOTICE Be sure to install wheel with raised hub
inboard.
4. Slide axle stud (B) through mounting bracket.
5. Insert retaining pin (D) through hole on axle stud.
6. Repeat steps 2 thru 5 to secure second wheel.
7. Line up holes in support leg (E) with holes in
generator frame.
8. Attach support leg using four capscrews (F) and
four flange nuts (G). Tighten with 10 and 13 mm
wrenches.
9. Return generator to normal operating position
(resting on wheels and support leg).
Verify Engine Oil Level
The generator engine is shipped from the factory filled
with oil (API SJ or higher 10W-30). This allows for
generator operation in the widest range of temperature
and climate conditions. Before starting the engine,
check oil level and ensure that engine is serviced as
described in Maintenance.
NOTICE Any attempt to crank or start the engine
before it has been properly filled with the recommended
oil could result in equipment failure.
Refer to Maintenance for oil fill information.
Damage to equipment resulting from failure to follow this
instruction will void warranty.
NOTICE See Oil in the Maintenance section to review
oil recomendations. Verify provided oil in engine is the
correct viscosity for current ambient temperature.
D
A
B
C
G
E
F
Not for
Reproduction
10 BRIGGSandSTRATTON.COM
Add Fuel
Fuel must meet these requirements:
Clean, fresh, unleaded gasoline.
A minimum of 87 octane/87 AKI (91 RON). For
high altitude use, see High Altitude.
• Gasoline with up to 10% ethanol (gasohol) is
acceptable.
NOTICE Use of unapproved fuels could damage
generator and voids warranty.
DO NOT use unapproved gasoline such as E15 and E85.
DO NOT mix oil in gasoline or modify engine to run on
alternate fuels.
To protect the fuel system from gum formation, mix in a
fuel stabilizer when adding fuel. See Storage. All fuel is
not the same. If you experience starting or performance
problems after using fuel, switch to a different fuel
provider or change brands. This engine is certified to
operate on gasoline. The emission control system for this
engine is EM (Engine Modifications).
1. Clean area around fuel fill cap, remove cap.
2. Slowly add unleaded gasoline (A) to fuel tank
(B). Be careful not to fill above the baffle (C).
This allows adequate space for fuel expansion as
shown.
3. Install fuel cap and let any spilled fuel evaporate
before starting engine.
High Altitude
At altitudes over 5,000 ft. (1524 m), a minimum
85 octane / 85 AKI (89 RON) gasoline is acceptable.
To remain emissions compliant, high altitude
adjustment is required. Operation without this
adjustment will cause decreased performance,
increased fuel consumption, and increased emissions.
See an authorized dealer for high altitude adjustment
information. Operation of the engine at altitudes
below 2,500 ft. (762 m) with the high altitude kit is not
recommended.
System Ground
The generator has a system ground that connects the
generator frame components to the ground terminals
on the AC output receptacles. The system ground is
connected to the AC neutral wire (the neutral is bonded
to the generator frame).
Special Requirements
There may be Federal or State Occupational Safety
and Health Administration (OSHA) regulations, local
codes, or ordinances that apply to the intended use of
the generator. Please consult a qualified electrician,
electrical inspector, or the local agency having
jurisdiction:
In some areas, generators are required to be
registered with local utility companies.
If the generator is used at a construction site,
there may be additional regulations which must be
observed.
Connecting to a Building’s Electrical
System
Connections for standby power to a building’s electrical
system must use a listed transfer switch installed by
a current licensed electrician. The connection must
isolate the generator power from the utility power and
must comply with all applicable laws and electrical
codes.
FUEL
TANK
C
B
A
WARNING
Generator voltage could cause
electrical shock or burn resulting in death or
serious injury.
Use listed transfer equipment, suitable for the intended
use, to prevent backfeed by isolating generator from
electric utility workers.
When using generator for backup power, notify utility
company.
Use a ground fault circuit interrupter (GFCI) in any damp
or highly conductive area, such as metal decking or steel
work.
DO NOT touch bare wires or receptacles.
DO NOT use generator with electrical cords which are
worn, frayed, bare or otherwise damaged.
DO NOT operate generator in the rain or wet weather.
DO NOT handle generator or electrical cords while
standing in water, while barefoot, or while hands or feet
are wet.
DO NOT allow unqualified persons or children to operate
or service generator.
WARNING Fuel and its vapors are extremely
flammable and explosive which could
cause burns, fire or explosion
resulting in death or serious injury.
WHEN ADDING FUEL
Turn generator engine OFF and let it cool at least 2 minutes
before removing fuel cap. Loosen cap slowly to relieve
pressure in tank.
Fill fuel tank outdoors.
DO NOT overfill tank. Allow space for fuel expansion.
If fuel spills, wait until it evaporates before starting engine.
Keep fuel away from sparks, open flames, pilot lights,
heat, and other ignition sources.
Check fuel lines, tank, cap and fittings frequently for
cracks or leaks. Replace if necessary.
DO NOT light a cigarette or smoke.
Not for
Reproduction
11
Portable Generator Location
Before starting the portable generator there are two
equally important safety concerns regarding carbon
monoxide (CO) poisoning and fire that must be
addressed.
NOTICE Satisfying the RISK OF CARBON
MONOXIDE POISONING location requirements may
not satisfy the fire location requirements. Satisfying the
RISK OF FIRE location requirements may not satisfy
the CARBON MONOXIDE POISONING location
requirements.
Operation Location of Portable Generator to
REDUCE THE RISK OF CARBON MONOXIDE
POISONING
All fossil fuel burning equipment, such as a portable
generator, contains carbon monoxide (CO) gas in the
engine exhaust, a poisonous gas that could kill you in
minutes. You CANNOT smell it, see it, or taste it. Even
if you do not smell exhaust fumes, you could still be
exposed to carbon monoxide gas. The following must
be completed prior to starting the portable generator
engine:
By law it is required in many states to have a
Carbon Monoxide (CO) alarm (A) in operating
condition in your home. Install/maintain battery-
operated carbon monoxide alarms or plug-in
carbon monoxide alarms with battery back-up
according to the manufacturer’s instructions. A
CO alarm is an electronic device that detects
hazardous levels of CO. When there is a buildup
of CO, the alarm will alert the occupants by
flashing visual indicator light and alarm. Smoke
alarms cannot detect CO gas.
Operate this product ONLY outside far away from
windows, doors and vents to reduce the risk of
carbon monoxide gas from accumulating and
potentially being drawn towards occupied spaces.
DO NOT run this product inside homes, garages,
basements, crawlspaces, sheds, or other partially-
enclosed spaces even if using fans or opening
doors and windows for ventilation. Carbon
monoxide can quickly build up in these spaces
and can linger for hours, even after this product
has shut off.
Your neighbor(s) home may be exposed to the
engine exhaust from your portable generator and
must be considered when deciding on a location
for the safe operation of your portable generator.
ALWAYS place this product downwind and point
the engine exhaust away from occupied spaces.
If you start to feel sick, dizzy, or weak while using this
product, get to fresh air RIGHT AWAY. See a doctor.
You may have carbon monoxide poisoning.
A
Not for
Reproduction
12 BRIGGSandSTRATTON.COM
EXAMPLE OF LOCATION TO REDUCE THE RISK OF CARBON MONOXIDE
POISONING
DO NOT OPERATE IN ANY OF THE FOLLOWING LOCATIONS
Only use OUTSIDE
and FAR AWAY from
windows, doors and vents.
Direct exhaust AWAY
from windows, doors,
and vents.
KEEP
FAR AWAY
CO Alarm
in Living Areas
E
X
H
A
U
S
T
(
C
O
)
Generator too
close to home
and exhaust
directed towards
windows, doors
and vents.
Garage
Attic
Living Area
Basement
Crawlspace
Entryway,
Porch
E
X
H
A
U
S
T
(
C
O
)
Not for
Reproduction
13
EXAMPLE OF LOCATION TO REDUCE THE RISK OF FIRE
Operation Location of Portable Generator to
REDUCE THE RISK OF FIRE
WARNING Exhaust heat/gases could ignite
combustibles, structures or damage fuel tank
causing a fire, resulting in death or serious
injury.
Portable generator must be at least 5 ft. (1.5 m) from
any structure, overhang, trees, windows, doors, any wall
opening, shrubs, or vegetation over 12 inches (30.5 cm)
in height.
DO NOT place portable generator under a deck or other
type of structure that may confine airflow.
Smoke alarm(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Carbon monoxide alarms cannot
detect smoke.
DO NOT place portable generator in manner other than
shown.
Direct exhaust AWAY from
windows, doors, and vents.
E
X
H
A
U
S
T
(
C
O
)
5 ft. (1.5 m) min.
5 ft. (1.5 m) min.
Not for
Reproduction
14 BRIGGSandSTRATTON.COM
Features and Controls
Read this Operator’s Manual and safety rules before operating your generator.
Compare the illustrations with your generator, to familiarize yourself with the locations of various controls
and adjustments. Save this manual for future reference.
A - Hour Meter — Displays and records how many
hours your generator has run (up to 9,999.9).
B - Engine Switch — Set this switch to ON (I) before
starting engine. Set switch to OFF (0) to shut off
engine.
C - Main Breaker — The receptacles are provided
with a rocker switch main circuit breaker to protect
the generator against electrical overload.
D - 120/240 Volt AC, 30 Amp Locking Receptacle
— May be used to supply electrical power for the
operation of 120 and/or 240 Volt AC, 30 Amp,
single phase, 60 Hz electrical, lighting, appliance,
tool and motor loads.
E - Circuit Breakers (AC) — The 120 Volt AC, 20A
GFCI duplex receptacles are provided with “push
to reset” circuit breakers to protect the generator
against electrical overload.
F - 120 Volt AC, 20 Amp, GFCI Duplex Receptacles
— May be used to supply electrical power for the
operation of 120 Volt AC, 20 Amp, single phase,
60 Hz electrical, lighting, appliance, tool and motor
loads.
G - 120 Volt AC, 20 Amp, Duplex Receptacles
May be used to supply electrical power for the
operation of 120 Volt AC, 20 Amp, single phase,
60 Hz electrical, lighting, appliance, tool and motor
loads.
H - Oil Fill Cap/Dipstick — Check and add engine oil
here.
J - Oil Drain Plug — Drain engine oil here.
K - Grounding Fastener — Consult your local agency
having jurisdiction for grounding requirements in
your area.
L - Spark Arrester Muffler — Exhaust muffler lowers
engine noise and is equipped with a spark arrester
screen.
M - Air Cleaner — Protects engine by filtering dust
and debris out of intake air.
N - Choke Lever — Used when starting a cold engine.
P - Recoil Starter — Used to start the engine
manually.
Q - Fuel Valve — Used to turn fuel supply on and off
to engine.
R - Fuel Tank — Capacity of 7.5 U.S. gallons (28.4 l).
Items Not Shown:
Engine Identification — Provides model, type and
code of engine. Please have these readily available if
calling for assistance.
Identification Label — Provides model, revision and
serial number of generator. Please have these readily
available when calling for assistance.
H
B
R
A
M
C
D
P
L
N
E
F
J
K
Q
G
Not for
Reproduction
15
Cord Sets and Receptacles
Use only high quality, well-insulated, grounded
extension cords with the generator’s receptacles.
Inspect extension cords before each use.
Check the ratings of all extension cords before you use
them. Check the operator’s manuals of devices for the
manufacturer’s recommendations.
A double pole rocker switch main circuit breaker is
provided to protect the locking receptacle. If this circuit
breaker is tripped, all receptacles are disconnected.
120/240 Volt AC, 30 Amp, Locking Receptacle
Use a NEMA L14-30 plug with this receptacle.
Connect a 4-wire cord set rated for 250 Volt AC loads
at 30 Amps (or greater). You can use the same 4-wire
cord if you plan to run a 120 Volt load.
This receptacle powers 120/240 Volt AC, 60 Hz,
single phase loads requiring up to 5000 watts of
power (5.0 kW) at 20.8 Amps for 240 Volts or two
independent 120 Volt loads at 20.8 Amps each. The
outlet is protected by a two pole rocker switch circuit
breaker.
NOTICE
Receptacles may be marked with rating
value greater than generator output capacity.
NEVER attempt to power a device requiring more
amperage than generator or receptacle can supply.
DO NOT overload the generator. See Don’t Overload
Generator.
120 Volt AC, 20 Amp, Duplex Receptacle
The duplex receptacle is protected against overload by
a push-to-reset circuit breaker.
Use receptacle to operate 120 Volt AC, single-phase,
60 Hz electrical loads requiring up to 2,400 watts
(2.4 kW) at 20 Amps of current. Use cord sets that are
rated for 125 Volt AC loads at 20 Amps (or greater).
120 Volt AC, 20 Amp, GFCI Duplex Receptacles
Each GFCI duplex receptacle is protected against
overload by a push–to–reset circuit breaker.
Use each receptacle to operate 120 Volt AC, single-
phase, 60 Hz electrical loads requiring up to 2,400 watts
(2.4 kW) at 20 Amps of current. Use cord sets that are
rated for 125 Volt AC loads at 20 Amps (or greater).
WARNING Damaged or overloaded electrical
cords could overheat, arc, and burn
resulting in death or serious injury.
ONLY use cords rated for your loads.
Follow all safeties on electrical cords.
Inspect cord sets before each use.
240V
120V
120V
W (Neutral)
X (Hot)
Y (Hot)
NEMA L14-30
Ground (Green)
4-Wire Cord Set
Not for
Reproduction
16 BRIGGSandSTRATTON.COM
Ground Fault Protection
The duplex receptacles are protected with Ground
Fault Circuit Interruption (GFCI). This meets applicable
federal, state and local codes. The generator’s locking
receptacle is not protected by Ground Fault Circuit
Interruption (GFCI).
The GFCI protects against electrical shock that may be
caused if your body becomes a path which electricity
travels to reach ground. This could happen if you touch
a “Live” appliance or wire, or are touching plumbing or
other materials that connect to the ground.
When protected by a GFCI, one may still feel a shock,
but the GFCI should cut current off quickly enough so
that a person in normal health should not suffer any
serious electrical injury.
Testing the GFCI
Test your GFCI outlet prior to each use, as follows:
Push the “Test” button. The “Reset” button should
pop out, which should allow no power to reach the
outlet. Use a test lamp in each outlet to test this.
• If the GFCI tests good, restore power by pressing
the “Reset” button firmly until it is fully in place and
locks in that position. If the GFCI outlet does not
reset properly, do not use the outlet. Call or
take your generator to a local service center.
If the GFCI trips by itself at any time, reset and
test the outlet. If the reset button does not pop
out when the test button is pressed, do not
use the outlet. Call or take your generator to
a local service center.
WARNING
Generator voltage could cause
electrical shock or burn resulting in death or
serious injury.
Contact with the hot and neutral conductor at the same
time can cause electrical shock or burn, even if the circuit
is GFCI protected.
Before using the GFCI receptacle, ALWAYS push the
test button to insure it works.
Not for
Reproduction
17
Operation
Starting the Engine
Disconnect all electrical loads from the generator. Use
the following start instructions:
1. Make sure unit is on a level surface.
NOTICE Failure to start and operate the unit on a
level surface will cause the unit not to start or shut
down during operation.
2. Turn the fuel valve (A) to the ON (I) position.
3. Push choke lever (B) to CHOKE ( ) position.
4. Set engine switch (C) to ON (I) position.
5. Grasp recoil handle and pull slowly until slight
resistance is felt. Then pull rapidly one time only
to start engine.
If engine starts, proceed to step 7.
If engine fails to start, proceed to step 6.
6. Move choke lever to HALF choke position, and
pull recoil handle twice.
If engine fails to start, repeat steps 5 thru 7.
7. Slowly move choke lever to RUN (
) position. If
engine falters, move choke lever to HALF choke
position until engine runs smoothly, and then to
RUN ( ) position .
NOTICE If engine floods, place choke lever in
RUN ( ) position and crank until engine starts.
NOTICE If engine starts after 3 pulls but fails to run,
or if unit shuts down during operation, make sure unit
is on a level surface and check for proper oil level in
crankcase. This unit may be equipped with a low oil
protection device. If so, oil must be at proper level for
engine to start.
A
C
WARNING Starter cord kickback (rapid
retraction) will pull hand and arm toward
engine faster than you can let go which
could cause broken bones, fractures,
bruises, or sprains resulting in serious injury.
When starting engine, pull cord slowly until resistance is
felt and then pull rapidly to avoid kickback.
NEVER start or stop engine with electrical devices
plugged in and turned on.
WARNING Exhaust heat/gases could ignite
combustibles, structures or damage
fuel tank causing a fire, resulting in
death or serious injury.
Contact with muffler area could cause burns
resulting in serious injury.
DO NOT touch hot parts and AVOID hot exhaust gases.
Allow equipment to cool before touching.
Keep at least 5 ft. (1.5 m) of clearance on all sides of
generator including overhead.
It is a violation of California Public Resource Code,
Section 4442, to use or operate the engine on any forest-
covered, brush-covered, or grass-covered land unless
the exhaust system is equipped with a spark arrester, as
defined in Section 4442, maintained in effective working
order. Other states or federal jurisdictions may have
similar laws.
Contact the original equipment manufacturer, retailer,
or dealer to obtain a spark arrester designed for the
exhaust system installed on this engine.
Replacement parts must be the same and installed in the
same position as the original parts.
B
Not for
Reproduction
18 BRIGGSandSTRATTON.COM
Connecting Electrical Loads
1. Let engine stabilize and warm up for a few
minutes after starting.
2. Ensure main breaker is in ON (I) position.
3. Plug in and turn on the desired 120 and/or
240 Volt AC, single phase, 60 Hz electrical loads.
NOTICE When plugging into the 120 Volt
receptacles, plug items to be powered in sequence as
shown below.
NOTICE
DO NOT connect 240 Volt loads to 120 Volt
duplex receptacles.
DO NOT connect 3-phase loads to generator.
DO NOT connect 50 Hz loads to generator.
DO NOT OVERLOAD THE GENERATOR. See
Don’t Overload Generator.
NOTICE
Exceeding generators wattage/amperage
capacity could damage generator and/or electrical
devices connected to it.
DO NOT exceed the generator’s wattage/amperage
capacity. See Don’t Overload Generator in the Operation
section.
Start generator and let engine stabilize before connecting
electrical loads.
Connect electrical loads in OFF position, then turn ON for
operation.
Turn electrical loads OFF and disconnect from generator
before stopping generator.
Stopping the Engine
1. Turn OFF and unplug all electrical loads from
generator panel receptacles. NEVER start or stop
engine with electrical devices plugged in and
turned ON.
2. Let engine run at no-load for several minutes
to stabilize internal temperatures of engine and
generator.
3. Push engine switch to OFF (0) position.
4. Move fuel valve to OFF (0) position.
Low Oil Shutdown
If the engine oil drops below a preset level, an oil
switch will stop the engine. Check oil level with
dipstick.
If oil level is between ADD and FULL mark on
dipstick:
1. DO NOT try to restart the engine.
2. Contact an Authorized Briggs & Stratton Service
Dealer.
3. DO NOT operate engine until oil level is corrected.
If oil level is below ADD mark on dipstick:
1. Add oil to bring level to FULL mark.
2. Restart engine and if the engine stops again a low
oil condition may still exist. DO NOT try to restart
the engine.
3. Contact an Authorized Briggs & Stratton Service
Dealer.
4. DO NOT operate engine until oil level is corrected.
Cold Weather Operation
Under certain weather conditions (temperatures
below 40°F [4°C] combined with high humidity), your
generator may experience icing of the carburetor and/
or the crankcase breather system. To reduce this
problem, you need to perform the following:
1. Make sure generator has clean, fresh fuel.
2. Turn the fuel valve to the ON (I) position.
3. Use SAE 5W-30 oil.
4. Check oil level daily or after every eight (8) hours
of operation.
5. Maintain generator following Maintenance
Schedule in Maintenance section.
6. Shelter unit from elements.
WARNING Fuel and its vapors are extremely
flammable and explosive which could
cause burns, fire or explosion
resulting in death or serious injury.
DO NOT stop engine by moving choke lever to
CHOKE
( ) position.
1
4
2
3
5
6
Not for
Reproduction
19
Creating a Temporary Cold Weather Shelter
1. For temporary shelter, the original shipping carton
can be used.
2. Cut off top carton flaps and one long side of
carton to expose muffler side of unit. If required,
tape up other sides of carton to fit over generator
as shown.
NOTICE If required, remove wheel kit to fit carton
over generator as shown.
3. Cut appropriate slots to access receptacles of
unit.
4. Face exposed end away from wind and elements.
5. Locate generator as described in the section
Generator Location. Keep exhaust gas from
entering a confined area through windows, doors,
ventilation intakes or other openings.
6. Start generator as described in the section
Starting the Engine, then place carton over
generator. Keep at least 5 ft. (1.5 m) clearance
on all sides of generator including overhead with
shelter in place.
7. Remove shelter when temperatures are above
40°F [4°C].
8. Turn engine OFF and let cool two (2) minutes
before refueling. Let any spilled fuel evaporate
before starting engine.
Building a Cold Weather Shelter
1. Using non combustible material with a fire rating
of at least one hour, build a shelter that will
enclose three sides and the top of the generator.
Make sure muffler side of generator is exposed.
NOTICE Contact your local building material supplier
for non combustible materials with a fire rating of at
least one hour.
NOTICE Be sure shelter can easily be repositioned
for change in wind direction.
2. DO NOT enclose generator any more than shown.
Shelter should hold enough heat created by the
generator to prevent icing problem.
NOTICE If a wheel kit is installed on the generator,
enlarge shelter accordingly.
3. Follow steps 3 through 8 as described previously
in Creating a Temporary Cold Weather Shelter.
Wind
WARNING Exhaust heat/gases could ignite
combustibles, structures or damage
fuel tank causing a fire, resulting in
death or serious injury.
Contact with muffler area could cause burns
resulting in serious injury.
DO NOT touch hot parts and AVOID hot exhaust gases.
Allow equipment to cool before touching.
Keep at least 5 ft. (1.5 m) of clearance on all sides of
generator including overhead.
Remove shelter when temperatures are above 40°F [4°C].
WARNING POISONOUS GAS HAZARD.
Engine exhaust contains carbon monoxide,
a poisonous gas that could kill you in
minutes. You CANNOT smell it, see it, or
taste it. Even if you do not smell exhaust fumes, you
could still be exposed to carbon monoxide gas.
Operate this product ONLY outside far away from
windows, doors and vents to reduce the risk of carbon
monoxide gas from accumulating and potentially being
drawn towards occupied spaces.
Install battery-operated carbon monoxide alarms or
plug-in carbon monoxide alarms with battery back-up
according to the manufacturer’s instructions. Smoke
alarms cannot detect carbon monoxide gas.
DO NOT run this product inside homes, garages,
basements, crawlspaces, sheds, or other partially-
enclosed spaces even if using fans or opening doors
and windows for ventilation. Carbon monoxide can
quickly build up in these spaces and can linger for hours,
even after this product has shut off.
ALWAYS place this product downwind and point the
engine exhaust away from occupied spaces.
If you start to feel sick, dizzy, or weak while using this
product, get to fresh air RIGHT AWAY. See a doctor. You
may have carbon monoxide poisoning.
Not for
Reproduction
20 BRIGGSandSTRATTON.COM
Don’t Overload Generator
Capacity
You must make sure your generator can supply
enough rated (running) and surge (starting) watts for
the items you will power at the same time. Follow these
simple steps:
1. Select the items you will power at the same time.
2. Total the rated (running) watts of these items.
This is the amount of power your generator must
produce to keep your items running. See Wattage
Reference Guide.
3. Estimate how many surge (starting) watts you will
need. Surge wattage is the short burst of power
needed to start electric motor-driven tools or
appliances such as a circular saw or refrigerator.
Because not all motors start at the same time, total
surge watts can be estimated by adding only the
item(s) with the highest additional surge watts to
the total rated watts from step 2.
Example:
Total Rated (Running) Watts = 3075
Highest Additional Surge (Starting) Watts = 1800
Total Generator Output Required = 4875
Power Management
To prolong the life of your generator and attached
devices, it is important to take care when adding
electrical loads to your generator. There should be
nothing connected to the generator outlets before
starting its engine. The correct and safe way to
manage generator power is to sequentially add loads
as follows:
1. With nothing connected to the generator, start the
engine as described in this manual.
2. Plug in and turn on the first load, preferably the
largest load you have.
3. Permit the generator output to stabilize (engine
runs smoothly and attached device operates
properly).
4. Plug in and turn on the next load.
5. Again, permit the generator to stabilize.
6. Repeat steps 4 and 5 for each additional load.
NEVER add more loads than the generator capacity.
Take special care to consider surge loads in generator
capacity, as described above.
* Wattages listed are approximate only. Check tool or
appliance for actual wattage.
Tool or Appliance
Rated*
(Running)
Watts
Additional
Surge
(Starting)
Watts
Essentials
Light Bulb - 75 watt 75 -
Deep Freezer 500 500
Sump Pump 800 1200
Refrigerator/Freezer - 18 Cu. Ft. 800 1600
Water Well Pump - 1/3 HP 1000 2000
Heating/Cooling
Window AC - 10,000 BTU 1200 1800
Window Fan 300 600
Furnace Fan Blower - 1/2 HP 800 1300
Kitchen
Microwave Oven - 1000 Watt 1000 -
Coffee Maker 1500 -
Electric Stove - Single Element 1500 -
Hot Plate 2500 -
Family Room
DVD/CD Player 100 -
VCR 100 -
Stereo Receiver 450 -
Color Television - 27” 500 -
Personal Computer w/17” monitor 800 -
Other
Security System 180 -
AM/FM Clock Radio 300 -
Garage Door Opener - 1/2 HP 480 520
Electric Water Heater - 40 Gallon 4000 -
DIY/Job Site
Quartz Halogen Work Light 1000 -
Airless Sprayer - 1/3 HP 600 1200
Reciprocating Saw 960 960
Electric Drill - 1/2 HP 1000 1000
Circular Saw - 7 1/4” 1500 1500
Miter Saw - 10” 1800 1800
Table Planer - 6” 1800 1800
Table Saw/Radial Arm Saw - 10” 2000 2000
Air Compressor - 1-1/2 HP 2500 2500
Tool or
Appliance
Rated (Running)
Watts
Additional Surge
(Starting) Watts
Window Air
Conditioner
1200 1800
Refrigerator 800 1600
Deep Freezer 500 500
Television 500
Light (75 Watts) 75
3075 Total
Running Watts
1800 Highest
Additional Surge
Watts
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88

Simplicity 030657-00 Manuel utilisateur

Catégorie
Groupes électrogènes
Taper
Manuel utilisateur
Ce manuel convient également à